CP10 Sensor Installation and Maintenance Instructions

Similar documents
Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

TP1 and TP2 Temporary Cone Shaped Strainers

DF1 and DF2 Diffusers

MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap

DCV10 Stainless Steel Disc Check Valve for use with Condensate Pumps

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

TSS21 Sealed Thermostatic Steam Tracer Trap

Fig 12, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

AVC32 Carbon Steel Air Vent for Steam Systems

Fig 1, Fig 12, Fig 13, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

PV4 and PV6 Piston Valves

BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications

FV Flash Vessel Installation and Maintenance Instructions

Dri-Line Mk3 Monnier Compressed Air Drain Trap

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators

Dri-Line Mk2 Spirax-Monnier Compressed Air Drain Trap

TA10A and TA10P Steam Tracing Temperature Control Valves Installation and Maintenance Instructions

KBV21i and KBV40i Air Actuated Boiler Blowdown Valves

DCV1, DCV3 and DCV3LT Disc Check Valves Installation and Maintenance Instructions

AE30 Automatic Air Eliminators / Air and Gas Vents for Liquid Systems

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Dial Adjustment)

CVS10 Sanitary Check Valves

IFTGS14 Ball Float Steam Trap ½" and ¾" with Integral Spiratec Sensor

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Knob Adjustment)

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions

MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection

AE14 Automatic Air Vents for Liquid Systems Installation and Maintenance Instructions

DCV6 Disc Check Valve

AVM7 Stainless Steel Thermostatic Air Vent

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors

SRV66 Sanitary Pressure Reducing Valve

MF2M Monnier Miniature Compressed Air Filter

HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions

FTGS14 Ball Float Steam Trap DN15 (½") to DN25 (1")

CS10-1 Stainless Steel Clean Steam Separator

LP31 Level Probe. 1. Safety information. 2. General product information. 3. Installation. 4. Wiring. 5. Maintenance

M10HTi ISO Tobacco Ball Valve Screwed, SW, BW and Flanged versions

BT6-B Sanitary Balanced Pressure Thermostatic Steam Trap

Manual Actuated Boiler Blowdown Valves

IX1 Spirax-Monnier International Compressed Air Filter Installation and Maintenance Instructions

Fig 3, 7, 33, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers

CA44, CA44S, CA46 and CA46S Air and Gas Traps

M33F ISO, M33S ISO and M33V ISO Ball Valves Installation and Maintenance Instructions

BCV31 DN40 - Blowdown Control Valve

BTM7, BTS7 and BTS7.1 Stainless Steel Thermostatic Clean Steam Traps

Spirax Compact FREME Flash Recovery Energy Management Equipment

APT14, APT14HC and APT14SHC Spares 2

BCV31 DN20 - Blowdown Control Valve

TDC46M, TDS46M and UTDS46M Thermodynamic Steam Traps with Maintainable Seat Installation and Maintenance Instructions

Airodyn, BRair and BRoil Compressed Air Drain Traps

M70i ISO and M80i ISO Stainless Steel Ball Valves for Sanitary Systems Installation and Maintenance Instructions

TW Temperature Control Valve

S and SF Inverted Bucket Steam Traps

ML3M Monnier Miniature Compressed Air Lubricator

BPT13 Balanced Pressure Thermostatic Steam Traps

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats

PC10HP Pipeline Connector (ASME 600)

Type 130 and HL10 'Safeguard High Limit Control' Installation and Maintenance Instructions

Fig 7, 33, 33.1, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers Installation and Maintenance Instructions

FT53, IFT53, FT54, IFT54, FT57 and IFT57 Ball Float Steam Traps - DIN

MFP14-PPU (Vented) Automatic Packaged Pump Units

SA Control Valve types: BM, BMF, BX, SB, NS, KA, KB, KC (Normally open) BMRA, BMFRA, BXRA, SBRA, NSRA, KX, KY (Normally closed)

BRV71 and BRV73 Pressure Reducing Valves

BDV1 and BDV2 Blowdown / Depressurisation Valves

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats Installation and Maintenance Instructions

SRV2S Pressure Reducing Valve

CA10S, CA14 and CA14S Air and Gas Traps

LP10-4 Level Probe. 1. Safety information. 2. General product information. 3. Installation. 4. Wiring. 5. Maintenance IM-P402-92

Vane Flow Switches Colima FLU Series

MPC1M, MPC2M and MPC2AM Monnier High Efficiency Compressed Air Filter / Regulators

QuickHeat TM Packaged Heat Exchanger Solutions

Spirax SafeBloc TM DBB3 Double Block and Bleed Bellows Sealed Stop Valve. 1. Safety information. 2. General product information. 3.

