These Instructions apply to all high-voltage installations where Statnett has operational responsibility.

Similar documents
These Instructions apply to all high-voltage installations where Statnett has operational responsibility.

These Instructions apply to all low-voltage installations where Operations Manager HV in Statnett has authority as Operations Manager LV.

The Statkraft Way. Switching Supervisor

Low Voltage Electricity System Safety Rules & Associated Safety Guidance

PSSI 1 High Voltage Switching

ELECTRICAL SAFETY. Unsafe work practices near electricity can kill you! You are responsible for protecting yourself from electrical shock.

Control of Hazardous Energy Lockout / Tagout Program

Management Plan for Electrical Safety ISD #535

LOCK-OUT / TAG-OUT SYSTEM & PROCEDURE

To Loughborough University (LU) Facilities Management (FM) Health and Safety Policy

Nordel GRID DISTURBANCE AND FAULT STATISTICS

Safe Schools: A Health and Safety Check

Operating Process Work on Low Voltage or Mechanical Apparatus

Original Date of Issue: 04/09

Electrical. Version 1.0

NORDIC AND BALTIC GRID DISTURBANCE STATISTICS 2014

Status Date Prepared Reviewed Endorsed Approved

E2.14 Control of Hazardous Energy. Effective Date: 03/01/2018

PSSI 3 High Voltage Metal-Enclosed Switchgear

STCP 01-1 Issue 005 Operational Switching

SAFETY DIRECTIVE 2.0 DEPARTMENTS AFFECTED. This Administrative Directive shall apply to all Town of Marana departments and employees.

ISOLATION ISSUE 2 1 AIM 2 4 REASONS FOR INCLUSION 3 6 PLANT AND EQUIPMENT REQUIREMENTS 3 7 SYSTEM & PROCEDURAL REQUIREMENTS 4 8 PEOPLE REQUIREMENTS 6

Responsibilities / Accountability

Lockout/Tagout Plan Environmental Health & Safety Office July 2017

SAFETY QUALITY TECHNOLOGY. Guidance on Safe Isolation Procedures

NORTHERN POWERGRID. Distribution Safety Rules 2015 Edition

Energy Networks Management Safety Procedures DEFINITIONS

ELECTRICAL (COMPREHENSIVE) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR CFR , ,

STCP 01-1 Issue 008 Operational Switching

Field Instruction. This instruction outlines the minimum requirements for all Horizon Power workers who undertake Vegetation Management Work.

SAINT MARY S COLLEGE OF CALIFORNIA STANDARD HAZARDOUS ENERGY CONTROL PROGRAM INCLUDING LOCKOUT/TAGOUT. Prepared by

THE UNIVERSITY OF NORTH CAROLINA

Lockout/Tagout Program

Electrical Safety Program

STCP 08-2 Issue 004: Circuit Live Trip & DAR Tests

Lockout / Tag out Program

Energy Control. Suite 2A, 55 Frid Street Hamilton, ON L8P 4M3 office: cell:

IEC April Authorized Sole Agent : PT. Wisma Niagatama Perkasa. Phone : (031) Fax. : (031)

Lockout/Tagout Program

LOCK-OUT/TAG-OUT (LO/TO) SAFETY PROGRAM

2. The purpose of this program is to achieve the following objectives:

230-LOCKOUT/TAGOUT PROGRAM

Issue: Issued By: Environment, Health & Safety Part: Hazard Identification and Assessment Revision #: 2 Revision

DUQUESNE UNIVERSITY LOCKOUT/TAGOUT PROGRAM

Sample Written Program for The Control of Hazardous Energy (Lockout/Tagout)

TAMPA ELECTRIC COMPANY ENERGY SUPPLY HAZARDOUS ENERGY CONTROL LOCKOUT PROGRAM

Document Control Summary Status: Replacement for Electricity High Voltage SOP v1.0 Version: V1.1 Date: July 2017 Author/Title: Owner/Title:

LOCKOUT/TAGOUT: Operating Procedure TABLE OF CONTENTS

Construction & Building Industry Safety Guideline. Electrical Isolations

It is essential that the maintenance staff is qualified for electrical works and follows safety procedures.

Page: 7/15/2009. Energy control procedures Use of lockout/tagout equipment to ensure safe work practices.

