Mounting and Operating Instructions EB 3017 EN. Self-operated Regulators

Similar documents
Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Type Type Differential Pressure Regulators (opening)

Mounting and Operating Instructions EB EN. Self-operated Pressure Regulators. Type 2335 Excess Pressure Valve with pilot valve

Mounting and Operating Instructions EB 2555 EN. Self-operated Pressure Regulators. Pressure Reducing Valves Type 50 ES Type 50 EM.

Mounting and Operating Instructions EB 3009 EN. Self-operated Regulators. Type RS Check Valve (backflow protection)

Mounting and Operating Instructions EB 2172 EN. Series 43 Temperature Regulators. Type 43-5 and Type Type Type 43-6

Mounting and Operating Instructions EB 2558 EN. Self-operated Pressure Regulators. Type Pressure Build-up Regulator

Mounting and operating instructions EB 2530 EN. Self-operated Pressure Regulator. Pressure Reducing Valve Type M 44-2

Pressure Reducing Valve for Steam Type 2333 A

Series 42 Self-operated Regulators Differential Pressure Regulators with Type 2424/Type 2428 Actuator (closing) Type Type 42-28

Self-operated Pressure Regulators for special applications

Self-operated Regulators Accessories Differential Pressure and Flow Regulators

Series 44 Self-operated Pressure Regulators. Type 44-0 B Pressure Reducing Valve. ANSI version

EB EN. Type 44-0 B Steam Pressure Reducing Valve Type 44-1 B Pressure Reducing Valve. Translation of original instructions

Series 44 Self-operated Pressure Regulators. Type 44-1 B Pressure Reducing Valve. Type 44-6 B Excess Pressure Valve. ANSI version

Mounting and Operating Instructions EB 8546 EN. Supply Pressure Regulator Type Fig. 1 Supply pressure regulators

Type Pressure Regulator. for increased air capacity. Fig. 1: Type Pressure Regulator. Mounting and Operating Instructions EB EN

Mounting and Operating Instructions EB EN. Type Supply Pressure Regulator. with increased air capacity

Self-operated Pressure Regulators Type 2405 Pressure Reducing Valve

Self-operated Pressure Regulators Type Universal Pressure Reducing Valve

Self-operated Pressure Regulators Type 2405 Pressure Reducing Valve

T 2523 EN Type 2406 Excess Pressure Valve Self-operated Pressure Regulators ANSI version

Series 44 Self-operated Pressure Regulators. Type 44-1 B Pressure Reducing Valve. Type 44-6 B Excess Pressure Valve

Type 3709 Pneumatic Lock-up Valve. Translation of original instructions. Mounting and Operating Instructions EB 8391 EN

Mounting and Operating Instructions EB 8546 EN. Type 4708 Supply Pressure Regulators. Translation of original instructions. Type Type

Type 4708 Supply Pressure Regulator

Application Notes for Valve Sizing Sizing valves for steam service with the aid of sizing charts

Type 4708 Supply Pressure Regulator

Mounting and Operating Instructions EB 9520 EN. Differential Pressure and Flow Meter Media 05

Mounting and Operating Instructions EB 9520 EN. Differential Pressure and Flow Meter Media 05

Declaration of Conformity as per Directive 97/23/EC

Type 4708 Supply Pressure Regulator

Mounting and Operating Instructions EB 9519 EN. Differential Pressure and Flow Meter Media 5. Zero adjuster

AVP-F. p setting range (bar) Code No. 003H6200

Differential pressure and flow controller (PN 16) AVPQ - return mounting, adjustable setting

Differential pressure controller (PN 25) AVP - return and flow mounting, adjustable setting

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

Products for Cryogenic Applications

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

Declaration of Conformity as per Directive 97/23/EC

Technical Data Sheet T 2025

Declaration of Conformity as per Directive 97/23/EC

Bermad Pressure Reducing. Model: 42T

KBV21i and KBV40i Air Actuated Boiler Blowdown Valves

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

Installation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM.