M111 Spiraflo Transducer

TD45 Thermodynamic Steam Trap Installation and Maintenance Instructions

STERI-TROL Clean Service 'S' Series Two-port Control Valves DN15 (½") to DN100 (4")

Thermocirc Installation and Maintenance Instructions

BDV60 Blowdown Vessel Installation and Maintenance Instructions

A3S Bellows Sealed Stop Valve Installation and Maintenance Instructions

SCA Series Inverted Bucket Steam Traps

AVS32 Stainless Steel Air Vent for Steam Systems Installation and Maintenance Instructions

BCVi43 Blowdown Control Valve

BSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

CA16 and CA16S-14 Air and Gas trap Installation and Maintenance Instructions

FT16 Ball Float Steam Trap Installation and Maintenance Instructions

1. General safety information. 2. General product information. 3. Installation. 4. Commissioning. 5. Operation. 6. Maintenance. 7.

Fig 1, Fig 12, Fig 13, Fig 14, Fig 16 and Fig 16L Strainers Installation and Maintenance Instructions

IP2M, IP2AM and IP2DM Monnier International Compressed Air Filter/ Regulators

PC3000, PC3001 and PC4000, PC4001 Pipeline Connectors

SRV461S and SRV463S Stainless Steel Direct Acting Pressure Reducing Valves

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

AE50S Automatic Air and Gas Vent for Liquid Systems Installation and Maintenance Instructions

FT43, FT44, FT46 and FT47 Ball Float Steam Traps Installation and Maintenance Instructions

TD10, TD52M and TD259 Thermodynamic Steam Traps Installation and Maintenance Instructions

BTD52L Thermodynamic Steam Trap Installation and Maintenance Instructions

BSA and BSAT Bellows Sealed Stop Valves Installation and Maintenance Instructions

Colima TOR Magnetic Level Switches

UBP32 Sealed Balanced Pressure Thermostatic Steam Trap for use with PC_ Pipeline Connectors Installation and Maintenance Instructions

FTC62 and FTS62 Ball Float Steam Traps Installation and Maintenance Instructions

595-K/L and 596-K/L Series Self Operated Valves Installation and Maintenance Instructions

Transcription:

4030150/9 IM-P403-26 EMM Issue 9 CP10 Sensor Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Maintenance 5. Spare parts Copyright 2017 IM-P403-26 EMM Issue 9 1 Printed in GB

1. Safety information Safe operation of these products can only be guaranteed if they are properly installed, commissioned, used and maintained by qualified personnel (see Section 1.11) in compliance with the operating instructions. General installation and safety instructions for pipeline and plant construction, as well as the proper use of tools and safety equipment must also be complied with. Do not install the probe outdoors without additional weather protection. Drain / vent holes must be kept clean - do not cover. 1.1 Intended use Referring to the Installation and Maintenance Instructions, name-plate and Technical Information Sheet, check that the product is suitable for the intended use / application. The products comply with the requirements of the European Pressure Equipment Directive 2014/68/EU and fall within category 'SEP'. It should be noted that products within this category are required by the directive not to carry the mark. i) The products have been specifically designed for use on steam and water, which are in Group 2 of the above mentioned Pressure Equipment Directive. The products use on other fluids may be possible but, if this is contemplated, Spirax Sarco should be contacted to confirm the suitability of the product for the application being considered. ii) Check material suitability, pressure and temperature and their maximum and minimum values. If the maximum operating limits of the product are lower than those of the system in which it is being fitted, or if malfunction of the product could result in a dangerous overpressure or overtemperature occurrence, ensure a safety device is included in the system to prevent such over-limit situations. iii) Determine the correct installation situation and direction of fluid flow. iv) Spirax Sarco products are not intended to withstand external stresses that may be induced by any system to which they are fitted. It is the responsibility of the installer to consider these stresses and take adequate precautions to minimise them. v) Remove protection covers from all connections and protective film from all name-plates, where appropriate, before installation on steam or other high temperature applications. 1.2 Access Ensure safe access and if necessary a safe working platform (suitably guarded) before attempting to work on the product. Arrange suitable lifting gear if required. 1.3 Lighting Ensure adequate lighting, particularly where detailed or intricate work is required. 2 IM-P403-26 EMM Issue 9