Status Date Prepared Reviewed Endorsed Approved

LOCKOUT/TAGOUT PROGRAM

University of Arkansas Office of Environmental Health and Safety

Electrical Safety Work Practices

Lockout/Tagout - Control of Hazardous Energy Program

Control of Hazardous Energy Program (Lockout/Tagout)

Central Washington University

WESTERN CONNECTICUT STATE UNIVERSITY LOCKOUT/TAGOUT PROCEDURE S-107

I003 Lock Out - Tag Out - Try Out. Document information

Lockout / Tagout Safety Program

PAGE 1 OF 7 HEALTH, SAFETY & ENVIROMENTAL MANUAL PROCEDURE: S230 Lock-Out Tag-Out (LOTO) Program REV 4.0 8/13/2012

LOCKOUT/TAGOUT POLICY

Big 5 Site Training Support Information

MARIPOSA COUNTY LOCKOUT/TAGOUT PROGRAM

SOP GEN-007I Energy Isolation

National Grid UK Electricity Transmission plc. NATIONAL SAFETY INSTRUCTION and Guidance

Power Unit 075. Maintain Substation Circuit Breakers

Control of Hazardous Energy Program (LOTO)

Safety Regulations and Procedures

Project: Consultant : MEP Contractor: PREPARED BY: DORMAN SMITH SWITCHGEAR - DUBAI REVIEWED BY CONSULTANT : Page 1 of 15

: Electric Power Generation, Transmission, and Distribution. Region IV - OSHA

References 6 k thermal overload relays, adjustable from 0.11 to 16 A

Infrared Thermography Inspection Guidelines. Date Issued:

CONTROL OF HAZARDOUS ENERGY (LOCKOUT/TAGOUT) PROGRAM

Preparer: Owner: Approver: EHS Team Member TES Manager Site Manager

DuPage County Environmental, Safety, Health & Property Loss Control Program Hazardous Energy Control (Lockout/Tagout)

PROCEDURES FOR STANDBY

Lockout Tagout Policy

MISSOURI UNIVERSITY OF SCIENCE & TECHNOLOGY Procedure: 3.6

Health and Fire Safety Review 2/15

PSSI 10 Plant and Apparatus Containing Dielectric Gas

Hazardous Energy Control (Lockout-Tagout)

Lockout/Tagout - Energy Control Program

CITY AND COUNTY OF DENVER CR&CF RISK UNIT Safe Operating Procedure

ES18 Security Theory/Regulations Answer Schedule

MAINTENANCE AND SAFETY OF CNG REFUELLING STATIONS

LOCKOUT/TAGOUT PLAN August 2015

CONTROL OF HAZARDOUS ENERGY (LOCKOUT/TAGOUT)

SM6. instructions for use. connection with compartment for incoming cable from the top. MV distribution factory built assemblies at your service

WORKING AFTER-HOURS OR ALONE GUIDELINE

Lifting Operation & Lifting Equipment Procedure

Plant Isolation Lock out/tag out Procedure

Electrical Safety. Hazard Awareness

ANNUAL RELIABILITY AND POWER QUALITY REPORT for the year ended 30 June 2017

Hazardous Energy Control/Lockout

Health & Safety Policy & Plan. Rightway Roofing.

CONTROL OF HAZARDOUS ENERGY LOCKOUT/TAGOUT PROGRAM

Lockout/Tagout Training Overview. Safety Fest 2013

CONFINED SPACE AWARENESS

Transcription:

Based on the Norwegian document number 1169509 rev. 10 Page: 1 of 7 1 Governing policy and legislation These Instructions for the Switching Supervisor are subject to Statnett s Funksjonspolicy for elsikkerhet (Functional Policy for Electrical Safety). They are a supplement to, and superceded by FSE 2006 (Safety regulations related to the maintenance and operation of electrical installations) which is pursuant to the "Lov om tilsyn med elektriske anlegg og utstyr" (Act relating to the Inspection of Electrical Installations and Electrical Equipment). 2 Purpose and validity The purpose of these Instructions is to ensure a high level of safety during work on or in the vicinity of Statnett electrical installations and during their operation, by requiring adequate planning of all activities and the implementation of necessary safety practices to avoid any risk to life, health or property. These Instructions apply to all high-voltage installations where Statnett has operational responsibility. 3 Intended audience All Statnett employees and external personnel who are authorised Switching Supervisors on electrical installations where Statnett has operational responsibility, and personnel who are conducting tasks ordered by the Switching Supervisor, according to these instructions. 4 Definitions Switching Supervisor: Person appointed to have responsibility for ensuring that all necessary switching operations in high-voltage installations are conducted safely. Safety Supervisor HV (high voltage): Person appointed to have responsibility for electrical safety at the worksite. Operations Manager HV (high voltage): Person appointed by the owner/manager to carry out and be responsible for the ongoing management and maintenance of the electrical installations.