Instruction Manual Contact Pressure Vacuum Gauge

Rp [ ] Sv min. [ ] C215QP-B 15 1/ C215QP-D 15 1/ C220QP-F 20 3/ [ ]

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS

Pneumatic switch module 3/2-way valve (On/Off) Types P Types FP Function tested for use of the float in Ex-zone 0

Ball Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300 DN 40, 50, 65

SRV66 Sanitary Pressure Reducing Valve

Installation, Operating and Maintenance Instructions. V914 Cast Iron Flanged Swing Check Valve V914

PRESSURE REDUCING VALVE RP45 (EN)

Pressure reducing valves Index

Differential pressure controller (PN 16) AHP - return mounting, adjustable setting

VALFONTA INSTRUCTIONS: OPERATION AND INSTALLATION PRESSURE REDUCING VALVE MODEL PRV44

GM-7000 Series CE Approved Gas Control Valve

Steam Trap BK 15 (DN40, DN 50) Original Installation Instructions English

V DFX Series. Direct-Operated Tank Blanketing Regulator Manual D103808X012

Ball Float Steam Trap UNA 43 PN 16/CL 125/JIS 10K UNA 46 PN 40/CL 150/CL 300/JIS 10K/JIS 20K DN 80, 100, 150, 3", 4", 6"

Declaration of Conformity as per Directive 97/23/EC and Manufacturer s Declaration as per Directive 98/37/EC

RR 16 Commercial & Industrial Regulator

Serie ECO 3T. Threaded end back flow preventer with controllable reduced pressure zone. made in. Application fields. Protection E U R O P E

SCA Series Inverted Bucket Steam Traps

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS

1. Preface Important Safety Notes Brief Product Information Product Working Principle Installation Guidelines...

Electropneumatic Positioner Type 4763 Pneumatic Positioner Type 4765

Reduce pressure zone device suitable for high and medium hazard rated applications Flanged end connections

Pneumatic proportional controller Types M Types FM Function tested for use of the float in Ex-zone 0

HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions

TA10A and TA10P Steam Tracing Temperature Control Valves Installation and Maintenance Instructions

Reduce pressure zone device suitable for high and medium hazard rated applications BSP screwed connections

BCV31 DN20 - Blowdown Control Valve

CAST IRON SAFETY VALVE TYPE 6301

TECHNICAL CATALOGUE PRESSURE REDUCING VALVES EUROPRESS

FTGS14 Ball Float Steam Trap DN15 (½") to DN25 (1")

Size : Ends : Min Temperature : Max Temperature : Materials : Cast iron body

Steam trap BK 37 BK 28 BK 29 BK 37 ASME BK 28 ASME BK 29 ASME

Pressure reduction controller (PN 16, 25, 40)

Gas Pressure Regulator HON 200

VALFONTA INSTRUCTIONS: OPERATION AND INSTALLATION PRESSURE REDUCING VALVE MODEL M2

Pressure and Flow Control Valves DBGM, German and European Patents

Installation, Operating and Maintenance Manual Overflow Regulator Type 94/ 94 E

USER MANUAL Version: 1/2017

Steam Trap BK BK 212-ASME. Original Installation Instructions English

TP1 and TP2 Temporary Cone Shaped Strainers

RR 16 Commercial & Industrial Regulator

VALVCHEQ BACKFLOW PREVENTERS FIGURE RP03

CA10S, CA14 and CA14S Air and Gas Traps

Pressure Independent Control Series

Inverted Bucket Steam Trap IB 16A-7

Spilt body Flange ball valve. TC-205MFF-PN1640 User Manual English Version. Document No: TC-205MFF-PN1640.Ur-manual. Date: 2007/04/2617. Version: 1.

Automatic Balancing Valve Pressure difference controller with integrated flow limiter AB-PM DN

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats

MZX. Three-Port Seat Valves SPECIFICIATIONS AND GUIDE TO SELECTION

TECHNICAL CATALOGUE PRESSURE REDUCING VALVES EUROPRESS

1805 Series Relief Valves

6301 TYPE CAST IRON SAFETY VALVES

Transcription:

Self-operated Regulars Flow and Differential Pressure Regular Type 42-37 Flow and Differential Pressure or Flow and Pressure Regular Type 42-39 Type 42-37 Type 42-39 Fig. 1 Flow and differential pressure or pressure regulars Mounting and Operating Instructions EB 3017 EN Edition September 2008

Contents Contents Page 1 Design and principle of operation.................... 4 2 Installation............................... 7 2.1 Mounting position............................ 8 2.2 Control line, equalizing tank and needle valve.............. 8 2.3 Strainer................................ 10 2.4 Shut-off valve............................. 10 2.5 Pressure gauge............................ 10 3 Operation............................... 11 3.1 Start-up................................ 11 3.2 Set point adjustment.......................... 11 3.2.1 Set point for flow rate......................... 11 3.2.2 Set point for differential pressure.................... 15 3.2.3 Pressure set point in Type 42-39 Flow and Pressure Regular..... 16 3.3 Decommissioning........................... 16 4 Cusmer service........................... 17 5 Maintenance Troubleshooting.................... 18 6 Nameplates.............................. 19 7 Technical data............................ 20 8 Dimensions.............................. 21 Definitions of the signal words used in these instructions CAUTION! indicates a hazardous situation which, if not avoided, may result in injury. Note: Supplementary explanations, information and tips NOTICE indicates a property damage message. 2 EB 3017 EN

