CA16 and CA16S-14 Air and Gas trap Installation and Maintenance Instructions

Similar documents
FT16 Ball Float Steam Trap Installation and Maintenance Instructions

1. General safety information. 2. General product information. 3. Installation. 4. Commissioning. 5. Operation. 6. Maintenance. 7.

CA44, CA44S, CA46 and CA46S Air and Gas Traps

AE14 Automatic Air Vents for Liquid Systems Installation and Maintenance Instructions

AVS32 Stainless Steel Air Vent for Steam Systems Installation and Maintenance Instructions

AE50S Automatic Air and Gas Vent for Liquid Systems Installation and Maintenance Instructions

Fig 1, Fig 12, Fig 13, Fig 14, Fig 16 and Fig 16L Strainers Installation and Maintenance Instructions

SCA Series Inverted Bucket Steam Traps

Thermocirc Installation and Maintenance Instructions

TD45 Thermodynamic Steam Trap Installation and Maintenance Instructions

CA10S, CA14 and CA14S Air and Gas Traps

A3S Bellows Sealed Stop Valve Installation and Maintenance Instructions

IFTGS14 Ball Float Steam Trap ½" and ¾" with Integral Spiratec Sensor

FTGS14 Ball Float Steam Trap DN15 (½") to DN25 (1")

AVC32 Carbon Steel Air Vent for Steam Systems

UBP32 Sealed Balanced Pressure Thermostatic Steam Trap for use with PC_ Pipeline Connectors Installation and Maintenance Instructions

BTD52L Thermodynamic Steam Trap Installation and Maintenance Instructions

TD10, TD52M and TD259 Thermodynamic Steam Traps Installation and Maintenance Instructions

CA46S Austenitic Stainless Steel Air and Gas Trap DN40 and DN50

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

DCV1, DCV3 and DCV3LT Disc Check Valves Installation and Maintenance Instructions

AE30 Automatic Air Eliminators / Air and Gas Vents for Liquid Systems

BSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

CA44 and CA44S Carbon Steel Air and Gas Traps Flanged DN15 to DN25

MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap

Fig 12, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

DCV6 Disc Check Valve

AVM7 Stainless Steel Thermostatic Air Vent

Fig 1, Fig 12, Fig 13, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

Airodyn, BRair and BRoil Compressed Air Drain Traps

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators

TA10A and TA10P Steam Tracing Temperature Control Valves Installation and Maintenance Instructions

TSS21 Sealed Thermostatic Steam Tracer Trap

CA14 SG Iron Air and Gas Trap ½" and ¾" (Screwed)

DF1 and DF2 Diffusers

CVS10 Sanitary Check Valves

HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions

BPT13 Balanced Pressure Thermostatic Steam Traps

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

KBV21i and KBV40i Air Actuated Boiler Blowdown Valves

DCV10 Stainless Steel Disc Check Valve for use with Condensate Pumps

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

FT43, FT44, FT46 and FT47 Ball Float Steam Traps Installation and Maintenance Instructions

BTM7, BTS7 and BTS7.1 Stainless Steel Thermostatic Clean Steam Traps

Fig 3, 7, 33, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers

Fig 7, 33, 33.1, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers Installation and Maintenance Instructions

S and SF Inverted Bucket Steam Traps

TDC46M, TDS46M and UTDS46M Thermodynamic Steam Traps with Maintainable Seat Installation and Maintenance Instructions

BT6-B Sanitary Balanced Pressure Thermostatic Steam Trap

Dri-Line Mk3 Monnier Compressed Air Drain Trap

PV4 and PV6 Piston Valves

BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications

M10HTi ISO Tobacco Ball Valve Screwed, SW, BW and Flanged versions

MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection

CS10-1 Stainless Steel Clean Steam Separator

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats

FT53, IFT53, FT54, IFT54, FT57 and IFT57 Ball Float Steam Traps - DIN

M33F ISO, M33S ISO and M33V ISO Ball Valves Installation and Maintenance Instructions

