Safety. Operating instructions Magnetic relief valve VAN DANGER. Contents WARNING CAUTION. Changes to edition 11.11

Similar documents
Safety. Operating instructions Solenoid valve for gas VG 6 VG 15/10 DANGER. Contents WARNING CAUTION. Changes to edition 09.14

Safety. Operating instructions Filter module VMF Measuring orifice VMO Fine-adjusting valve VMV DANGER. Contents WARNING CAUTION

Safety. Operating instructions Solenoid valve for gas VG 10/15 VG 65 DANGER. Contents WARNING CAUTION. Changes to edition 11.14

Safety Please read and keep in a safe place Operating instructions Linear flow control VFC Linear flow control with actuator IFC

Safety Please read and keep in a safe place Operating instructions Linear flow control VFC Linear flow control with actuator IFC

Safety. Operating instructions Bypass/pilot gas valve VBY 8 DANGER. Contents WARNING CAUTION Elster GmbH Edition 01.15

Safety. Operating instructions. Pressure switches for gas DG..H, DG..N. Pressure switch for gas DG..I DANGER. Contents WARNING CAUTION

Safety. Operating instructions Gas pressure regulators 60DJ, J78R, GDJ DANGER WARNING. Contents CAUTION Edition 12.10

Safety. Operating instructions Safety shut-off valve JSAV DANGER. Contents WARNING CAUTION. Changes to edition 02.12

Safety. Operating instructions Safety shut-off valve JSAV DANGER. Contents WARNING CAUTION. Changes to edition Edition 08.

Safety. Operating instructions Manual valves AKT, flow adjusting cocks GEHV, GEH, LEH DANGER. Contents WARNING CAUTION. Changes to edition 06.

Safety. Operating instructions. Pressure switches for gas DG..H, DG..N. Pressure switch for gas DG..I DANGER. Contents WARNING CAUTION

Safety. Operating instructions Solenoid valve for gas VAS 6 9 Double solenoid valve VCS 6 9 DANGER. Contents WARNING CAUTION. Changes to edition 07.

Safety. Operating instructions Manual valves AKT, flow adjusting cocks GEHV, GEH, LEH DANGER. Contents WARNING CAUTION. Changes to edition 03.

Safety. Operating instructions. Pressure switches for gas DG..H, DG..N. Pressure switch for gas DG..I DANGER. Contents WARNING CAUTION

Safety. Operating instructions Motorized valve for gas VK DANGER. Contents WARNING CAUTION. Changes to edition Elster GmbH Edition 06.

Safety. Operating instructions Pressure switches for gas DG..H, DG..N Pressure switch for gas DG..I DANGER. Contents WARNING CAUTION

Safety. Operating instructions Solenoid valve for gas VAS 6 9 Double solenoid valve VCS 6 9 DANGER. Contents WARNING CAUTION. Changes to edition 04.

Pressure regulator with solenoid valve VAD Air/gas ratio control with solenoid valve VAG Variable air/gas ratio control with solenoid valve VAV

Tightness control TC. Product brochure GB 3 Edition AGA

Pressure regulator with solenoid valve VAD Air/gas ratio control with solenoid valve VAG

Tightness controls TC 1 3 and TC 4

Governor with solenoid valve VAD Air/gas ratio control with solenoid valve VAG

Safety DANGER WARNING CAUTION. Contents. Changes to edition Elster GmbH Edition Please read and keep in a safe place

Safety. Operating instructions. White meters BK V2 to BK V12. (component of a diaphragm gas meter) DANGER. Contents WARNING CAUTION

Pressure regulators with solenoid valve VAD, VAG, VAV, VAH Flow rate regulator VRH Pressure regulators with double solenoid valve VCD, VCG, VCV, VCH

Safety 0 50 Please read and keep in a safe place Operating instructions Solenoid valve for gas VAS 1, double solenoid valve VCS 1

Safety. Operating instructions Burners for gas ZIO 165, ZIO 200 DANGER. Contents WARNING CAUTION Edition 11.11

Solenoid gas valve. The solenoid gas valve is also applicable as a main gas valve Pilot gas valve for forced draft burners

OPERATING INSTRUCTIONS

Safety. Operating instructions Burners for gas BIO, BIOA DANGER WARNING. Contents CAUTION Edition Please read and keep in a safe place

GasBloc Multifunctional gas control Combined regulator and safety shut-off valves Electrically modulating GB-M(P) 055 D01

Old documentation - Only for your information! Product is not available any more!

