Translation Principles of testing and certification for insulating hose assemblies on cable cutting devices

Similar documents
Measurement accessories METPOINT OCV for the measurement in systems up to 40 bar

Geopress. Instructions for Use. Year built: from 01/2004 en_int

Flexible hoses - Non-metallic materials

Doors in watertight bulkheads of cargo ships and passenger ships

Type 2000 INOX. Quickstart. English Deutsch Français. 2/2-way angle seat valve 2/2-Wege Schrägsitzventil Vanne à siège incliné 2/2 voies

ISO 6804 INTERNATIONAL STANDARD. Rubber and plastics inlet hoses and hose assemblies for washing-machines and dishwashers Specification

ISO 4081 INTERNATIONAL STANDARD. Rubber hoses and tubing for cooling systems for internal-combustion engines Specification

SECTION PRESSURE TESTING OF PIPING

User Manual for the Application of Hose Assemblies for High-Pressure Water Jet Machines

Supplementary Operator s Manual 42/24-14 EN Rev. 3

Pressure Calibrators. Series PC..., PM...

Flamco Airfix D-E. Installation and operating instructions. 1999, Flamco eps

INTERNATIONAL OIML R 32 RECOMMENDATION. Rotary piston gas meters and turbine gas meters ORGANISATION INTERNATIONALE INTERNATIONAL ORGANIZATION

F-08 HIGH-PRESSURE HOSE USED IN CO2 SYSTEM

Road and rail tankers with level gauging Part 2 Metrological controls and tests. Page 1 of 42 OIML TC8/SC1/WG3/R 80-2 CD1 Draft of July

ASSE International Product (Seal) Listing Program

Pneumatic high-pressure controller Model CPC7000

Smart Water Application Technologies (SWAT) TM

DK46 - DK800 Supplementary instructions

SNOW PICKETS` Climbing and Mountaineering Equipment. Foreword

BELAY LANYARD. Climbing and Mountaineering Equipment. Foreword

Key Comparison of Safety Requirements in Europe, North America and Australia for Electronic Products

ISO/TC 131/SC Hydraulic fluid power Test methods for hoses and hose assemblies

TIGHTNESS. Glass sealing Thanks to our glass-sealing technology, ODU products can meet the most demanding tightness requirements.

HEAT, COLD, SOLAR ULTRAVIOLET & INCLEMENT WEATHER

Rigel 601 CHECKBOX. Instruction Manual. 348A551 Issue 2.0. April Seaward Electronic Ltd. Issue 2.0

Technical Information Conducal CLY421

Operating Instructions

Operating Instructions in compliance with Pressure Equipment Directive 2014/68/EU. FAS Brass Check Valve RDL

Product Specification Spring Finger

TECHNICAL SPECIFICATION

A Rationale for Pressure Relief Device(s) Qualification Requirements (LH2)

better measurement Simply a question of SCHMIDT Flow Sensor SS The cost-effective alternative in pressurised systems up to 10 bars.

Mounting and Operating Instructions EB 2558 EN. Self-operated Pressure Regulators. Type Pressure Build-up Regulator

Technical Standard Order

Mobile High Pressure Compressor Unit for Compressing Air and Breathing Air. PE 250-TE with compressor control (optional equipment)

Gas plug-in hose, straight-through form. Instructions for Use. suitable for gas socket model G2019T, G2016T. G2023 from 01/1990.

Guidelines to the standard IEC60601

Operating Instructions

Micro Dial-Flowmeter. Instructions for Use

GM Series Dual-Block Multi-Function Gas Control Valves

ISO INTERNATIONAL STANDARD. Small craft Liquefied petroleum gas (LPG) systems

Operating Instruction English. Revision A Date author NH This operating instruction is not subject to updating. Airgun

DNVGL-CP-0187 Edition March 2016

Pneumatic high-pressure controller Model CPC7000

ARKANSAS TECH UNIVERSITY FACILITIES MANAGEMENT HEALTH AND SAFETY MANUAL (LOCKOUT/TAGOUT) 30.0

CY LSOH Screened Halogen Free Control Cables with improved fire performance

Oxygen Dialflow Meter. Instructions for Use

Safety Standards. of the Nuclear Safety Standards Commission (KTA)

Summary of Substantive Changes between the 2004 e1 and 2017 editions of ASSE 1011, Hose Connection Vacuum Breakers

Oxygen Dialflow Meter. Instructions for Use

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

SUPPLY OF ISOLATION AND APPLIANCE VALVES PTS - APPLIANCE BALL VALVE

A hose layline contains important information for specifying the replacement assembly: manufacturer, hose trade name, working pressure and hose ID.

