Gasloc Multifunctional gas control Combined regulator and safety shut-off valves Electrically modulating G-M(P) 055 D01 Two stage operating mode G-(LEP)Z 055 D01 3.0 Printed in Germany Edition 05.11 Nr. 0 1 1 6 Technical Description Multiple actuator to EN 16 comprising electro-magnetically controlled regulator unit for modulating or two stage mode: - Modulator with adjustable min. and max. limiter - Ignition gas, optional - Constant volume flow using servo pressure regulator with servo regulator - Max. operating pressure 65 mbar (6,5 kpa) - Different variants according to application Application Suitable for gases to EN 37 and other gaseous inert media. Approvals EU type test approval as per EU Gas Appliance Directive. G-M(P) 055 D01 CE-0085 CM 0036 G-(LEP)Z 055 D01 CE-0085 CM 0036 Approvals in other important gasconsuming countries.
Combinations Multifunctional gas control valve G-M(P) 055 D01 Specification Main types electro-magnetically controlled servo pressure regulator two stage adjustably servo-pressure regulator Operating valve Solenoid valve [class Safety valve Solenoid valve [class] minimum modulator current [ma] maximum modulator current [ma] two stage operating mode 30 V AC min. and max. burner pressure adjustable Dirt trap device Ignition gas connection Gas pressure switch Line socket MPA 109x G-M 055 D01 G-MP 055 D01 G-Z 055 D01 165 165 standard optional not available Type key of Gasbloc G- XXXXX XXX DXX SXX Pressure instrument glands On inlet and outlet sides Control of V1 and V 0 = common = separated Outlet pressure Inlet pressure 0 = 0 mbar bis 65 mbar = 1,5-0 mbar bis 65 mbar = 3-0 mbar bis 65 mbar S = Series (type-independent) Gas train schematic diagram 1 = two class solenoid valves with pressure regulator = two class solenoid valves without pressure regulator Valve design 0 = Double valve 1 = Single valve, right angle = Single valve, straight Design type (generation) D Construction size, nominal diameter 05 = p max. = 65 mbar 3 = Rp 1/ 5 = Rp 1/ 7 = Rp 3/ Opening behaviour + main volume restrictor without = fast-opening, fast-closing -L = slow-opening -E = adjustable start gas -P = pilotgas connection -G = Gas/Air ratio -D = main flow setting -N = Zero-Governor -M = electrical modulating type -W = Whirlwind version -Z = two stage Solenoid valve modes Mode 1 V1 and V can be activated and opened either together or separately. Mode V1 and V are opened and activated separately. Pilot gas outlet is released and V1 opens. When the flame has been detected, release is performed and V opens. Gasloc Description of main components Pressure regulator and modulator The pressure control unit and servo regulator compensates for pressure fluctuations in the supply network. This ensures a constant volume flow at constant injector pressure. The injector pressure can be regulated by controlling an electrical modulator between adjustable minimum and maximum values. In the two-stage operating mode, the control toggles between the maximum and minimum values. Filter Fine-meshed strainer to protect fitting. Pilot gas Pilot gas connection between V1 and V. Gas pressure switch Optional equipment Monitors gas pressure on the inlet side for gas leakage protection. The pressure switch can be pre-adjusted and sealed to customer specifications. lock diagram A Filter Automatic shut-off valves C Pressure regulator D Servo-pressure regulator E Electrical modulator F Pilot gas outlet p 1 Test nipple, inlet Test nipple, outlet A p 1 V1 V C E D Solenoid valves Solenoid valves as per EN 161, Class. DC coils are protected against voltage transients. F 6
