SAFE CAPACITY TEST: INNOVATION AND SAVINGS

Similar documents
PRC CO ² -LASER PRESENTATION

2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic. Pressure Measurement Engineered solutions for all applications

Advanced Pump Control for Irrigation Applications

EasySas. The most advanced airlock electronics on the market. Recyclable product. Eco-design. Energy savings

Ingersoll Rand. X-Series System Automation

Vertiv is E-Rate Eligible

Operating Manual for the Evance Iskra R9000 Wind Turbine

FIRE PROTECTION. In fact, hydraulic modeling allows for infinite what if scenarios including:

Upgrading Vestas V47-660kW

PRAHER PLC-MP AQUASTAR MANAUL 2009

CCT-7320/ROC-2313 Reverse Osmosis Controller

Visualize Nitrogen Gas Consumption

IST-203 Online DCS Migration Tool. Product presentation

Application Note AN-107

Product Information. Three in One: Gas Meter Tariff Device Volume Corrector. Ultrasonic Gas Meter ECOSONIC X12

Control the air. Control your business.

LEA_EN_PZL Dynamometric Scale. Instruments and Systems for Geotechnical and Structural Monitoring

The HumiSys. RH Generator. Operation. Applications. Designed, built, and supported by InstruQuest Inc.

SIL Safety Manual. ULTRAMAT 6 Gas Analyzer for the Determination of IR-Absorbing Gases. Supplement to instruction manual ULTRAMAT 6 and OXYMAT 6

CO 2 and O 2 scrubbers

Robotic Pool Cleaners

GRUNDFOS industry GRUNDFOS CR MONITOR. Intelligent warning

T EK-SUB 4800C 19 mm Submersible Level Transmitter

Thames Water Utilities Limited (TWUL) Wholesale Data logger installation for revenue meters - terms, conditions and guidance

Coriolis Mass Flow Meter

Protection of motor circuits

Model EXAxt AV550G. Averaging Oxygen Analyzer

CASE STUDY. Compressed Air Control System. Industry. Application. Background. Challenge. Results. Automotive Assembly

Nirvana Variable-Speed Drive, Contact-Cooled Rotary Screw Air Compressors

CSO/STORMWATER MANAGEMENT. HYDROVEX HHV-E Vortex Driven Regulator

The RCM Analyst - Beyond RCM

better measurement Simply a question of SCHMIDT Flow Sensor SS The cost-effective alternative in pressurised systems up to 10 bars.

Control & Maintenance. INT69 Diagnose INT69 TM Diagnose. Protect the heart of your system

SAFETY DEMONSTRATION TESTS ON HTR-10

Automatic Isokinetic Sampler. ST5 Evo

V MW. Exceptional performance and reliability at high-wind-speed sites. vestas.com

The M-Series Eletta Flow Meter High accuracy DP Flow Meter with multiple functions

Online data sheet FLOWSIC30 GAS FLOW METERS

User Manual 1 P a g e Rev. V1.6-EN 11/08/2014

Screw Compressors 11-22kW

frequently asked questions

Cover Page for Lab Report Group Portion. Pump Performance

Small Scale Wind Technologies Part 2. Centre for Renewable Energy at Dundalk IT CREDIT

Master Control Systems, Inc. Variable Speed Fire Pump Controllers

Model 130M Pneumatic Controller

COMPANY PROFILE. Sales to 90 countries worldwide

SPIROVENT VACUUM DEGASSERS

PositionMaster EDP300 Extended Diagnostics. Compact, well-proven, and flexible

ISO INTERNATIONAL STANDARD

QPEO2/037N Credit Value: 15 QCF Level: 2 GLH: 68 Maintaining electrical equipment/systems

LP Separator Level Control by Variable Speed and Multi Stage Brine Reinjection Pumps at Kawerau and Nga Awa Purua Geothermal Projects, New Zealand

4-7 kw/ hp. Dual Output Compressors (Air/Nitrogen) Driving Nitrogen Forward

Quantos Automated Dosing Solution Preparation Precise concentrations Process compliance Minimize out-of-specs

University of Tennessee Safety Program

Vibration and Pulsation Analysis and Solutions

The Future of Hydraulic Control in Water-Systems

Gas Network Craftsperson

The Criticality of Cooling

The benefits of the extended diagnostics feature. Compact, well-proven, and flexible