Operation Manual. Hand tool for AMP DUOPLUG Customer Manual PN: en (Translation of the original German version)

Integral type Differential pressure flowmeter VNT Series

ES18 Security Theory/Regulations Answer Schedule

Guide for Evaluating Your Hose Assembly Supplier

This document is a preview generated by EVS

OKLAHOMA CITY COMMUNITY COLLEGE CONTROL OF HAZARDOUS ENERGY PROGRAM. Environmental Health and Safety. Established:

ASSEMBLY INSTRUCTIONS S O L O N STANDARD MODULES

P-04 Stainless Steel Corrugated Hoses and Metal Bellows Expansion Joints

Operating Instructions - Rescue Equipment. RAM Support LRS-T EN Edition (translation of the original operating instructions)

Safety. Operating instructions Solenoid valve for gas VG 6 VG 15/10 DANGER. Contents WARNING CAUTION. Changes to edition 09.14

Operating Instructions Hand Test Pump BHP 700

PSSI 6 Demarcation of Work Areas in Substations

ISO 3996 INTERNATIONAL STANDARD. Road vehicles - Brake hose assemblies for hydraulic braking Systems used with non-petroleum-base brake fluid

32374 R. Jazowski 4/4/ D. W. Mudge G. Sivik 1 of 8 ODN TITLE: Installation & Operation Manual for Nautilus G2 Connectors

PART Q CONTROL OF HAZARDOUS ENERGY (LOCKOUT-TAGOUT)

Ground Fault Circuit Interrupter(GFCI) Policy

IAPMO GUIDE CRITERIA FOR BALL VALVES IAPMO IGC PURPOSE

PRODUCT SPECIFICATION. SFP+ Cage and Cage Assembly 1 of 8 A

High-performance submersible pressure transmitter For level measurement Model LH-10

Draft Indian Standard WIRE ROPE SLINGS AND SLING LEGS- SPECIFICATION (Second Revision) ICS ;

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

3-Way Safety Block DSV

BRITISH STANDARD BS 341-4: Transportable gas container valves. Part 4: Pressure relief devices ICS

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Type Type Differential Pressure Regulators (opening)

General Requirements of the NEC Advanced Course. Building Officials and Inspectors Educational Association

Operating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073

Steam Trap BK 15 (DN40, DN 50) Original Installation Instructions English

MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection

SUPPLY OF ISOLATION AND APPLIANCE VALVES PTS - ISOLATION BALL VALVE

EUROPEAN pr I-ETS TELECOMMUNICATION September 1995 STANDARD

Intertek Testing Services Taiwan Ltd.

User Manual PTW-DensiX. D / Di/Zi

Safety Manual VEGAVIB series 60

Type Operating Instructions. 2/2-way solenoid valve 2/2-Wege Magnetventil Electrovanne 2/2 voies.

Semoflex Roboschlepp The PUR cable for cable chains

PLEASE NOTE: Pressures for 200mm (8ins) and 250mm (10ins) are based on the use of METALFLEX Braided Braid

Supplementary Installation and Operating Instructions. Variable Area Flow Meters SGK-1 Ex SGK-2 Ex SGK-3 Ex. Category: II 2G Ex IIC II 3G Ex IIC

Contents. Operating instructions. Pressure switch, heavy-duty version Model PSM-520

Rules for the Installation, Inspection and Testing of Air Reservoirs (Other than on Locomotives)

IDL01. Battery Powered Precision Digital Gauge for Leak Testing. Stainless Steel Sensor. class 0.05

LESER Deutschland Standard Functional Tightness Test (Cryo) Content

Information Sheet. About this information sheet. Floor and wall loadings. Attachment of process module to floor. PlasmaPro Estrelas100

ATEX heated hoses of series WEX7

Mounting and Operating Instructions EB 2172 EN. Series 43 Temperature Regulators. Type 43-5 and Type Type Type 43-6

E/ECE/324/Rev.2/Add.133 E/ECE/TRANS/505/Rev.2/Add.133

Flexible Metal Hose Products

Transcription:

Translation Principles of testing and certification for insulating hose assemblies on cable cutting devices Status as of 2014-01 Principles of testing Insulating hose assemblies on cable cutting devices GS-ET-40 Energy, textile & electrical media products department Testing and certification facility in DGUV Test Gustav-Heinemann-Ufer 130 50968 Cologne, Germany GS-ET-40 Page1 of 13