Dri-Line Mk2 Spirax-Monnier Compressed Air Drain Trap

FTC62 and FTS62 Ball Float Steam Traps Installation and Maintenance Instructions

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions

BDV1 and BDV2 Blowdown / Depressurisation Valves

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats Installation and Maintenance Instructions

TP1 and TP2 Temporary Cone Shaped Strainers

APT14, APT14HC and APT14SHC Spares 2

CP10 Sensor Installation and Maintenance Instructions

PC3_ and PC4_ Pipeline Connectors

Spirax SafeBloc TM DBB3 Double Block and Bleed Bellows Sealed Stop Valve. 1. Safety information. 2. General product information. 3.

M70i ISO and M80i ISO Stainless Steel Ball Valves for Sanitary Systems Installation and Maintenance Instructions

SRV66 Sanitary Pressure Reducing Valve

TW Temperature Control Valve

BRV71 and BRV73 Pressure Reducing Valves

BCV31 DN40 - Blowdown Control Valve

SRV2S Pressure Reducing Valve

IX1 Spirax-Monnier International Compressed Air Filter Installation and Maintenance Instructions

MF2M Monnier Miniature Compressed Air Filter

ML3M Monnier Miniature Compressed Air Lubricator

PC10HP Pipeline Connector (ASME 600)

BSA and BSAT Bellows Sealed Stop Valves Installation and Maintenance Instructions

PTF4 Pivotrol Pump (patented) version Dual Mechanism - Pressure Powered Pump

BCV31 DN20 - Blowdown Control Valve

FV Flash Vessel Installation and Maintenance Instructions

SA Control Valve types: BM, BMF, BX, SB, NS, KA, KB, KC (Normally open) BMRA, BMFRA, BXRA, SBRA, NSRA, KX, KY (Normally closed)

Manual Actuated Boiler Blowdown Valves

MFP14-PPU (Vented) Automatic Packaged Pump Units

PC3000, PC3001 and PC4000, PC4001 Pipeline Connectors

SRV461S and SRV463S Stainless Steel Direct Acting Pressure Reducing Valves

STERI-TROL Clean Service 'S' Series Two-port Control Valves DN15 (½") to DN100 (4")

BCVi43 Blowdown Control Valve

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Dial Adjustment)

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Knob Adjustment)

Spirax Compact FREME Flash Recovery Energy Management Equipment

IP2M, IP2AM and IP2DM Monnier International Compressed Air Filter/ Regulators

LP31 Level Probe. 1. Safety information. 2. General product information. 3. Installation. 4. Wiring. 5. Maintenance

Type 130 and HL10 'Safeguard High Limit Control' Installation and Maintenance Instructions

1. Preface Important Safety Notes Brief Product Information Product Working Principle Installation Guidelines...

595-K/L and 596-K/L Series Self Operated Valves Installation and Maintenance Instructions

MPC1M, MPC2M and MPC2AM Monnier High Efficiency Compressed Air Filter / Regulators

Transcription:

1483250/3 IM-P148-10 ST Issue 3 CA16 and CA16S-14 Air and Gas trap Installation and Maintenance Instructions 1 General safety information CA16 and CA16S-14 ½" and ¾" 2 General product information 3 Installation 4 Commissioning 5 Operation 6 Maintenance CA16S 1" 7 Spare parts Printed IM-P148-10 in the ST UK Issue 3 Copyright 20021

