SPECIFICATION SHEET. OMEGAFLEX, Ltd. TracPipe Flexible Gas Piping Specification Sheet Specification date. ProjectName

Similar documents
For use in Natural Gas & Liquefied Petroleum Gas Applications

User Information Sheet 015

IAPMO GUIDE CRITERIA FOR BALL VALVES IAPMO IGC PURPOSE

FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS

User Information Sheet 024

Installation pipework on industrial and commercial premises

Flexible & Intelligent

// ADapters GUIDelines

Pipe threads for tubes and fittings where pressure-tight joints are not made on the threads. (requires PTFE sealing tape or liquid sealant).

INSERT FITTINGS INSERT FITTINGS

Pro-Flex,LLC. Flexible Gas Piping Systems. & Flak Jacket TM CSST. Installation/Training Guide. Pro-Flex,LLC

Residential and Commercial Price List

Residential and Commercial Price List

Certificate and test report Nr. J144CON Coupling system for solar thermal applications. Test according to SPF test procedure: Test class A1

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

General Performance Data Hose Ref Minimum Bend. Safety Pressure at 20 C (BAR) Working Pressure at. Flow Rate at 3 bar (lit/min) Working Pressure

G92 Series BASOTROL Automatic Pilot Gas Valve

Declaration of Performance (DOP)

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

PVC FASTTAP SADDLES for IPS Mains. Main Size OUTLET 1 FPT 3/4 CTS (7/8 OD) COMPRESSION 1 CTS (1 1/8 OD) COMPRESSION 3/4 IPS COMPRESSION

BIMBAR INFLATABLE PACKERS AND ACCESSORIES

IGEM/UP/2 Edition 3 Communication 1771 Installation pipework on industrial and commercial premises

GAS DISTRIBUTION PRODUCTS TRANSITION FITTINGS

RS Pro 300mm Long EPDM 15bar Braided Stainless Steel Hose RS Stock No

CPVC Transition Fittings - Female Adapter. CPVC X LEAD FREE BRASS Lead Free Max working pressure F ASTM D 2846

Continental Industries TRANSITION FITTINGS or FAX Visit

Flexible Gas Hose Installation and Operating Instructions To be left with the operator after installation

HYDRALECTRIC LIMITED,

Model MTB-ASME Vertical Bladder Tanks

DN 1/2" to 2" Female / Female BSP - 5 C + 60 C Max Pressure : 5 Bars Specifications : Anti blow-out stem Double o ring NBR on stem Full bore

Mounting and operating instructions EB 2530 EN. Self-operated Pressure Regulator. Pressure Reducing Valve Type M 44-2

Model: AT-1000 L.P.G. FREEZE VALVE

Rapidmain Installation Guide

Model MTB-ASME Vertical Bladder Tanks

Consult with manufacturers concerning permeation of the pipe walls, jointing materials, valve seats, etc.

Model: AT-1000 L.P.G. FREEZE VALVE

Ecoflex pre-insulated pipe energy efficiency made easy

COMPRESSION TUBE FITTINGS

GM-7000 Series CE Approved Gas Control Valve

World Area Differences Technical Information

HYDRALECTRIC LIMITED,

SUMMITTM 400 & 600. Natural Gas Barbecues. Step-By-Step Guide

6. Features & Benefits Installation Considerations Jointing Instructions Pipe Sizing Calculations & Tables

Tightness testing and direct purging of small Liquefied Petroleum Gas/Air, Natural Gas and Liquefied Petroleum Gas installations

ACS.CoNGLP1 SAFETY ASSESSMENT CRITERIA INITIAL & RE-ASSESSMENT DOMESTIC NATURAL GAS TO LPG GENERIC

INTERLOCKED METAL HOSE

ACS.CoNGLP1 SAFETY ASSESSMENT CRITERIA INITIAL & RE-ASSESSMENT DOMESTIC NATURAL GAS TO LPG GENERIC

Gas Lines. Technical Manual. Sumitomo (SHI) Cryogenics of America, Inc Vultee Street Allentown, PA U.S.A.