EASYTOUCH. Because automation makes it all so simple. pentairpool.com

SEMEM3-65 Servicing anaesthetic and ventilation equipment

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

INNCOM SYSTEM MONITORING MARRIOT HOTEL DOWNTOWN PHILADELPHIA, PA. Report 9. July 2, CH2M HILL Project No

ASERCOM guidelines for the design of multiple compressor racks using frequency inverters

High altitude wind generation The Rotokite

Power Quality Increased Reliability. Components

AE R1 February 2015

THE CANDU 9 DISTRffiUTED CONTROL SYSTEM DESIGN PROCESS

JOLLY2. Installation user s manual. 6 different operating modes selectable. version 3.3. DATA TO BE FILLED OUT BY THE INSTALLER (Page 1)

THE WATER-COOLED INDUSTRIAL RANGE

Improving distillation tower operation

New Generation System M, leading the World in the Non-Invasive Measurement of Critical Real-Time Parameters.

Micro Motion 3098 Gas Specific Gravity Meter

Simplicity in VRU by using a Beam Gas Compressor

An intuitive and innovative answer to your anaesthesia challenges

HumiSys HF High Flow RH Generator

COMPARISON OF DIFFERENTIAL PRESSURE SENSING TECHNOLOGIES IN HOSPITAL ISOLATION ROOMS AND OTHER CRITICAL ENVIRONMENT APPLICATIONS

Application of CHE100 in Frequency Conversion Alteration of Air Compressor System

Net$ync II. Net$ync II. System Controllers

Vortex flowmeters. Product family introduction Principle of operation Product review Applications Key product features

CONTROL VALVE TESTING

Technical Data Sheet High Performance Digital Gas Mass Flow Meters and Controllers Features Description

Why do I need to do an Arc-Flash Analysis?

Health and Fire Safety Review 2/15

OEM Manual MODEL 2305 ECONOMICAL DIGITAL SINGLE CYLINDER SCALE

OPERATION. Estimated kerf width compensation. HPR260 Manual Gas Instruction Manual 4-9

TECHNICAL COMMERCIAL OFFER TURBOGENERATOR UNITS «TURBOSPHERE»

COMPARING PLUG & SEAT REGULATORS & CONTROL VALVES. Lamar Jones. Equipment Controls Company 4555 South Berkeley Lake Road Norcross, GA 30071

Name Phone Logo

New AQF Filter Polymer Filtration System

Series Environmental Chambers

AUTOMATIC HOSE TEST UNIT, TYPE SPU

Understanding safety life cycles

2017 Edition GUIDANCE NOTE GN 8 INVERTER DRIVES FOR FANS AND PUMPS GN 8 - INVERTER DRIVES FOR FANS AND PUMPS

Cathodic Protection Retrofit Options Comparison of Current Distribution

SATURN EVO COLOR A N A E S T H E S I A S Y S T E M. Manufacturer of high quality anaesthesia products

E2K-L. Liquid Level Sensor That Is Unaffected by the Color of the Pipe or Liquid. Liquid Level Sensor. Ordering Information

ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION

Unique solutions for Oxygen and Nitrogen supply

Improve Process Reliability

Transcription:

SAFE CAPACITY TEST: INNOVATION AND SAVINGS

TWO STAGE POWER DISTRIBUTION Summary Executive Summary 3 Traditional Load Bank Testing 3 The Safe Capacity Test: Innovation and Savings 4 Tradition vs Innovation 5 The Safe Capacity Test: Working Principle 5 Safe Capacity Test: Typologies 7 Safe Capacity Test: Benefits 10 Safe Capacity Test: Conclusions 10 2

Executive Summary Optimizing energy consumption and improving system efficiency is the main goal for every UPS system installation. With this in mind, Vertiv medium and high power UPS have now been endowed with an embedded functionality to process a closed-loop circulation of power through their own rectifier and inverter, acting as an internal load bank. This eco-friendly and low risk test of UPS performances is called Safe Capacity Test and guarantees significant savings in terms of time, money and set-up operations, thanks to the ability to perform the burn-in test directly on site and without the need for an external load bank. Traditional Load Bank Testing UPS are critical to business continuity and load bank tests are usually performed to ensure that the UPS can meet their own specification as it is a way of validating the correct operational performance of the overall system. Traditional load bank tests, however, tend to be complex and expensive because, in addition to the excessive amount of energy wasted, they require hundreds of meters of costly copper cable and thousands of dollars in case the load banks need to be rented. Moreover, the presence of an external load bank creates a hazardous environment due to the large amount of operations and activities during cable connections. QS2 UPS 96% Power dissipation TO LOAD FROM UTILITY 4% Heat dissipation Figure 1: Traditional Load Bank Test 3

