COOPER POWER SERIES. DE250 deadbreak elbow connector installation instructions interface A. Screened Separable Connectors MN650025EN

Similar documents
COOPER POWER SERIES. DS250 deadbreak straight connector installation instructions interface A. Connectors MN650027EN

DT400/436 Tee Connector Installation Instructions

COOPER POWER SERIES. 200 A 15/25 kv class deadbreak straight connector installation instructions. Deadbreak Apparatus Connectors MN650043EN

COOPER POWER SERIES. 200 A 15/25 kv class elbow installation instructions. Deadbreak Apparatus Connectors MN650042EN

COOPER POWER SERIES. 600 A 15, 25 and 35 kv class bushing adapter installation instructions. Deadbreak Apparatus Connectors MN650058EN

COOPER POWER SERIES. 200 A 15, 25, and 35 kv class portable feedthru installation instructions. Loadbreak Apparatus Connectors MN650037EN

COOPER POWER SERIES. 600 A 15, 25, and 35 kv class PUSH-OP bushing adapter cap installation instructions. Deadbreak Apparatus Connectors MN650050EN

COOPER POWER SERIES. 200 A 15, 25, and 35 KV class insulated standoff bushing installation instructions. Loadbreak Apparatus Connectors MN650039EN

COOPER POWER SERIES. 600 Ampere Deadbreak Grounded Standoff Bushing 15 & 25 kv and 35 kv Class Installation Instructions. Bushings MN650045EN

200 A, 15 and 25 kv class loadbreak bushing insert installation instructions

COOPER POWER SERIES. Manual or Hostick Operable, Padlockable 150 A Tap-Changer Switch Installation Instructions. Tap-Changer Switch MN800015EN

COOPER POWER SERIES. D-73P3 bypass switches installation instructions. Switches MN008005EN. Effective April 2016 Supersedes S June 2013

COOPER POWER SERIES. EL Bay-O-Net Current-Limiting Fuse Installation Instructions. Fusing Equipment MN132023EN

COOPER POWER SERIES. UltraSIL Polymer-Housed Distribution-Class MOV Surge Arrester Installation Instructions. Surge Arresters MN235006EN

Effective March 2015 Supersedes S August 2002

COOPER POWER SERIES. Series winding ratio test procedure instructions. Voltage Regulators MN225060EN. 120 Vac VOLTMETER

COOPER POWER SERIES. Under-oil arrester disconnector installation/operation instructions. OEM Equipment MN800010EN

COOPER POWER SERIES. QD8 Quik-Drive tap-changer VR or VL reversing switch stationary contact assembly kit number A48 installation instructions

COOPER POWER SERIES. 600 A, 15, 25, and 35 kv Class Cleer Grounding Elbow Installation Instructions. Loadbreak Apparatus Connectors MN650056EN

DAI630TB2669 Dead Front Arrester Installation Instruction

COOPER POWER. SERIES VariSTAR type composite light-duty under-oil (CLU) MOV arrester installation instructions. Surge Arresters MN235023EN

COOPER POWER SERIES. 50 A 2:1 series multiple (dual voltage) switch cap/wrench, lever or hotstick operable handles installation instructions

Effective May 2017 Supersedes July 2009 (S ) 600 A 35 kv Class T-OP II connector assembly installation instructions 200 A PROTECTIVE CAP LRTP

COOPER POWER SERIES. UltraSIL polymer-housed VariSTAR surge arrester IEC for MV systems to 36 kv installation instructions

COOPER POWER SERIES. VariSTAR Storm Trapper high energy MOV arrester installation instructions. Surge Arresters MN235017EN

COOPER POWER SERIES. 600 A 35 kv class PUSH-OP deadbreak connector installation instructions. Deadbreak Apparatus Connectors MN650052EN

COOPER POWER SERIES. 200 A 35 kv class LE series elbow installation instructions. Loadbreak Apparatus Connectors MN650010EN

600 A 35 kv class PUSH-OP deadbreak connector installation instructions

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with optional integral jacket seal installation instructions. Loadbreak Connectors MN650008EN

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with integral jacket seal* for use on tape and wire shielded cable installation instructions

COOPER POWER. SERIES VariSTAR type AZE station class surge arresters installation and maintenance instructions. Surge Arresters MN235022EN 0.