Safety instructions General safety instructions The regulars must be installed, started up and serviced by fully trained and qualified personnel only, observing the accepted industry codes and practices. Make sure employees or third persons are not exposed any danger. The regular complies with the requirements of the European Pressure Equipment Directive 97/23/EC. The declaration of conformity issued for a valve bearing the CE marking includes information on the applied conformity assessment procedure. The declaration of conformity can be provided on request. For appropriate operation, make sure that the regular is only used in applications where the operating pressure and temperatures do not exceed the operating values based on the sizing data submitted in the order. Note that the manufacturer does not assume any responsibility for damage caused by external forces or any other external facrs. Any hazards which could be caused in the regular by the process medium or operating pressure are be prevented by means of appropriate measures. Proper shipping and appropriate srage are assumed. Note: Non-electric valve versions which do not have a valve body lined with an insulating coating do not have their own potential ignition source according the ignition risk assessment stipulated in EN 13463-1: 2002, section 5.2, even in the rare incident of an operating fault. Therefore, they do not fall within the scope of Directive 94/9/EC. For connection the equipotential bonding system, observe the requirements specified in section 6.3 of EN 60079-14: 2003 (VDE 0165 Part 1). EB 3017 EN 3

Design and principle of operation 1 Design and principle of operation The regulars limit the flow rate in the pipeline. The set point for the flow rate is adjusted at the restriction and the set point for the differential pressure or the downstream pressure is adjusted at the actuar. The largest signal is always used actuate the valve. The regulars mainly consist of the Type 2423 Valve with seat, plug and restriction gether with the Type 2427 or Type 2429 Closing Actuar with operating diaphragms. Valve and actuar are delivered separately and must be assembled on site using a coupling nut The medium flows through the valve in the direction indicated by the arrow. The position of the restriction (1.1) and the area released by the valve plug (3) determine the flow rate and the differential pressure p across the plant. The valve is fully balanced. The forces acting on the valve plug created by the upstream and downstream pressures are balanced by a balancing bellows (5) or balancing diaphragm (Type 2423 balanced by a diaphragm, DN 125 250). The principle of operation of the regulars with valves balanced by a bellows or diaphragm only differ concerning the pressure balancing. The valves balanced by a diaphragm have a balancing diaphragm (Fig. 3) instead of a bellows (Fig. 2). The downstream pressure p 2 acts on the inside and the upstream pressure p 1 on the outside of the diaphragm. As a result, the forces acting on the valve plug are balanced out. Type 42-37: The high pressure of p is transmitted through the control line (18) the diaphragm chamber D. The high pressure of the flow rate (V. ) upstream of the restriction (1.1) is transmitted through the control line (19) the diaphragm chamber C. This pressure is equal the low pressure of p. The low pressure of V. downstream of the restriction is transmitted through holes in the plug and diaphragm stems the diaphragm chamber A. If, for example, the differential pressure rises, the positioning force at the botm operating diaphragm (13.2) rises, o. This change in force causes the diaphragm stems (12.2 and 12.1) and the valve plug (3) move in the closing direction until the set point adjusted at the set point spring (16) is reached. If the flow rate increases, the differential pressure at the restriction (1.1) and the resulting positioning force at the p diaphragm (13.1) increase. This change in differential pressure at the restriction causes the p diaphragm stem (12.1) push the plug stem and the valve plug (3) in the closing direction until the adjusted flow set point is reached. The largest signal is always used actuate the valve. The overload protection (force limiter with internal excess pressure limiter) (15) protects the seat, plug and plant during extreme operating conditions against overloading. Type 42-39: The principle of operation is almost the same as for Type 42-37. However, the high pressure of the flow rate V. is separate from the low pressure of the differential pressure p in the Type 2429 Actuar. The diaphragm chambers for these pressures have their own control line connections. 4 EB 3017 EN

