COOPER POWER SERIES. 200 A 15/25 kv class elbow installation instructions. Deadbreak Apparatus Connectors MN650042EN

Similar documents
COOPER POWER SERIES. 200 A 15/25 kv class deadbreak straight connector installation instructions. Deadbreak Apparatus Connectors MN650043EN

COOPER POWER SERIES. 200 A 15, 25, and 35 KV class insulated standoff bushing installation instructions. Loadbreak Apparatus Connectors MN650039EN

COOPER POWER SERIES. 600 A 15, 25 and 35 kv class bushing adapter installation instructions. Deadbreak Apparatus Connectors MN650058EN

DT400/436 Tee Connector Installation Instructions

COOPER POWER SERIES. 200 A 15, 25, and 35 kv class portable feedthru installation instructions. Loadbreak Apparatus Connectors MN650037EN

COOPER POWER SERIES. DE250 deadbreak elbow connector installation instructions interface A. Screened Separable Connectors MN650025EN

COOPER POWER SERIES. DS250 deadbreak straight connector installation instructions interface A. Connectors MN650027EN

COOPER POWER SERIES. 600 Ampere Deadbreak Grounded Standoff Bushing 15 & 25 kv and 35 kv Class Installation Instructions. Bushings MN650045EN

COOPER POWER SERIES. 600 A 15, 25, and 35 kv class PUSH-OP bushing adapter cap installation instructions. Deadbreak Apparatus Connectors MN650050EN

COOPER POWER SERIES. 200 A 35 kv class LE series elbow installation instructions. Loadbreak Apparatus Connectors MN650010EN

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with optional integral jacket seal installation instructions. Loadbreak Connectors MN650008EN

200 A, 15 and 25 kv class loadbreak bushing insert installation instructions

COOPER POWER SERIES. Series winding ratio test procedure instructions. Voltage Regulators MN225060EN. 120 Vac VOLTMETER

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with integral jacket seal* for use on tape and wire shielded cable installation instructions

COOPER POWER SERIES. UltraSIL Polymer-Housed Distribution-Class MOV Surge Arrester Installation Instructions. Surge Arresters MN235006EN

COOPER POWER SERIES. EL Bay-O-Net Current-Limiting Fuse Installation Instructions. Fusing Equipment MN132023EN

COOPER POWER SERIES. Manual or Hostick Operable, Padlockable 150 A Tap-Changer Switch Installation Instructions. Tap-Changer Switch MN800015EN

S Loadbreak Apparatus Connectors WARNING: WARNING:

COOPER POWER SERIES. D-73P3 bypass switches installation instructions. Switches MN008005EN. Effective April 2016 Supersedes S June 2013

COOPER POWER SERIES. QD8 Quik-Drive tap-changer VR or VL reversing switch stationary contact assembly kit number A48 installation instructions

Effective March 2015 Supersedes S August 2002

COOPER POWER SERIES. Under-oil arrester disconnector installation/operation instructions. OEM Equipment MN800010EN

DAI630TB2669 Dead Front Arrester Installation Instruction

COOPER POWER SERIES. 600 A, 15, 25, and 35 kv Class Cleer Grounding Elbow Installation Instructions. Loadbreak Apparatus Connectors MN650056EN

Effective May 2017 Supersedes July 2009 (S ) 600 A 35 kv Class T-OP II connector assembly installation instructions 200 A PROTECTIVE CAP LRTP

COOPER POWER SERIES. VariSTAR Storm Trapper high energy MOV arrester installation instructions. Surge Arresters MN235017EN

COOPER POWER. SERIES VariSTAR type composite light-duty under-oil (CLU) MOV arrester installation instructions. Surge Arresters MN235023EN

COOPER POWER SERIES. 50 A 2:1 series multiple (dual voltage) switch cap/wrench, lever or hotstick operable handles installation instructions

COOPER POWER SERIES. 600 A 35 kv class PUSH-OP deadbreak connector installation instructions. Deadbreak Apparatus Connectors MN650052EN

COOPER POWER SERIES. UltraSIL polymer-housed VariSTAR surge arrester IEC for MV systems to 36 kv installation instructions

600 A 35 kv class PUSH-OP deadbreak connector installation instructions

COOPER POWER. SERIES VariSTAR type AZE station class surge arresters installation and maintenance instructions. Surge Arresters MN235022EN 0.

