FT16 Ball Float Steam Trap Installation and Maintenance Instructions

Similar documents
CA16 and CA16S-14 Air and Gas trap Installation and Maintenance Instructions

AVS32 Stainless Steel Air Vent for Steam Systems Installation and Maintenance Instructions

AE50S Automatic Air and Gas Vent for Liquid Systems Installation and Maintenance Instructions

Thermocirc Installation and Maintenance Instructions

UBP32 Sealed Balanced Pressure Thermostatic Steam Trap for use with PC_ Pipeline Connectors Installation and Maintenance Instructions

SCA Series Inverted Bucket Steam Traps

Fig 1, Fig 12, Fig 13, Fig 14, Fig 16 and Fig 16L Strainers Installation and Maintenance Instructions

IFTGS14 Ball Float Steam Trap ½" and ¾" with Integral Spiratec Sensor

FTGS14 Ball Float Steam Trap DN15 (½") to DN25 (1")

TD45 Thermodynamic Steam Trap Installation and Maintenance Instructions

A3S Bellows Sealed Stop Valve Installation and Maintenance Instructions

1. General safety information. 2. General product information. 3. Installation. 4. Commissioning. 5. Operation. 6. Maintenance. 7.

BTD52L Thermodynamic Steam Trap Installation and Maintenance Instructions

TD10, TD52M and TD259 Thermodynamic Steam Traps Installation and Maintenance Instructions

MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap

CA44, CA44S, CA46 and CA46S Air and Gas Traps

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

AE14 Automatic Air Vents for Liquid Systems Installation and Maintenance Instructions

CA10S, CA14 and CA14S Air and Gas Traps

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

FT43, FT44, FT46 and FT47 Ball Float Steam Traps Installation and Maintenance Instructions

BSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions

AVC32 Carbon Steel Air Vent for Steam Systems

TSS21 Sealed Thermostatic Steam Tracer Trap

Fig 12, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

Fig 1, Fig 12, Fig 13, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

AVM7 Stainless Steel Thermostatic Air Vent

FT53, IFT53, FT54, IFT54, FT57 and IFT57 Ball Float Steam Traps - DIN

HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions

TA10A and TA10P Steam Tracing Temperature Control Valves Installation and Maintenance Instructions

DF1 and DF2 Diffusers

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators

CA46S Austenitic Stainless Steel Air and Gas Trap DN40 and DN50

BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

BTM7, BTS7 and BTS7.1 Stainless Steel Thermostatic Clean Steam Traps

MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection

S and SF Inverted Bucket Steam Traps

DCV10 Stainless Steel Disc Check Valve for use with Condensate Pumps

PV4 and PV6 Piston Valves

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

KBV21i and KBV40i Air Actuated Boiler Blowdown Valves

TDC46M, TDS46M and UTDS46M Thermodynamic Steam Traps with Maintainable Seat Installation and Maintenance Instructions

FTC62 and FTS62 Ball Float Steam Traps Installation and Maintenance Instructions

Fig 3, 7, 33, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers

Fig 7, 33, 33.1, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers Installation and Maintenance Instructions

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats

DCV1, DCV3 and DCV3LT Disc Check Valves Installation and Maintenance Instructions

Airodyn, BRair and BRoil Compressed Air Drain Traps

BPT13 Balanced Pressure Thermostatic Steam Traps

AE30 Automatic Air Eliminators / Air and Gas Vents for Liquid Systems

CA44 and CA44S Carbon Steel Air and Gas Traps Flanged DN15 to DN25

Dri-Line Mk3 Monnier Compressed Air Drain Trap

Dri-Line Mk2 Spirax-Monnier Compressed Air Drain Trap

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats Installation and Maintenance Instructions

DCV6 Disc Check Valve

CVS10 Sanitary Check Valves

TP1 and TP2 Temporary Cone Shaped Strainers

Spirax SafeBloc TM DBB3 Double Block and Bleed Bellows Sealed Stop Valve. 1. Safety information. 2. General product information. 3.

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions

BDV1 and BDV2 Blowdown / Depressurisation Valves

CP10 Sensor Installation and Maintenance Instructions

M33F ISO, M33S ISO and M33V ISO Ball Valves Installation and Maintenance Instructions

BT6-B Sanitary Balanced Pressure Thermostatic Steam Trap

PC3_ and PC4_ Pipeline Connectors

CA14 SG Iron Air and Gas Trap ½" and ¾" (Screwed)

M70i ISO and M80i ISO Stainless Steel Ball Valves for Sanitary Systems Installation and Maintenance Instructions

CS10-1 Stainless Steel Clean Steam Separator

M10HTi ISO Tobacco Ball Valve Screwed, SW, BW and Flanged versions

PC10HP Pipeline Connector (ASME 600)

