V DGX Series. Direct-Operated Regulators Manual D103834X012

Similar documents
V DFX Series. Direct-Operated Tank Blanketing Regulator Manual D103808X012

Type CT88 Backpressure Regulator

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

Pressure Reducing Regulator Manual

299H Series. Introduction. P.E.D. Categories. Specifications. Installation. Warning. Installation Guide English September 2012

Type 310A-32A Pressure Reducing Regulator and Type 310A-32A-32A Working Monitor Regulator

Types S100K and S102K Pressure Regulators

Type EZH Relief or Backpressure Regulator

1805 Series Relief Valves

1805 Series Relief Valves

Type ACE97. Introduction. Installation. P.E.D. Categories. Specifications. Overpressure Protection. Installation Guide English May 2002

64 Series Pressure Reducing Regulators

MEGR-1627 Instruction Manual

Type 1367 High-Pressure Instrument Supply System with Overpressure Protection

1301 Series High-Pressure Regulators

627 Series Pressure Reducing Regulators

T208VR Series Tank Blanketing Vacuum Regulator

Types 627W and 627WH Direct-Operated Pressure Reducing Liquid Regulators

Type R622 Pressure Reducing Regulator

61 Series Pilots for Pilot-Operated Pressure Reducing Regulators

Types 1808 and 1808A Pilot-Operated Relief Valves or Backpressure Regulators

Type HSR Pressure Reducing Regulator for Residential, Commercial, or Industrial Applications

Types S108K and S109K Pressure Reducing Regulators with Integral Slam-Shut Device

Type FEQ Slam-Shut Valve

1305 Series Pressure Reducing Regulators

RB Series Regulating System

Y692VB Series Vacuum Breaker

Type 63EG Relief Valve or Backpressure Regulator

MEGR-1912 Instruction Manual

VALVCHEQ BACKFLOW PREVENTERS FIGURE RP03

627 Series Pressure Reducing Regulators

Type ACE95jr Tank Blanketing Valve

Types ACE95 and ACE95Sr Tank Blanketing Valves

Type 299 Pressure Reducing Regulators

CSB400 Series Commercial / Industrial Pressure Reducing Regulators

Type 310A-32A Pressure Reducing Regulator and Type 310A-32A-32A Working Monitor Regulator

61 Series Pilots for Pilot-Operated Pressure Reducing Regulators

Type Cronos Pressure Reducing Regulator

PRO-50 Instrument Supply Regulator

Type EZL Pressure Reducing Regulator for Low Differential Pressure Applications

Product Manual. Description. Specifications. CVS Type 1301F and CVS Type 1301G Regulator. Introduction

CP200 Series Commercial / Industrial Pressure- Loaded Pressure Reducing Regulator

RHPS Series RD(H)F40 User Manual. Read the complete manual before installing and using the regulator.

CSB400 Series Commercial / Industrial Pressure Reducing Regulators

CS800 Series Commercial / Industrial Pressure Reducing Regulators

English. Introduction. Safety Instructions. All Products. Inspection and Maintenance Schedules. Parts Ordering. Specifications WARNING WARNING