Push-in fittings NPQH

Horizontal Bladder Tanks

Model MTB-ASME Horizontal Bladder Tanks

Instruments AQDC. Aluminium Quick Disconnects. Light-weight, quick and reliable method a making a number of pneumatic connections.

Vertical Bladder Tanks

Installation/Training Guide PRO-FLEX CSST

The Duopex Gas. to make every job quick and easy. it provides a revolutionary alternative for the professional plumber and 02_DUOPEX GAS GAS MANUAL

Operating Instructions in compliance with Pressure Equipment Directive 2014/68/EU. FAS Manual Brass Shut-Off Valve DN10 through DN22

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS

Push-in fittings NPQH

Overview EUSSAM12. Carry out tightness testing and direct purging of gas installations

COMPRESSION TUBE FITTINGS 1/16 THROUGH 2 -INCH, 2 MM THROUGH 50 MM-METRIC

OPERATING INSTRUCTIONS

Shri Krishna Test House, B-70/1, Gali No. 8, New Modern Shahdara, Mansarover Park, Delhi. Discipline Mechanical Testing Issue Date

MATERIALS FOR PLUMBING SYSTEMS FITTING AND INSTALLATION GUIDE

Homestead Series 820 AWWA Butterfly Valves

Installation, Operating and Maintenance Instructions. V914 Cast Iron Flanged Swing Check Valve V914

Module 6. Tightness Testing

Page 1 of 18 Gastite Quiz Part 2

A Rationale for Pressure Relief Device(s) Qualification Requirements (LH2)

PN LINE. Technical remarks PN 11 PN 13 PN 14 PN 15 PN 17 PN 18 PN 20 PN 23 PN 25 PN 26 PN 27 PN 28 PN 29 PN 37 PN 38 PN 39 PN 40 PN 43 PN 10 8_9 10_12

AWWA C504 COMPLIANT VALVES FROM 3 THRU 108

PE 2708 CTS & IPS GAS PIPE

SIMPLAIR PIPING TOOL. JXT Company

PROCEDURE TWO-PLY TESTABLE BELLOWS D 1 OF 5 TWO PLY BELLOWS TEST PROCEDURE

Hoses and Lances 20,000 PSI

G96 Series BASOTROL Dual Operator Valve

Push-in fittings CRQS, stainless steel

ISO INTERNATIONAL STANDARD. Small craft Liquefied petroleum gas (LPG) systems

Declaration of performance

DS MB, MBF THREE PORT VALVES

Cautions : 1. Be careful when you release the Stop Fitting with some internal pressure

Engineering Data Sheet

CRIMP gas Pex-AL PIPING System

Operating Instructions in compliance with Pressure Equipment Directive 2014/68/EU. FAS Straight-Way Valve with Packing Gland

HUPF Series DESCRIPTION APPLICATION INSTRUCTION SHEET GAS PRESSURE REGULATOR WITH INCORPORATED FILTER EN1C-0003NL05 R1205.

Liquefied Petroleum Gas Market Regulations S.L

BGA158 Series CE Approved Class B Shutoff Gas Valve

Two Ferrule Tube Fittings 316 stainless steel ranging from 1/8" to 1" (6mm to 25mm) O.D.

DuoSafe. DuoSafe Inch Systems. Larger sizes on request

V5197A. Firing Rate Gas Valve APPLICATION FEATURES PRODUCT HANDBOOK

Using propane cylinders safely

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

BGA158, BGA171 and BGA110 Series Shutoff Gas Valve

CI-SfB 732 (5-1) x. - laboratory fittings

Casing Spacer Technology Leaders

Intro: by firechim on October 3, 2013

ARCHIVED. Compliance Document for New Zealand Building Code Clause G10 Piped Services. Prepared by the Department of Building and Housing

H15 Series BASO 100% Shutoff, Automatic Pilot Valve

2014 DESIGN & INSTALLATION GUIDE

APT Electrofusion Ducting

Electro Controls. Pressure WattsIndustries.co.uk

Transcription:

