Electrical Safety Management for Facility / Operations Work Environments

Similar documents
Electrical Safety Management for Research Work Environments

Management Plan for Electrical Safety ISD #535

ELECTRICAL (COMPREHENSIVE) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR CFR , ,

Ground Fault Protection for Electrical Tools

Department of Electrical Engineering & Computer Science. Electrical Safety. for Staff and Students in EECS Instructional Laboratories

Ground Fault Circuit Interrupter(GFCI) Policy

Safe Schools: A Health and Safety Check

LOCK-OUT/TAG-OUT (LO/TO) SAFETY PROGRAM

Lockout/Tagout Program

Page: 7/15/2009. Energy control procedures Use of lockout/tagout equipment to ensure safe work practices.

Electrical. OSHA Office of Training and Education 1

Original Date of Issue: 04/09

Lockout/Tagout - Energy Control Program

ARKANSAS TECH UNIVERSITY FACILITIES MANAGEMENT HEALTH AND SAFETY MANUAL (LOCKOUT/TAGOUT) 30.0

Electrical Safety. Introduction

11/2/2017. Course Objectives. Overview

LOCKOUT-TAGOUT PROGRAM

Hazardous Energy Control (Lockout-Tagout)

CONTROL OF HAZARDOUS ENERGY (LOCKOUT/TAG OUT PROGRAM) Washington State University Tri-Cities (all departments)

This training session covers electrical safety for unqualified persons. Unqualified persons are machine operators, operators of powered industrial

Lock Out/Tag Out Control of Hazardous Energy

DRAFT LOCKOUT/TAG OUT PROGRAM (CONTROL OF HAZARDOUS ENERGY)

Health and Fire Safety Review 2/15

Electrical. Version 1.0

Definitions found in several locations:

Electrical Safety PPT-SM-ELECTSFTY V.A.0.0

CONTROL OF HAZARDOUS ENERGY LOCKOUT/TAGOUT PROGRAM

THE OSHA LOCK-OUT/TAG-OUT STANDARD

LOCKOUT / TAGOUT PROGRAM

Electrical Safety Work Practices

LOCKOUT/TAGOUT PLAN August 2015

H. Control of Hazardous Energy: Lockout/Tag Out

LOCKOUT/TAGOUT PROGRAM

Lockout Tagout Program

ELECTRICAL SAFETY. Unsafe work practices near electricity can kill you! You are responsible for protecting yourself from electrical shock.

University of Arkansas Office of Environmental Health and Safety

DUQUESNE UNIVERSITY LOCKOUT/TAGOUT PROGRAM

Lockout/Tagout Program

Lockout/Tagout - Control of Hazardous Energy Program

Elements of a Lockout/Tagout Program OSHA

Gettysburg College. Energy Control Program

Electrical Safety Program

Lock Out - Tag Out Safety Program

Lockout/Tagout Program Occupation Safety & Health Standards for General Industry 29 CFR

University of Vermont Department of Physical Plant Burlington, Vermont

Health, Safety, Security and Environment

Lockout/Tagout Training Overview. Safety Fest 2013

SAFETY DIRECTIVE 2.0 DEPARTMENTS AFFECTED. This Administrative Directive shall apply to all Town of Marana departments and employees.

Hazardous Energy Program Lockout/Tagout

DuPage County Environmental, Safety, Health & Property Loss Control Program Hazardous Energy Control (Lockout/Tagout)

CONTROL OF HAZARDOUS ENERGY (LOCKOUT/TAGOUT)

Health & Safety Policy and Procedures Manual SECTION 6 ELECTRICAL SAFETY / CONTROL OF HAZARDOUS ENERGY

CONTROL OF HAZARDOUS ENERGY IN THE WORKPLACE

LOCKOUT/TAGOUT PROGRAM

PAGE 1 OF 7 HEALTH, SAFETY & ENVIROMENTAL MANUAL PROCEDURE: S230 Lock-Out Tag-Out (LOTO) Program REV 4.0 8/13/2012

Lockout / Tagout Safety Program

E2.14 Control of Hazardous Energy. Effective Date: 03/01/2018

Lockout / Tag out Program

2. The purpose of this program is to achieve the following objectives:

Control of Hazardous Energy Lockout / Tagout Program

Safety Manual: Hazardous Energy. January, 2017

1 Purpose. 2 Responsibilities. 3 Policy Content ENVIRONMENTAL, HEALTH AND SAFETY STANDARDS. TITLE: CONFINED SPACE ENTRY Document Number: *