1301 Series High-Pressure Regulators

EZH and EZHSO Series Pressure Reducing Regulators

Types 749B and R130 Changeover Manifolds

Type FL Pressure Reducing Regulators

Type 1190 Low-Pressure Gas Blanketing Regulator

Types ACE95 and ACE95Sr Tank Blanketing Valves

Fisher DVI Desuperheater Venturi Inline

T208 Series Tank Blanketing Vapor Recovery Regulators

Types 95L and 95H Pressure Regulators

1200B2 Series Service Regulators. Instruction Manual

2.0 INSTALLATION & SERVICE

Type ACE95jr Tank Blanketing Valve

971 Series Pressure Reducing Regulators

630 Series Regulators and Relief Valves

VALVCHEQ BACKFLOW PREVENTERS FIGURE RP03

WW-720. Pressure Reducing Control Valve

Types ACE95 and ACE95Sr Tank Blanketing Valves

299H Series Pressure Reducing Regulators

Design DSA Steam-Atomized Desuperheater

Type 92S Pilot-Operated Steam Regulator

299H Series Pressure Reducing Regulators

Type 99 Pressure Reducing Regulators

299H Series Pressure Reducing Regulators

66 Series Direct-Operated Regulators and Vacuum Service Equipment

1800C and 1800C-HC Series Service Regulators

OPERATING AND MAINTENANCE MANUAL

Type Y692 Gas Blanketing Regulator System

Type EZL Pressure Reducing Regulator for Low Differential Pressure Applications

299H Series. 1% Accuracy for Fixed Factor Billing (PFM) I nlet Pressure up to 175 psig / 12.1 bar. Rugged Construction. Compact.

299H Series Pressure Reducing Regulators

S300 Series. Valve Link. Features. Fisher Controls

WW-720. Pressure Reducing Control Valve

Model TB 3-16 TECHNICAL BULLETIN. Secure-Gard Pilot Operated Vent Valve (POVV) BENEFITS TYPICAL APPLICATIONS FEATURES

TESCOM 50-4X Series Safety, Installation & Start-Up Procedures

Bermad Pressure Reducing. Model: 42T

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

TECHNICAL DATA Q= C. Table 1 - Specifications

CSB600 Series Commercial / Industrial Pressure Reducing Regulators

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

Fisher DSA Steam-Atomized Desuperheater

Tank Blanketing Pressure Regulators RHPS Series

INSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION

VS100 Series Slam-Shut Device

LRS(H)4 Pressure-Reducing Regulator User Manual

Type HSR Pressure Reducing Regulator for Residential, Commercial or Industrial Applications

RD(H)20/25 Pressure-Reducing Regulator User Manual

THE BP-301 SERIES. Operating and Service Manual. Series includes all variants of BP-301 (LF 0.1Cv / MF 0.5Cv)

Types 1098-EGR and 1098H-EGR Pressure Reducing Regulators

Reduce pressure zone device suitable for high and medium hazard rated applications BSP screwed connections

Mooney * Noise Controller Installation, Operation, and Maintenance Manual

Combination Air Valve

SLAM-SHUT VALVE. Type OSE CONTENTS INTRODUCTION CHARACTERISTICS. Scope of Manual. Material. Product Description. Connections

Fisher and Whisper Disk Diffusers

Float Operated Level Controllers

Transcription:

V2015.3 DGX Series Direct-Operated Regulators Manual D103834X012

Contents 1. Introduction... 3 2. Specifications... 3 3. Features... 3 4. Dimensions... 4 5. Principle of Operation... 5 6. Performance Curves... 7 7. Installation and Startup... 8 PRV Installation... 8 PRV Startup and Shutdown... 9 BPV Installation...10 BPV Startup and Shutdown...12 8. Maintenance...13 Routine Maintenance...13 Periodic Check...13 Troubleshooting...13 9. Spare Part Kits...14 10. Model Description...15 11. Ordering Information...15 22

