Performance tests of two insertion type thermal mass flow meters

Similar documents
Impact of imperfect sealing on the flow measurement of natural gas by orifice plates

485 Annubar Primary Flow Element Installation Effects

TEK-THERMAL 1700B. Thermal Mass Flowmeter. FLOW. Technology Solutions

EDF R&D Industrial flow metering test facility : main past achievements and innovative plans for the future

Products Solutions Services. Gas Flow Measurement

INTERNATIONAL OIML R 32 RECOMMENDATION. Rotary piston gas meters and turbine gas meters ORGANISATION INTERNATIONALE INTERNATIONAL ORGANIZATION

Flow metering in gases Introduction to COMBIMASS family

Vortex Flow Meter Wafer or Flange Connection. - Steam - Liquid - Gas

The Discussion of this exercise covers the following points:

COMPUTATIONAL FLOW MODEL OF WESTFALL'S LEADING TAB FLOW CONDITIONER AGM-09-R-08 Rev. B. By Kimbal A. Hall, PE

Pro-V Multivariable Flowmeter Model M22 In-line Vortex

Single Phase Pressure Drop and Flow Distribution in Brazed Plate Heat Exchangers

Paper 2.2. Operation of Ultrasonic Flow Meters at Conditions Different Than Their Calibration

ONSITE PROVING OF GAS METERS. Daniel J. Rudroff WFMS Inc West Bellfort Sugar Land, Texas. Introduction

A review of best practices for Selection, Installation, Operation and Maintenance of Gas meters for Flare Applications used for Managing facility

Traceable calibration of automatic weighing instruments in dynamic operation

deltaflowc deltaflowc Venturi or Probe

ONSITE PROVING OF GAS TURBINE METERS Daniel J. Rudroff Invensys Metering Systems

Calculating Total Uncertainty of Temperature Calibration with a Dry Block. Calibration White Paper. Beamex.

Gas flow calibrations performed at the National Metrology Institute of South Africa (NMISA)

VersaFlow Vortex 100 Vortex Flow Meter Technical Datasheet. Specification. The all-in-one solution. Highlights. Industries.

ADVANCES in NATURAL and APPLIED SCIENCES

analytical bulk flow distance FLOW level pressure temperature industrial communication

Compiled by: B Beard. Approved by: SH Carstens. Description of requirements and procedures for compact provers to be used as verification standards.

Universities of Leeds, Sheffield and York

LUGB Vortex Flowmeter

TWO PHASE FLOW METER UTILIZING A SLOTTED PLATE. Acadiana Flow Measurement Society

COMPAFLOW. Compressed Air. Volumetric flow. Gas. Mass flow. Steam. Net volumetric flow. Liquid

Lab 3 Introduction to Quantitative Analysis: Pumps and Measurements of Flow

Unique mounting features for Thermal Mass Flow Meters. By Martin Raab in cooperation with CaTeC b.v.

Pro-V Multivariable Flowmeter Model M22 In-line Vortex

CORESTA RECOMMENDED METHOD N 6

INTERACTION BETWEEN WIND-DRIVEN AND BUOYANCY-DRIVEN NATURAL VENTILATION Bo Wang, Foster and Partners, London, UK

Ultrasonic Flowmeter USZ 08

EFFECTIVE DESIGN OF CONVERTER HOODS. 111 Ferguson Ct. Suite 103 Irving, Texas U.S.A. 400 Carlingview Dr. Toronto, ON M9W 5X9 Canada.

THE PRESSURE SIGNAL CALIBRATION TECHNOLOGY OF THE COMPREHENSIVE TEST

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

P06 & P012 Pitot-Static Probes

Level MEASUREMENT 1/2016

A Depletion Compensated Wet Bath Simulator For Calibrating Evidential Breath Alcohol Analyzers

CHARACTERISTICS OF LEAK DETECTION BASED ON DIFERENTIAL PRESSURE MEASUREMENT

P8 to P60 Pitot-Static Probes

ISO INTERNATIONAL STANDARD. Natural gas Measurement of properties Volumetric properties: density, pressure, temperature and compression factor

MEMORANDUM. Investigation of Variability of Bourdon Gauge Sets in the Chemical Engineering Transport Laboratory

ISO INTERNATIONAL STANDARD

THERMAL MASS FLOW MEASUREMENT FOR GASES

Deborah Houssin-Agbomson, Jean-Yves Letellier, Philippe Renault, Simon Jallais

JCSS accredited laboratory Endress+Hauser Japan

Vortex Meters for Liquids, Gas, and Steam

better measurement Simply a question of SCHMIDT Flow Sensor SS The cost-effective alternative in pressurised systems up to 10 bars.