TWO STAGE POWER DISTRIBUTION The Safe Capacity Test: Innovation and Savings With the safe capacity test, on the other hand, the UPS can test its entire power train, including the rectifier, inverter, contactors, fuses, power busses, cabling, bypass static switch, magnetics and filter capacitors, all without an external load connected. This feature saves time and money during startup, commissioning tests and also after a system upgrade or repair, thanks to the ability to use the rectifier and inverter in a closed loop power circulation that allows the UPS to perform the safe capacity test at full load. UPS QS4 TO LOAD FROM UTILITY Figure 2: Safe Capacity Test Vertiv service technical field engineers are trained to perform the safe capacity test easily and quickly during commissioning or preventive maintenance with disconnectable loads to ensure optimum calibration, maximum efficiency and inherent redundancy. The safe capacity test is available for the Vertiv state-ofthe-art Liebert Trinergy Cube large modular UPS and Liebert EXL S1 large monolithic UPS. Liebert Trinergy Cube Liebert EXL S1 4

Tradition vs Innovation Assuming that a 1 MW system is tested using a traditional load bank test and compared to a safe capacity test, the differences in terms of money and time for load bank connections and burn-in tests can be seen in the table and graphs below: OPERATION TRADITIONAL TEST SAFE CAPACITY TEST Cable Connection to Load Bank (1) 8 h 0 h Burn-In Test 24 h 24 h Load Bank Rental (weekly) 4000 7000 0 Electrician Expense for Cable 80 /h 0 Connection (2) Energy Waste (3)(4) 2.400 100 Total Time 32h 24h Total Money (5) > 8000 100 1 Installation and dismantling by an electrician 2 Labour hours referred to the load bank connection 3 Considering 24 hours operation at full load at an average electrical utility rate of 0.1 /kwh 4 Considering an AC/AC UPS efficiency of 96% 5 Considering an average weekly rental cost of 5,000 Hours 35 30 25 20 15 10 9000 8000 7000 6000 5000 4000 3000 2000 1000 0 5 0 TIME SAVINGS Cable connection Burn-in test Total Traditional test Electrician Traditional test MONEY SAVING Energy waste Safe capacity test Load bank rental Safe capacity test Total Figure 3: Comparison Charts Traditional Test vs Safe Capacity Test The end results of the safe capacity test vs traditional load bank test are: ycost savings: no load banks to rent yquick operation: no temporary load connections to make ygreen operation: no wasted energy ysafe operation: less hazardous due to minor electrical activities The Safe Capacity Test: Working Principle Understanding how the safe capacity test works is simple: instead of flowing directly from the double conversion chain to the load, power is forced to follow a closed loop circulation from the inverter back to the rectifier through the static bypass. This continuous circulation of power allows the converters to be loaded and energized as if the UPS were connected to a traditional load bank test, but with the enormous advantages of energy consumption being maintained at a minimum level. In fact, energy dissipation during circulation is just that related to the UPS AC/AC efficiency which is dissipated into heat. State-of-the-art UPS have an average double conversion efficiency higher than 96%, thus, the energy dissipated is less than 4% of the overall power circulating into the loop, which makes the safe capacity test an eco-friendly and energy saving solution. In order to allow the continuous circulation of power, the UPS software uses a digital control technique to adjust and modify the phase angle of the inverter output. This is feasible because the inverter and the static bypass are in parallel and the power flow between parallel voltage sources is easily manipulated by varying their phase angle. If one of the sources has a wider phase angle than the other, it is in a leading state and in a condition of delivering power. This is the situation we can find during the safe capacity test. Initially, when the power is introduced from the mains, the double conversion mode starts operating normally, but when the test begins, the static switch is opened and the inverter - now in parallel with utility - varies its output phase angle to deliver power to the static switch and allow a closed loop. The wider the phase angle, the higher the power delivered by the inverter. At this point, in order to avoid the reintroduction of power into the mains, the 5