1. Introduction DGX Series are multipurpose direct-operated regulators that use fluid pressure to drive the actuator and automatically maintains the outlet pressure or inlet pressure constant. They are available in Pressure Reducing (PRV) and Backpressure (BPV) configurations to control outlet pressure or inlet pressure respectively. They have high-capacity, fast response, tight-shutoff, superior control and stability and can be used in a variety of gas and liquid industrial applications such as: Nitrogen, Carbon Dioxide, Natural Gas, Oil, Water, Methanol, Alcohol, Naphtha and similar media. 2. Specification items DGX Series Pressure Reducing DGX series Backpressure Body Size End Connection DN 15, 20 and 25 / 1/2, 3/4 and 1 In. NPT, ANSI 150 RF, ANSI 300 RF, PN 16/25/40 RF Inlet Pressure Range 1 to 40 bar / 14.5 to 580 psig (Table 1) 0.35 to 20.7 bar / 5.1 to 300 psig (Table 1) Spring Range See Table 2 See Table 3 Flow Coefficients Cv DN 15 / NPS 1/2 Cv: 2.8; DN 20 / NPS 3/4 Cv: 4.2; DN 25 / NPS 1 Cv: 4.3 DN 15 / NPS 1/2 Cv: 3.6; DN 20 / NPS 3/4 Cv: 7.1; DN 25 / NPS 1 Cv: 8 Flow Characteristic Quick Open Shutoff Classification ANSI Class VI Accuracy Up to 10% Temperature Capabilities Nitrile (NBR): -29 to 80 C / -20 to 176 F Fluorocarbon (FKM): -7 to 120 C (1) / 19 to 248 F (1) Body WCC, CF8M Material Diaphragm, Seals Nitrile (NBR), Fluorocarbon (FKM) Trim Parts SST 1. Fluorocarbon (FKM) is limited to 93 C / 199 F in hot water. 3. Features Modular construction design High regulating accuracy Fast speed of response Tight shutoff Wide pressure range, multipurpose Simple construction for easy maintenance 3

4. Dimensions Figure 1. DGX Series PRV Flange RF End Connection Dimensions Figure 2. DGX Series BPV Flange RF End Connection Dimensions E E A B A B C C D D Figure 3. DGX Series PRV NPT End Connection Dimensions E Figure 4. DGX Series BPV NPT End Connection Dimensions E A B A A B C C D D Product dimensions are referred below, all the dimension A in charts are measured with the adjusting screw extended at maximum lengths. DGX Series Size Body Size D Weight A B C E CL PN NPT DN In. mm In. mm In. mm In. mm In. mm In. mm In. mm In. kg lbs 15 1/2 12.9 28 20 3/4 DGX PRV 386 15.2 344 13.5 84.3 3.3 184 7.2 184 7.2 160 6.3 167 6.6 12.9 28 25 1 13.3 29 15 1/2 12.7 28 20 3/4 DGX BPV 386 15.2 344 13.5 84.3 3.3 184 7.2 184 7.2 160 6.3 167 6.6 12.7 28 25 1 13.1 28.9 44

5. Principle of Operation Figure 5. DGX Series PRV Operational Schematic ADJUSTING SCREW SPRING CASE TRIM PARTS CONTROL SPRING DIAPHRAGM BODY SENSING LINE INLET OUTLET INLET PRESSURE OUTLET PRESSURE ATMOSPHERIC PRESSURE DGX Series PRV is a direct-operated pressure reducing regulator. When operating, fluid flows from the inlet chamber, up through the orifice, and exits the outlet chamber. Downstream pressure is registered at the underside of the diaphragm through an external sensing line that is connected to the lower diaphragm casing. The pressure under the actuator diaphragm is balanced by the spring force acting at the topside of the diaphragm, through the action of the actuator stem which moves to or away from the orifice to achieve pressure reducing and retaining. Downstream pressure is set by turning the adjusting screw. When downstream flow demand decreases, downstream pressure increases, and the pressure registered under the actuator diaphragm also increases. The pressure underneath the diaphragm moves the diaphragm upward and the valve stem together with the valve plug move towards the orifice, decreasing fluid flow, and downstream pressure is maintained at a new equilibrium state. When downstream flow demand increases, downstream pressure decreases, and the pressure registered under the actuator diaphragm also decreases. Spring force now moves the diaphragm downward and the valve stem together with the valve plug move away from orifice, increasing fluid flow, and downstream pressure is maintained at a new equilibrium state. Figure 6. DGX Series BPV Operational Schematic ADJUSTING SCREW SPRING CASE CONTROL SPRING DIAPHRAGM TRIM PARTS SENSING LINE BODY INLET OUTLET INLET PRESSURE OUTLET PRESSURE ATMOSPHERIC PRESSURE DGX Series BPV is a direct-operated backpressure regulator. When operating, fluid flows from the inlet chamber through the orifice and exits on the outlet chamber. Inlet pressure is registered at the underside of the diaphragm through an external sensing line that is connected to the lower diaphragm casing. The pressure under the actuator diaphragm is balanced by the spring force acting at the topside of the diaphragm. Through the action of the actuator stem, the valve plug moves to or away from the orifice to achieve pressure retaining. Upstream pressure is set by turning the adjusting screw. When the inlet pressure is above the set pressure, the pressure registered at the actuator diaphragm increases. The pressure underneath the diaphragm moves the diaphragm upward and the valve stem together with the valve plug move away from the orifice, and then it opens the backpressure regulator and allows more flow to the downstream. When the inlet pressure is below the set pressure, the pressure registered at the actuator diaphragm decreases. Spring force now moves the diaphragm downward and the valve stem together with the valve plug move towards the orifice, decreasing fluid flow, and then it closes the backpressure regulator. 5