Type Operating Instructions. 2/2-way solenoid valve 2/2-Wege Magnetventil Electrovanne 2/2 voies.

VMR VMR-OTN VMR 6 bar

Safety. Operating instructions Excess air burner BIC..L DANGER. Contents WARNING CAUTION Elster GmbH Edition 06.17

GasMultiBloc Combined regulator and safety valve Infinitely variable air/ gas ratio control mode MBC-300-VEF MBC-700-VEF MBC-1200-VEF

GasBloc Multifunctional gas control Combined regulator and safety shut-off valves Integrated gas-air system GB-GD 057 D01

Old documentation - Only for your information! Product is not available anymore!

GasBloc Multifunctional gas control Combined regulator and safety shut-off valves single-stage atmospheric operating mode GB-(LEP) 057 D01

Old documentation - Only for your information! Product is not available any more!

GM-7000 Series CE Approved Gas Control Valve

Dual Safety Shutoff Valves with Proof of Closure and NEMA 4x Enclosure. DMV-D/624L Series DMV-DLE/624L Series

Compact pressure switches for gas and air

Dual Solenoid Gas Valve Installation

Gas Filters DN15 DN300. delta-elektrogas.com EE151 03/17

GM Series Dual-Block Multi-Function Gas Control Valves

Type 0404 / /2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation

Dual Safety Shutoff Valves with Proof of Closure and NEMA 4x Enclosure. DMV-D/624L Series DMV-DLE/624L Series

Valve Proving System VDK 200 A S06*

Valve Proving System VDK 200 A S02

WhirlWind Combined fully integrated gas/air control and safety system GB-WND 055 D01

EVRM-NC EVRM-6NC. delta-elektrogas.com. Safety solenoid valves for gas Manual reset - Normally closed DN10 DN300.

Dual Modular Safety Shutoff Valves with Two-stage operation. DMV-ZRD/602 Series DMV-ZRDLE/602 Series

WhirlWind Multifunctional gas control Fully integrated gas-air system with control and safety function GB-WND 055 D01

GasMultiBloc Combined regulator and safety shut-off valves Single-stage function MB-D(LE) B01

Indicates possible material damage. Contents. All interventions may only be carried out by qualified Pressure regulators with solenoid valve

Proportional pressure regulators VPPE

SV - Safety Shutoff Valve with Proof of Closure 1/2" NPT - 2" NPT. SV/614 Series SV-DLE/614 Series

TANDEM MODULATOR FOR OUTLET GAS FLOW: STEPPED (836 TANDEM) - CONTINUOUS (837 TANDEM) SERVO-CONTROLLED PRESSURE REGULATOR

200 PSI FAST-FILL AIR SOURCE KIT

Dual Modular Safety Shutoff Valves with Proof of Closure. DMV-D/622 Series DMV-DLE/622 Series

4/2 way Pneumatic Solenoid Valve

UL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function Gas Control Valves

O.K. Safety first. Table of Contents. Approvals. Attention IFGC CSA UL ANSI NFPA CDN USA

Dual Modular Safety Shutoff Valves. DMV-D/602 Series DMV-DLE/602 Series

GasMultiBloc Combined regulating and safety valve Infinitely variable air/gas ratio control mode MB-VEF B01

Dual Modular Safety Shutoff Valves DMV-D 525/11 DMV-DLE 525/11

Dual Modular Safety Shutoff Valves with Proof of Closure and NEMA Type 4x Enclosure DMV-D 704/624 DMV-D 704/634 DMV-DLE 704/624 DMV-DLE 704/634

MULTIFUNCTIONAL CONTROL FOR GAS BURNING APPLIANCE

OPERATING INSTRUCTIONS MANUAL FOR QACV PNEUMATIC DOSING PUMP

Dual Modular Safety Shutoff Valves with Two-stage operation and Proof of Closure. DMV-ZRD/612 Series DMV-ZRDLE/612 Series

Dual Modular Safety Shutoff Valves. DMV-D/602 Series DMV-DLE/602 Series

BGA158 Series CE Approved Class A Shutoff Gas Valve

Gas Pressure Regulator HON 300

Operating Manual VSA100A. tina29e1 ( )

BGC258 Series BASOTROL Gas Valve

Dual Modular Safety Shutoff Valves with Two-stage operation and Proof of Closure DMV-ZRD/612 Series DMV-ZRDLE/612 Series

Dual Modular Safety Shutoff Valves with Two-stage operation. DMV-ZRD/602 Series DMV-ZRDLE/602 Series

