Water Mist Systems Inspection, Testing, and Maintenance of Water Mist Systems

Similar documents
TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

III. Identify the initial installation requirements for standpipe systems

TECHNICAL DATA. Trimpac 257a. September 16, 2013

TECHNICAL DATA. Trimpac 256a. October 31, 2013

TECHNICAL DATA. System water supply pressure enters the priming chamber of the deluge valve (A.1) through the 1/4 (8 mm) priming line, which

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection

MODEL NUMBER: PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank

MODEL NUMBER: M20005 AIR SOURCE KIT. 30% Duty Compressor on. 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S

IMPORTANT SAFETY INSTRUCTIONS

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE

200 PSI HIGH-FLOW AIR SOURCE KIT

200 PSI FAST-FILL AIR SOURCE KIT

Hill PHOENIX Second Nature Medium Temperature Secondary Refrigeration Start-Up Guide

42045 Heavy Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor Only) Heavy Duty ADA Base Model Kit: 110/145 PSI (ADA Compressor Only)

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO

200 PSI COMPRESSORS - MODEL NUMBERS

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

420C AIR COMPRESSOR KIT PART NO C AIR COMPRESSOR KIT PART NO

TECHNICAL DATA. Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve.

OBSOLETE DESIGN DATA. Foam 301a. February 9, 1998

TECHNICAL DATA OBSOLETE

444C DUAL PERFORMANCE VALUE PACK

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

400C & 450C DUAL PERFORMANCE VALUE PACKS

TECHNICAL DATA Q= C. Table 1 - Specifications

TECHNICAL DATA. Q= Cv S

R E D I C O N T R O L S

100C Air Compressor Kit

Government of Bermuda Department of Maritime Administration BERMUDA SHIPPING NOTICE

GREIG FILTERS, INC. OPERATION MANUAL

TECHNICAL DATA. Page 1 of 8. model f /2 (dn40) & 2 (dn50)

ECS Protector Nitrogen Inerting Vent (PAV-WN)

120 PSI FAST-FILL AIR SOURCE KIT 25% Duty Compressor on 1.5 Gallon Air Tank

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

Steam System Best Practices 14 Best Practices for Guide Lines for Boiler Plant Log Books

ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION

TECHNICAL DATA. than the water inlet pressure to the concentrate

TECHNICAL DATA ACCELERATOR MODEL E-1

Guideline No.M-05(201510) M-05 AIR COMPRESSOR. Issued date: 20 October China Classification Society

OPERATION MANUAL NTF-15

TECHNICAL DATA PILOT PRESSURE REGULATED DELUGE SYSTEM CONTROLLED BY PNEUMATIC RELEASE. 1. DESCRIPTION (Refer to Figures 1, 2 or 3.

TECHNICAL DATA PILOT PRESSURE REGULATED DELUGE SYSTEM CONTROLLED BY ELECTRIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

OPERATION MANUAL NTF-60 Plus

TECHNICAL DATA. Table 1 - Specifications

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO

Piped Air SCBA Refilling System Standard

Copyright, 2005 GPM Hydraulic Consulting, Inc.

TotalPac X Single interlock Preaction system Electric release

Budget Range Operators Handbook

INSTALLATION OPERATION MAINTENANCE

TECHNICAL DATA. TRIMPAC Model B-5 & B-5B

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST

Product Sheet Spraymist Unit

450P AUTOMATIC PORTABLE COMPRESSOR EXTREME SERIES

Welker Sampler. Model GSS-1. Installation, Operation, and Maintenance Manual

Hydraulic Reliability & Preventive Maintenance Report

Installation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM.

PC1131 Electric Air Compressor

TECHNICAL DATA. Trimpac 251a. Spetember 16, 2013

Thermocirc Installation and Maintenance Instructions

Portable Oil Lube Air Compressors

Guidance on the maintenance and inspection of fixed CO 2 fire-extinguishing systems

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model 50 Systems Outfitted with ABM-725 Monitor C O M P A N Y

TECHNICAL DATA. the Viking Pilot Pressure Regulating Valve 1 Model A-1 Speed Control Assembly: OBSOLETE. the Viking Speed Control Assembly 1

COMPRESSOR MANUAL. (888)

TECHNICAL DATA OBSOLETE

AcornVac Vacuum Plumbing Systems - Trouble Shooting Guide

1 HP / 1.6 GALLON AIR COMPRESSOR OPERATING MANUAL

FireLock NXT Preaction Valve with Series 798 Pneumatic/Pneumatic Actuator

Part IV: Troubleshooting

1020 Industrial Drive, Orlinda, TN fax

CARTRIDGE FILTERS. Models: CF50, CF75, CF100, CF150,

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO

South-Tek Systems - Nitrogen Generation Corrosion Inhibiting System. Designed for: Dry or Preaction Fire Protection Systems (FPS)

TECHNICAL DATA CAUTION

400H HARDMOUNT AIR COMPRESSOR KIT PART NO H HARDMOUNT AIR COMPRESSOR KIT PART NO

Preaction System with Model DV-5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200)

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model 50-P-Mini Portable Systems Outfitted with ABM-725 Monitor

GAS COMPRESSION SYSTEM

Unit 24: Applications of Pneumatics and Hydraulics

TECHNICAL DATA DELUGE VALVE, MODEL F-1 STRAIGHT THROUGH STYLE

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER

Operating Instructions Model and Hydrostatic Test Pump

Preaction System with Model DV-5 Deluge Valve Single Interlock, Supervised Dry Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200)

Model PSI Compressor with 3-Gallon Air Tank 12VDC

Winter Shut Down Procedure

Installation, Operation & Maintenance Manual

BUBBLER CONTROL SYSTEM

Dri-Line Mk3 Monnier Compressed Air Drain Trap

Inert Air (N2) Systems Manual

2 HP / 4 GALLON AIR COMPRESSOR OPERATING MANUAL

SPECIFICATIONS Type: Twin stack, single phase Tank: 4 gallon Air Output: PSI; PSI Max PSI: 125 PSI HP: 1.