RiskTopics. Lockout/Tagout October 2017

Hazardous Energies Control and Lockout/Tagout Program

230-LOCKOUT/TAGOUT PROGRAM

Lockout Tagout Policy

PALM BEACH STATE COLLEGE PERSONAL PROTECTIVE EQUIPMENT (PPE) JOB HAZARD ASSESSMENT

University of Tennessee Safety Program

Ground Fault Protection on Construction Sites

MISSOURI UNIVERSITY OF SCIENCE & TECHNOLOGY Procedure: 3.6

General Requirements of the NEC Advanced Course. Building Officials and Inspectors Educational Association

OKLAHOMA CITY COMMUNITY COLLEGE CONTROL OF HAZARDOUS ENERGY PROGRAM. Environmental Health and Safety. Established:

CONTROL OF HAZARDOUS ENERGY (LOCKOUT/TAGOUT) PROGRAM

Electrical Safety. Unqualified Worker

Electrical Safety For Managers Updated For E. ElectricalTrainingPro.com

Control of Hazardous Energy Program (Lockout/Tagout)

SAINT MARY S COLLEGE OF CALIFORNIA STANDARD HAZARDOUS ENERGY CONTROL PROGRAM INCLUDING LOCKOUT/TAGOUT. Prepared by

Lockout/Tagout Safety Policy

Lockout/Tagout. Page. Introduction. Purpose. 2 Background. 2 Who s Covered?... 3 Responsibilities. 3 Explanation of Key Terms. 4.

PART Q CONTROL OF HAZARDOUS ENERGY (LOCKOUT-TAGOUT)

DREW UNIVERSITY FALL PROTECTION PROCEDURE (DRAFT 12/11)

Facilities Management

: Electric Power Generation, Transmission, and Distribution. Region IV - OSHA

THE UNIVERSITY OF NORTH CAROLINA

List all key terms and acronyms used in the procedure, and their definitions.

Lockout Tagout Program

Lockout/Tagout Manual

SAMPLE WRITTEN PROGRAM for Control of Hazardous Energy LOCKOUT TAGOUT

WESTERN CONNECTICUT STATE UNIVERSITY LOCKOUT/TAGOUT PROCEDURE S-107

LOCKOUT/TAGOUT PROGRAM

LO/TO LOCKOUT/TAGOUT PROGRAM

Management Plan for Confined Spaces

Welding With Arc Welding Equipment

Product Information Report Lockout/Tagout Hazardous Energy Control

Lockout/Tagout Program

LOCK OUT \ TAG OUT PROGRAM

PALM BEACH STATE COLLEGE PERSONAL PROTECTIVE EQUIPMENT (PPE) JOB HAZARD ASSESSMENT

Energy Control. Suite 2A, 55 Frid Street Hamilton, ON L8P 4M3 office: cell:

Lockout/Tagout Plan Environmental Health & Safety Office July 2017

MARIPOSA COUNTY LOCKOUT/TAGOUT PROGRAM

Transcription:

Page #: 1 of 8 Last Reviewed/Update Date: 3/25/09 Electrical Safety Management for Facility / Operations Work Environments 1. Purpose / Background Purpose: The purpose of this SOP is to describe requirements and procedures relative to management of electrical hazards to which MIT operations support and facilities employees are potentially exposed in the course of installation, repair, maintenance, or troubleshooting ( work on ) electrical equipment, devices, and circuits. EHS and the MIT campus in general, have implemented an environment, health and safety management system (EHSMS) to address environmental and occupational safety risks. This SOP is part of a manual which forms the basis of the EHSMS. In order to ensure compliance with these requirements, EHSMS processes are expected to include this SOP as indicated or as otherwise appropriate. Background: Electrical shock hazards are common throughout the various activities undertaken by facilities support operations and should be managed effectively through various measures. Safe work practices should be understood and practiced by those who work on electrical equipment or circuits. The consistent implementation of risk and safety management policy is required and is the focus of this SOP. In addition, OSHA regulates workplace electrical hazards as identified in the References section of this SOP. These are the primary focus and objective of this SOP. 2. Scope This scope of this SOP primarily affects the MIT Department of Facilities (hereinafter referred to employees DOF, or Facilities ) regarding management of electrical safety hazards reasonably expected to be found in operational working environments. This SOP affects EHS functions such as program development, training development, and the EHSMS in order to manage conformance with requirements relative to MIT DOF employees who are engaged in any installation, repair, maintenance, or troubleshooting who, in the course of their work can be reasonably expected to perform tasks on or near exposed electrical equipment at greater than 50 volts AC, where conductive un-insulated or unshielded parts of the circuit are present. Facilities groups or projects that hire contractors to work on electrical equipment, devices, or circuits are required to implement the Contractors section of this SOP. Electrical safety hazards present in research-related work environments or projects are addressed in a separate SOP (Electrical Safety Management for Research Work Environments). Laboratory design, redesign, or modification, requires the assistance of topic experts, e.g., regulatory, code enforcement, engineering, and others, to ensure that all appropriate electrical safety hazards and controls are identified, evaluated, and managed. It is not intended to provide guidance for contractors or for repair or maintenance staff. Review or use of this SOP does not qualify an employee or student to work on electrical equipment.