BGA158 Series CE Approved Class B Shutoff Gas Valve

GasMultiBloc Combined regulator and safety shut-off valves Two-stage function MB-ZRD(LE) B01

Flowmeter. Original operating manual DFM

SPECIFICATIONS CAPACITY

Gas Filters DN15 DN300. elektrogas.com EE151 06/13

Dual Modular Safety Shutoff Valve with NEMA 4x Enclosure. DMV-D/604L Series DMV-DLE/604L Series

200 PSI HIGH-FLOW AIR SOURCE KIT

SPECIFICATIONS ATTENTION

GasMultiBloc Combined regulator and safety shut-off valves Two-stage function Integrated bypass valve MB-ZRD(LE) B07

3-Way Safety Block DSV

GS-20/25 and GS-40/45 Series Single-block Multi-function Gas Control Valves

Type 2000 INOX. Quickstart. English Deutsch Français. 2/2-way angle seat valve 2/2-Wege Schrägsitzventil Vanne à siège incliné 2/2 voies

Dual Modular Safety Shutoff Valves with NEMA 4x Enclosure DMV-D 704/604 DMV-DLE 704/604

3G Operating instructions. Digital Purge Gas Valve 3G Type: Document no.: D0001 Version: 01. July 2011/Rev.

120 PSI FAST-FILL AIR SOURCE KIT 25% Duty Compressor on 1.5 Gallon Air Tank

Simple Set Max. Pressure Independent Control Valves 2 Way 2-1/ /09/18

Instruction manual. for. high purity gas pigtails 200 bar / 300 bar

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

Rocker valve. Type Operating Instructions. Bedienungsanleitung Manuel d utilisation

EG15*... SERIES. SOLENOID GAS VALVES WITH 1/2 CONNECTION AND OPERATING PRESSURE UP TO 500 mbar DESCRIPTION

Solenoid valves VZWF, force pilot operated

Transcription:

0084 Edition 0. D F L I E DK S P GR TR CZ PL RUS H www.docuthek.com Operating instructions Magnetic relief valve Translation from the German 0 Elster GmbH Contents Magnetic relief valve... Contents... Safety.... Checking the usage... Intended use... Type code... Part designations... Installation... Wiring... Preparing the wiring... Connecting a without position indicator... Connecting a with position indicator...4 Finishing the wiring....4 Tightness test...4 Replacing the O-ring on the flange....4 Commissioning.... Replacing the actuator... Maintenance... Accessories... Pressure switch DG..VC... Seal set VA....6 Technical data...6...6 Position indicator... 7 Service life... 7 Declaration of conformity...8 Approval for Russia...8 Contact...8 Safety Please read and keep in a safe place Please read through these instructions carefully before installing or operating. Following the installation, pass the instructions on to the operator. This unit must be installed and commissioned in accordance with the regulations and standards in force. These instructions can also be found at www.docuthek.com. Explanation of symbols,,,... = Action = Instruction Liability We will not be held liable for damage resulting from non-observance of the instructions and non-compliant use. Safety instructions Information that is relevant for safety is indicated in the instructions as follows: DAGER Indicates potentially fatal situations. WARIG Indicates possible danger to life and limb. CAUTIO Indicates possible material damage. All interventions may only be carried out by qualified gas technicians. Electrical interventions may only be carried out by qualified electricians. Conversion, spare parts All technical changes are prohibited. Only use OEM spare parts. Transport On receipt of the product, check that the delivery is complete (see Part designations). Report any transport damage immediately. Storage Store the product in a dry place. Ambient temperature: see Technical data. Changes to edition. The following chapters have been changed: Declaration of conformity Updating of symbols -