Based on the Norwegian document number 1169509 rev. 10 Page: 2 of 7 5 Switching Supervisor 5.1 Primary Duty Officer at the Northern and Southern Regional Centres 5.1.1 Following applicable routines, a Primary Duty Officer is appointed at the relevant regional centre. The Primary Duty Officer also takes on the role of Switching Supervisor and has authority to conduct switching operations. The Primary Duty Officer may delegate switching tasks to another authorized Switching Supervisor. 5.2 Switching 5.2.1 The Switching Supervisor shall plan and normally conduct all switching operations himself/herself. For complex switching operations, a written switching plan should be used, either in the form of previously defined lists of operations, or a dedicated switching plan for the operation concerned. 5.2.2 When switching operations take place at the local substation, all instructions and switching must be recorded in the duty log. The Switching Supervisor must give each switching order as a spoken order, and the person carrying out the order must repeat it aloud and write it down before carrying it out. If the other party fails to repeat an order, the Switching Supervisor must request the order to be repeated. A switching order must comprise details of the function identification tag on the breaker and the word IN or OUT. When the switching task has been completed, the person who has carried out the order must confirm this to the Switching Supervisor by stating the breaker s function identification tag and new position. Persons who perform switchings locally shall either have authorization "GP" in the security card database, have authorization Safety Supervisor HV for work on or in the vicinity of earthed and short-circuited installations for the substation, or have specific authorization from the Operations Manager HV to perform switchings associated with function testing, ref. section 5.2.4. 5.2.3 If it is not possible to operate a breaker from the control board or display, substation personnel must immediately contact the Switching Supervisor before continuing the switching operation, cf. section 5.4 Switching from an unsafe position and section 5.5 Noninterlocking operations. 5.2.4 The Switching Supervisor may delegate switching tasks associated with function testing of specified switches to personnel who have Safety Supervisor HV authorization or specific authorization from the Operations Manager HV. Both parties must note the breaker s function identification tag in writing. Cf. section 5.4 Switching from an unsafe position and section 5.5 Non-interlocking operations. 5.3 Switching and other measures in association with work on or in the vicinity of earthed and short-circuited installations 5.3.1 For operations not involving remote-controlled substations, the Switching Supervisor must plan all switching operations with the substation personnel or the person appointed as Safety Supervisor HV, and ensure that all switching operations that are necessary before work can start, have been completed as specified in section 5.2.2.

Based on the Norwegian document number 1169509 rev. 10 Page: 3 of 7 5.3.2 The Switching Supervisor must ensure that disconnection and, if necessary, terminal earthing has been carried out. 5.3.2.1 When terminal earthing is performed by use of mobile earthing equipment, a Safety Supervisor HV must be appointed.local voltage testing is mandatory, and there must be two persons present. At least one of these persons must hold Safety Supervisor authorization HV (The Swiching Supervisor must check this). For the other person, an access permit is required (ref. Instructions for access to Statnett's electrical installations) for the installation. If the Switching Supervisor carries out manual terminal earthing, this must be recorded and checked in the electronic duty log. At a local level, the earthing equipment must be labelled with the words: "Manual terminal earthing may only be removed by order from the Switching Supervisor". 5.3.3 The Switching Supervisor is responsible for providing labelling on all disconnectors, circuit breakers, and/or disconnecting circuit breakers (DCBs), and terminal earthing affected by switching orders. Labelling must be performed at regional control centres and all places in the substation control room from where switching operations may be carried out (on screen, control/selector switches etc.). In addition, motor fuses that are disconnected as protection against reconnection/disconnection (cf. section 5.3.4) must be labelled. Persons who perform labelling shall have authorization "GP" in the security card database or have authorization Safety Supervisor HV for work on or in the vicinity of earthed and shortcircuited installations for the substation. 5.3.4 The Switching Supervisor is responsible for preventing reconnection by blocking all disconnectors and DCBs that could become energized, either by removing motor fuses (these must be labelled, cf. section 5.3.3), or shutting off the supply of compressed air, or locking service devices, or blocking the operating mechanism. Terminal earthing must be blocked against disconnection in a similar manner. At SF6 installations, terminal earthing must be locked in the connected position. When locking DCB switches these must be physically locked in the disconnected position by means of a lock or splint. Persons who perform preventing reconnection shall have authorization "GP" in the security card database or have authorization Safety Supervisor HV for work on or in the vicinity of earthed and short-circuited installations for the substation. 5.3.5 The Switching Supervisor is responsible for ensuring terminal earthing and disconnectors are inspected (visually), and for obtaining feedback on the inspection. When preparing for inspection of DCBs, the Switching Supervisor must order the person conducting the inspection to check for normal SF6-pressure at all three breaker poles. If the pressure is too low in one or more of the breaker poles, the breaker is not to be considered disconnected (ref.5.3.2.1). Persons who perform inspection shall have authorization "GP" in the security card database or have authorization Safety Supervisor HV for work on or in the vicinity of earthed and short-circuited installations for the substation. 5.3.6 The Switching Supervisor is responsible for verbally appointing a Safety Supervisor HV to carry out the work. When appointing a Safety Supervisor HV, the Switching Supervisor must inform the Safety Supervisor HV of all safety measures that have been implemented (disconnection, labelling, safeguards against reconnection, terminal earthing). 5.3.7 The Switching Supervisor is responsible for ensuring that a log is kept of all connections, messages and appointments that are related to the task.