Effective January 2017 Supersedes July 2011 (I ) VariSTAR Type AZG4 Surge Arresters Installation and Maintenance Instructions

COOPER POWER SERIES. Operation Counter Replacement Instructions. Reclosers MN280047EN. Effective May 2016 Supersedes S December 2003

S Loadbreak Apparatus Connectors WARNING: WARNING:

S Surge Arresters

COOPER POWER SERIES. Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions. Reclosers MN280051EN

COOPER POWER SERIES. VFI SF6-insulated vacuum fault interrupter installation, operation and maintenance instructions. Switchgear MN285004EN

Installation Instructions for the Walking Beam Interlock for Eaton EHD, FDB, FD, HFD, FDC, FW, HFW, FWC, Circuit Breakers and Molded Case Switches

Effective May 2017 Supersedes August 2005 (S )

Inspection Recommendations

ROPV R40 E Series User Manual

Medium voltage standard-duty, heavyduty, and extreme-duty single-phase, unfused capacitor units and accessories

S Surge Arresters. Handling and Storage. Standards. Acceptance and Initial Inspection

INTRODUCTION BILL OF MATERIALS SPECIFICATIONS & TOOLS PROCEDURES OPERATION OF SEATPOST GIANT LIMITED WARRANTY

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

Pressure Dump Valve Service Kit for Series 2300 Units

DEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers

Teledyne Oil & Gas North Williamson Blvd. Daytona Beach, FL USA (phone) (fax)

Sterile Visual Flow Indicator

STYLE 3414/3416 & 3421/3423 Apollo Monitor with Foldaway Legs OPERATING & MAINTENANCE INSTRUCTIONS

Operation Manual Enabling Pole-Top Communication Via the TripSaver II Magnet Tool

DISASSEMBLING & REASSEMBLING CARTRIDGE INSTALLING SEATPOST ON BIKE

TactAir PCP Fill Kit/Adapter. Operation Manual

Norrsken Family Booklet

INSTALLATION & MAINTENANCE INSTRUCTION

Pressure Dump Valve Service Kit for Series 3000 Units

S Vacuum Switches. Contents. Type VCS-1 Single-Phase Vacuum Capacitor Switch Installation and Operation Instructions

Repair instructions. Pivot bushing replacement. XL-AS10001RM-en-DE Rev B

E2K-L. Liquid Level Sensor That Is Unaffected by the Color of the Pipe or Liquid. Liquid Level Sensor. Ordering Information

FLANGED TWO-PIECE BALL VALVES

Permanent Roof Anchors

Hot Tapping Machine. OPERATIONS MANUAL and OPERATING INSTRUCTIONS

FLANGED TWO-PIECE BALL VALVES

INSTRUCTION MANUAL MP4AR Remote Convection Gauge Range: 1 x 10-3 Torr to 1 x 10+3 Torr

2-1- Shipping Receiving Lifting Location on Site Installation Stages 6

Constant Pressure Crude Oil Container Model CPCCP

ESA Elbow Sealing Adapter Kit

E8AA. Pressure Sensor of Stainless Steel Construction Is Ideal for a Wide Range of Applications. Pressure Sensor (Stainless Steel Diaphragm)