Design and principle of operation Type 42-37 1.3 1.2 1.1 1 2 3 Type 42-39 Type 2423 Valve balanced by a bellows 19 4 8 5 7 19 20 11 12.1 A 9 A V 13.1 V B B C 13.2 18 15 C D 21 D 18 12.2 21 Type 2427 16 Actuar Type 2429 17 Actuar 1 Valve body 8 Venting (DN 125 and higher) 1.1 Restriction for flow set point 9 Differential pressure spring 1.2 Lock nut 11 Coupling nut 1.3 Cap 12.1 Top diaphragm stem 2 Seat 12.2 Botm diaphragm stem 3 Plug 13.1 Top operating diaphragm 4 Plug stem 13.2 Botm operating diaphragm 5 Balancing bellows 15 Overload protection (force 7 Spring limiter with internal excess pressure limiter) Fig. 2 Sectional drawings of regular with valve balanced by a bellows 16 Set point spring 17 Set point adjustment 18 Control line on site 19 Control line (+) V. 20 Control line (+) p 21 Restriction dampen signal EB 3017 EN 5

Design and principle of operation Type 42-37/Type 42-39 DN 125 250 Balanced by a diaphragm Type 2423 Valve balanced by a diaphragm Type 2427/2429 Actuar 1 Valve body 1.1 Restriction for flow set point 1.2 Lock nut 1.3 Cap 2 Seat 3 Plug 5 Balancing diaphragm 7 Plug stem 18 Control line Fig. 3 Sectional drawing of regular with valve balanced by a diaphragm Note on Type 42-37 DoT and Type 42-39 DoT These regulars can also be used for temperature control and limitation in combination with Type 2231 Temperature Regular by using a double adapter DoT. Refer the following Mounting and Operating Instructions in this case: EB 3019 EN for DoT double adapter and EB 2231 EN for Type 2231 2235 Control Thermostats. 6 EB 3017 EN

Installation 2 Installation Install Type 42-37 Regular in the low pressure line (return flow) of the plant. Install Type 42-39 Regular in the high pressure line (flow) of the plant. Refer installation schematics in Fig. 4. On selecting the position of installation, make sure that the regular can still be easily accessed after completion of the plant. NOTICE The regular must be installed free of stress. If necessary, support the piping near the connections. However, do not attach supports the valve or actuar. Type 42-39 in flow pipe Differential pressure and flow rate control Type 42-37 in return flow pipe Differential pressure and flow rate control Type 42-39 in flow pipe Pressure and flow rate control 1 Shut-off valve 2 Strainer 3 Flow and differential pressure regular 4 Equalizing tank, required for medium temperatures above 150 C or for steam applications 5 Needle valve 6 Pressure gauge 7 Bypass with capped valve (recommended) for set point adjustment Fig. 4 Installation schematics (p) and typical installation (botm) EB 3017 EN 7

Installation Note: Install a strainer (e.g. SAMSON Type 2 N/2 NI) upstream of the regular prevent sealing particles, welding spatter or other impurities carried along by the process medium from impairing the proper functioning of the valve, especially tight shut-off. 2.1 Mounting position See Fig. 5 for permissible mounting positions. Standard mounting position Install valve without actuar in a horizontal pipeline with the connection for the actuar facing downwards. Make sure the medium flows through the valve in the direction indicated by the arrow. Then connect the actuar the valve using the coupling nut (11). NOTICE Protect the regular when it is used control freezing process media. On shutting down the plant in areas not free from frost, depressurize and empty the regular and remove it from the pipeline. 2.2 Control line, equalizing tank and needle valve Control lines Control lines preferably using 8 x 1 mm steel or stainless steel pipe must be provided at the site of installation. Connect the control line for pressure tapping in Type 42-37 the pipeline upstream of the consumer. Make sure the pressure tapping point is at least 3 x DN away from any instruments (pipe manifolds, distriburs, other valves) that can cause turbulence in the flow Standard mounting position all versions Above 80 C, steam applications All versions in DN 15 80 and up max. 80 C Only versions with fixed plug guide and up max. 80 C Fig. 5 Permissible mounting positions (Fig. 6.1). How the line is routed generally depends on the installation location. The same rules apply the control line installed on site for Type 42-39 (connected downstream of the consumer). We recommend connecting the control line at the side of the main pipeline (Fig. 5.4). Do not change the pipe diameter of the main pipeline so that it is off center! Type 42-37 Attach the supplied low-pressure control line the regular as shown in Fig. 2. At the site of installation, route the high-pressure control line with 8 mm (standard), 10 mm or 12 mm pipe diameter from the botm diaphragm chamber the high-pressure line (flow) of the plant. 8 EB 3017 EN