Effective January 2017 Supersedes July 2011 (I ) VariSTAR Type AZG4 Surge Arresters Installation and Maintenance Instructions

COOPER POWER SERIES. Operation Counter Replacement Instructions. Reclosers MN280047EN. Effective May 2016 Supersedes S December 2003

S Surge Arresters

COOPER POWER SERIES. Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions. Reclosers MN280051EN

COOPER POWER SERIES. VFI SF6-insulated vacuum fault interrupter installation, operation and maintenance instructions. Switchgear MN285004EN

Installation Instructions for the Walking Beam Interlock for Eaton EHD, FDB, FD, HFD, FDC, FW, HFW, FWC, Circuit Breakers and Molded Case Switches

Effective May 2017 Supersedes August 2005 (S )

ESA Elbow Sealing Adapter Kit

ROPV R40 E Series User Manual

Norrsken Family Booklet

Media-Isolated Mag Plus Probe Low Pressure-ISO Kit

Medium voltage standard-duty, heavyduty, and extreme-duty single-phase, unfused capacitor units and accessories

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

DEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers

S Surge Arresters. Handling and Storage. Standards. Acceptance and Initial Inspection

Instruction Manual. Model TC1-S TopSide Clamp. top side clamp. For your personal safety READ and UNDERSTAND instructions before using tools.

Operating Instructions for BAIR22-6 AIR-POWERED CRIMPING TOOL

750 Cable Cutter INSTRUCTION MANUAL

The Outer Seal is highly abrasion resistant and provides mechanical stiffness to the splice in order to better match the cable stiffness.

Instruction Manual. PE Pipe Squeeze-off Tool Model TR650

Booster Pump PB4-60 Replacement Kits

INTRODUCTION BILL OF MATERIALS SPECIFICATIONS & TOOLS PROCEDURES OPERATION OF SEATPOST GIANT LIMITED WARRANTY

TECHNICAL BULLETIN PINPOINT CONDUIT COUPLING AND SPLICING RECOMMENDATIONS

USER MANUAL FLOW SELECTOR PM1000 SAVE THESE INSTRUCTIONS. Federal (USA) law restricts this device to sale by or on the order of a physician.

DK ton, Double-acting, Die-type Crimping Tool

DISASSEMBLING & REASSEMBLING CARTRIDGE INSTALLING SEATPOST ON BIKE

3" UC Ultra-Chuck Durable Lightweight Air Inflated Bladder Chuck Operation/Repair Manual. (76.2 mm) DOUBLE E COMPANY, INC.

SIX R (P ) AND SEVEN R (P ) POSITION CYLINDERS Service Information

Model No Product Name Handpiece Only Complete System

OPERATING and MAINTENANCE INSTRUCTIONS MAXIS Grips

Operating Instructions

Inspection Recommendations

APPENDIX D HYDRO-VAC

Operation Manual Enabling Pole-Top Communication Via the TripSaver II Magnet Tool

S Vacuum Switches. Contents. Type VCS-1 Single-Phase Vacuum Capacitor Switch Installation and Operation Instructions

Hydraulic Punch Drivers

STYLE 3414/3416 & 3421/3423 Apollo Monitor with Foldaway Legs OPERATING & MAINTENANCE INSTRUCTIONS

Installation and Operating Instructions for Automotive Winch Synthetic Rope

INSTRUCTION MANUAL MP4AR Remote Convection Gauge Range: 1 x 10-3 Torr to 1 x 10+3 Torr

Triple Tine Mechanical Grapple

ULTRA HIGH PRESSURE PAINT GRATE CLEANER FCT-JS OPERATION AND MAINTENANCE MANUAL

Accu-Tab Systems 1000 Series by Axiall Corporation

SANTA CRUZ BICYCLES Cable Routing Procedure MY17

Instruction Manual LIMITED 1 YEAR WARRANTY. Hydraulic Punch Driver Read this material before using this product.

12 Inch Barn Light. Owner s Manual

MECH-TECH SYSTEMS CCU MODEL FOR GLOCK PISTOLS

Installation, Operation, and Maintenance Manual

GM-7000 Series CE Approved Gas Control Valve

Permanent Roof Anchors

Hydraulic Punch Drivers

Angled Sign Light with Shade

REL-510H WARNING NOTICE 12 TON SINGLE ACTING REMOTE HYDRAULIC CRIMPING HEAD

Teledyne Oil & Gas North Williamson Blvd. Daytona Beach, FL USA (phone) (fax)

Compact Triple Cabinet Outlet Station Model Installation and Operating Instructions

Pressure Dump Valve Service Kit for Series 2300 Units

Instructions for Installing and Operating Clark Reliance EA101 Series Levalarm

Compact Triple Cabinet Outlet Station Model B Installation and Operating Instructions