ULTRA HIGH PRESSURE PAINT GRATE CLEANER FCT-JS OPERATION AND MAINTENANCE MANUAL

3M Liqui-Cel EXF-14x28 and 14x40 Series Membrane Contactor

Instruction Manual. PE-25/32/37 Tapping Machines. POLYTAPP Valves

IMPACT RING BIT SYSTEM Care & Maintenance Instructions

GETZ EQUIPMENT INNOVATORS PART NO.: 9G59554 MODEL: MS 36 SC-R HYDROSTATIC TEST PUMP

OPERATION AND INSTRUCTION MANUAL Swivel Anchor Model: HD26248

OPERATING and MAINTENANCE INSTRUCTIONS MAXIS Grips

Operating Instructions for BAIR22-6 AIR-POWERED CRIMPING TOOL

FLANGED MULTI-PORT BALL VALVES

Model No Product Name Handpiece Only Complete System

WHEATLEY Series 500 Swing Check Valve

PROPORTIONING VALVE. Model 150 INSTRUCTION MANUAL. March 2017 IMS Company Stafford Road

GRAVITY BIKE RACK ASSEMBLY & OPERATING INSTRUCTIONS

UE- 90- X X X X X X O P E R AT I N G M A N UA L 0 TO 90 HYDRAULIC UPENDER

Booster Pump PB4-60 Replacement Kits

Angled Sign Light with Shade

Instruction Manual LIMITED 1 YEAR WARRANTY. Hydraulic Punch Driver Read this material before using this product.

Vertical Lifeline. Ladder Climb. User Instructions. 3M Occupational Health and Environmental Safety. Fall Protection Equipment

Portable Massage Table User Manual

VL 2K LIFT D-L WINCH INSTRUCTIONS (Applies to P/Ns , , , , , )

INSTALLATION COMMISSIONING, OPERATION & MAINTENANCE MANUAL

Hydraulic Punch Drivers

COSASCO MODEL 60 RETRACTABLE 1500 PSI SYSTEM RETRACTOR KIT Work Instruction

Triple Tine Mechanical Grapple

SANTA CRUZ BICYCLES Cable Routing Procedure MY17

3 Scotch-Weld Polyurethane Reactive Adhesive Applicator Replacement Part Installation Guide

3M Liqui-Cel EXF-10x28 Series Membrane Contactor

DBML-60/80 Squeeze Tool

Owner s Manual & Safety Instructions

QUALITY ALUMINUM BOAT LIFTS, INC. INSTRUCTIONS. Dominator Lake Lift

Instruction Manual. Model TC1-S TopSide Clamp. top side clamp. For your personal safety READ and UNDERSTAND instructions before using tools.

plasmarc air curtain For use with m3 Plasma System and PT-36 Plasma Torch ESAB Assembly Number: Instruction Manual gas the bottom of the plate.

Transcription:

Screened Separable Connectors MN650025EN Effective November 2016 Supersedes September 2013 (IS550-10-1) DE250 deadbreak elbow connector installation instructions interface A COOPER POWER SERIES

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. i

Contents DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY... I SAFETY FOR LIFE... III SAFETY INFORMATION... III Safety instructions... iii PRODUCT INFORMATION.... 1 Introduction...1 Acceptance and Initial Inspection...1 Handling and Storage...1 Standards...1 INSTALLATION INSTRUCTIONS.... 1 Installation Instructions...1 ii

! SAFETY FOR LIFE Safety for life Eaton s Cooper Power series products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high-voltage lines and equipment, and support our Safety For Life mission.! SAFETY FOR LIFE Safety information The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians, who are familiar with this equipment should install, operate, and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as arc flash clothing, safety glasses, face shield, hard hat, rubber gloves, clampstick, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION Indicates a hazardous situation which, if not avoided, may result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high- and low-voltage lines and equipment. G103.3 WARNING Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. G101.0 WARNING This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage. G102.1 WARNING Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. G122.3 iii