OMEGAFLEX, Ltd. TracPipe Flexible Gas Piping Specification Sheet Specification date ProjectName Model Number(s) - FGP-SS4-50 FGP-SS4-40 FGP-SS4-32 FGP-SS4-28 FGP-SS4-22 FGP-SS4-15 FGP-SS4-12 Note: This Information Sheet should be read in conjunction with the TracPipe Design and Installation Specification available from www.tracpipe.co.uk If further information is required, please e-mail tech-help@omegaflex.net A. Standards & Certifications: All Semi-Rigid CSST gas piping system components must be: A.1 BS 7838 or BS EN 15266 Certified (CSST) Semi Rigid Flexible Gas Piping with Mechanical Attachment AutoFlare Fittings that conform to the latest BS standards for safe performance up to DN50. A.2 BS 7838 Specification for corrugated stainless steel semi-rigid pipe and associated fittings for low-pressure gas pipework of up to DN 50. A.3 BS 6891 Installation of low pressure gas pipework of up to 35 mm (R1.1/4) in domestic premises (2nd family gas). - Specification A.4 BS 5482 Code of practice for domestic butane and propane-gas burning installations Part 1: Installations at permanent dwellings, residential and commercial premises, with installation pipework sizes not exceeding DN25 for steel and DN28 for corrugated stainless steel or copper. A.5 IGEM/UP/2 Edition 2. The Institution of Gas Engineers and Managers communication 1729, Installation pipework on industrial and commercial Premises. B. Stainless Steel Tubing: B.1 Tubing shall be made from 300 series Stainless Steel Strip conforming to BS 7838. B.2 Tubing shall not be subjected to heat treating or annealing after the corrugation forming operation. B.3 Tubing shall be suitable for operation with Natural Gas, LP (Propane) and Butane. B.4 Tubing is rated for 500millibar (.5bar) (BS 7838 & BS EN 15266). 1

C. Polyethylene Jacket: C.1 The jacket shall be extruded from fire-retarded Polyethylene. C.2 Chlorinated plastics such as PVC are not permitted. C.3 Polyethylene is to be resistant to UV (ultra-violates). D. AutoFlare Mechanical Attachment Fittings: D.1 Fittings shall be made from yellow brass. D.2 Fittings shall be equipped with a stainless steel insert to pilot on the tubing ID (internal diameter) and provide a reliable flaring operation. D.3 AutoFlare fittings are available in straight male (BSP), straight female, copper compression, tee, reducer tee and coupling configurations. D.4 Fittings shall provide a metal-to-metal seal no (rubber, pastes or plastic based gaskets) E.1 Shut-off valves: (ECV or AECV) must be approved for fuel gas service and shall be rated for the same pressure as the gas piping system installed. F. Exposed Stainless Steel Protection: F.1 TAPE WRAP-AFTER GAS TIGHTNESS TEST Care must be taken after pressure test to ensure that no stainless steel pipe is visible. Any portions of exposed stainless steel behind the fitting nut shall be wrapped with self-bonding silicone tape TracPipe P/N FGP-915-10H-12, (25mm wide), or FGP-915-20H12PO, (50mm wide). This will reduce the possibility of later external corrosive attack. G. Unvented Voids: G.1 Pipe in Pipe System G.1 Ducts having a small cross sectional area and volume, (i.e. 0.01/m2 or less and 0.1/m³ or less, respectively), are considered to be adventitiously ventilated. G.2 BS EN 1775 and IGEM/UP/2 Edition 2, provided that the route is the shortest practicable, the integrity of the cover is maintained, and the end fittings (where the gas tight cover ends) are in a ventilated area. G.3 TracPipe s cover has been independently tested by BSI at pressures from 20mbar to 2bar to demonstrate that it performs satisfactorily as a sleeve, allowing free passage for gas flow between the stainless steel pipe and the outer cover to the end fittings, throughout this pressure range. G.4 The pipework is sleeved continuously through the unventilated duct or void, with the sleeve ventilated at one or both ends into a safe place. G.5 The unventilated duct or void is filled with a crushed inert infill to reduce to a minimum the volume of any gas which may accumulate. 2