INSTRUCTION MANUAL. Includes: OPERATION SETUP USE & CARE SERVICE. SPORTS ATTACK LLC

BUTTERFLY VALVES Series 800

This document to be used with Hurley traditional Davits

GALISO SOAP OPTION FOR PCT-ADW-D

Pressure Relief Valve Instruction Manual

Sterile Visual Flow Indicator

GASGUARD VENT LINE3 Ammonia Sensor OPERATING & INSTALLATION MANUAL

Quadratec Delrin Door Hinge Pin Bushings for Jeep Wrangler YJ & TJ 94-06

UE- 90- X X X X X X O P E R AT I N G M A N UA L 0 TO 90 HYDRAULIC UPENDER

Vertical Lifeline. Ladder Climb. User Instructions. 3M Occupational Health and Environmental Safety. Fall Protection Equipment

USER S GUIDE & SAFETY MANUAL USER S GUIDE & SAFETY MANUAL Duct Rodder

Transcription:

Deadbreak Apparatus Connectors MN650042EN Effective February 2017 Supersedes December 2009 (S550-10-1) 200 A 15/25 kv class elbow installation instructions COOPER POWER SERIES

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. i

Contents DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY... i Safety for life... iii Safety information... iii Safety instructions... iii Product information.... 1 Introduction...1 Additional information............................................................................1 Acceptance and initial inspection...1 Handling and storage...1 Quality standards................................................................................1 Installation instructions.... 2 Preparation of concentric neutral cable...3 Elbow and probe contact installation...4 ii

! SAFETY FOR LIFE Safety for life Eaton s Cooper Power series products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high-voltage lines and equipment and support our Safety For Life mission.! SAFETY FOR LIFE Safety information The instructions in this manual are not intended as a sub stitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians, who are familiar with this equipment should install, operate and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high- and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as flash clothing, safety glasses, face shield, hard hat, rubber gloves, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements:! DANGER Indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a hazardous situation which, if not avoided, could result In death or serious injury. CAUTION Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. CAUTION Indicates a hazardous situation which, if not avoided, could result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with high voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high- and low-voltage lines and equipment. WARNING Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. WARNING This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply may result in death, severe personal injury and equipment damage. WARNING Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. iii

WARNING All associated apparatus must be de-energized during installation, operation and/or maintenance. Product information Introduction The Eaton Cooper Power series Deadbreak Elbow Connector is a fully-shielded and insulated plug-in termination for connecting underground cable to transformers, switching cabinets and junctions equipped with deadbreak bushings. The elbow connector and bushing comprise the essential components of all deadbreak connections. Wide cable ranges are sized to accept cables insulated at either 175 mil or 220 mil within a given conductor size. The wider cable ranges increase installation flexibility. The coppertop (bimetal) compression connector is a standard item to transition from the cable to the deadbreak probe. An aluminum crimp barrel is inertia-welded to a copper lug. The aluminum barrel makes the connector easy to crimp and the copper lug ensures a reliable, tight, cool operating connection with the probe contact. CAUTION The 200 A Deadbreak Elbow Connector is designed to be operated in accordance with normal safe operating procedures. These instructions are not intended to supersede or replace existing safety and operating procedures. The elbow connector should be installed and serviced only by personnel familiar with good safety practices and the handling of high-voltage electrical equipment. Read this manual first Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment Additional information These instructions cannot cover all details or variations in the equipment, procedures, or process described nor provide directions for meeting every possible contingency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for the user s purpose, contact your Eaton representative. Figure 1. 200 A, 15/25 kv class de225 deadbreak elbow connector Acceptance and initial inspection Each deadbreak connector is completely assembled, inspected and tested at the factory. It is in good condition when accepted by the carrier for shipment. Upon receipt of a deadbreak connector, inspect the connector thoroughly for damage and loss of parts incurred during shipment. If damage or loss is discovered, file a claim with the carrier immediately. Handling and storage If the deadbreak connector is to be stored for an appreciable time before installation, provide a clean, dry storage area. Locate the connector so as to minimize the possibility of physical damage. Quality standards ISO 9001:Certified Quality Management System. 1