These Principles of testing serve as verification that the requirements of the German Product Safety Act (ProdSG) with respect to the use of cable cutting devices have been complied with in accordance with DIN EN 50340 and GS-ET 23. These principles will be revised and supplemented periodically in consideration of knowledge gained in the area of occupational health and safety, as well as technical progress. The most recent edition shall always be binding for tests conducted by the Electrical engineering testing and certification body. These Principles of testing serve to render more precisely the requirements and tests found in DIN EN 50340 and in GS-ET 23 for motor-operated cable cutting devices. This is the English translation of the German test principle. The German original version is obligatory. Changes from the edition 2013-10: 3.3 Number of test devices adapted 4.4.4 Reference to test standard specified Page2 of 13

Table of Contents Page 1 General 4 1.1 Scope of application 4 1.2 Testing and/or certification process 4 1.3 Test specifications 4 2 Terms 5 3 Test conditions 6 4 Requirements and tests 7 4.1 General requirements 7 4.1.1 Insulating hose assembly 7 4.1.2 Insulating hose assembly measurement 7 4.1.3 External materials and properties 8 4.2 Inscriptions 8 4.2.1 Insulating hose 8 4.2.2 Insulating hose assembly 9 4.3 Electrical testing 9 4.3.1 Leakage current 9 4.4 Mechanical testing 12 4.4.1 Hydrostatic testing 12 4.4.2 Testing with mechanical pressure impact 12 4.4.3 Burst testing 12 4.4.4 Cold bend testing 13 Page3 of 13

5 Testing at manufacturer facilities 13 5.1 Piece testing 13 5.2 Random testing 13 1. General Considerations behind the Principles of testing: Only insulating hoses are tested within the framework of the electrical testing. Other components associated with the insulating hose assembly (e.g. fittings, bend/kink protection, etc.) are not taken into consideration. It has also been determined that it is not possible to reproducibly make a cut of (0.1 +0.1 ) width on the insulating hose. Testing according to Section 5.4.2 Long-term exposure is not practical for application on cable cutting devices because these insulating hose assemblies are not subjected to the underlying loads. Change of length testing according to Section 5.4.5 is not practical because the determination of compliance with a minimum length is tested using an insulating hose assembly at least 10 m long. 1.1 Scope of application 1.1.1 These Principles of testing apply to insulating hydraulic hose assemblies used on cable cutting devices. Cable cutting devices are used in order to determine whether cables with nominal voltages up to 30 kv (maximum permissible operating voltage up to 36 kv) and nominal frequencies up to 60 Hz are exposed to live voltage at the workplace in conjunction with organisational measures. Testing is carried out in accordance with DIN VDE 0105 Part 1 (2005-06), Section 6.2.3. 1.1.2 These Principles of testing may be applied accordingly to insulating hydraulic hose assemblies with exposure greater than 30 kv up to 60 kv (maximum permissible operating voltage over 36 kv up to 72.5 kv). Page4 of 13

1.2 Testing and/or certification process The testing and/or certification process will be initiated upon signing of the contract by the contractual partners. The technical documentation set forth in Section 3 is to be submitted together with the contract. All test objects and test pieces required for testing are set forth in Section 3.3 and are to be made available at no charge. Additional components and materials are to be made available at the request of the testing laboratory. 1.3 Test specifications The standards listed below were taken into consideration while preparing these Principles of testing: DIN EN 62237 Live working Insulating hoses with fittings for use with hydraulic tools and equipment 2 Definitions 2.1 Insulating hose Insulating, pressure resistant hose used as part of an insulating hose assembly. 2.2 Insulating hose assembly Insulating, pressure resistant component consisting of an insulating hose with fittings at each end for the connection of parts of hydraulic equipment at different electrical potentials 2.3 Connecting elements A pair of fittings to permit a connection between hydraulic components 2.4 Maximum operating pressure Operating pressure specified by the manufacturer that must not be exceeded during operation of the cable cutter. Page5 of 13