Installation Type 42-39 Attach the supplied control lines the regular as shown in Fig. 2. When used as a flow and differential pressure regular, additionally route a control line at the site of installation from diaphragm chamber C the low-pressure line (return flow) of the plant. When used as a flow and pressure regular, leave the connection for diaphragm chamber C open. Control line kit A control line kit for tapping pressure directly at the valve body is available as an accessory from SAMSON. Refer Data Sheet T 3095 EN. Needle valve If the regular tends hunt, we recommend installing a SAMSON needle valve in the control line routed on site at the actuar connection. Correct! 6.4 Connection at the side correct Incorrect! 6.3 Connection at the p incorrect Incorrect! Note: Needle valves, equalizing tanks and compression-type screw fittings can be supplied as required. These accessories are listed in the Data Sheet T 3095 EN. Equalizing tank An equalizing tank is required for liquids above 150 C. Prior start-up, fill the equalizing tank with the medium be regulated. This prevents hot medium coming in direct contact with the diaphragm. Depending on how the regular is installed, install the equalizing tank in any control line used with hot media. The mounting position of the equalizing tank is indicated by an adhesive label on the tank itself as well as by an arrow and the word "p" stamped on the p of the tank. 6.2 Connection at the botm incorrect min. 3 x DN min. 3 x DN M DN min. 3 x DN DN = Nominal size 6.1 Control line connection, depending on how the pipeline is routed Fig. 6 Connection of control lines EB 3017 EN 9

Installation Install the equalizing tank near the pressure tapping point in the flow pipe or at the same height as the valve (Fig. 7) ensure that the control line reaches from at least the mid axis the valve the actuar. This ensures that a hot medium can cool down sufficiently. NOTICE Adhere the mounting position and distances prescribed, otherwise the safe functioning of the regular cannot be guaranteed. 2.3 Strainer A strainer installed in the flow pipe prevents foreign matter and dirt particles in the medium from entering the regular. The SAMSON product range includes the Type 2 N/2 NI Strainer (refer Data Sheet T 1015 EN). Install the strainer upstream of the regular. Make sure the direction of medium flow corresponds with the direction indicated by the arrow on the strainer. The filter element must be suspended downwards or be located at the side for applications with steam. Remember leave enough space remove it. T 1 >150 C 2.4 Shut-off valve We recommend installing a hand-operated shut-off valve (Fig. 4) both upstream of the strainer and at the outlet of the return flow pipe be able shut down the plant for cleaning and maintenance, and when the plant is not used for longer periods of time. Minimum length of control line Type 42-37 T 2 <150 C 2.5 Pressure gauge To monir the pressures in the plant, install a pressure gauge both upstream and downstream of the regular. Install the pressure gauge on the downstream side behind the downstream pressure tapping point. Fig. 7 Type 42-37 with equalizing tank 10 EB 3017 EN

Operation 3 Operation 3.1 Start-up CAUTION! First start up the regular after mounting all the components, e.g. valve, actuar and control lines. Make sure the control lines are open and correctly connected before start-up. Note: On filling the plant, make sure the restriction (1.1) is open by turning the adjustment screw counterclockwise as far as it will go. Open all the valves on the consumer side. Slowly open the shut-off valves starting on the return flow pipe first. In case of valves balanced by a bellows in DN 125 or larger, vent the bellows housing (8) at the spper located at the side of the bellows housing. If needle valves are installed in the control lines, open them before start-up. Fill equalizing tanks with the process medium before start-up. Rinsing the plant After filling the plant, first completely open the consumers. If this is not possible open the bypass. Open the restriction for flow rate adjustment with a differential pressure set point spring at maximum compression. Rinse out the pipeline at full flow rate for several minutes. Check the installed strainer (e.g. by measuring the pressure drop) afterwards. Clean the strainer, if necessary. NOTICE The pressure at the actuar must not exceed the nominal pressure by 1.5 times on testing the pressure of the plant when the regular is already installed The control lines must route the test pressure the actuar at the same time prevent the actuar diaphragms from being damaged. When Type 42-39 is used as a flow and pressure regular, do not connect the control line diaphragm chamber C. 3.2 Set point adjustment 3.2.1 Set point for flow rate Note: Before adjusting the flow rate, you first need adjust the set point for the differential pressure (or pressure) its maximum value, To do this, turn the nut (17) clockwise load the set point spring (16). The control valves and shut-off valves as well as all consumers or a bypass valve, if applicable, must be opened reach the maximum flow rate, but without the high differential pressure (pressure) being able close the valve. Turn the restriction (1.1) until the required flow rate is reached, by reading, for example, the flow rate reading off a heat meter (see Table 1 Flow rate set point ranges). Note: Always start the adjustment from a closed restriction! EB 3017 EN 11