Product information Introduction Eaton s Cooper Power series 250 A, 24 kv deadbreak elbow connectors are used to terminate polymeric cable to equipment, such as transformers, switchgear, motors etc. equipped with a bushing having interface A per CENELEC EN 50180 and EN 50181. The deadbreak elbow is fully screened, fully submersible, and meets the requirements of IEC 60502 4 and CENELEC HD 629.1 S2. The deadbreak elbow connectors can be mounted vertically, horizontally or any angle in between with proper cable support. Installation instructions Cable stripping and scoring tools, available from various tool manufacturers, are recommended for use when installing deadbreak elbows. After preparing the cable, the elbow housing is pushed onto the cable. The probe contact is threaded into the compression connector using the supplied installation tool or an approved equivalent. Use a hotstick to perform installation and removal operations. 100 mm Read this manual first Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment. Additional information These instructions cannot cover all details or variations in the equipment, procedures, or process described nor provide directions for meeting every possible contingency during installation, operation, or maintenance. For additional information, contact your representative. 320 mm Insulation Screen Acceptance and initial inspection Each deadbreak elbow connector is completely inspected and tested at the factory. It is in good condition when accepted by the carrier for shipment. Upon receipt of a deadbreak elbow connector, inspect it thoroughly for damage and loss of parts incurred during shipment. If damage or loss is discovered, file a claim with the carrier immediately. Screen Wires Handling and storage Be careful during handling and storage of the deadbreak elbow connector to minimize the possibility of damage. If the deadbreak elbow connector is to be stored for any length of time prior to installation, provide a clean, dry storage area. Standards ISO 9001Certified Quality Management System CAUTION All associated apparatus must de de-energized during installation and/or maintenance. Cable Sheath Complete elbow kit includes: Elbow Body with Test Point and Cap Compression Connector Probe Contact Probe Installation Tool Bail Assembly Silicone Lubricant Instruction Sheet 1

Tool/accessories needed: Tape Measure Wire Brush Knife Cable Stripping Tool Crimping Tool Cable Cleaner Cable Cutters Emery Cloth Step 1. 1. Train the cable to the desired finished position. Be sure that the cable is long enough to permit movement of the elbow connector from the apparatus bushing to a standoff bushing. 2. Cut the cable 100 mm past the centerline of the bushing. NNote: This is the initial length of the cable to ensure that the screen wires are long enough to reach the system earthing point and the earthing eye on the elbow connector. The cable will be cut to its final length below. 3. Remove the cable sheath for a distance of 320 mm from the end of the cable. Step 2. 1. Fold the screen wires back over the sheath and secure them with two layers of vinyl tape. 2. Reposition the cable to its final position and cut it 20 mm from the bushing centerline. 3. Remove 145 mm of insulation screen. NNote: The insulation screen (semi-con) needs to be terminated in a clean, square cut. Care should be taken to prevent damage to the primary insulation. If the primary insulation is damaged during scoring or ring cut, the cable must be re-terminated. The end of the insulation screen is a high stress area. If the primary insulation requires sanding, it should be done by both hands using a back and forth motion similar to the way a shoe is shined and sanded equally around the circumference of the cable leaving no flat spots. Only a 120 gritt or finer aluminum-oxide (emery cloth) should be used. Do not use any other abrasives. 20 mm Cut 145 mm Primary Insulation Ring Cut Insulation Screen Vinyl Tape 2

CAUTION Equipment Damage. Nicks in the primary insulation at the ring cut point will lead to partial discharge and eventual dielectric breakdown of the primary insulation. Nicks at this location cannot be repaired. (See note below.) Step 3. 1. Remove L mm of primary insulation. See table. Be careful not to damage the conductor. CONNECTOR L BIMETALLIC 50 COPPER 40 2. Chamfer the edge of the primary insulation no more than 5 mm at 45 degrees to ease installation. 3. Apply three (3) layers of vinyl tape if a sealing boot, cold shrink sleeve or heat shrink sleeve is to be used. This will prevent scoring the inside of the boot or sleeve. 4. If an additional cable seal is required, follow the instructions in the cable sealing kit. "L" Vinyl Tape Conductor Chamfer Step 4. 1. Remove vinyl tape before installing connector. 2. If the conductor is aluminum, thoroughly wire brush the exposed conductor. 3. Immediately insert the conductor into the crimp barrel as far as it will go. Ensure that the flat surface of the compression connector faces the bushing. 4. Crimp the connector starting at the shoulder, as shown. Rotate the crimping tool 90 degrees for each successive crimp. See Crimp Chart on page 4. 5. Remove any excess inhibitor that may have come out of the connector. Wipe the excess inhibitor towards the eye of the connector. 6. Remove any sharp edges after crimping. 4 3 2 1 Primary Insulation Proceed to Step 4. 3