Page #: 2 of 8 Last Reviewed/Update Date: 3/25/09 3. Prerequisites Generally, a qualified EHS professional with adequate experience in the relevant regulatory standards, industry standards, and understanding of electrical safe work practices may implement and monitor the requirements of this SOP. In addition, good familiarity with DOF operations and organization is desirable. Only Qualified (see Definitions, Section 10) employees may work on or near electrical equipment which contain greater than 50 volts AC, wherever conductive parts of the circuit are exposed during work on or near the equipment. With regard to work practices for electrical safety, MIT DOF employees who hold State licenses to do electrical work and who have completed practical work experience are considered Qualified as a function of their professional certification and practice. MIT DOF employees whose work requires potential exposure to the hazards described in Scope (above) that are not licensed electricians are considered a primary target group for this SOP. In order to become Qualified to work on or near exposed, live circuits between 50 volts and 400 volts, the employee must complete the requirements for training within MITs EHSMS and described within this SOP, and sufficient supervised practical work with Qualified electrical staff. Training: Employees who require Qualified status as described in Scope must complete electrical safety training prior to working independently on activities covered by this SOG. Limitations: The SOP is not designed to cover all electrical or safety hazards an employee may encounter, nor the measures to reduce the hazards. Additional guidance to identify, evaluate, and control electrical hazards can be obtained through consultation with the EHS s safety and industrial hygiene staff, or the Department of Facilities. Installation, modification, or repair of building electrical systems are not permitted by employees who become Qualified as a result of implementation of this SOP. 4. Guidelines Guidance and recommendations for basic good work practice can be found in the References section below. EHSMS Roles and responsibilities of EHS relative to the EHSMS can be found in the EHMS manual. Generally, with respect to MIT DOF, the EHS Coordinator for DOF will ensure that specified job tasks or positions are evaluated with respect to electrical hazards as described in Scope. Based on this evaluation, these employees will be required to participate in the training and implement respective safe work practices. 5. Roles & Responsibilities 5.1. Employees shall: 5.1.1 Participate in safety training as required by the EHSMS and DOF supervisory requirements for related tasks/work. 5.1.2 (DOF supervisors) Review the electrical SOP and follow its guidance.

Page #: 3 of 8 Last Reviewed/Update Date: 3/25/09 5.1.3 Contact the EHS and/or the Department of Facilities for guidance, with questions, or when unsafe electrical hazards are recognized or suspected. 5.2 Department of Facilities/EHS coordinator shall: 5.2.1 The EHS Coordinator for DOF will ensure that specified job tasks or positions are evaluated with respect to electrical hazards as described in Scope. 5.2.2 Maintain a list of qualified Department of Facilities personnel who are capable of working independently within the scope of this SOP. 5.2.3 (Supervisory and employees) Repair or remove defective or unsafe electrical equipment. 5.2.4 Whenever feasible, control hazardous energy sources through application of MIT s Lock-out/Tagout procedures when affected employees will service or maintain equipment or systems that contain hazardous energy. (Note: As used here, affected employee means: An employee whose job requires him/her to operate or use a machine or equipment on which servicing or maintenance is being performed under lockout or tagout, or whose job requires him/her to work in an area in which such servicing or maintenance is being performed. OSHA s lock-out/tag-out standard 29 CFR 1910.147.) Note: Employees covered by this SOG, e.g., non-electrical trained Department of Facilities employees, are not permitted to perform lock-out/tag-out procedures. 5.2.5 Verify that equipment has been effectively de-energized in accordance with MIT s Lock-out/Tagout procedures unless Department personnel are trained, qualified, and authorized by the EHS and Department of Faculties to perform equipment/systems lock-out/tag-out procedures. 5.3. EHS shall: 5.3.1 Work with the Department of Facilities to evaluate an employee s capabilities to understand safe electrical work practices, as outlined, herein, and qualify the employee to work independently. 5.3.2 Maintain a list of personnel trained on safe electrical work practices. 5.3.3 Maintain, update, and reissue the Facilities Electrical Safe Operating Guide. 5.3.4 Periodically offer the required training courses for Qualified work as required in OSHA 1910.330 through 335. Courses may be offered for Basic or Advanced electrical hazards based upon the working experience and knowledge of employee. 5.4 Contractors Electrical Safety Electrical service, repair, and maintenance contractors shall provide the DLC that they are contracting with, evidence or assurance of the status of all employees, with respect to OSHA requirements for Qualified and Authorized staff. Contractors shall ensure that employees assigned to work in DLCs have licensure issued by Massachusetts for electrical trades work, and sufficient job experience for the work under contract. 6. Training Affected Facilities staff, as described in Scope and Prerequisites, must complete electrical safety training provided through the EHSMS. Generally, training requirements are determined by job position/title as well as determined through supervisor and the DOF EHS Coordinator. Upon successful completion of training and adequate supervised practical experience, the staff member may perform work on electrical circuits as described in Scope, using appropriate skills, knowledge, and as defined in OSHA s regulatory requirements. Only Qualified MIT staff may work on electrical equipment which have greater than 50 volts AC, wherever conductive parts of the circuit are exposed during work on or near the equipment. In order to