Step 1 Step 2 Step 3 Step 4 1 15/ 16 " (49.2 mm) Conductor Wire brush conductor Insulation shield Insulation 1/ 8 " Bevel 5 3 / 4 " (145 mm) 8 1 / 2 " (216 mm) Bend neutral wires down and out of the way Jacket seal Installation instructions Cable stripping and scoring tools, available from various tool manufacturers, are recommended for use when installing deadbreak elbows. After preparing the cable, the elbow housing is pushed onto the cable. The probe contact is threaded into the coppertop connector using the supplied installation tool or an approved equivalent. Use a hotstick to perform installation and removal operations. Complete elbow kit includes: Elbow Body with Test Point Coppertop Compression Connector Probe Contact Probe Installation Tool Bail Assembly Silicone Lubricant Instruction Sheet Tools/Accessories needed: Tape Measure Wire Brush Knife Cable Stripping Tool Crimping Tool Cable Cleaner Cable Cutters Emery Cloth 2

Preparation of concentric neutral cable Step 1 Measure down from top of the cable a minimum of 8 1/2. Remove cable jacket (if jacketed cable is used) to expose neutral wires. Unwind neutral wires. NNote: If an Eaton Cooper Power series jacket seal is used, follow instructions supplied with the jacket seal kit. Step 2 Measure down from top of the cable 5 3/4. Remove the insulation shield. Take care not to nick or gouge insulation. Step 3 Measure down from the top of the cable 1 15/16. Remove the insulation and conductor shield to expose the bare conductor. Take care not to nick the conductor. Place a 1/8 bevel on the insulation to ease installation. Step 4 If not already in place, apply a suitable jacket seal over the jacket and exposed neutral wires. Proceed to Step 5. Step 5 Step 6 Step 7 Clean and lubricate First crimp placed below knurl Clean excess inhibitor grease Attach ground lead to elbow ground tab Clean and lubricate Clean and lubricate cable entrance Attach lead to system ground 3

Elbow and probe contact installation Step 5 Clean the exposed conductor using a wire brush. Place the coppertop (bimetal) connector on the conductor. Make sure threaded hole in connector faces the apparatus bushing. Crimp the connector in place using a tool and die combination listed in Table 1. Start crimping just below the knurled line and rotate each successive crimp to prevent bowing. Do not overlap crimps. Place as many crimps on the connector as will fit. Step 6 Clean excess inhibitor grease from coppertop connector by wiping toward threaded eye. Clean insulation with a lint free cloth saturated with a cleaning solution. Wipe insulation toward insulation shield. Apply a thin coating of grease to the insulation. Clean and lubricate the cable entrance of the elbow. Place elbow on cable. With a twisting motion, push elbow onto cable until threaded eye of coppertop connector is visible in the elbow interface. Step 7 Use the provided hex-probe installation tool to install probe contact into the compression connector. Take care not to cross-thread probe. Proper torque is applied when the tool achieves a 180 bend. NNote: If a different installation tool is used it must apply a torque of 60-80 in-lbs to achieve proper installation. Attach a ground lead to the grounding eye of the elbow. Step 8 Clean the elbow and bushing interface and apply a thin uniform layer of silicone lubricant to both interfaces. Push the elbow onto the bushing until it is fully seated. Hook the legs of the bail assembly into the tabs of the bushing clamp. Thread the eyebolt of the bail assembly tight against the back of the pulling eye of the elbow. (See Figure 2.) Table 1. Crimp chart Connector 5/8" Diameter 3/4" Diameter Conductor size No. 4 Thru 2/0 stranded 3/0-4/0 Stranded TOOL Y34 Y35 OR Y39 MD6 Y34 Y35 OR Y39 MD6 A243 U243 UBG W243 WBG U247 U247 U467 W247 Burndy DIE BG A25AR U25ART U687 W687 A27AR U27ART NOSE TOOL UT-3 UT-5 UT-15 UT-5 UT-15 Thomas & betts DIE 5/8" TV 54 H TV 66 TOOL O WH1, WH2 or WH3 O WH1, WH2 or WH3 Kearney 5/8" DIE NOSE 9/16" 9/16" 737 747 737 747 ACA Conductor TOOL 12A 12A Accessories (ALCOA) DIE B24 EA B39 EA Anderson Tool VC-5, VC-6 VC-5, VC-6 Edison Electric Institute Reference 8A 10A 4

Stainless steel bail Figure 2. De225 deadbreak elbow connector dimensional information WARNING This is a Deadbreak Connector System. All associated apparatus must be de-energized before and during installation and/or operation. 5

This page intentionally left blank. 6

This page intentionally left blank. 7

! SAFETY FOR LIFE Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No. MN650042EN (Replaces S550-10-1 Rev 00) February 2017 Eaton is a registered trademark. All trademarks are property of their respective owners. For Eaton s Cooper Power series product information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.