Step 5. 1. Clean the insulation with a lint-free cloth and a suitable cleaner. 2. Apply a thin layer of lubricant to the primary insulation of the cable and the interior of the cable end of the moulded elbow housing 3. Push the elbow onto the cable as far as it will go. Ensure that the threaded hole of the connector is visible through the interface end of the elbow. F 19.6-24.1 MM DE250 250A 24 kv DE250 250A 24 kv Probe Hex Key.770-.950 IN F 19.6-24.1 MM.770-.950 IN Lubricate 4 3 2 1 Step 6. 1. Insert the probe into the threaded hole of the connector. Ensure that the threads are not crossed. 2. Tighten the probe with the supplied hex wrench. The proper torque is reached when the hex key has bent 90 to 180. 3. Connect one of the screen wires to the earthing eye on the elbow. 4. Connect the screen wires to earth. Table 1. Crimp Chart Catalog Number Material Cable Size mm2 Die Index CDE250P16 Bimetallic - plated CDE250U16 Bimetallic 16 CDE250C16 Copper CDE250P25 Bimetallic - plated CDE250U25 Bimetallic 25 CDE250C25 Copper CDE250P35 Bimetallic - plated 16 CDE250U35 Bimetallic 35 CDE250C35 Copper CDE250P50 Bimetallic - plated CDE250U50 Bimetallic 50 CDE250C50 Copper CDE250P70 Bimetallic - plated CDE250U70 Bimetallic 70 18 CDE250C70 Copper CDE250P95 Bimetallic - plated CDE250U95 Bimetallic 95 20 CDE250C95 Copper CDE250P120 Bimetallic - plated CDE250U120 Bimetallic 120 22 CDE250C120 Copper 4

Step 8. 1. Hook the legs of the bail assembly onto the bail tabs on the bushing or bushing clamp. Thread the eyebolt of the bail assembly tight against the back of the pulling eye of the elbow. DE250 250A 24 kv Lubricate F 19.6-24.1 MM.770-.950 IN Step 7. 1. Clean the bushing and connector interfaces and apply a thin layer of lubricant to each. 2. Push the elbow onto the bushing until it is fully seated. 5

Pulling Eye Stainless Steel Bail Bail Tab CAUTION The apparatus bushing and elbow connector should not support the weight of the cable. Clamp the cable immediately below the cable screen adapter. Failure to comply may result in equipment damage. WARNING Capacitive Test Point Operating Instructions. Use only voltage indicating instruments specifically designed for test points. Use of conventional voltage sensing devices may provide false No Voltage indications. The test point must be dry and free of contaminants when checking for voltage. After indication is taken; clean, dry, and lubricate the test point cap with silicone grease and assemble to test point. The capacitive test point is not sufficiently accurate, nor is it intended for actual voltage measurements or phasing operations. A reading of no voltage from the test point should not be the only indication of a de-energized circuit obtained before touching the connector. Other procedures can include direct conductor voltage testing or grounding using a live-line tool. Optional spring bail Optional Spring Bail 1. Hook the legs of the bail assembly into the tabs of the bushing flange. Lift the bail from the lifting eye and center it on the back of the pulling eye of the elbow. 6

This page intentionally left blank. 7

! SAFETY FOR LIFE Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries 2016 Eaton All Rights Reserved Printed in USA Publication No. MN650025EN November 2016 Eaton is a registered trademark. All trademarks are property of their respective owners. For Eaton's Cooper Power series product information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.