I.CHEM.E. SYMPOSIUM SERIES NO. 97 BUOYANCY-DRIVEN NATURAL VENTILATION OP ENCLOSED SPACES

Pro-V Multivariable Flowmeter

Influence of Reynolds number on Cd of Critical flow venturi nozzle and validation with ISO standards

Radar, Ultrasonic and RF Level Transmitters

PVP Copyright 2009 by ASME

deltaflowc deltaflowc Gas Massflowmeter Venturi- and Probe Type

AIR PRESSURE CONTROLLED MASS MEASUREMENT SYSTEM

CFD SIMULATIONS OF GAS DISPERSION IN VENTILATED ROOMS

Guide No. 2/2009. Design, training and equipment Martin Firlus. Physikalisch Technische Bundesanstalt Braunschweig und Berlin

WaterSense Specification for Spray Sprinkler Bodies. Version 1.0

Constant Pressure Inlet (CCN) Operator Manual

Features. Description

E. Agu, M. Kasperski Ruhr-University Bochum Department of Civil and Environmental Engineering Sciences

Operational experiences with the EuroLoop Liquid Hydrocarbon Flow Facility

This document is a preview generated by EVS

Model 601CV. Mass Flow Controller. Product Features:

For Multi-Parameter Meters see mvx

Operating Instructions DB41

THE IMPLEMENTATION OF TOROIDAL THROAT VENTURI NOZZLES TO MAXIMIZE PRECISION IN GAS FLOW TRANSFER STANDARD APPLICATIONS

Technical Report. Comparison of Ventilation Standard Calibration Methods

Visual Observation of Nucleate Boiling and Sliding Phenomena of Boiling Bubbles on a Horizontal Tube Heater

Operating instructions Pitot Static Tube

For Multi-Parameter Meters see mvx

Study of Thermal Effect on Calibration of an Ultrasonic Flow Meter

HUMOR 20. High Accuracy Humidity Calibrator. Water T, p1 HUMOR 20 V1.0

Flowmeter Shootout Part II: Traditional Technologies

Analogue and Digital Mass Flow Meters and Controllers for Gases MASS-STREAM

An innovative technology for Coriolis metering under entrained gas conditions

Correction of Pressure Drop in Steam and Water System in Performance Test of Boiler

Non-intrusive Natural Gas Flow Measurement

Part 6: Critical flow orifices

Oil And Gas Office Houston Fax Test Separator / Off-Shore Metering

INSTRUMENTS A THERMAL MASS FLOW SENSOR USING A CONSTANT DIFFERENTIAL TEMPERATURE ABOVE THE AMBIENT GAS TEMPERATURE

Numerical and Experimental Investigation of the Possibility of Forming the Wake Flow of Large Ships by Using the Vortex Generators

Influence of Ambient Temperature on Performance of a Joule-Thomson Refrigerator

A. M. Dalavi, Mahesh Jadhav, Yasin Shaikh, Avinash Patil (Department of Mechanical Engineering, Symbiosis Institute of Technology, India)

Experimental Analysis on Vortex Tube Refrigerator Using Different Conical Valve Angles

Integral type Differential pressure flowmeter VNT Series

Optimization of Ejector's Performance With a CFD Analysis. Amanda Mattos Karolline Ropelato Ricardo Medronho

Thermal Mass Flowmeters. 5 Mass Flowmeters

PROCESS MONITORING AND CONTROL

Comparative temperature measurements in an experimental borehole heat exchanger. Vincent Badoux 1, Rita Kobler 2

INFLUENCE OF MEASURING PROCESS AUTOMATION ON UNCERTAINTY OF MASS STANDARD AND WEIGHTS CALIBRATION.