G.6 In certain situations TracPipe can be used as a pipe in pipe installation.( refer to annex F in the latest revision of the TracPipe Design and Installation Guide H. Ventilation: H.1 Vertical and horizontal ducts containing TracPipe Corrugated Stainless Steel piping shall be ventilated to ensure that minor gas leakage does not cause the atmosphere within the duct to become unsafe. H.2 Vertical ducts may run freely through a number of stories or take the form of an enclosure at each story s level. Where ducts are continuous, ventilation can normally be achieved by the provision of openings sized in accordance with Table 1. Where the duct takes the form of an enclosure at each storey level, ventilation is normally required at high level only in each storey. Table 1. Free area of ventilation openings Cross sectional area Minimum free area of each of duct m2 opening m2 Not Exceeding 0.01 0 0.01 and not exceeding 0.05 0.05 and not exceeding 7.5 Exceeding 7.5 Cross sectional area of duct 0.05 1/150 of the cross sectional area of 3

I. Bend radius: TracPipe CSST runs should be installed with bend radiuses noted in Table 2. The bend radius should be measured at the inside of the bend. Table 2. Bend radii for TracPipe TracPipe Bend radius Size Recommended Minimum mm mm mm 12 76 15 15 76 20 22 76 25 28 125 76 32 125 76 40 125 76 50 150 102 J. Fire stopping: J.1 Buildings containing flats and maisonettes, installation pipes shall be fire stopped as they pass from one floor to another unless in their own protected shaft which is ventilated top and bottom to outside atmosphere. J.2 When pipes pass through the protecting structure (i.e. compartment walls or floors) all openings should be kept as small, and as few in number as practicable, and should be suitably fire stopped in such a manner as to allow thermal movement of the pipe and ensure the fire resistance is not impaired. J.3 Any proprietary fire stopping should, when tested in accordance with the appropriate part of BS 476, achieve the relevant periods of fire resistance for the structure in respect of load bearing capacity, integrity and insulation. K. Pipe Supports and Fittings: K.1 Sizes to DN15: 2.0 metres for vertical runs and 1.5 metres for horizontal runs. K.2 Sizes DN22 and above: 2.5 metres for vertical runs and 2.0 metres for horizontal runs. 4

L. Burial: L.1 Externally- Pipework up to DN32 should be buried in accordance with BS 6891: 2005(1) for natural gas and BS 5482-1: 2005(2) for Liquefied Petroleum Gas (LPG). For sizes DN40 and DN50, the requirements of IGEM/UP/2 Edition 2(3) should be followed for both natural gas and LPG. Joints must not be buried. L.2 BS 6891: 2005 (1) and BS 5482-1 (2) requires that TracPipe up to DN 32 should be buried externally at the following depths: Table 3. Burial Depths Pipework Location Minimum depth of cover (mm) Buried pipework in soil 375 Buried pipework below vehicular traffic 375 Buried below concrete with only pedestrian access 40 For TracPipe DN40 and DN50, IGEM/UP/2 Edition 2 (3) requires: Pipework Location Minimum depth of cover (mm) Carriageways 450 Path footways 375 Verges 375 Other fields and agricultural land 1100 Other private ground 375 L.3 Internally- TracPipe can be buried directly in concrete floors and should be installed in accordance with Table 3.There should be a minimum of 25mm depth of cover of screed above the TracPipe. Joints must not be buried. M. TracPipe Certification/Training M.1 Installers should be TracPipe certified. M.2 Omegaflex offers FREE on-site certification/training to any Installer, Mechanical Engineer or Architects. 5