Table 1. Pressure Ranges Body Material End Connection PRV Pressure Range (2) BPV Pressure Range Inlet Pressure Set Pressure Set Pressure Inlet Pressure (3) bar psig bar psig bar psig bar psig CL150 RF 1 to 16.9 14.5 to 245 0.35 to 14 5.1 to 203 0.35 to 10 5.1 to 145 0.35 to 16.9 5.1 to 245 CL300 RF 1 to 40 14.5 to 580 0.35 to 20.7 5.1 to 300 0.35 to 13.8 5.1 to 200 0.35 to 20.7 5.1 to 300 WCC PN 16 1 to 40 14.5 to 580 0.35 to 20.7 5.1 to 300 0.35 to 13.8 5.1 to 200 0.35 to 20.7 5.1 to 300 PN 25 1 to 40 14.5 to 580 0.35 to 20.7 5.1 to 300 0.35 to 13.8 5.1 to 200 0.35 to 20.7 5.1 to 300 PN 40 1 to 40 14.5 to 580 0.35 to 20.7 5.1 to 300 0.35 to 13.8 5.1 to 200 0.35 to 20.7 5.1 to 300 NPT 1 to 40 14.5 to 580 0.35 to 20.7 5.1 to 300 0.35 to 13.8 5.1 to 200 0.35 to 20.7 5.1 to 300 CL150 RF 1 to 15.6 14.5 to 226 1 to 13 14.5 to 189 0.35 to 8.7 5.1 to 126 0.35 to 15.6 5.1 to 226 CL300 RF 1 to 40 14.5 to 580 0.35 to 20.7 5.1 to 300 0.35 to 13.8 5.1 to 200 0.35 to 20.7 5.1 to 300 CF8M PN 16 1 to 30.2 14.5 to 438 0.35 to 20.7 5.1 to 300 0.35 to 13.8 5.1 to 200 0.35 to 20.7 5.1 to 300 PN 25 1 to 30.2 14.5 to 438 0.35 to 20.7 5.1 to 300 0.35 to 13.8 5.1 to 200 0.35 to 20.7 5.1 to 300 PN 40 1 to 30.2 14.5 to 438 0.35 to 20.7 5.1 to 300 0.35 to 13.8 5.1 to 200 0.35 to 20.7 5.1 to 300 NPT 1 to 40 14.5 to 580 0.35 to 20.7 5.1 to 300 0.35 to 13.8 5.1 to 200 0.35 to 20.7 5.1 to 300 Note: 1. Based on the maximum temperature of 120 C / 248 F (or refer to steel flange standard HG/T20592 and HG/T20615). 2. Inlet pressure and Set pressure rating range: Gas application: 1.2:1~ 20:1, Liquid application:1.2:1~10:1. In the meantime, differential pressure for liquid application should be no more than (inlet pressure + atmospheric pressure) x Km (Km=0.7). 3. Maximum inlet pressure in BPV equals set pressure plus build-up. Table 2. DGX Series PRV Spring Ranges Type bar Spring Range psig Spring Color Spring part Number 0.35 to 0.6 5 to 8.7 Yellow ERSA04992A0 0.5 to 1.05 7.3 to 15 Blue ERAA09412A0 PRV 0.95 to 2.3 14 to 33 White ERSA05005A0 2.1 to 3.4 30 to 49 Green ERAA09413A0 3.2 to 8.5 46 to 123 Black ERSA05006A0 8.0 to 20.7 116 to 300 Red ERAA07059A0 Table 3. DGX Series BPV Spring Ranges Type bar Spring Range psig Spring Color Spring part Number 0.35 to 1.05 5 to 15 Yellow ERSA04992A0 BPV 0.9 to 2.3 13 to 33 White ERSA05005A0 2.1 to 5.1 30 to 74 Black ERSA05006A0 4.7 to 13.8 68 to 200 Red ERAA07059A0 66