AFC. SDPROC and AFC Analog Mass Flow Controller ANALOG MASS FLOW CONTROLLERS. Principles of Operation. Design Features

and its weight (in newtons) when located on a planet with an acceleration of gravity equal to 4.0 ft/s 2.

pren CEN standard-draft pr EN 12261

Flow meter. bellow vaporizer. APL valve. Scavenging system

Pressure reduction controller (PN 16, 25, 40)

Device Description. Operating Information. CP Q (eq. 1) GT. Technical Bulletin TB-0607-CFP Hawkeye Industries Critical Flow Prover

A numerical Euler-Lagrange method for bubble tower CO2 dissolution modeling

Transcription:

Performance tests of two insertion type thermal mass flow meters I CARE 1, J VEAU 2, Ph GENOUX 3 1 CETIAT, Domaine scientifique de la Doua, 25 avenue des Arts, 69100 Villeurbanne, France 2 EDF R&D, Département STEP, 6 quai Watier, BP 49, 78401 Chatou, France 3 EXERA, 4 Cité d Hauteville, 75010 Paris, France E-mail : isabelle.care@cetiat.fr Abstract. Thermal mass flow meters are widely used in industry for process and plant mass flow metering for a wide range of gas types. The interest of this type of flow meter lies in the fact that the induced pressure drop is negligible; the wide turndown allows measurement of gas consumption as well as leaks. However, the operating conditions of flow meters are sometimes far from the conditions for which the manufacturer specifications are given and the objective of the performed tests is therefore the evaluation of the measurement error which can occur when the use conditions deviate from the calibration conditions. First, tests in ideal conditions (no upstream disturbances, ambient conditions of pressure, temperature and humidity) have been performed to check if the flow meters meet their manufacturer s specifications. Then, some operating conditions have been changed. The investigated parameters were the gas temperature, the gas humidity, the in-line pressure, the orientation of the sensor relative to the flow direction and the distance to upstream disturbances. Tests have been conducted with upstream distances equal to, smaller and higher than the minimum distance required by the manufacturer. The study presented in this paper has been conducted for two insertion type thermal mass flow meters. 1. Introduction The working principle of an insertion type thermal mass flow meter is based on the measurement of the cooling effect of a flowing gas on a heated probe. Insertion type devices have two probes that are inserted in the flowing gas as shown in Figure 1. Each probe is a resistive temperature sensor. The Authors, published by EDP Sciences. This is an open access article distributed under the terms of the Creative Commons Attribution License 4.0 (http://creativecommons.org/licenses/by/4.0/). Article available at http://cfmetrologie.edpsciences.org or https://doi.org/10.1051/metrology/201702001

Figure 1 Insertion thermal mass flow meter One monitors the gas temperature while the other is heated. The heat flux between this probe and the gas, H, is proportional to the mass flow rate, qm, and the temperature difference, T: = The measurement of the electrical power brought to heat the probe is directly related to the heat exchange flux with the flowing gas and then with the mass flow rate. The insertion type thermal mass flow meter allows measurements of gas flow rates in, even large, circular pipes and rectangular ducts with a cost-effective and easy installation. With a large turndown, it can also measure operational flow rates as well as leakage. However, as the heat exchange flux depends also to some secondary parameters such as viscosity, thermal conductivity of the fluid, the behavior of the meter can be influenced by the nature of the flowing fluid. The technical commission Flow-metering, Level-metering of EXERA 1,, have defined a test program aiming at evaluating the performances of insertion type thermal mass flow meters not only in laboratory conditions used in the manufacturers specifications sheets, but also in some conditions representative of on-site environment. 1 EXERA is a French association gathering companies that operate measuring instruments, automatisms and actuators, and are willing to exchange information on their measurement experiences. For more information, please visit www.exera.com 2

2. Evaluated Flow meters and test program The insertion type thermal mass flow meters were lent by the manufacturers who approved the proposed test program. Manufacturer Table 1 Evaluated flow meters Model E+H PROLINE T-MASS 65I FCI ST 100 Tests were performed in the CETIAT s (France) COFRAC accredited gas flow laboratory. The reference flow rate was measured using a set of critical nozzles with a measuring uncertainty of 0.31% of the flow rate and the tests were conducted with air as gas fluid. First the measured performances of the flowmeters were compared to the manufacturer s specifications at atmospheric pressure, ambient temperature and under ideal conditions. These one were defined in terms of minimum upstream and downstream straight lengths. A DN 100 pipe was used for these tests Then, some test conditions were changed to evaluate their influence on the measurement of the flow meters. These conditions were : Temperature, Relative humidity, Pressure, Distance from upstream disturbances. All these tests were performed with the flow meter inserted in a DN100 pipe. An additional test was performed in a DN300 pipe with appropriate upward and downward straight lengths. Results are presented here anonymously for reason of confidentiality. The detailed results are exclusively available to EXERA members in reports [1] and [2]. 3