N. Fittings: Part Number Description Size FGP-FST-12 AutoFlare DN12 x 3/8"R DN12 FGP-FST-15 AutoFlare DN15 x 1/2"R DN15 FGP-FST-22 AutoFlare DN22 x 3/4"R DN22 FGP-FST-28 AutoFlare DN28 x 1"R DN28 FGP-FST-32 AutoFlare DN32 x 1.1/4"R DN32 FGP-FST-40 AutoFlare DN40 x 1.1/2"R DN40 FGP-FST-50 AutoFlare DN50 x 2"R DN50 FGP-TM-12 Termination Mount DN12 DN12 FGP-TM-15 Termination Mount DN15 DN15 FGP-TM-22 Termination Mount DN22 DN22 FGP-TM-28 Termination Mount DN28 DN28 FGP-TF15-15 TracPipe Tee DN15xDN15xDN15 FGP-TF22-22 TracPipe Tee DN22xDN22xDN22 FGP-TF28-T28 TracPipe Tee DN28xDN28xDN28 FGP-TF22-T15 TracPipe Tee DN22xDN22xDN15 FGP-TF28-T15 TracPipe Tee DN28xDN28xDN15 FGP-RT-1001DN Tracpipe Tee DN28xDN22xDN15 FGP-RT-1002DN Tracpipe Tee DN28xDN22xDN22 FGP-RT-752DN TracPipe Tee DN22xDN15xDN15 FGP-CPLG-12 TracPipe Coupling DN12 DN12 FGP-CPLG-15 TracPipe Coupling DN15 DN15 FGP-CPLG-22 TracPipe Coupling DN22 DN22 FGP-CPLG-28 TracPipe Coupling DN28 DN28 FGP-CPLG-32 TracPipe Coupling DN32 DN32 FGP-CPLG-40 TracPipe Coupling DN40 DN40 FGP-CPLG-50 TracPipe Coupling DN50 DN50 FGP-15x15mm 15mm Comp for DN15 Trac FGP-22x15mm 15mm Comp for DN22 Trac FGP-22x22mm 22mm Comp for DN22 Trac FGP-28x22mm 22mm Comp for DN28 Trac FGP-28x28mm 28mm Comp for DN28 Trac FGP-32x22mm 22mm Comp for DN32 Trac FGP-32x35mm 35mm Comp for DN32 Trac FGP-22-1000MTR BS746 1"Female for DN22 Trac FGP-28-1000MTR BS746 1"Female for DN28 Trac FGP-32-1000MTR BS746 1"Female for DN32 Trac FGP-22-500BSP 1/2" BSP Female for DN22 Trac FGP-22-750BSP 3/4" BSP Female for DN22 Trac FGP-28-500BSP 1/2" BSP Female for DN28 Trac FGP-28-750BSP 3/4" BSP Female for DN28 Trac FGP-32-750BSP 3/4" BSP Female for DN32 Trac 6

O. Final Torque: Tighten nut and body as though you were making up a flared tubing joint. Note the relation between hex flats at this point and continue to tighten for two additional hex flats (one-third turn) to obtain required torque and final leak- tight metal-to-metal seal. Maximum torques for sealing are: P. Description/Dimensions DN Torque: N.m Ft.lbs 12 65 48 15 68 50 22 73 54 28 122 90 32 284 210 40 365 270 50 447 330 DN 10 15 20 25 32 40 50 Inch 3/8 1/2 3/4 1 1 1/4 1 1/2 2 Jacket O.D. (max) mm 17 22 28 35 42 49 66 Inside Dia. (nom) mm 11 15 21 27 33 40 52 Wall Thk (mm) 0.25 0.25 0.25 0.25 0.3 0.3 0.3 7