Page #: 4 of 8 Last Reviewed/Update Date: 3/25/09 become Qualified to work on or near live circuits between 50 volts and 400 volts, requirements for training within MITs EHSMS and described within this SOP, as well as sufficient practical work experience working with Qualified electrical staff must be completed. Staff should contact the EHS to register for training. Training is a one-time requirement and should be completed by new staff within 60 days of assignment to a new position which involves exposures as described in Scope above. High-voltage work (at greater than 400) is not covered in this SOP or by training given through the EHSMS. 7. Monitoring Requirements A periodic evaluation of a sample of Qualified employees should be done to determine if training requirements have been met or if additional safe work practices should become part of training and recommended safe work practices. 8. Record Management 8.1 Department of Facilities: Maintain a roster of qualified personnel and identify employees (new or transfer) who require training with respect to hazards identified in Purpose and Scope. Ensure that employees of DOF receive the appropriate training and work experience necessary to become Qualified where indicated. Participate in the requirements of the EHSMS with respect to inspections and training updates. 8.2 EHS : 8.2.1 Provide training with sufficient frequency to support DOF schedules. Maintain a roster of personnel trained on electrical safety work practices. 8.2.2 Maintain documentation of behavior-based assessments of qualified Department of Facilities personnel. 9. References This section should list any additional resources that may be useful in performing the procedures. These may include: 9.1 Standards OSHA Standards for General Industry, 29 CFR 1910., Subpart S, U.S. Department of Labor, Occupational Safety and Health Administration OSHA Standards for the Construction Industry, 29 CFR 1926. U.S. Department of Labor, Occupational Safety and Health Administration Massachusetts Electrical Code, 527 CMR 12.00 National Fire Protection Association; 70 and 70 E. 9.2 Other SOP/ SOGs SOP/SOGs referred to in any other section of this SOP should be listed here. Electrical Safety Management for Contractors