1 General safety information Safe operation of these units can only be guaranteed if they are properly installed, commissioned and maintained by a qualified person (see Section 11 of the attached Supplementary Safety Information) in compliance with the operating instructions. General installation and safety instructions for pipeline and plant construction, as well as the proper use of tools and safety equipment must also be complied with. Warning The cover gasket contains a thin stainless steel support ring which may cause physical injury if not handled and disposed of carefully. Isolation Consider whether closing isolating valves will put any other part of the system or personnel at risk. Dangers might include; isolation of vents and protective devices or alarms. Ensure isolation valves are turned off in a gradual way to avoid system shocks. Pressure Before attempting any maintenance consider what is or may have been in the pipeline. Ensure that any pressure is isolated and safely vented to atmospheric pressure before attempting to maintain the product, this is easily achieved by fitting Spirax Sarco depressurisation valves type DV (see separate literature for details). Do not assume that the system is depressurised even when a pressure gauge indicates zero. Temperature Allow time for temperature to normalise after isolation to avoid the danger of burns and consider whether protective clothing (including safety glasses) is required. If parts made from Viton have been subjected to a temperature approaching 315 C (599 F) or higher, they may have decomposed and formed hydrofluoric acid. Avoid skin contact and inhalation of any fumes as the acid will cause deep skin burns and damage the respiratory system. Disposal These products are recyclable. No ecological hazard is anticipated with the disposal of these products providing due care is taken, EXCEPT; Viton: - Can be landfilled, when in compliance with National and Local regulations. - Can be incinerated, but a scrubber must be used to remove Hydrogen Fluoride, which is evolved from the product and with the compliance to National and Local regulations. - Is insoluble in aquatic media. 2 IM-P148-10 ST Issue 3

2 General product information 2.1 General description The CA16 is a maintainable austenitic stainless steel ball float air and gas trap. It is supplied with a soft Viton valve cone given designation CA16 (DN15 and DN20 only) or with a metal valve cone given designation CA16S-14 both having horizontal screwed connections. The cover will be drilled and tapped 3 / 8" BSP or NPT for the purpose of fitting a balance line. Note: For additional information see the Technical Information Sheet TI-P148-05. 2.2 Sizes and pipe connection ½", ¾" and 1" screwed BSP or NPT. Fig. 1 CA16and CA16S-14 ½" and ¾" Viton valve cone CA16 only Fig. 2 CA16S-14 1" IM-P148-10 ST Issue 3 3

2.3 Limiting conditions Body design conditions PN25 PMA - Maximum allowable pressure 25 bar g (362.5 psi g) TMA - Maximum allowable temperature 300 C (572 F) TMO - Maximum operating temperature CA16 200 C (392 F) CA16S-14 300 C (572 F) PMO - Maximum operating pressure 25 bar g (362.5 psi g) D PMX Maximum differential pressure 14 bar (203 psi) Designed for a maximum cold hydraulic test pressure of: 37.5 bar g (544 psi g) 2.4 Operating range CA16S-14 Temperature C 300 200 100 0 0 5 10 15 20 25 Pressure bar g CA16 Temperature C 300 200 100 0 0 5 10 15 20 25 Pressure bar g The product should not be used in this region. D PMX - Maximum differential pressure Depending on the specific gravity of the liquid being drained Specific gravity 1.0 0.9 0.8 0.7 0.6 CA16 14 bar 14 bar 11 bar 8 bar 5 bar CA16S-14 14 bar 14 bar 11 bar 8 bar 5 bar 4 IM-P148-10 ST Issue 3

3 Installation Note: Before actioning any installation observe the 'Safety information' in Section 1. Referring to the Installation and Maintenance Instructions, name-plate and Technical Information Sheet, check that the product is suitable for the intended installation: 3.1 Check materials, pressure and temperature and their maximum values. If the maximum operating limit of the product is lower than that of the system in which it is being fitted, ensure that a safety device is included in the system to prevent overpressurisation. 3.2 Determine the correct installation situation and the direction of fluid flow. 3.3 Remove protective covers from all connections. 3.4 The trap must be fitted with the float arm in a horizontal plane so that the float mechanism is free to rise and fall in a vertical plane. The trap must be fitted below what it is draining. Point arrow on name-plate downwards. One of the advantages of the float trap for draining air and gas systems is that no bleed is required for satisfactory operation. However, because the trap has no bleed a separate balance line is needed to prevent it becoming air or gas locked. It should be noted that the balance line is piped back to the upstream side. Important note: A balance line is essential for the correct operation of this product. For convenience of maintenance it is recommended that a union is fitted in the balance line near to the trap cover. Note: If the trap is to discharge to atmosphere ensure it is to a safe place, the discharging fluid may be at a temperature of 100 C (212 F). Example showing installation and balance line arrangement For more examples of installation and balance line arrangements, see page 6. Balance line Strainer Fig. 3 Method of draining foot of rising pipe or relay drain in horizontal run CA16 air and gas trap IM-P148-10 ST Issue 3 5