TWO STAGE POWER DISTRIBUTION rectifier absorbs power and produces direct current to support the inverter and complete the power circulation. During this entire process, the UPS is capable of testing its own power train and components because the calibrations and measurements are the same as if the test were performed with an external and expensive load bank. From an operational standpoint, when the test is performed, the appointed service technical field engineer opens the output switch of the UPS and activates the safe capacity test by simply setting a dedicated UPS parameter. Subsequently, the technician sets up the active (P) and reactive (Q) power that must be supplied (thus indirectly setting up the phase angle as well). This couple (P & Q) will simulate the load. In particular: yactive power parameter (P): when enabled, it defines the active power amount in kw supplied to the bypass line by the inverter and is available only when the inverter is started. yfor this parameter, the minimum value is 0 kw while the maximum is equal to 120% of the maximum UPS active power. yreactive power parameter (Q): when enabled, it defines the reactive power in kvar supplied to the bypass line by the inverter and is available only when the inverter is started. For this parameter, the minimum and maximum values are saturated at ± 120% of maximum UPS apparent power. A negative value means the generation of lagging reactive power while a positive value means the generation of leading reactive power. Consequently, the two parameters above can be used to test the UPS at different load percentages (e.g.: 25%, 50%, 75%, 100%) up to an overload condition of 120%. The inverter, bypass and rectifier, indeed, simply let the energy flow as if they were powering a real load connected to the output of the UPS. UPS (P, Q) QS4 TO LOAD FROM UTILITY Measuring Parameters Less than 4% heat dissipation Figure 4: Working Details of a Safe Capacity Test 6

Safe Capacity Test: Typologies 1) Safe Capacity Test on a Single Monolithic System This test typology occurs when the inverter runs in parallel with the mains through the static bypass switch and energy circulates between the inverter and the rectifier in a closed loop. 2) Safe Capacity Test on a Distributed Parallel System The above procedure can also be executed on each Liebert EXL S1 UPS, composing a distributed parallel system. This can be done by temporarily removing it from the parallel system disconnecting all its parallel cables. 3) Safe Capacity Test on a Multiple Module System This safe capacity test described is also available with a multiple module system, such as Liebert Trinergy Cube or a Liebert EXL S1 centralized parallel system with MSS. a) Single Core Test The safe capacity test is performed on one single core of the Liebert Trinergy Cube or on a single Liebert EXL S1 that composes the centralized parallel system. b) Multiple Core Test The safe capacity test will be performed on one subset of cores of the Liebert Trinergy Cube or on a subset of Liebert EXL S1 units composing the centralized parallel system with MSS. c) Full System Test The safe capacity test is performed on a full Liebert Trinergy Cube system or on all the Liebert EXL S1 units composing the centralized parallel system with MSS. UPS QS4 TO LOAD FROM UTILITY Figure 5: Safe Capacity Test on a Single Monolithic System 7

STATIC BYPASS UPS/CORE 1 UPS/CORE N FROM UTILITY TO LOAD Figure 6: Single Core Safe Capacity Test on a Multiple Module System 8

STATIC BYPASS UPS/CORE 1 UPS/CORE 2 UPS/CORE N UPS/CORE N FROM UTILITY TO LOAD Figure 7: Multiple Core Safe Capacity Test on a Multiple Module System 9

Safe Capacity Test: Benefits Money Savings The safe capacity test eliminates the need to rent a load bank and the waste of energy related to its use. Time Savings The safe capacity test can be performed easily and swiftly by a service technical field engineer without requiring special equipment, saving time needed to install, connect and further dismantle the load banks to the UPS output. Safe Capacity Test: Conclusions The safe capacity test is an alternative and more effective method of testing the capabilities of a UPS by simply allowing the circulation of power in a closed loop inside the unit, then from the inverter and back to the rectifier through the static bypass. Moreover, the test eliminates all expenses in terms of time, money and energy consumption associated with traditional load bank testing. All these features, combined with the substantial reduction in terms of risks and complexity during operations, make the safe capacity test a highly flexible and practical testing methodology. Energy Savings The safe capacity test is an eco-friendly approach, since the only energy losses come from the heat dissipation of converters. As a consequence, energy consumption is highly reduced if compared to a traditional load bank test. Risk Savings The safe capacity test eliminates all hazards and risks associated to the use of load banks, such as their movement, noise and temporary connections. Flexibility The safe capacity test can easily be performed directly on-site during commissioning, after a system repair or upgrade, as well as during preventive maintenance. The test does not require special equipment and, above all, it avoids the possibility of hard and laborious cable connection through doors and panels. 10

11

VertivCo.com Vertiv Infrastructure Limited, George Curl Way, Southampton, SO18 2RY, VAT Number: GB188146827 2017 Vertiv Co. All rights reserved. Vertiv, the Vertiv logo and Liebert GXT4 are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. Assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.