Based on the Norwegian document number 1169509 rev. 10 Page: 4 of 7 5.3.7.1 The Switching Supervisor must record the number of portable earthing equipment the Safety Supervisor intends to use in connection with the work. 5.3.7.2 The Safety Supervisor must state the number of portable earthing equipment that have been removed. The Switching Supervisor must then check that this tallies with the number recorded in connection with the appointment of the Switching Supervisor. 5.3.8 The Switching Supervisor is responsible for ensuring that all safety measures (implemented by the Switching Supervisor) are reversed when the Safety Supervisor HV has declared the operation completed, and has issued notification that the installation will be reenergised. Persons who perform reversal of safety measures locally in the substation (labelling, prevention, inspection) shall have authorization "GP" in the security card database or have authorization Safety Supervisor HV for work on or in the vicinity of earthed and shortcircuited installations for the substation. 5.3.9 The Switching Supervisor is responsible for ensuring that the installation is reenergised in a suitable manner, without any risk to persons or property. 5.4 Switching from an unsafe position. 5.4.1 Switches must be deenergised on both sides during all switching operations carried out from a position where the pressure increase, should a short circuit or switch failure occur, could cause injury 1. The same applies to work involving outdoor circuit breakers. Voltage tests should be carried out to check that the switches are deenergised. The same requirements apply to voltage testing equipment, voltage tests and test personell as those given in 5.3.2. 5.4.2 Two people must always be present during this type of switching work. At least one of these must have Safety Supervisor HV authorization or specific authorization for the task from the Operations Manager HV. For the other person, an access permit is required (ref. Instructions for access to Statnett's electrical installations) for the installation. 5.4.3 The Switching Supervisor must check that the correct order of switching operations and corresponding function identification tags has been noted by the person carrying out the switching order. 5.5 Non- interlocking 2 operations 5.5.1 If non-interlocked operations are necessary in a high-voltage installation a detailed description is required to explain how this is to be carried out. 5.5.2 These detailed instructions must be sent by the relevant Substation Manager or person he has authorised, to the Operations Manager for approval. 5.5.3 Approved instructions must be sent to the Switching Supervisor by email. 1 Indoor installations that fail to meet the requirements in FEF 2006 4-9 and guidelines. Documentation that FEF 4-9 requirements have been met is mandatory if the requirement regarding deenergised switches is not applicable. 2 Entails removing mechanical locking or other construction-type safety locking set up to prevent undesirable situations developing in connection with switching operations in a high-voltage installation.