Examples showing installation and balance line arrangement Balance line Strainer Air receiver CA16 air and gas trap Fig. 4 Trap draining separator on compressed air main Balance line CA16 air and gas trap Strainer Fig. 5 Trap draining small receiver 4 Commissioning After installation or maintenance ensure that the system is fully functional. Carry out tests on any alarms or protective devices. 6 IM-P148-10 ST Issue 3

5 Operation The CA16(S) float trap is a continuous discharge trap, removing liquid from air and gas systems. As soon as liquid enters the main chamber of the trap, the float rises and the lever mechanism attached to it opens the main valve - keeping the system drained of liquid at all times. When air or gas arrives, the float drops and shuts the main valve tightly against the seat. The balance line is necessary to prevent the trap from becoming air locked. Float traps are renowned for their instantaneous load handling capability, clean tight shut-off and resistance to waterhammer and vibration. 6 Maintenance Note: Before actioning any maintenance program observe the 'Safety information' in Section 1. Warning The cover gasket contains a thin stainless steel support ring which may cause physical injury if not handled and disposed of carefully. 6.1 General information Use only Spirax Sarco replacement parts. When reassembling make sure that all joint faces are clean. After maintenance ensure that the system is fully functioning. 6.2 How to fit the main valve assembly (CA16S-14): (Refer to Fig. 6, page 8) - Unscrew the support, pivot frame and valve seat. - Ensure that the seat /gasket faces are clean and dry. - Fit a new valve seat into the body. Do not use gasket paste. - Attach the support frame and pivot frame to the body with the assembly set screws but do not tighten. - Fit the float arm to the pivot frame using the pin and by moving the complete assembly, centre the valve head onto the seat orifice. - Tighten the assembly set screws to the recommended torque (see Table 1). 6.3 How to fit the valve cone (CA16): (Refer to Fig. 6, page 8) - Withdraw the pivot pin to release the float and lever. - Push out the soft Viton valve cone and replace with a new one. - Reassemble the float and lever into the bracket and replace the pin. - Check the operation by raising and lowering the float several times making sure that the valve cone centres properly on the seat. Table 1 Recommended tightening torques or Item Size N m (lbf ft) mm 2 ½" - 1" 17 M10 x 30 29-33 (21.3-24.3) 5 ½" - 1" 17 M12 40-45 (29.4-33.1) 7 ½" - 1" Cheesehead M5 x 20 10-12 (7.3-8.8) IM-P148-10 ST Issue 3 7

7 Spare parts The spare parts available are shown in heavy outline. Parts drawn in a broken line are not supplied as spares. Available spares Viton valve cone CA16 (packet of 3) 9 Main valve assembly with float CA16 5, 6, 7, 8, 9, 15, 16, 17 CA16S-14 5, 6, 7, 8+9, 15, 16, 17 Complete set of gaskets (packet of 3 sets) 3, 6 How to order spares Always order spares by using the description given in the column headed 'Available spares' and state the size and type of trap. Example: 1 - Main valve assembly for ½" Spirax Sarco CA16 air and gas trap. 2 3 5 6 16 17 15 7 8 9 Main valve assembly with float Fig. 6 8 IM-P148-10 ST Issue 3