8

TABLE G4 - Approximate pressure drop (mbar per metre) through TracPipe CSST at a given flow rate (cubic mettres per hour), for NATURAL GAS (relative density 0.60) m^3/hr DN10 DN15 DN20 DN25 DN32 DN40 DN50 Notes: 0.25 0.0121 0.0027 0.0004 0.0002 - - - 0.50 0.0534 0.0115 0.0018 0.0006 0.0002 0.0001-0.75 0.1272 0.0266 0.0042 0.0015 0.0004 0.0002-1.00 0.2357 0.0482 0.0076 0.0026 0.0007 0.0003 0.0001 1.25 0.3803 0.0765 0.0120 0.0041 0.0011 0.0005 0.0001 1.50 0.5621 0.1116 0.0175 0.0060 0.0017 0.0008 0.0001 1.75 0.7821 0.1535 0.0240 0.0082 0.0023 0.0010 0.0002 2.00 1.0413 0.2023 0.0315 0.0108 0.0030 0.0014 0.0002 2.25 0.2581 0.0402 0.0137 0.0038 0.0017 0.0003 2.50 0.3210 0.0499 0.0170 0.0047 0.0021 0.0004 2.75 0.3910 0.0607 0.0206 0.0057 0.0026 0.0004 3.00 0.4681 0.0725 0.0246 0.0068 0.0030 0.0005 3.25 0.5523 0.0855 0.0290 0.0080 0.0035 0.0006 3.50 0.6438 0.0996 0.0337 0.0094 0.0041 0.0007 3.75 0.7426 0.1147 0.0388 0.0108 0.0047 0.0008 4.00 0.8487 0.1310 0.0443 0.0123 0.0054 0.0009 4.25 0.9621 0.1484 0.0501 0.0139 0.0060 0.0010 4.50 1.0828 0.1669 0.0563 0.0156 0.0068 0.0012 4.75 0.1865 0.0628 0.0174 0.0075 0.0013 5.00 0.2072 0.0698 0.0193 0.0083 0.0014 5.25 0.2290 0.0771 0.0214 0.0092 0.0016 5.50 0.2520 0.0847 0.0235 0.0101 0.0017 5.75 0.2761 0.0928 0.0257 0.0110 0.0019 6.00 0.3013 0.1012 0.0280 0.0119 0.0021 6.25 0.3276 0.1100 0.0305 0.0130 0.0022 6.50 0.3551 0.1191 0.0330 0.0140 0.0024 6.75 0.3838 0.1287 0.0356 0.0151 0.0026 7.00 0.4135 0.1386 0.0384 0.0162 0.0028 7.25 0.4444 0.1489 0.0412 0.0174 0.0030 7.50 0.4765 0.1595 0.0442 0.0186 0.0032 7.75 0.5097 0.1706 0.0472 0.0198 0.0035 8.00 0.5440 0.1820 0.0504 0.0211 0.0037 8.25 0.5795 0.1938 0.0536 0.0224 0.0039 8.50 0.6162 0.2059 0.0570 0.0238 0.0042 8.75 0.6540 0.2185 0.0604 0.0252 0.0044 9.00 0.6929 0.2314 0.0640 0.0267 0.0047 9.25 0.7331 0.2447 0.0677 0.0281 0.0049 9.50 0.7743 0.2584 0.0715 0.0297 0.0052 9.75 0.8168 0.2724 0.0753 0.0312 0.0055 10.00 0.8604 0.2869 0.0793 0.0328 0.0058 12.00 1.2512 0.4161 0.1150 0.0471 0.0083 14.00 0.5699 0.1574 0.0639 0.0114 16.00 0.7483 0.2066 0.0833 0.0149 18.00 0.9515 0.2626 0.1051 0.0188 20.00 1.1796 0.3254 0.1295 0.0233 25.00 0.5125 0.2014 0.0365 30.00 0.7430 0.2889 0.0526 35.00 1.0170 0.3920 0.0717 40.00 0.5106 0.0938 45.00 0.6447 0.1189 50.00 0.7942 0.1469 55.00 0.9591 0.1780 60.00 1.1393 0.2120 65.00 0.2490 70.00 0.2890 75.00 0.3320 80.00 0.3781 85.00 0.4271 90.00 0.4791 95.00 0.5341 100.00 0.5921 1) Pressure drop information based on Standard Conditions of 21C and 1 bar. 2) Flow rates / pressure drop information above include losses for four 90-degree bends and two end fittings. For tubing runs with additional bends or fittings, increase pipe length by the values given in Table G7. 9