6. Performance Curves Size: DN 25 Initial Setpoint: Inlet Pressure 30 bar, Outlet Pressure 20.7 bar, Flow Rate 2400 SCFH Outlet Pressure, bar 10% Droop 24 bar 40 bar air flow, SCFH PRV Flow Performance Curve Size: DN 25 Initial Setpoint: Inlet Pressure 13.8 bar, Flow Rate 2400 SCFH inlet Pressure, bar air flow, SCFH BPV Flow Performance Curve 7

7. Installation and Startup Protection device should be installed to release pressure and protect the system during regulator failure or set pressure increase. PRV Installation Installing, operating and maintaining PRV and BPV should be performed by qualified personnel. 1. Before installing PRV : Check for damage which might have occurred during shipment. Inspect regulator body inlet and outlet ports and remove any dirt or foreign material that may be present. Blow out any debris or dirt in the tubing and the pipeline. Check if the pressure in the pipeline is within the pressure range stated on the regulator nameplate. Make sure fluid flow through the regulator is in the same direction as the arrow on the body. 2. Install PRV away from fire source, vibration, water accumulation and ice formation areas, and the environment temperature should comply with the requirements. In low temperature areas, heat tracing measures may be considered to heat the pipelines of the PRV in winter. At special occasions, such as installations in areas with heavy snow, may require a hood or enclosure to protect the PRV from snow load and vent freeze over. 3. Body installed vertically with the actuator spring case pointing upward is required. 4. Do not forcefully install the regulator when connecting the inlet and outlet pipelines. 5. If a quick exhausting device or valve is to be installed downstream of the PRV, make sure to leave enough gas piping volume between the PRV and the device to avoid sharp pressure drop due to rapid changing flow rates. 6. The filter should be installed on the upstream of the PRV and leave enough straight run of pipe downstream. Attach a 10 mm / 0.39 in. OD sensing line with a 1/4 NPT fitting no less than 5 x DN (the nominal diameter of the pipework) away from the PRV outlet port and at a point away from any source of turbulence and no less than 5 x DN (the nominal diameter of the pipework) away from downstream block valve. When outlet pressure is at or above 0.5 bar / 7.25 psig, gas velocity should not exceed 50 m/s. When outlet pressure is below 0.5 bar / 7.25 psig, gas velocity should not exceed 25 m/s. The nominal diameter of the pipework connecting the regulator shall not be smaller than the nominal diameter of the regulator. Remove or isolate (utilizing blind flange) the regulator when the pipeline is undergoing pressure test or purging to avoid damaging the regulator. 88