1.4 Hazardous liquids or gases in the pipeline Consider what is in the pipeline or what may have been in the pipeline at some previous time. Consider: flammable materials, substances hazardous to health, extremes of temperature. 1.5 Hazardous environment around the product Consider: explosion risk areas, lack of oxygen (e.g. tanks, pits), dangerous gases, extremes of temperature, hot surfaces, fire hazard (e.g. during welding), excessive noise, moving machinery. 1.6 The system Consider the effect on the complete system of the work proposed. Will any proposed action (e.g. closing isolation valves, electrical isolation) put any other part of the system or any personnel at risk? Dangers might include isolation of vents or protective devices or the rendering ineffective of controls or alarms. Ensure isolation valves are turned on and off in a gradual way to avoid system shocks. 1.7 Pressure systems Ensure that any pressure is isolated and safely vented to atmospheric pressure. Consider double isolation (double block and bleed) and the locking or labelling of closed valves. Do not assume that the system has depressurised even when the pressure gauge indicates zero. 1.8 Temperature Allow time for temperature to normalise after isolation to avoid danger of burns. If parts made from the PTFE have been subjected to a temperature approaching 260 C (500 F) or higher, they will give off toxic fumes, which if inhaled are likely to cause temporary discomfort. It is essential for a no smoking rule to be enforced in all areas where PTFE is stored, handled, or processed as persons inhaling the fumes from burning tobacco contaminated with PTFE particles can develop 'polymer fume fever'. 1.9 Tools and consumables Before starting work ensure that you have suitable tools and / or consumables available. Use only genuine Spirax Sarco replacement parts. 1.10 Protective clothing Consider whether you and / or others in the vicinity require any protective clothing to protect against the hazards of, for example, chemicals, high / low temperature, radiation, noise, falling objects, and dangers to eyes and face. IM-P403-26 EMM Issue 9 3

1.11 Permits to work All work must be carried out or be supervised by a suitably competent person. Installation and operating personnel should be trained in the correct use of the product according to the Installation and Maintenance Instructions. Where a formal 'permit to work' system is in force it must be complied with. Where there is no such system, it is recommended that a responsible person should know what work is going on and, where necessary, arrange to have an assistant whose primary responsibility is safety. Post 'warning notices' if necessary. 1.12 Handling Manual handling of large and / or heavy products may present a risk of injury. Lifting, pushing, pulling, carrying or supporting a load by bodily force can cause injury particularly to the back. You are advised to assess the risks taking into account the task, the individual, the load and the working environment and use the appropriate handling method depending on the circumstances of the work being done. 1.13 Residual hazards In normal use the external surface of the product may be very hot. If used at the maximum permitted operating conditions the surface temperature of some products may reach temperatures of 239 C (462 F). Many products are not self-draining. Take due care when dismantling or removing the product from an installation (refer to 'Maintenance instructions'). 1.14 Freezing Provision must be made to protect products which are not self-draining against frost damage in environments where they may be exposed to temperatures below freezing point. 1.15 Disposal Unless otherwise stated in the Installation and Maintenance Instructions, this product is recyclable and no ecological hazard is anticipated with its disposal providing due care is taken, except: PTFE: - Can only be disposed of by approved methods, not incineration. - Keep PTFE waste in a separate container do not mix it with other rubbish, and consign it to a landfill site. 1.16 Returning products Customers and stockists are reminded that under EC Health, Safety and Environment Law, when returning products to Spirax Sarco they must provide information on any hazards and the precautions to be taken due to contamination residues or mechanical damage which may present a health, safety or environmental risk. This information must be provided in writing including Health and Safety data sheets relating to any substances identified as hazardous or potentially hazardous. 4 IM-P403-26 EMM Issue 9