Based on the Norwegian document number 1169509 rev. 10 Page: 5 of 7 5.6 Work in the vicinity of a high-voltage installation (not live working) 5.6.1 The Substation Manager or Transmission Line Manager, or other person granted this authority, must appoint a Safety Supervisor HV for work in the vicinity of a live installation. 5.6.2 The Safety Supervisor HV is responsible for all safety measures at the work site. 5.6.3 The Switching Supervisor must not make any test switchings subsequent to a power outage, without first informing the Safety Supervisor HV. 5.7 Live working 5.7.1 Live working may only be conducted by persons who have received the necessary training. Detailed work procedures must be prepared. These procedures must be approved by the Operations Manager. The presence of approved procedures is to be checked by the Switching Supervisor. 5.7.2 The Switching Supervisor must ensure that auto-reclose is blocked at both ends of the line, and that automatic connection and disconnection of reactive devices connected to bus bars at both ends of the line is blocked. 5.7.3 Test switchings following a power outage are not permitted until the Safety Supervisor HV has been informed. 5.7.4 The Switching Supervisor must notify the Safety Supervisor before doing manual switching work on associated busbars at each end of the line. Generators and reactive devices with automatic connection and disconnection functions connected to busbars at both ends of the line can be synchronized to the grid or disconnected from the grid. 5.7.5 The Switching Supervisor should appoint a Safety Supervisor HV for the operation in accordance with Instructions for the Safety Supervisor HV in case of Live Work. 5.7.6 The HV Safety Supervisor is responsible for all safety measures at the work site. 5.7.7 The Switching Supervisor is responsible for ensuring that the safety measures mentioned in sections 5.6.2, 5.6.3 and 5.6.4 are reversed or dismantled following notification from the Safety Supervisor HV that live working has ceased. 5.8 Notification of an earth fault on the grid 5.8.1 The Switching Supervisor must notify the Safety Supervisor HV if an earth fault is registered on the grid. 5.9 Notification of lightning activity on the grid 5.9.1 The Switching Supervisor must notify the Safety Supervisor HV if lightning is registered on the grid.

Based on the Norwegian document number 1169509 rev. 10 Page: 6 of 7 5.10 Notification of pressure drop in secured SF6- and DCB switches 5.10.1 The Switching Supervisor must report to the Safety Supervisor if a pressure drop is registered in secured SF6- and DCB switches. 6 Abstinence from intoxicants The person appointed as Switching Supervisor must agree to refrain from consuming alcohol or other intoxicants during the 8 hours prior to starting work. 7 Confirmation of compliance Responsibility for checking compliance with instructions lies with the document holder and approving body. The position of Operations Manager HV includes authority to draw up and approve work procedures, guidelines and instructions in areas covered by Funksjonspolicy for elsikkerhet (Functional Policy for Electrical Safety Norwegian document only). 8 Enclosures and references References: Funksjonspolicy for elsikkerhet (Functional Policy for Electrical Safety Norwegian document only) (SDOK-515-2) Instructions for the Safety Supervisor HV (doc.no. 1198675 in IFS) Instruction for access to Statnett's electrical installations (doc.no. 1251620 in IFS) Instruks vedrørende "Stedfortreder for driftsleder" (Instruction regarding "deputy HV Operations Manager" Norwegian document only) (doc.no. 1163219 in IFS) Procedures for communication between the Safety Supervisor HV and the Switching superviser (doc.no. 2110202 in IFS) Procedures for use of SMS notifications by personnel in high voltage Installations (doc.no. 1492241 in IFS) Prosedyre for arbeid på Petersenspole (Procedure for work on Petersen coil Norwegian ducument only) (doc.no. 2016530 in IFS) Prosedyre for planlegging og gjennomføring av arbeid i lavspenningsanlegg/kontrollanlegg (Procedure for planning and implementing of work in low voltage installations/control switchboard/cabinets Norwegian document only)(doc.no. 1744998 in IFS) Safety regulations related to the maintenance and operation of electrical installations (FSE 2006) (www.dsb.no) Lov om tilsyn med elektriske anlegg og utstyr (Act relating to the Inspection of Electrical Installations and Electrical Equipment only in Norwegian) (www.lovdata.no)

Based on the Norwegian document number 1169509 rev. 10 Page: 7 of 7 9 Version log Valid as of Revision classification Description of important changes (New/Updated/Vocabulary/None) 01.01.18 Update 5.2.2, 5.3.3, 5.3.4, 5.3.5 and 5.3.8: Added requirement regarding security card database "GP" authorization og authorization as Safety Supervisor HV. 5.3.2.1: Added requirement regarding appointing Safety Supervisor HV. This clause previously was a part of clause 5.3.2.