Page #: 5 of 8 Last Reviewed/Update Date: 3/25/09 Electrical Safety Management for Research Work Environments 9.3 Supplementary Documents Electrical Safety for Electrical Trades, NIOSH, Pub No. 2002-123. Electrical Safety Handbook Guidelines for the Massachusetts Institute of Technology William McShea DOF Contractor Policy 9.4 Basic safe work practices The following sections represent basic procedures, configurations, and practices that should be adhered to when working with electrical circuits or devices. This section does not represent training and should not be used in lieu of training as described in the EHSMS and above.] Standard Electrical Safety Practices: Observe the following practices when working with electricity or electrical equipment: Plug power equipment into wall receptacles with devices power switches in the off position. Unplug electrical equipment by grasping the plug and pulling. Do not use the cord to unplug equipment. Check the electrical outlet (receptacle) for missing or damaged parts, broken face plates or receptacle plastic, missing screws, loose plug tension, etc. Do not plug equipment into defective receptacles. Regularly evaluate wiring and equipment cords for fraying, cracking, or exposed inner wires (typically found where the cord and plug meet.) Check for damaged cord connections and defective cords clamps or grommets where the power cord enters the equipment or attach to the plug. Remove and discard: cheater plugs (devices that permit grounded, three-prong plugs to be inserted into two-prong receptacles); non-standard extension cords such as those with terminal junction box receptacles, or other jury-rigged equipment. Plug only one device into each receptacle outlet. Never over load circuits by using multi-outlet strips, boxes, or adapters. Contact MIT s Electrical Services if a circuit breaker or Ground Fault Circuit Interrupter (GFCI) unexpectedly trips, a wire or fuse box feels warm or a burning or electrical odor is noticed. These issues could indicate an electrical defect requiring repair to prevent hazard exposure, fire, etc. Recognize the difference between personnel and equipment protective devices. Over current protection devices, (e.g., circuit breakers, fuses, etc.), are designed to protect equipment and structures from fire, not people from electric shock. GFCIs are designed to protect people by detecting a ground fault and shutting down before an employee receives an electrical shock. See below. Ensure that high current consumer electrical equipment such as toaster ovens, blenders, etc. or other appliances are grounded or double insulated design. Identify the location and ensure accessibility to electrical circuit breaker panels, circuits and equipment disconnects controlling equipment, and work area lighting. Maintain a 36 clearance around all electrical panels or permanent electrical equipment installations. Ensure power cords are not draped over hot pipes, radiators, or sharp objects. Treat all exposed conductors, even when "de-energized", as if they are live until they are confirmed to be locked and tagged out-of-service. Never remove a lock or tag. Label each shut off or disconnect unless the circuit it controls is obvious.

Page #: 6 of 8 Last Reviewed/Update Date: 3/25/09 Use the right length, size (gauge) and type (service rating) of cord to prevent wiring overload. Refer to manufacturers limitations of use and determine current load that devices will create. Use circuits, cords, and outlets within capacity and use limitations. Use GFCI's where/when appropriate; See below. Never insert objects, (e.g., pencils, fingers, metal tools, paper clips, conductive debris, etc.) into receptacles or unused conduit openings in junction or circuit breaker boxes. Tag defective electrical equipment with a do not operate tag, remove from service, and either discard or provide to a qualified and authorized electrical repair person for maintenance, repair, or disposal. Emergency Assistance, Response, and Rescue: Consider the following action in the event of an employee contact with live electrical current: Shut off the electrical current if the victim is still in contact with the energized circuit. Call or have someone else call for Police, Fire, or Emergency Medical Services (EMS). If another person calls for EMS, have them return to verify that the call and contact was made. If you are unable to reach the main circuit switchgear (circuit breakers) quickly, pry the victim from the circuit with a non conductive object such as dry wood or plastic. Never touch or contact the victim Stay with the victim until emergency medical responders arrive. Do not leave the victim unless there is no other option. Once you know that the victim is no longer energized, call to the victim to see if s/he is conscious. If conscious, reassure them and tell the victim not to move. Quickly examine the victim for signs of: Unconscious: If the victim is unconscious, check for signs of breathing. While you do this, move the victim as little as possible. If the victim is not breathing, someone trained in CPR should begin artificial rescue breathing, and check to see if the victim has a pulse. Quick action is essential! To be effective, CPR must be performed within 4 minutes. Bleeding: If there is major bleeding, place a cloth over the wound and apply pressure. If the wound is in an arm or leg and continues bleeding, gently elevate the injured area while keeping pressure on the wound. Keep the victim warm and talk to him or her until EMS arrives. Ground Fault Circuit Interrupters (GFCI): GFCIs are designed to protect people from serious injury or death. A GFCI is a fast-acting device that detects a difference in current between two circuit conductors. If either conductor contacts an unintended electrical path (a situation known as a ground fault), the GFCI opens the circuit in a fraction of a second. Should a difference as small as 4 to 6 ma be detected, the GFCI is tripped and the current is shut off. GFCI's are usually in the form of a duplex receptacle. They are also available in portable and plug-in designs and as circuit breakers that protect an entire branch circuit. GFCI's can operate on both twoand three-wire ground systems. For a GFCI to work properly, the neutral conductor (white wire) must (1) be continuous, (2) have low resistance, and (3) have sufficient current-carrying capacity which is generally the case with a good condition circuit and outlet. GFCI's help protect from electrical shock by continuously monitoring the circuit. However, a GFCI does not protect from line-to-line hazards such as simultaneously touching two "hot" wires (240 volts) or touching a "hot" and neutral wire simultaneously.