APT14, APT14HC and APT14SHC Spares 2

SRV2S Pressure Reducing Valve

BCV31 DN40 - Blowdown Control Valve

PTF4 Pivotrol Pump (patented) version Dual Mechanism - Pressure Powered Pump

SRV66 Sanitary Pressure Reducing Valve

FV Flash Vessel Installation and Maintenance Instructions

IX1 Spirax-Monnier International Compressed Air Filter Installation and Maintenance Instructions

MF2M Monnier Miniature Compressed Air Filter

ML3M Monnier Miniature Compressed Air Lubricator

TW Temperature Control Valve

PC3000, PC3001 and PC4000, PC4001 Pipeline Connectors

BCV31 DN20 - Blowdown Control Valve

MFP14-PPU (Vented) Automatic Packaged Pump Units

BRV71 and BRV73 Pressure Reducing Valves

BSA and BSAT Bellows Sealed Stop Valves Installation and Maintenance Instructions

SA Control Valve types: BM, BMF, BX, SB, NS, KA, KB, KC (Normally open) BMRA, BMFRA, BXRA, SBRA, NSRA, KX, KY (Normally closed)

1. Preface Important Safety Notes Brief Product Information Product Working Principle Installation Guidelines...

Manual Actuated Boiler Blowdown Valves

BCVi43 Blowdown Control Valve

Blowdown vessels Meeting the requirements of HSE PM60

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Dial Adjustment)

Spirax Compact FREME Flash Recovery Energy Management Equipment

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Knob Adjustment)

Ball Float Steam Trap UNA 43 PN 16/CL 125/JIS 10K UNA 46 PN 40/CL 150/CL 300/JIS 10K/JIS 20K DN 80, 100, 150, 3", 4", 6"

Ball Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300 DN 40, 50, 65

QuickHeat TM Packaged Heat Exchanger Solutions

DP17, DP17E, DP17G, DP17R, DP17Y and DP27G Pilot Operated Pressure Reducing Valves

595-K/L and 596-K/L Series Self Operated Valves Installation and Maintenance Instructions

IP2M, IP2AM and IP2DM Monnier International Compressed Air Filter/ Regulators

Transcription:

1430050/1 IM-P143-04 ST Issue 1 FT16 Ball Float Steam Trap Installation and Maintenance Instructions 1 General safety information 2 General product information 3 Installation ½" and ¾" shown 4 Commissioning 5 Operation 6 Maintenance 7 Spare parts Printed IM-P143-04 in the ST UK Issue 1 Copyright 20011

1 General safety information Safe operation of the unit can only be guaranteed if it is properly installed, commissioned and maintained by a qualified person (see Section 11 of the attached Supplementary Safety Information) in compliance with the operating instructions. General installation and safety instructions for pipeline and plant construction, as well as the proper use of tools and safety equipment must also be complied with. Warning The cover gasket contains a thin stainless steel support ring which may cause physical injury if not handled and disposed of carefully. Isolation Consider whether closing isolating valves will put any other part of the system or personnel at risk. Dangers might include; isolation of vents and protective devices or alarms. Ensure isolation valves are turned off in a gradual way to avoid system shocks. Pressure Before attempting any maintenance consider what is or may have been in the pipeline. Ensure that any pressure is isolated and safely vented to atmospheric pressure before attempting to maintain the product, this is easily achieved by fitting Spirax Sarco depressurisation valves type DV (see separate literature for details). Do not assume that the system is depressurised even when a pressure gauge indicates zero. Temperature Allow time for temperature to normalise after isolation to avoid the danger of burns and consider whether protective clothing (including safety glasses) is required. Disposal The product is recyclable. No ecological hazard is anticipated with the disposal of this product providing due care is taken. 2 IM-P143-04 ST Issue 1

2 General product information 2.1 Description The FT16 is a 316 austentic stainless steel ball float steam trap with integral air venting facility. It is available with horizontal screwed connections. As an option a manually adjustable needle valve can be added for use as a steam lock release designated the FT16-C. If required the cover can be drilled and tapped 3 /8" BSP or NPT for the purpose of fitting a drain valve. Note: For further information see the following Technical Information Sheet, TI-P143-02, which gives full details of:- Materials, sizes and pipe connections, dimensions, weights, operating ranges and capacities. FT16 ½" and ¾" FT16 1" FT16-C Fig. 1 2.2 Sizes and pipe connections ½", ¾" and 1" screwed BSP or NPT. 2.3 Limiting conditions Maximum body design conditions PN25 PMA - Maximum allowable pressure 25 bar g (362.5 psi g) TMA - Maximum allowable temperature 300 C (572 F) PMO - Maximum operating pressure 16.5 bar g (239 psi g) TMO - Maximum operating temperature 300 C (572 F) Designed for a maximum cold hydraulic test pressure of: 38 bar g (551.0 psi g) 2.4 Operating range Temperature C 300 200 100 Steam saturation curve 0 0 5 10 15 16.5* 20 25 Pressure bar g The product must not be used in this region * PMO Maximum operating pressure recommended for saturated steam 16.5 bar g. DPMX - Max differential pressure Trap FT16-4.5 FT16-10 FT16-14 DPMX 4.5 bar 10 bar 14 bar IM-P143-04 ST Issue 1 3