Operation Turn clockwise close the restriction. This reduces the flow rate. Turn counterclockwise open the restriction. This raises the flow rate. You can also use the adjustment diagrams for water in Figs. 8, 9 and 10 on the following pages help you make the flow rate adjustment. Note: The differential pressure at the restriction p restriction is fixed at either 0.2 bar or 0.5 bar (see nameplate) by the differential pressure spring(s) (9) in the actuar. Unscrew cap (1.3) and undo lock nut (1.2). Turn the adjustment screw clockwise as far as it will go. Find the flow set point in the diagram and determine how many turns are required. Turn the screw counterclockwise (based on a closed restriction) until the selected set point is adjusted. Check the flow rate at the heat meter and correct, if necessary. When the required flow rate is reached, lock the screw in position with the lock nut (1.2) and screw cap (1.3) back on. Lead-seal cap, if necessary. Close the open bypass valve again, if applicable. Table 1 Flow rate set point ranges for water Type 2423 Balanced by a bellows Nominal size DN 15 20 25 32 40 50 65 80 100 125 150 200 250 Flow rate set point ranges for water in m³/h Differential pressure at restriction p restriction = 0.2 bar Differential pressure at restriction p restriction = 0.5 bar 0.05 2 0.15 3 0.15 3 0.25 4.5 Type 2423 Balanced by a diaphragm 0.25 3.5 0.4 5.3 0.4 7 0.6 9.5 0.6 11 0.9 16 Nominal size DN 125 150 200 250 Flow rate set point ranges for water in m³/h Differential pressure at restriction p restriction = 0.2 bar 11 120 18 180 20 320 26 350 0.9 16 2 24 2 28 3.5 40 3.5 35 6.5 55 6.5 63 11 90 11 80 18 120 18 120 20 180 20 180 26 260 26 220 30 300 12 EB 3017 EN

Operation p restriction = 0.5 bar Turns of set point adjustment (orifice) prestriction = 0.2 bar Adjustment diagrams valid for water Turns of set point adjustment (orifice) Fig. 8 Adjustment diagram for Type 2423 balanced by a bellows, DN 15 80 EB 3017 EN 13

Operation p restriction = 0.5 bar Turns of set point adjustment (orifice) prestriction = 0.2 bar Adjustment diagrams valid for water Turns of set point adjustment (orifice) Fig. 9 Adjustment diagram for Type 2423 balanced by a bellows, DN 100 250 14 EB 3017 EN

Operation Adjustment diagrams valid for water Turns of set point adjustment (orifice) DN 125, DN 150 A = 320 cm 2 p restriction = 0.2 bar Balanced by a diaphragm DN 200, DN 250 A = 320 cm 2 p restriction = 0.2 bar Balanced by a diaphragm Fig. 10 Adjustment diagram for Type 2423 balanced by a diaphragm, DN 125 DN 250 3.2.2 Set point for differential pressure Note: Before adjusting the differential pressure, reduce the maximum flow rate by approximately 5 % by closing a shut-off valve on the consumer side or the bypass. If a morized valve is used in the plant, close this by approximately 10 % of its travel. Turn the nut (17) counterclockwise unload the set point springs (16) and adjust the differential pressure set point. While doing this, compare the pressures upstream and downstream of the consumer by reading off the installed pressure gauges (see Fig. 4). If you want adjust small differential pressure set points, we recommend using a differential pressure gauge instead of two pressure gauges. Turn the nut (17) clockwise increase the set point. Turn the nut (17) counterclockwise reduce the set point. EB 3017 EN 15

Operation 3.2.3 Pressure set point in Type 42-39 Flow and Pressure Regular Adjust the pressure set point at the nut (17). While doing this, read the pressure off the installed pressure gauge on the downstream side. Turn the nut (17) clockwise increase the downstream pressure. Turn the nut (17) counterclockwise reduce the downstream pressure. 3.3 Decommissioning Close the shut-off valves starting from the upstream side (high-pressure line). CAUTION! On performing any work on the regular, make sure the relevant section of the pipeline is depressurized and, depending on the process medium, drained as well. For high temperatures, allow the regular cool down ambient temperature before starting any work on it. Interrupt or shut off the control line avoid any hazards which could be caused by moving parts. As valves are not free of cavities, remember that residual process medium might still be contained in the valve. We recommend remove the valve from the pipeline. Make sure that all the plant sections connected the control lines are also depressurized. If this is not the case, shut off the control lines. 16 EB 3017 EN