DGX Series PRV Installation Schematic filter upstream block valve pressure gauge downstream block valve DN 10 DN 5 DN 5 INLET PRESSURE OUTLET PRESSURE ATMOSPHERIC PRESSURE All vents should be kept open to permit free flow of gas to the atmosphere. Protect openings against entrance of snow, insects or any other foreign material that may plug the vent. Under enclosed conditions or indoors, escaping gas may accumulate and be an explosion hazard. PRV Startup Procedures 1. Make sure bypass valve is closed. Open the system Shutoff Valve. 2. Slowly open the inlet block valve in front of the PRV. 3. Slightly open the outlet block valve behind the PRV. 4. When used in liquid service, the PRV has bleed design to exhaust the air trapped under the actuator diaphragm depending on medium type. Slowly unscrew the bleed plug to exhaust the air. Then, screw and tighten the plug. Exercise caution at all times. 5. Keep in this position until pressure is stabilized. 6. Fully open the outlet block valve. PRV Outlet Pressure Settings To change the outlet pressure, unscrew the jam nut and slowly turn the adjusting screw and set the outlet pressure to the desired setting, screw the jam nut. Screw the adjusting screw into the spring case to increase pressure. Screw the adjusting screw out of the spring case to decrease pressure. PRV Shutdown Procedures 1. Close the inlet block valve. 2. Close the outlet block valve. 3. Unload the adjusting spring. 4. Slowly open the outlet block valve to release downstream pressure. 5. Keep the outlet block valve open, release inlet pressure and all remaining pressure in PRV. ADJUSTING SCREW Protective device should be installed to release pressure and protect the system during regulator failure or set pressure increase. VENT 9

BPV Installation Installing, operating and maintaining BPV should be performed by qualified personnel. 1. Before installing BPV : Check for damage which might have occurred during shipment. Inspect regulator body inlet and outlet ports and remove any dirt or foreign material that may be present. Blow out any debris or dirt in the tubing and the pipeline. Check if the pressure in the pipeline is within the pressure range stated on the regulator nameplate. Make sure fluid flow through the regulator is in the same direction as the arrow on the body. 2. Install BPV away from fire source, vibration, water accumulation and ice formation areas and the environment temperature should comply with the requirements. In low temperature areas, heat tracing measures may be considered to heat the pipelines of the BPV in winter. At special occasions, such as installations in areas with heavy snow, may require a hood or enclosure to protect the BPV from snow load and vent freeze over. 3. Body installed horizontally with the actuator spring case pointing upward is required. 4. Do not forcefully install the regulator when connecting the inlet and outlet pipelines. 5. If a quick exhausting device or valve is to be installed downstream of the PRV, make sure to leave enough gas piping volume between the PRV and the device to avoid sharp pressure drop due to rapid changing flow rates. 6. The filter should be installed on the upstream of the BPV and leave enough straight run of pipe upstream. Attach a 10 mm / 0.39 in. OD sensing line with a 1/4 NPT fitting no less than 5 x DN (the nominal diameter of the pipework) away from the BPV on the upstream and at a point away from any source of turbulence and no less than 5 x DN (the nominal diameter of the pipework) away from the upstream block valve. 1010

DGX Series BPV Installation Schematic filter upstream block valve pressure gauge downstream block valve DN 5 DN 5 INLET PRESSURE OUTLET PRESSURE ATMOSPHERIC PRESSURE Remove or isolate (utilizing blind flange) the regulator when the pipeline is undergoing pressure test or purging to avoid damaging the regulator. 11