Page #: 7 of 8 Last Reviewed/Update Date: 3/25/09 The National Electric Code (NEC) requires that GFCI's be used in the following: Receptacles located within 6 feet of a sink. Receptacles installed outdoors. Electrical use near water. Electrical equipment user is grounded (by touching grounded material). Circuits that provide power to portable tools or outdoor receptacles. Temporary wiring or extension cords are used. Functional Testing: Test GFCI's regularly by pressing the "test" button. If the circuit does not trip, the GFCI is faulty and must be replaced. Tag the receptacle and contact DOF. Indicate locations or equipment where GFCI are required by MIT but may not be appropriate, e.g., receptacles dedicated to refrigerators or other heavy equipment. Extension Cords: (See: 4.6, Flexible Cord and Cable; EHS s SOP, Guideline for Inspecting Extension Cords.) Use only three-wire, grounded extension cords and temporary electrical feeder units using NEMA grounded receptacles and plug caps. Cords and feeders must be of sufficient rating to transmit power required by tools, equipment, and machinery. Inspect extension cords before use and daily to ensure they are free of defects. See EHS s Guideline for Inspecting Extension Cords SOP. Use only one extension cord for each piece of equipment. Never use multiple extension cords (daisy chaining). Never repair damaged extension cords. If repairs are necessary, return to Electrical Services or remove the plug and discard in the trash. Replace damaged cords with cords meeting MIT extension cord safety criteria and approved by MIT. Contact the EHS for guidance. Prohibited Uses: Extension cords should not be: Used for more than about 3 months time Placed where they could create a trip or fall hazard. Used as a substitute for fixed wiring of a structure. Attached to building surfaces. Run through holes in walls, ceilings, or floors; or through doorways, windows, or similar openings. Concealed behind building walls or ceilings, or under floors or carpets. Used when damaged, e.g., missing ground pin, damaged, cracked, or spliced insulation. Used where inspection would be difficult, where damage would be likely, or where long-term electrical supply is needed. Other items to consider including (where applicable): Listing or labeling extension cords. Outdoor use. Different Voltages. Flexible Cords and Cables (e.g. extension cords, equipment electrical): Prohibitions: Flexible cords and cables may not be:

Page #: 8 of 8 Last Reviewed/Update Date: 3/25/09 Placed where they could create a trip or fall hazard. Used as a substitute for fixed wiring of a structure. Attached to building surfaces. Routed through holes in walls, ceilings, or floors; or through doorways, windows, or similar openings. Concealed behind building walls, ceilings, or floors. Used when damaged, e.g., missing ground pin, damaged, cracked, or spliced insulation. Used where frequent inspection would be difficult, where damage would be likely, or where long-term electrical supply is needed. Proper Flexible Wiring Use: Electrical cords supplement fixed wiring by providing the flexibility required for maintenance, portability, isolation from vibration, and emergency and temporary power needs. Flexible wiring can be used for extension cords or power supply cords. Power supply cords can be removable or permanently attached to the appliance. Electrical Equipment Clearance: Maintain a minimum working clearance of 36 inches on each side of electrical enclosures, e.g., circuit breaker boxes, electrical panels, etc. Working clearance may not be less than 30 inches wide in front of the covered electric equipment / enclosures. (Supplemental language: The space in front of electrical enclosures may not be used for storage. This access and working space shall be kept clear at all times for operation and maintenance personnel and may not be used for intermittent/incidental storage of nonpermanent equipment or furniture, which could interfere with ready access to the electric equipment in the event of an emergency.) 10. Definitions Authorized : Trained by MIT s EHS on electrical safety principles and practices and control of hazardous energy methods and techniques, and authorized by MIT s Electrical Services (Department of Facilities) and EHS to perform lock-out/tag-out and electrical installation, modification, repair, replacement, or rehabilitation. Qualified Person : A person trained through the MIT s EHSMS on electrical safety principles and practices, and authorized by his/her supervisor to have the skills, knowledge and abilities to safely perform the work to which he/she is assigned (expected to work on or near electrical equipment as described in this SOP). Work on or near exposed electrical conductors : Working in proximity to circuits or parts of circuits which, in a manner during the work task in question is not protected by normal configuration or insulation of the electrical parts or circuit. Work that involves tools or techniques that intentionally or otherwise could be reasonable expected to contact potentially conductive parts of the circuit are affected. This would include painting near circuit or circuit parts where normal coverings are removed or missing, installation or repair of non electrical parts or systems near exposed or uncovered electrical panels, and work within electrical enclosures for testing, repair, or modification of any part of the device or system.