Functional diagram G-M(P) 055 D01 Legend 15 1 13 1 11 7 5 6 3 1 p 1 V1 V p p 10 16 9 8 1 Fine-meshed strainer Housing 3 Valve V1 Closing spring 5 Plunger V1 6 Test nipple 7 Solenoid V1 8 Valve V 9 Ignition gas connection 10 Solenoid V 11 Working diaphragm 1 Return spring 13 Operating valve 1 Electrical connection 15 Servo-pressure regulator 16 Modulator coil Current-pressure characteristic G-M(P) 055 D01 for G-(LEP)Z 055 D01: only on/off p [mbar] 1 1 Injector pressure 10 8 6 0 0 0 0 60 80 100 10 10 160 I [ma] Modulator current 3 6
Dimensions [mm] Electrical connection 58 ø 9 Ignition gas connection M8 x 1 x M - 7 deep Rp 1/ ISO 7/1 10 0,5 Standard ox with cable connection IP 0 Molex Crimp System 3001 1,5 1,5 30,5 ø 55 3 15, 8 58 60 3 8, 18,9 105 Adjusting devices Reference value setting min. and max. burner pressure Solenoid coils Pressure test nipple P Pressure test nipple P 1 Volume flow pressure difference characteristic G-M(P) 055 D01 - electrical modulating as per DIN EN 16 G-(LEP)Z 055 D01 - two stage as per DIN EN 16 Inlet pressure range (mbar) nd gas family P NOM. P MAX. P MIN. Natural gas-h-e Natural gas-l 0 5 5 30 17 0 Permissible deviation Pressure regulator class C - nd gas family + 10 % - 15 % as per EN 16 6
Volume flow pressure difference characteristic G-M(P) 055 D01 - electrical modulating as per DIN EN 16 G-(LEP)Z 055 D01 - two stage as per DIN EN 16 Inlet pressure range (mbar) 3rd gas family P NOM. P MAX. P MIN. Propane 37 5 5 Permissible deviation Pressure regulator class C - 3rd gas family ±10 % as per EN 16 Volume flow pressure difference characteristic G-M(P) 055 D01 - electrical modulating as per DIN EN 16 G-(LEP)Z 055 D01 - two stage as per DIN EN 16 Inlet pressure range (mbar) 3rd gas family utane/propane P NOM. P MAX. 57,5 P MIN.,5 Permissible deviation Pressure regulator class C - 3rd gas family ±10 % as per EN 16 Volume flow pressure difference characteristic G-M(P) 055 D01 G-(LEP)Z 055 D01 100 80 60 0 recommended work range 30 p [mbar] 0 10 8 6 5 3 ased on + 15 C, 1013 mbar, dry 1 0,1 0, 0,3 0, 0,,6 0,8 1 3 5 6 7 8 910 0 Vn 3 [m /h] Luft / Air / Aria dv = 1,00 5 6 0, 0,3 0, 0,,6 0,8 1 3 5 6 7 8 910 0 30 Vn 3 [m /h] Erdgas/Natural gas/gaz Naturel/Gas metano dv = 0,65
Gasloc Multifunctional gas control Combined regulator and safety shut-off valves Electrically modulating G-M(P) 055 D01 Two stage operating mode G-(LEP)Z 055 D01 Specifications Nominal diameter DN 15 Gas connection Rp 1/ G 3/ ISO 7/1 DIN ISO 8 OD Flange with tube thread Rp 1/ G 3/ ISO 7/1 ID DIN ISO 8 OD Pilot gas connection Max. inlet pressure Outlet pressure rang e of regulator Nominal flow Ambient temperature Automatic shut-off valves Group Pressure regulator Degree of protection Opening time Closing time Switch on duration Voltage/frequency Load of coil ( V, 30 V) Electrical Data of Modulator G-M Electrical Data of Modulator G-Z Electrical connection Optional equipment Installation position We reserve the right to make any changes in the interest of technical progress. M8 x 1 ø mm 65 mbar (6.5 kpa) 1.5 mbar (0,15 kpa) to 0 mbar (0.0 kpa) - neutral gas 3.0 mbar (3 kpa) to 37 mbar (3.7 kpa) - liquid gas max - min 3 mbar (0.3 kpa) 3,3 m 3 /h (Air) at p 5 mbar (0.5 kpa), governed -15 C to +70 C 0 C to +70 C at LPG Class as per EN 16 Class C IP 0 Fast-opening < 1 s < 1 s 100 % ED ~(AC) - 60 Hz V +10 % 15 % ~(AC) - 60 Hz 30 V +10 % 15 % x 5,5 VA Operating voltage max. (DC) 8 V Operating current max. 165 ma Resistance at +0 C 15 Ω Operating voltage 30 V AC Operate only with Dungs connecting plug Resistance at +0 C 9800 Ω Molex System connection coil or Option: Connection box with integrated cable Modulator connection 6.3 x 0.8 mm Flat plug-in sleeves Electrical connections in Rast 5 Automatic burner control MPA 109x Gas pressure switch GW A5 Solenoid at any position between vertical and horizontal axis. Head Offices and Factory Karl Dungs GmbH & Co. KG Siemensstraße 6-10 D-73660 Urbach, Germany Telefon +9 (0)7181-80-0 Telefax +9 (0)7181-80-166 Postal adress Karl Dungs GmbH & Co. KG Postfach 1 9 D-7360 Schorndorf, Germany e-mail info@dungs.com Internet www.dungs.com 6 6