Overpressuring any portion of this equipment may cause equipment damage, leaks in the backpressure regulator, or personal injury due to bursting of pressure containing parts. The backpressure regulator should be inspected for damage regularly and after any overpressure condition. The pressure range for relief / backpressure regulator is 0.35 to 13.8 bar / 5 to 200 psig. Every spring set range for the regulator is on the nameplate. The maximum inlet pressure depends on the body materials and operating temperatures. The information about regulator maximum inlet pressure please see the pressure ranges section. The backpressure regulator should be inspected for damage regularly and after any overpressure condition. Before startup, the regulator must be tested in accordance with the procedure specified in the Maintenance section. Liquid Option Only Bleed Plug BPV Startup Procedures 1. Make sure bypass valve is closed, open the system shutoff valve. 2. Slowly open the outlet block valve behind the BPV. 3. Slowly open the inlet block valve in front of the BPV. 4. When used in liquid service, the BPV has bleed design to exhaust the air trapped under the actuator diaphragm depending on medium type. Slowly unscrew the bleed plug to exhaust the air. Then, screw and tighten the plug. Exercise caution at all times. BPV Inlet Pressure Settings To change the inlet pressure, unscrew the jam nut and slowly turn the adjusting screw and set the inlet pressure to the desired setting, screw the jam nut. Screw the adjusting screw into the spring case to increase pressure. Screw the adjusting screw out of the spring case to decrease pressure. BPV Shutdown Procedures 1. Close the upstream BPV inlet block valve. 2. Close the downstream BPV outlet block valve. 3. Unload the adjusting spring. 4. Slowly open the outlet block valve to release downstream pressure. 5. Keep the outlet block valve open, release inlet pressure and the remaining pressure in BPV. 1212

If using DGX Series BPV on hazardous or flammable gas service, personal injury and property damage could occur due to fire or explosion of vented gas that may have accumulated. To prevent such injury or damage, provide piping or tubing to vent the gas to a safe, well-ventilated area. Also, when venting a hazardous gas, the piping or tubing should be located far enough away from any buildings or windows so to not create a further hazard, and the vent opening should be protected against anything that could clog it. Handle with care during maintenance, carefully vent the pressure in the actuator and other pressured parts, use recommended torques for assembly. 8. Maintenance Before maintenance, close the inlet and outlet block valves and exhaust the gas pressure in the valve body and piping. When removing or replacing parts such as the orifice or diaphragm, be careful not to damage them. Ensure movable parts can move freely after reassembly. Recommission according to the Installation and Startup procedures. Ensure all connections are tight and check for leaks. Emerson Process Management Regulator Technologies, Inc. (Emerson ) provides training for your maintenance personnel. For other information, consult your local Sales Office. Routine Maintenance The frequency of routine maintenance depend on the medium type and service condition to keep safety: 1. Make sure that there is no leakage on the regulator. 2. Observe the gauges to make sure that the pressure being controlled is stable and at the correct set point. 3. Clean the outside of the regulator. Periodic Check The frequency of periodic check depend on the medium type and service condition to make sure the proper functioning of the regulator. Apart from monitoring the set pressure: 1. Check DGX Series PRV lock up pressure every 1 to 3 months: Open the upstream valve, using the downstream pressure gauge to monitor the pressure, slowly close the downstream valve, ensure that the downstream pressure does not increase. 2. Check DGX Series BPV lock up pressure every 1 to 3 months: Slowly increase the inlet pressure until the relieving pressure starts to rise, then slowly decrease the inlet pressure until the valve closed, ensure the downstream pressure does not increase. 3. Clean internal parts every 3 to 6 months like the Disk, Diaphragm, O-rings and Seat Ring. Give due diligence to check and replace deformed and worn out seals upon necessary. 4. Check wear parts every 3to 6 months for damage and replace upon necessary, replace crush installed O-rings after disassembly. Note: Must use Emerson parts for replacements. 13