Cusmer service 4 Cusmer service Should any malfunctions or any defect occur, SAMSON's After-Sales Service is prepared help you on site. You can also send the defective regular directly your local SAMSON representative for repair. Addresses of SAMSON subsidiaries, agencies and service centers are listed in the product catalogs and in the Internet at www.samson.de. To allow SAMSON find the fault and have an idea of the installation situation, specify the following details (refer the nameplate): Type and nominal size of the valve Threaded or flanged end connections Model number Upstream and downstream pressure Flow rate in m 3 /h Has a strainer been installed? Sketch of the installation with exact position of regular and all additional installed components (shut-off valves, pressure gauges, etc.). EB 3017 EN 17

Maintenance Troubleshooting 5 Maintenance Troubleshooting The regulars are maintenance free. Nevertheless, they are subject natural wear, particularly at the seat, plug and operating diaphragm. Depending on the operating conditions, the regular needs be checked at regular intervals avoid possible malfunctions. Details on faults and the recommended action can be found in the table below. Table 2 Troubleshooting Malfunction Possible reasons Recommended action Flow rate or differential pressure exceeds its set point Flow rate or differential pressure set point is not reached Control loop hunts Seat and plug untight Operating diaphragm defective Control line blocked Valve o large for flow control or o small for differential pressure control Seat and plug untight Wrong set point range selected Safety equipment, e.g. pressure limiter, has been triggered Insufficient pressure drop across the plant Strainer blocked Direction of flow, valve incorrectly installed Valve o large for the control task at hand Restriction (or needle valve) is missing in a control line dampen pulsation Remove valve from pipeline. Clean seat and plug. Replace plug, if necessary. Otherwise send the regular SAMSON for repair. Replace diaphragm or send the regular SAMSON for repair. Remove control line and clean it. Recalculate K VS coefficient and contact SAMSON for further action. Remove valve from pipeline. Clean seat and plug. Replace plug, if necessary. Otherwise send the regular SAMSON for repair. Check set point range and contact SAMSON for further action. Check plant and unlock safety equipment. Compare existing differential pressure in the plant with the plant s drag. Differential pressure across the plant p min =. p restriction + (V/ KVS)². Drain and clean filter of the strainer Install the valve so that the direction of flow is the same as indicated by the arrow. Recalculate K VS coefficient. Contact SAMSON. Check restriction in the connection chamber D (Type 42-37) or chamber C (Type 42-39). If necessary, install a needle valve in the control line and start close it until the control loop becomes stable. Caution! Do not completely close needle valves. Contact SAMSON if the malfunction cannot be remedied using the table. 18 EB 3017 EN

Nameplates 6 Nameplates Valve and actuar both have a nameplate. DIN version ANSI version Valve 1 Valve type 2 Model number 3 Model number index 4 Order number or order date 5 K VS coefficient 8 Nominal size 9 Nominal pressure 10 Perm. differential pressure in bar 11 Perm. temperature in C 12 Body material Valve nameplates ANSI version 5 Nominal size 8 Perm. differential pressure in psi 9 Perm. temperature in F 10 Body material 11 CV coefficient (K VS x 1.17) 12 ANSI Class (pressure rating) Actuar nameplate Actuar 1 Model number 2 Model number index 3 Order number or order date 4 Effective diaphragm area 5 Labeling acc. DIN 6 Labeling acc. ANSI 7 Max. perm. pressure 8 Nominal size 9 Differential pressure at restriction 10 Set point range 11 Diaphragm material 12 Year of production Fig. 11 Nameplates EB 3017 EN 19