Checking the usage Intended use Magnetic relief valve, open when de-energized, for the monitoring of gas valves for tightness used in conjunction with a visual discharge unit. For purging excess or leakage gas. This function is only guaranteed when used within the specified limits see page 6 (Technical data). Any other use is considered as non-compliant. Type code Code Description Magnetic relief valve Size: T T-product 0 0 ominal size [D] R Rp internal thread PT internal thread Quick opening, quick closing K Mains voltage: 4 V DC P 00 V AC, 0/60 Hz Q 0 V AC, 0/60 Hz Y 00 V AC, 0/60 Hz W 0 V AC, 0/60 Hz Position indicator: S with visual indicator G R L Part designations with visual indicator and gold contacts Viewing side: right left Electrical connection: M0 cable gland 4 Type label Solenoid actuator Valve block 4 Connection flange Connection box 6 Position indicator 6..S,..G Mains voltage, electrical power consumption, ambient temperature, enclosure, inlet pressure p u and installation position: see type label. D-4908 Osnabrück, Germany CE-006U64 WARIG The solenoid body heats up during operation depending on ambient temperature and voltage. Installation > +80 C > 76 F CAUTIO Please observe the following to ensure that the magnetic relief valve is not damaged during installation: Do not store or install the unit in the open air. Ensure that there is sufficient space for installation. Sealing material and thread cuttings must not be allowed to get into the valve housing. We recommend that a filter be installed upstream of every system. Do not use compression fittings. Do not clamp the unit in a vice. Only secure the connection flange by holding the octagon with a suitable spanner. Risk of external leakage. The actuator cannot be rotated on magnetic relief valves..s and..g. The housing must not be in contact with masonry. Minimum clearance 0 mm. Installation position: black solenoid actuator in the vertical upright position or tilted up to the horizontal, not upside down. -

Plug 6 7 8 When installing two plugs on a with position indicator: label the sockets and plugs to avoid confusion. Wiring Use temperature-resistant cable (> 80 C). Disconnect the system from the electrical power supply. Shut off the gas supply. Wiring to E 6004-. Preparing the wiring If the M0 cable gland or plug is enclosed, push through the knock-out for the cable gland then remove the cover. The cover must not be taken off before pushing through the knock-out as it prevents damage to the connection box. If the M0 cable gland or plug is already fitted, you do not need to push through the knock-out. First push through the knock-out then unscrew the cover! 4 Socket 6 7 8 8a Connecting a without position indicator LV (+) (-) M0 cable gland 6 LV (+) (-) LV (+) = black (-) = blue 7 8 8a = (-) = LV (+) -

Connecting a with position indicator..s: 00 V, 0 V, 00 V, 0 V,..G: 4 V. open: contacts and closed, closed: contacts and closed. When using two plugs and sockets, label them to avoid confusion. CAUTIO Danger of interference between valve voltage and position indicator voltage. Route valve and position indicator cables separately through M0 cable glands or use two separate plugs. x LV (+) (-) Tightness test Close the solenoid valve. To be able to check the tightness, shut off the downstream pipeline close to the valve. 4. p u max 0 7 8 0 6 Open the magnetic relief valve. x x = black = red = white LV (+) (-) LV (+) = black (-) = blue Position indicator. p u max 9 Tightness OK: open the pipeline. Pipeline leaking: replace O-ring on flange. Unit leaking: dismantle the valve block and return it to the manufacturer. Replacing the O-ring on the flange 0 = (-) = LV (+) Finishing the wiring 9 Screw the cover onto the connection box. Insert new 4 O-ring see Accessories. 6 Check for tightness. -4

Commissioning..S,..G Visual indicator of position indicator: red = closed, white = open. Replacing the actuator Disconnect the system from the electrical power supply. Shut off the gas supply. 4 Accessories Pressure switch DG..VC Disconnect the system from the electrical power supply. Shut off the gas supply. Scope of delivery: A = self-tapping Torx screws (when installing the pressure switch, use these screws only), = O-rings (pressure switch), C = DG..VC with socket. 4 A C Remove the M0 cable gland or plug and socket. Monitoring the inlet pressure p u: The electrical plug of the DG..VC points towards the inlet flange. 6 7 8 p u p d Monitoring the outlet pressure p d: The electrical plug of the DG..VC points towards the outlet flange. 9 0 6 7 8 4 Fit the M0 cable gland or plug and socket. Connect the to the electrical power supply (see page (Wiring)). Maintenance Once per year, twice per year in the case of biologically produced methane; check for internal and external tightness (see page 4 (Tightness test)). Once per year, check electrical installations in line with local regulations; pay particular attention to the PE wire (see page (Wiring)). 9 A Insert can be rotated in 90 steps. 0 L COM O C -