2. General product information 2.1 General product description The CP10 sensor is a conductivity probe specified for use in total dissolved solids (TDS) and conductivity control systems. It is a sealed unit consisting of a central stainless steel sensor tip, PEEK insulator, PTFE sealing ring, stainless steel body, disc springs and washer. There are two threads on the CP10 sensor: - The electrical end connection is threaded M22 to accept the PT2 plug tail. - The probe-tip end is threaded G3/8 to suit the appropriate sensor chamber. The unit is supplied with an S-type stainless steel gasket. Electrical connection is via an IP65 connector (supplied separately). The CP10 sensor and PT2 plug tail are intended for use with a low voltage limited power source. These are approved by Underwriters Laboratory as Listed accessories for use with Spirax Sarco controllers. Fig. 1 CP10 sensor 2.2 Pressure / temperature limits Body design Maximum pressure / temperature Designed for a maximum cold hydraulic test pressure of: PN40 32 bar g at 239 C (464 psi g at 462 F) 60 bar g (870 psi g) Minimum conductivity generally10 S / cm or 10 ppm, but see controller IMI. IM-P403-26 EMM Issue 9 5

3. Installation Caution: Do not install the sensor outdoors without additional weather protection. Fit the sensor chamber in a vertical or horizontal pipeline with suitable isolation valves to allow inspection / cleaning of the sensors. Reducers may be fitted if required. Flow can be in either direction. The sensors themselves must be horizontal. The TP20 has a taper thread, and may be installed using PTFE sealing tape if required. The CP10 sensor is provided with an S-type stainless steel gasket for sealing. PTFE tape may be used on the CP10 threads, but check that the resistance to earth is less than 1 after installation. Fit the sensors to the chamber and tighten to a torque of 60 N m (44 lbf ft). Fit PT2 plug tail (or other Spirax Sarco plug tail) to the CP10 sensor and tighten. Caution: Ensure the PT2 wire is not exposed to a temperature greater than 120 C (248 F). S20 sensor chamber S10 sensor chamber Fig. 2 Typical applications: CP10 sensor TP20 Temperature sensor PT2 (or PT3) plug tail S11 sensor chamber CP10 sensor Ensure resistance from probe body to pipework / boiler shell is less than 1. 3.1 Electrical installation Cabling should be installed in accordance with BS 6739 - Instrumentation in Process Control Systems: Installation design and practice or local equivalent. CP10 sensor Sensor pin PT2 plugtail Red wire to sensor pin Junction box (for connection to conduit) " BSP 24 mm A/F 25 mm A/F Nut Insulation Blue wire earthed via PT2 and CP10 Connect screen to earth (blue wire) Screen To blowdown controller Fig. 3 Wiring diagram 6 IM-P403-26 EMM Issue 9

4. Maintenance We recommend that the CP10 is removed for cleaning and inspection at least once a year, though the frequency of maintenance will depend on the quality and flowrate of the boiler water or condensate. - Isolate and depressurise the system, (or with the system empty), remove the CP10 sensor. - Inspect male and female threads for signs of damage, which may have occurred through overtightening, leading to torn threads or even localised cold welding (galling / picking up). If damage has occurred replace the CP10 sensor. - If after inspection there is no damage to the thread proceed to clean the sensor tip with fine wet-or-dry paper, and the insulator with a cloth or bristle (not wire) brush. - Inspect the insulator and sensor tip for erosion, damage, or pitting, and refit or replace as necessary. - Retighten the CP10 sensor to a torque of 60 N m (44 lbf ft). Note: Always fit a new gasket. 5. Spare parts The spare parts available are detailed below. No other parts are supplied as spares. Available spares Gasket Stock No. 0957191 Pack of 10 How to order spares Always order spares by using the description given in the column headed 'Available spares' and state which product they are for. Example: 1 off Gasket (pack of 10) for a Spirax Sarco CP10 sensor - Stock number 0957191. IM-P403-26 EMM Issue 9 7

8 IM-P403-26 EMM Issue 9