2.5 Bend/kink protection Prevents the bending radius at each end of the insulating hose from falling below specified minimums. 2.6 Type test Testing carried out on a test object/test piece under subjection to certain assumptions in order to verify that defined requirements have been complied with. 2.7 Test object Insulating hose assembly 2.8 Test piece Part of the test object (hose section, connecting element, bend/kink protection, etc.) 3 Test conditions 3.1 General All tests on ready-for-use insulating hydraulic hose assemblies are to be carried out on the same test object each time. Insofar as it has not been set forth in the individual test sections, the tests are to be carried out at an ambient temperature of 20 C ± 5 K and a relative humidity of 30 to 70 %. All values required for testing must be maintained with such precision that ensuing test results will not be influenced by more than ± 5 %. 3.2 Test documentation to be submitted The following technical documentation is required for testing: Parts list(s) Engineering drawings for the insulating hose Data sheet for the hydraulic connecting elements (fittings) Data sheet for the insulating hose Manufacturer's declaration related to PAH contamination, or data sheets for the materials that may come into contact with the skin, if applicable. Page6 of 13

3.3 Required test objects and test pieces To be provided at no charge for testing: Test object: 1 piece, at original length 3 pieces, with free hose lengths as calculated according to Section 4.4.2 3 pieces, with free hose lengths of 2000 mm 9 pieces, with free hose lengths of 600 mm Test pieces: 1 piece, insulating hose (length = 400 mm) 1 piece, connecting element 1 piece, bend/kink protection (if used) 1 piece, protective tubing (if used) 1 piece, press fittings for protective tubing (if used) 4 Requirements and tests 4.1 General requirements 4.1.1 Insulating hose assembly The overall length of the insulating hose assembly must be flexible and be made of insulating material. Visual inspection and handling check of the insulating hose assembly as well as a review of the product data sheets. 4.1.2 Insulating hose assembly measurement The insulating hose assembly must consist of one piece and the insulating hose must not be shorter than 10 m when maximum operating pressure is applied. The insulating hose assembly must be completely filled with fluid and subsequently sealed on one end with suitable connecting element fittings. The other end of the insulating hose assembly is to be connected to the pressure source via a pressure gauge. The pump should be operated until reaching the maximum permissible operating pressure. The length of the insulating hose assembly should be measured after one minute. The test has been passed when the hose length does not fall below 10 m. Page7 of 13

4.1.3 External materials and properties 4.1.3.1 Parts, which may come in contact with the operator's skin when used, must not be comprised of any dangerous substances. Review of the safety data sheets for the materials used. Use the procedure according to ZEK 01.2-08 to check the amount of polycyclic aromatic hydrocarbon (PAH) with consideration given to PAH-substance list 04-11. 4.1.3.2 Touchable parts that may be contacted with proper usage must be free from sharp edges, burrs or similar features. Handling and visual inspection 4.2 Inscriptions 4.2.1 Insulating hose The following inscriptions must be permanently applied and clearly visible: - Indication of origin (manufacturer's name or trademark); - Year of manufacture; - Type designation; - Nominal diameter The prescribed inscriptions must be affixed at spacing intervals of not greater than 500 mm over the length of the insulating hose assembly. The spacing intervals between the inscriptions are to be measured. The inscriptions are to be visually checked for conspicuousness and completeness. Inscription durability is to be tested by rubbing them for 15 s with a water-soaked, lintfree cloth, and then rubbing them for 15 s with an ethyl alcohol-soaked, lint-free cloth. The test has been passed when the spacing intervals between the inscriptions are not greater than 500 mm apart and the inscriptions are still clearly legible and haven't become wavy or begun to detach following the wipe test. Page8 of 13

4.2.2 Insulating hose assembly The following inscriptions must be permanently applied and clearly visible at one location on the insulating hose assembly: - Indication of origin (manufacturer's name or trademark); - Month and year of manufacture; - Type designation; - Maximum operating pressure; - Graphic symbol (double triangle) (see Fig. 2 in DIN EN 50340 (VDE 0682-661): - 2011-04) The prescribed inscriptions may be affixed to, or in the vicinity of the connecting elements. If the markings are affixed to the insulating hose, they must be clearly distinguishable from the markings referenced in 4.2.1. The inscriptions are to be visually checked for conspicuousness, completeness and distinctiveness. Inscription durability is to be tested by rubbing them for 15 s with a water-soaked, lintfree cloth, and then rubbing them for 15 s with an ethyl alcohol-soaked, lint-free cloth. Engraved or embossed markings must not be subjected to durability testing. The test has been passed when the inscriptions are still clearly legible and haven't become wavy or begun to detach. 4.3 Electrical testing 4.3.1 Leakage current Insulating hose assemblies must provide sufficient isolation between the connecting elements based on the highest rated voltage at the supply frequency, even with external contamination and wear. The test object's leakage current must not exceed a value of 50 µa. Page9 of 13