4. x p u max 6 7 A C D A C D Adjusting range (adjusting Mean switching differential at min. tolerance = ± % and max. setting of the scale value) [mbar] [mbar] DG 7VC 7 0.7.7 DG 40VC 40 DG 0VC 0 0 8 DG 00VC 00 00 6 Deviation from the switching point during testing pursuant to E 84 Gas pressure switches: ± %. 8 9 Seal set VA When retrofitting accessories or when removing and reinstalling the magnetic relief valve, we recommend replacing the seals. For size : Seal set VA Order o. 749988, for size : Seal set VA Order o. 749989. Scope of delivery: A x double block seal, x O-rings (flange), C x O-rings (pressure switch), for test point/screw plug: D x sealing rings (flat sealing), x profiled sealing rings. Technical data Types of gas: natural gas, LPG (gaseous), biologically produced methane (max. 0. %-by-vol. H S) or air; other gases on request. The gas must be dry in all conditions and must not contain condensate. Max. inlet pressure p u : max. 00 mbar (7. psig). Leakage rate: 00 cm³/h (0. gal/h). Opening time: quick opening: s. Closing time: quick closing: < s. Ambient temperature: -0 to +0 C, no condensation permitted. Storage temperature: 0 to +40 C. Class A Group safety valve pursuant to E 6 and based on E 6. Mains voltage: 0 V AC, +0/-%, 0/60 Hz; 00 V AC, +0/-%, 0/60 Hz; 0 V AC, +0/-%, 0/60 Hz; 00 V AC, +0/-%, 0/60 Hz; 4 V DC, ± 0%. Cable gland: M0 x.. Electrical connection: electrical cable with max.. mm (AWG ) or plug with socket to E 70-80. Power consumption: Type 4 V DC 00 V AC 0 V AC 00 V AC 0 V AC 9 0 0 46 4 4 Switching frequency: per minute. Enclosure: IP 6. Duty cycle: 00%. Power factor of the solenoid coil: cos ϕ =. Valve housing: aluminium, valve seal: R. Connection flanges with internal thread: Rp to ISO 7-, PT to ASI/ASME. -6

Position indicator Contact rating: Type..S Voltage 0 V AC, 0/60 Hz Min. current (resistive load) Max. current (resistive load) 00 ma A..G 0 V DC ma 0. A Switching cycles: Switching current Switching cycles [A] cos ϕ = cos ϕ = 0.6 0. 00,000 00,000 0. 00,000 0,000 00,000 00,000 00,000 Position indicator switching frequency: per minute. Air flow rate with pressure loss p = mbar. p = mbar/ hpa/0,4 "WC x Q [m/h] Q [m/h] 0 4.4.. 9. 0 8. 40.0 0.0 0. Designed lifetime The Pressure Equipment Directive (PED) and the Energy Performance of uildings Directive (EPD) demand regular checks on and maintenance of heating systems in order to ensure a high level of use in the long term, a clean method of operation and safe function. The service life on which the construction is based, hereinafter referred to simply as the designed lifetime, is compiled from the relevant standards. You can find further explanations in the applicable rules and regulations and on the afecor website (www.afecor.org). This information on the designed lifetime is based on using the product in accordance with these operating instructions. The product must be serviced at regular intervals. Once the specified designed lifetime has been reached, the safety-related functions must be checked in accordance with the section entitled Maintenance. If the product passes the aforementioned function tests, you can continue to use it until the next scheduled maintenance operation. At this point, these tests must be repeated. If the product fails one of the aforementioned tests, it must be replaced immediately. This procedure applies to heating systems. For thermoprocessing equipment, observe national regulations. Designed lifetime (based on date of manufacture) in accordance with E 6, E 6 for : Type Designed lifetime Switching cycles Time [years] 0 to 00,000 0 to 0 00,000 0 Long-term use in the upper ambient temperature range accelerates the ageing of the elastomer materials and reduces the service life (please contact manufacturer). -7

Declaration of conformity We, the manufacturer, hereby declare that the product, marked with product ID o. CE-006U64, complies with the requirements of the listed Directives and Standards. Directives: 009/4/EC, 006/9/EC, 004/08/EC. Standards: E 6, E 6. The relevant product corresponds to the type tested by the notified body 006. The production is subject to the surveillance procedure pursuant to DI E ISO 900 according to annex II, paragraph of Directive 009/4/EC. Elster GmbH Scan of the Declaration of conformity (D, ) see www.docuthek.com Approval for Russia Certified by Gosstandart pursuant to GOST-TR. Approved by Rostekhnadzor (RT). Contact If you have any technical questions, please contact your local branch office/agent. The addresses are available on the Internet or from Elster GmbH. We reserve the right to make technical modifications in the interests of progress. -8 Elster GmbH Postfach 8 09, D-4908 Osnabrück Strotheweg, D-4904 Lotte (üren) T +49 4 4-0 F +49 4 4-70 info@kromschroeder.com, www.kromschroeder.com