Handle with care during maintenance, carefully vent the pressure in the actuator and other pressured parts, use recommended torques for assembly. Table 4. Troubleshooting Problem Possible Cause Possible Solution Regulator is not working PRV outlet pressure decreases BPV inlet pressure increases BPV lock-up pressure increases BPV lock-up pressure decreases PRV outlet pressure fluctuates BPV inlet pressure fluctuates PRV inlet pressure equals to outlet pressure Regulator is undersized or oversized Damaged diaphragm Inlet pressure too low Actual flow capacity surpass designed capacity Debris caught in the regulator Actual flow capacity surpass designed capacity Debris caught in the regulator Damaged, deformed or worn out diaphragm Deformed or worn out disk or disk holder Debris caught in between disk and orifice or parts being damaged PRV upstream pressure fluctuates Actual flow capacity much lower than normal Damaged diaphragm Control spring over adjusted Review sizing Replace diaphragm Increase inlet pressure Review sizing Remove debris Review sizing Remove debris Replace diaphragm Replace disk or disk holder Clean or replace disk and orifice Check upstream valve when upstream pressure fluctuates Replace diaphragm Review pressure range of the spring, and change the spring 9. Spare Parts Kits Includes: Diaphragm, O-rings, Orifice, Seat, etc. Table 5. Spare Parts Kit Regulator Type Elastomer Type Body Size Spare Part Numbers PRV BPV Nitrile (NBR) Fluorocarbon (FKM) Nitrile (NBR) Fluorocarbon (FKM) DN15/20/25 ERAA09343A0 ERAA09345A0 ERAA09346A0 ERAA09347A0 1414

10. Model Description DGX - - 15 CS P1 01 P F R Body Size, DN 15 20 25 Body Material CS Carbon Steel SS Stainless Steel (All trim parts are stainless steel) End Connection P1 PN 1.6 MPa RF P2 PN 2.5 MPa RF P4 PN 4.0 MPa RF A1 CL150 RF A3 CL300 RF NP NPT Spring Code 01 02 For details 03 of spring set 04 range please 05 see Table 6. 06 Sizing Charts Regulator Type Elastomer Medium Type P Pressure Reducing N/A Nitrile (NBR) N/A Gas Valve F Fluorocarbon (FKM) R Liquid B Back Pressure Regulator The product description example: DGX15 - CSP1-01PF Example: DGX15-CSP1-01PF indicates that this is a direct-operated pressure reducing valve. Medium type is gas. Nominal diameter is 15 mm. Body material is WCC. Trim material is stainless steel. End connection type is PN16 Flange RF. Spring code is 01. Elastomer type is Fluorocarbon (FKM). Table 6. Sizing Charts Regulator Type Body Size bar Spring Set Range psig Spring Code PRV BPV DN 15, 20 and 25 / 1/2, 3/4 and 1 In. DN 15, 20 and 25 / 1/2, 3/4 and 1 In. 0.35 to 0.6 5 to 8.7 01 0.5 to 1.05 7.3 to 15 02 0.95 to 2.3 14 to 33 03 2.1 to 3.4 30 to 49 04 3.2 to 8.5 46 to 123 05 8.0 to 20.7 116 to 300 06 0.35 to 1.05 5 to 15 01 0.9 to 2.3 13 to 33 03 2.1 to 5.1 30 to 74 05 4.7 to 13.8 68 to 200 06 11. Ordering Information Please provide information below when ordering. 1. Regulator nominal pressure, nominal size. 2. Inlet pressure, outlet pressure, flow capacity and characteristics. 3. Fluid type and operating temperature. 4. Body and Trim parts Material. 5. Accessories and other special requirements. 15

Emerson Process Management Asia Pacific Pte Ltd Regulator Technologies 1 Pandan Crescent Singapore 128461 T: +65 6770 8337 F: +65 6770 8028 FISHER JEON Gas Equipment (Chengdu) Co., Ltd No. 9, Wukedong 2nd Road, Wuhou Science Technic Park, Chengdu, 610045, P.R. China T: (028) 85360000 F: (028) 85371201 Service T: (028) 85366930 or (028) 85360000 Ext. 1613 Emerson Process Management Chennai Ltd Plot No. 5, 6, 7 and 8 Self Help Industrial Estate Keelkattalai, Chennai, India - 600117 T +91 44 6608 6600 F +91 44 4903 4400 For enquiries, please contact us at RegulatorTechnologiesAsia@emerson.com For further information, please visit www.ap.emersonprocess.com/regulators Neither Emerson TM, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user. Jeon is mark owned by one of the companies in the Emerson Process Management business unit of Emerson Electric Co. Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners. The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.