Testing is to be carried out on the test object with free hose lengths of (2000 ± 50) mm and without fluid. The ends of the test object are to be sealed with suitable connecting element fittings. The outer jacket layer of each test object is to be removed down to the webbing layer to a distance of (990 ± 5) mm from the connecting elements; centred over a length of (20 ± 2) mm and a width of (5 ± 1) mm (Fig. 1). To accomplish this, cut into the outer jacket with a disc-type milling cutter (Ø 63 mm, width 0.5 mm), longitudinally over a length of (20 ± 2) mm, until the webbing is visible. A second cut should be made parallel to the first cut at a distance of (5 ± 1) mm. Incisions should then be made with a knife into the outer jacket and, starting at the cut ends and progressing from cut-to-cut along the partial circumference, it should be peeled from the webbed layer. Each test object should be stored for at least 96 h; completely submerged in water with a specific electric resistance of (100 ± 15) Ωm and a temperature of (20 ± 5) C. At the end of the storage period, any residual moisture on the test objects should be wiped off using a clean lint-free cloth. Within 5 min. following water storage, each test object should be placed in a test configuration corresponding to Fig. 1. The two electrodes should then be attached to insulating stanchions at a minimum height of 800 mm above the floor. Electrode 1 should be connected to the high voltage potential source. Electrode 2 should be attached to the measuring device's connection cable. The high voltage potential connecting line should be installed on approximately the same axis as the test object is fastened to the connecting elements. The current across the test setup must not exceed 10 µa with the test voltage applied and without the test object in place. An AC test voltage (50 Hz to 60 Hz) corresponding to customer specifications should be applied for at least 5 min. without interruption in accordance with IEC 60060-1 and IEC 60060-2. The current should be measured during the last 4 min. of the test. The test has been passed when a sparkover or flashover does not occur on any of the three test objects and the measured current I 1 does not exceed 50 µa during the last 4 min. of the test. Page10 of 13

1. Outer jacket layer 2. Webbed layer Fig. 1: Depiction of outer jacket removal 1 Electrode 1 2 Electrode 2 3. Connecting element 4. Insulating stanchions L Test object with a free hose length of (2000 ± 50) mm Fig. 2 - Test configuration for measurement of the leakage current Page11 of 13

4.4 Mechanical testing 4.4.1 Hydrostatic testing The insulating hose assembly must withstand the loads under the conditions at maximum operation pressure. Testing is to be carried out on 3 test objects with free hose lengths of (600 ± 10) mm in accordance with DIN EN 62237 (VDE 0682-744):2005-12, Section 5.4.1. 4.4.2 Testing with mechanical pressure impact The insulating hose assembly must withstand the loads under the conditions with the smallest bending radius and at maximum operation pressure. Testing is to be carried out on 3 test objects with free hose lengths according to the following formula in accordance with DIN EN 62237 (VDE 0682-744):2005-12, Section 5.4.3: R L90 = π + 2D 2 L = R + 2D 180 π L 90 Determined length with a bend of approx. 90 ; L 180 Determined length with a bend of approx. 180 ; R Smallest bending radius; Outside hose diameter D 0 4.4.3 Burst testing The insulating hose assembly must withstand the loads under conditions at four times the maximum operation pressure. Testing is to be carried out on 3 test objects with free hose lengths of (600 ± 10) mm in accordance with DIN EN 62237 (VDE 0682-744):2005-12, Section 5.4.6. Page12 of 13

4.4.4 Cold bend testing The insulating hose assembly must withstand the loads and must not leak. Testing is to be carried out on 3 test objects with free hose lengths of (600 ± 10) mm in accordance with DIN EN 62237 (VDE 0682-744):2005-12, Section 5.4.7. Testing in accordance with DIN EN 62237 (VDE 0682-744):2005-12, Section 5.4.4 is to be carried out subsequent to this. 5 Testing at manufacturer facilities The tests described in this section should serve to uncover any discernible safetyrelated changes in the materials or the production process. The manufacturer can select test procedures better suited for its production process if the tests selected guarantee at least the same level of safety represented by the tests listed below: 5.1 Piece testing 5.1.1 Visual inspection of the inscriptions for legibility and completeness 5.2 Random testing 5.2.1 Measurement of the leakage current according to Section 4.3.1 Page13 of 13