Technical data 7 Technical data Table 3 Technical data Type 42-37 Type 42-39 Type 2423 Valve Balanced by a bellows Nominal size DN 15 DN 100 DN 125 DN 250 Nominal pressure PN 16, 25 or 40 (acc. DIN EN 12516-1) Pressure at which internal 160 cm² 1.2 bar excess pressure limiter responds (Type 42-37 only) 320 cm² 0.6 bar Max. perm. temperature Differential pressure or pressure set point Leakage rate Type 2423 Valve Balanced by a diaphragm Valve body See pressure-temperature diagram Actuar 1) With equalizing tank: Liquids up 220 C Without equalizing tank: Liquids up 150 C bar 0.1 0.6 0.2 1 0.5 1.5 1 2.5 2 5 4.5 10 2) 0.05 % of K VS coefficient Nominal size DN 125 DN 250 Nominal pressure PN 16, 25 or 40 (acc. DIN EN 12516-1) Pressure at which internal excess pressure limiter responds (Type 42-37 only) Max. perm. temperature Differential pressure or pressure set point Leakage rate 1) Higher temperatures possible on request 2) On request 160 cm² 1.2 bar 320 cm² 0.6 bar 640 cm² 0.3 bar Valve body See pressure-temperature diagram Actuar 1) Liquids up 150 C 0.1 0.6 bar 0.2 1 bar 0.5 1.5 bar 1 2.5 bar 2 5 bar 2) 0.05 % of K VS coefficient 20 EB 3017 EN

Dimensions 8 Dimensions Dimensional drawing Type 2423 Valve balanced by a diaphragm Type 42-37/Type 42-39 Fig. 12 Dimensions of Type 2423 Valve balanced by a diaphragm Table 4 Dimensions in mm and weights in kg Type 2423 Valve balanced by a diaphragm Type 2423 Valve balanced by a diaphragm Nominal size DN 125 DN 150 DN 200 DN 250 Length L 400 480 600 730 Height H1 910 935 1020 Height H2 295 325 345 375 Weight for PN 16 1) in kg Type 2423 Valve 65 85 248 268 Type 2427/2429 Actuar 32 32 35 35 1) PN 25/40: +10 % EB 3017 EN 21

Dimensions Dimensional drawing Type 2423 Valve balanced by a bellows Type 42-37/Type 42-39 Fig. 13 Dimensions of Type 2423 Valve balanced by a bellows 22 EB 3017 EN

Dimensions Table 5 Dimensions in mm and weights in kg Type 2423 Valve balanced by a bellows Type 2423 Valve balanced by a bellows Nominal size DN 15 20 25 32 40 50 65 80 100 125 150 200 250 Length L 130 150 160 180 200 230 290 310 350 400 480 600 730 Height H1 225 300 355 460 590 730 Height H2 Other 115 150 175 180 200 250 280 400 materials 1.4571 113 130 170 176 0.1 0.6 bar Height H 1) 675 790 845 Ø D = 285 mm, Actuar Ø D = 225 mm, A = 160 cm² A = 320 cm² Weight 2) 20.5 21 22 28.5 29 31.5 51 56 71 Height H 1) 675 770 825 1130 1160 1240 Set point range 0.2 1 bar 0.5 1.5 bar Actuar Ø D = 225 mm, A = 160 cm² 4) Ø D = 285 mm, A = 320 cm² Weight 2) 20.5 21 22 28.5 29 31.5 43 48 65 130 180 420 480 Height H 1) 675 770 825 1130 1160 1240 Actuar Ø D = 225 mm, A = 160 cm² 4) Ø D = 285 mm, A = 320 cm² Weight 2) 20.5 21 22 28.5 29 31.5 43 48 65 135 185 425 485 1 2.5 bar Height H 1) 675 770 825 1130 1160 1240 Actuar Ø D = 225 mm, A = 160 cm² Ø D = 285 mm, A = 320 cm² Weight 2) 20.5 21 22 28.5 29 31.5 43 48 65 135 185 425 485 Height H 1) 615 690 745 2 Actuar Ø D = 225 mm, A = 160 cm² 5 bar Weight 2) 20.5 21 22 28.5 29 31.5 43 48 65 1) Add 50 mm height H for Type 42-39 2) The weight applies the version with material specifications EN-JL 1040/PN 16. Add 10 % this weight for versions made of cast steel 1.0619/PN 40, spheroidal graphite iron EN-JS 1049/ PN 25 and 1.4581/1.4571. 3) p = 4.5 bar 10 bar on request 4) Optionally also with actuar 320 cm² (DN 65 100).We recommend actuar 320 cm² for regulars with double adapter (see T 3019 EN) in sizes DN 65 DN 100. EB 3017 EN 23

SAMSON AG MESS- UND REGELTECHNIK Weismüllerstraße 3 60314 Frankfurt am Main Germany Phone: +49 69 4009-0 Fax: +49 69 4009-1507 Internet: http://www.samson.de EB 3017 EN S/Z 2011-03