3. Results 3.1. Metrological performances The metrological performances were evaluated with air at atmospheric pressure and at the following conditions: Pipe diameter: DN 100 Flow rates: 5 between 0.01 Qmax and Qmax Upstream/downstream straight lengths: 40D/ Ambient air Results are presented below are typical ones obtained for one or the other of the two flow meters: Figure 2 Metrological performances of one of the two tested flow meters The flow meter is in compliance with the manufacturer s specifications both for analog output and for reading on the display over the whole flow range. 3.2. Influence of pressure, temperature and humidity conditions As the measurement is directly related to the heat exchange flux between the flow sensor and the flowing gas, some changes in the gas properties could have an influence of the results. these parameters have been tested by comparing results: with dry and humidified compressed air at 1 bar abs, with air at 10, 22 and 40 C, 4

with compressed air at 1 bar and 6 bar abs. The results of the tests are shown below: Figure 3 Influence of relative humidity of the air on one of the two tested flow meters It can be observed that the relative humidity of the air has no significant influence on the flow rate measured by the flow meter under test. 5

Figure 4 Influence of gas temperature on one of the two tested flow meters On the figure above, the ratio between the flow rate measured when the temperature of air is t divided by the median flow rate at the same temperature t is drawn against the temperature t. The tests have been performed at 10 C, 22 C and 40 C for three flow rates, Qmin, Qmedian and Qmax. Even if the temperature change has an impact of the fluid properties, it can be seen that the influence on the flow rate measured by the flow meter under test is not significant. 6

Figure 5 Influence of pressure on one of the two tested flow meters An dependence of the measurement to in-line pressure is sometimes given in the specification s sheet of the flow meter. This one is often expressed as an additional error in % of deviation/bar. The tests have been performed at 1, 3 and 6 bar abs and the results presented on the figure above show a slight dependence for the flow meter under test, in agreement with the manufacturer s specification except at the very low flow rate. 3.3. Influence of shortened upstream straight lengths In real conditions, it is sometimes difficult to reach the minimum straight lengths specified by the manufacturers. It is then interested to have an idea of the behavior of the flow meters in such conditions. If the velocity profile is distorted because of upstream disturbances, the error on the mean velocity might occur because the working principle of the flow rate measurement of this type of flow meter is based on the assumption of a well-established turbulent flow in the duct. To estimate the influence of shortened straight lengths, tests were performed with some disturbances at different distances upstream the flow meter. The disturbances which have been used are a single bend and a double non coplanar bend at different distances, according Table 2, below. 7

Table 2 Experimental conditions Disturbance type Upstream straight length Downstream straight length Single bend at 90 XD 5D XD XD + 5D XD 5D Non coplanar double bend at XD 90 XD + 5D The minimum upstream straight length is defined as XD, where X depends on the manufacturer and may also depend on the type of disturbance. Single bend Non coplanar double bend Figure 6 Photos of the disturbances The results are presented below first for a single bend and then for a double non coplanar bend. 8

Figure 7 Influence of an upstream single bend at 90 Figure 8 Influence of an upstream non coplanar double bend The results presented above show the significant influence of the straight length on the measured flow rate. 9

4. Conclusions Two insertion type thermal mass flow meters, available on the market, were evaluated in different conditions. A comparison with manufacturers specifications was performed with air as flowing fluid. Each of the two flow meters response is mainly within the manufacturers specifications. The flow meters were then evaluated in some extreme conditions representative of on-site conditions. The tested conditions were shortened upstream straight lengths, as well as change in temperature, pressure and relative humidity. A small dependence on the inline pressure is observed, demonstrating the primary mesurand of the thermal mass flowmeter is not a real mass flow. The dependence on upstream straight lengths shows how important it is to respect the manufacturer s recommendations. Thanks We would like to thank EXERA that funded the evaluation campaign, and its technical commission Flow-metering, Level-metering who defined the test protocol, and the manufacturers (Endress+Hauser and FCI through its French representative Engineering Mesures) for their financial and technical contributions. References [1] CARÉ I., Évaluation d un débitmètre massique thermique à insertion Proline t-mass 65I Endress+Hauser, Rapport EXERA E6070X17, 2017 [2] CARÉ I., Évaluation d un débitmètre massique thermique à insertion ST100 FCI, Rapport EXERA E6071X17, 2017 10