3 Installation Note: Before actioning any installation observe the 'Safety information' in Section 1. Referring to the Installation and Maintenance Instructions, name-plate and Technical Information Sheet, check that the product is suitable for the intended installation: 3.1. Check materials, pressure and temperature and their maximum values. If the maximum operating limit of the product is lower than that of the system in which it is being fitted, ensure that a safety device is included in the system to prevent overpressurisation. 3.2. Determine the correct installation situation and the direction of fluid flow. 3.3. Remove protective covers from all connections. 3.4 The trap must be fitted with the float arm in a horizontal plane so that it rises and falls vertically with the direction of flow as indicated on the body. Note: ½" and ¾" Traps require 110 mm withdrawal distance to remove the cover. 1" Traps require 160 mm withdrawal distance to remove the cover. Note: If the trap is to discharge to atmosphere ensure it is to a safe place, the discharging fluid may be at a temperature of 100 C (212 F). 4 Commissioning After installation or maintenance ensure that the system is fully functional. Carry out tests on any alarms or protective devices. 5 Operation The ball float steam trap is a continuous discharge trap, removing condensate the instant it forms. On start-up, the thermostatic air vent allows air to bypass the main valve preventing the system air binding. Hot condensate will close the air vent tightly, but as soon as it enters the main chamber of the trap, the float rises and the lever mechanism attached to it opens the main valve - keeping the system drained of condensate at all times. When steam arrives, the float drops and closes the main valve. Float traps are renown for their high start-up load handling capability, clean tight shut-off and resistance to waterhammer and vibration. 4 IM-P143-04 ST Issue 1

6 Maintenance Note: Before actioning any maintenance program observe the 'Safety information' in Section 1. Warning The cover gasket contains a thin stainless steel support ring which may cause physical injury if not handled and disposed of carefully. 6.1 General information Repairs can be carried out with the trap in the line. When reassembling make sure that all joint faces are clean and the dowel locates in the cover. 6.2 How to fit the main valve assembly (refer to Fig. 2, Section 7): - Unscrew the support and the pivot frame and valve seat (5, 7, 14 and 15). - Ensure the seat / gasket faces are clean and dry. - Fit the valve seat (5) to the body (Do not use gasket paste). - Attach the support frame (15) and the pivot frame (14) to the body with the assembly set screws (7), but do not tighten. - Fit the float arm to the pivot frame using the pin (17) and by moving the complete assembly centre the valve head onto the seat orifice. - Tighten the assembly set screws (7) to the recommended tightening torque (see Table 1). 6.3 How to fit the air vent assembly (refer to Fig. 2, Section 7): - Remove the spring clip, capsule and saucer plate (9). - Unscrew the seat. - Fit the new seat and frame. - Assemble the spacer plate, fit capsule and clip. Table 1 Recommended tightening torques or Item Size N m (lbf ft) mm 2 ½", ¾" and 1" 17 M10 x 30 29-33 (21.3-24.3) 9 ½", ¾" and 1" 17 50-55 (36.8-40.4) 5 ½", ¾" and 1" 17 40-45 (29.4-33.1) 11 ½", ¾" and 1" 21 40-45 (29.4-33.1) 7 ½", ¾" and 1" M5 x 20 10-12 (7.3-8.8) IM-P143-04 ST Issue 1 5

7 Spare parts Spare parts The spare parts available are shown in heavy outline. Parts drawn in broken lines are not supplied as spares. Available spares Main valve assembly with float 5, 6, 7, 8, 9, 14, 15, 17 Air vent assembly 9 Steam lock release and air vent assembly 9, 11, 12 Complete set of gaskets (packet of 3 sets) 3, 6, 12 How to order spares Always order spares by using the description given in the column headed 'Available spares' and state the size and type of trap. Example: 1 - Air vent assembly for ½" Spirax Sarco FT16 Steam Trap. Steam lock release 11 12 Air vent assembly 9 2 3 6 5 17 1514 7 Main valve assembly with float 8 Fig. 2 6 IM-P143-04 ST Issue 1

IM-P143-04 ST Issue 1 7

8 IM-P143-04 ST Issue 1