TABLE G5 - Approximate pressure drop (mbar per metre) through TracPipe CSST at a given flow rate (cubic mettres per hour), for PROPANE (relative density 1.52) m^3/hr DN10 DN15 DN20 DN25 DN32 DN40 DN50 Notes: 0.25 0.0327 0.0072 0.0011 0.0004 0.0001 0.0001-0.50 0.1445 0.0301 0.0048 0.0016 0.0005 0.0002-0.75 0.3445 0.0696 0.0109 0.0038 0.0010 0.0005 0.0001 1.00 0.6382 0.1261 0.0197 0.0068 0.0019 0.0009 0.0001 1.25 1.0297 0.2001 0.0312 0.0106 0.0030 0.0013 0.0002 1.50 1.5219 0.2918 0.0454 0.0154 0.0043 0.0019 0.0003 1.75 2.1178 0.4014 0.0623 0.0212 0.0059 0.0026 0.0004 2.00 2.8195 0.5291 0.0819 0.0278 0.0077 0.0034 0.0006 2.25 0.6751 0.1044 0.0353 0.0098 0.0043 0.0007 2.50 0.8395 0.1296 0.0438 0.0121 0.0053 0.0009 2.75 1.0225 0.1576 0.0532 0.0147 0.0064 0.0011 3.00 1.2242 0.1885 0.0635 0.0176 0.0076 0.0013 3.25 1.4446 0.2221 0.0748 0.0207 0.0089 0.0015 3.50 1.6839 0.2587 0.0870 0.0241 0.0103 0.0018 3.75 1.9423 0.2981 0.1001 0.0277 0.0118 0.0020 4.00 2.2197 0.3403 0.1142 0.0316 0.0134 0.0023 4.25 2.5162 0.3854 0.1292 0.0358 0.0151 0.0026 4.50 2.8321 0.4335 0.1452 0.0402 0.0170 0.0030 4.75 0.4844 0.1622 0.0449 0.0189 0.0033 5.00 0.5382 0.1800 0.0498 0.0209 0.0036 5.25 0.5949 0.1989 0.0550 0.0230 0.0040 5.50 0.6546 0.2187 0.0605 0.0252 0.0044 5.75 0.7172 0.2394 0.0662 0.0276 0.0048 6.00 0.7827 0.2612 0.0722 0.0300 0.0053 6.25 0.8512 0.2838 0.0785 0.0325 0.0057 6.50 0.9226 0.3075 0.0850 0.0351 0.0062 6.75 0.9970 0.3321 0.0918 0.0378 0.0067 7.00 1.0743 0.3577 0.0989 0.0407 0.0072 7.25 1.1546 0.3842 0.1062 0.0436 0.0077 7.50 1.2378 0.4117 0.1138 0.0466 0.0082 7.75 1.3241 0.4402 0.1216 0.0498 0.0088 8.00 1.4133 0.4696 0.1297 0.0530 0.0094 8.25 1.5055 0.5000 0.1381 0.0563 0.0100 8.50 1.6008 0.5314 0.1468 0.0597 0.0106 8.75 1.6990 0.5638 0.1557 0.0633 0.0112 9.00 1.8002 0.5972 0.1649 0.0669 0.0119 9.25 1.9044 0.6315 0.1744 0.0706 0.0126 9.50 2.0116 0.6668 0.1841 0.0744 0.0133 9.75 2.1219 0.7031 0.1941 0.0784 0.0140 10.00 2.2352 0.7403 0.2044 0.0824 0.0147 12.00 3.2506 1.0738 0.2963 0.1182 0.0212 14.00 1.4706 0.4055 0.1604 0.0289 16.00 1.9311 0.5322 0.2089 0.0378 18.00 2.4555 0.6765 0.2638 0.0480 20.00 3.0442 0.8383 0.3249 0.0593 25.00 1.3206 0.5053 0.0928 30.00 1.9143 0.7250 0.1339 35.00 2.6202 0.9836 0.1826 40.00 1.2812 0.2388 45.00 1.6176 0.3027 50.00 1.9927 0.3741 55.00 2.4064 0.4531 60.00 2.8587 0.5398 65.00 0.6340 70.00 0.7359 75.00 0.8454 80.00 0.9626 85.00 1.0873 90.00 1.2198 95.00 1.3599 100.00 1.5076 1) Pressure drop information based on Standard Conditions of 21C and 1 bar. 2) Flow rates / pressure drop information above include losses for four 90-degree bends and two end fittings. For tubing runs with additional bends or fittings, increase pipe length by the values given in Table G7. 10

TABLE G6 - Approximate pressure drop (mbar per metre) through TracPipe CSST at a given flow rate (cubic mettres per hour), for BUTANE (relative density 2.07) m^3/hr DN10 DN15 DN20 DN25 DN32 DN40 DN50 Notes: 0.25 0.0455 0.0099 0.0016 0.0005 0.0002 0.0001 0.0000 0.50 0.2012 0.0414 0.0065 0.0023 0.0006 0.0003 0.0000 0.75 0.4797 0.0957 0.0150 0.0051 0.0014 0.0007 0.0001 1.00 0.8886 0.1736 0.0271 0.0093 0.0026 0.0012 0.0002 1.25 1.4336 0.2755 0.0429 0.0146 0.0041 0.0018 0.0003 1.50 2.1190 0.4017 0.0623 0.0212 0.0059 0.0026 0.0004 1.75 2.9486 0.5525 0.0855 0.0290 0.0080 0.0036 0.0006 2.00 0.7283 0.1125 0.0381 0.0106 0.0046 0.0008 2.25 0.9292 0.1433 0.0484 0.0134 0.0058 0.0010 2.50 1.1555 0.1780 0.0600 0.0166 0.0072 0.0012 2.75 1.4073 0.2165 0.0729 0.0202 0.0087 0.0015 3.00 1.6849 0.2588 0.0870 0.0241 0.0103 0.0018 3.25 1.9883 0.3051 0.1025 0.0284 0.0121 0.0021 3.50 2.3177 0.3552 0.1192 0.0330 0.0140 0.0024 3.75 2.6732 0.4093 0.1372 0.0380 0.0161 0.0028 4.00 0.4673 0.1565 0.0433 0.0182 0.0032 4.25 0.5293 0.1771 0.0490 0.0206 0.0036 4.50 0.5953 0.1990 0.0551 0.0230 0.0040 4.75 0.6652 0.2222 0.0615 0.0256 0.0045 5.00 0.7391 0.2467 0.0682 0.0284 0.0050 5.25 0.8170 0.2725 0.0754 0.0312 0.0055 5.50 0.8989 0.2997 0.0828 0.0343 0.0060 5.75 0.9849 0.3281 0.0907 0.0374 0.0066 6.00 1.0749 0.3578 0.0989 0.0407 0.0072 6.25 1.1689 0.3889 0.1075 0.0441 0.0078 6.50 1.2670 0.4213 0.1164 0.0477 0.0084 6.75 1.3691 0.4550 0.1257 0.0514 0.0091 7.00 1.4753 0.4901 0.1354 0.0552 0.0098 7.25 1.5856 0.5264 0.1454 0.0592 0.0105 7.50 1.6999 0.5641 0.1558 0.0633 0.0112 7.75 1.8183 0.6031 0.1666 0.0675 0.0120 8.00 1.9409 0.6435 0.1777 0.0719 0.0128 8.25 2.0675 0.6852 0.1892 0.0764 0.0136 8.50 2.1983 0.7282 0.2010 0.0811 0.0145 8.75 2.3331 0.7726 0.2133 0.0859 0.0153 9.00 2.4721 0.8183 0.2258 0.0908 0.0162 9.25 2.6153 0.8653 0.2388 0.0959 0.0171 9.50 0.9137 0.2521 0.1011 0.0181 9.75 0.9634 0.2658 0.1064 0.0191 10.00 1.0144 0.2799 0.1119 0.0201 12.00 1.4714 0.4057 0.1605 0.0289 14.00 2.0151 0.5553 0.2177 0.0395 16.00 2.6460 0.7289 0.2836 0.0516 18.00 0.9264 0.3580 0.0654 20.00 1.1481 0.4411 0.0808 25.00 1.8086 0.6860 0.1266 30.00 2.6217 0.9842 0.1827 35.00 1.3353 0.2491 40.00 1.7393 0.3258 45.00 2.1959 0.4129 50.00 2.7051 0.5103 55.00 0.6181 60.00 0.7363 65.00 0.8649 70.00 1.0038 75.00 1.1532 80.00 1.3130 85.00 1.4833 90.00 1.6639 95.00 1.8550 100.00 2.0566 1) Pressure drop information based on Standard Conditions of 21C and 1 bar. 2) Flow rates / pressure drop information above include losses for four 90-degree bends and two end fittings. For tubing runs with additional bends or fittings, increase pipe length by the values given in Table G7. 11