COMPRESSOR REPLACEMENT PROCEDURE (R-134A)

Transcription:

Water Mist Systems Inspection, Testing, and Maintenance of Water Mist Systems Name of Property: Address: Phone Number: Inspector: Contract No.: Date: This Report Covers: Monthly Quarterly Annual Other Inspections Monthly Yes No N/A Water storage tank sight glass valves are open Yes No N/A Water circulation tank water level is full (unsupervised) Compressed Gas Cylinders Yes No N/A Cylinder pressure psi (bar) unsupervised Yes No N/A Cylinder control valve is open Yes No N/A Plant air, compressor, and receiver (supervised) Air pressure Standby Pump psi (bar) Yes No N/A Compressed gas supply inlet air pressure psi (bar) Outlet water pressure Pneumatic Valves psi (bar) Yes No N/A Cylinder valves in correct (open or closed) position Yes No N/A Master release valves in correct (open or closed position) System Control Valves Yes No N/A In the correct (open or closed) position Yes No N/A Sealed, locked, or supervised Yes No N/A Accessible Yes No N/A Free from damage or leaks Yes No N/A Proper signage Nozzles Yes No N/A In place, pointed in the intended direction, and free from external loading and corrosion Yes No N/A Blow-off cap (if required) in place and free to operate Fire Pumps Electrical Systems Yes No N/A Exercise isolating switch NFPA Water-Based Fire Protection Systems Forms 1 of 5

Yes No N/A Circuit breakers and circuit breaker fuses Fire Pumps Battery Systems Yes No N/A Remote corrosion, case clean and dry Yes No N/A Specific gravity/state or charge Yes No N/A Charter/charge rate Yes No N/A Equalize charge Quarterly Yes No N/A Water supply pressure psi Yes No N/A Water storage tank water level is full Yes No N/A Water tank pressure psi Yes No N/A Water storage cylinder (high pressure) water level is full (unsupervised) Yes No N/A Additive storage cylinder general condition Yes No N/A Water recirculation tank water level is full (supervised) Yes No N/A Compressed gas cylinder support frame and restraints Yes No N/A Compressed gas cylinder pressure psi Yes No N/A Moisture trap and oil injection in good condition Yes No N/A Release valve tubing in good condition Pipe and Fittings Yes No N/A Free of mechanical damage Yes No N/A Missing or damaged paint or coatings Yes No N/A Free of corrosion or rust Yes No N/A Misalignment or trapped sections Yes No N/A Low point drains not damaged or corroded Semi-annual Yes No N/A Water supply source in good condition Yes No N/A Water tank valves and appurtenances in good condition Yes No N/A Water storage cylinder is full Yes No N/A Additive agent level is full Yes No N/A Air compressor/receiver capacity checked Yes No N/A Enclosure integrity verified Annual Yes No N/A Water supply source in good condition Yes No N/A Interior of water tank inspected Yes No N/A Water quality checked Yes No N/A Water temperature ºF ( ºC) NFPA Water-Based Fire Protection Systems Forms 2 of 5

High-Pressure Water Storage Cylinder Yes No N/A Support frame/restraints in good condition Yes No N/A Vent plugs function during refiring Yes No N/A Filters on refill connection in good condition Yes No N/A Water recirculation tank supports and attachments in good condition Compressed Gas Cylinders Yes No N/A Inspect cylinder capacity and pressure rating Yes No N/A Check cylinder compliance specification Yes No N/A Compressed gas meets specifications Yes No N/A Air supply moisture content acceptable Test Quarterly Yes No N/A Test start/stop pressure settings for standby pump Annual psi start psi stop Yes No N/A Water supply tested psi gpm minute duration Yes No N/A Additive agent quality tested Yes No N/A Additive agent injection full discharge test Water Recirculation Tank Yes No N/A Low water level alarm functions Yes No N/A Float operated valve functions Yes No N/A Pressure at outlet during discharge psi Yes No N/A Backflow preventer functions Yes No N/A Air supply capacity and duration tested Pump Performance Test Use Form 19, Fire Pumps Annual Performance Tests Pneumatic Valves Yes No N/A Solenoid release of master valve functions Yes No N/A Manual release of master valve functions Yes No N/A Slave valves operate correctly Yes No N/A All pneumatic cylinder release valves reset Yes No N/A On-off cycling of valves tested Yes No N/A All control valves operated through full range of motion and returned to normal position Yes No N/A Range of motion and returned to normal position NFPA Water-Based Fire Protection Systems Forms 3 of 5

Yes No N/A Trip test of dry and preaction water mist system Full Flow Trip Test Yes No N/A Unobstructed discharge from all nozzles Yes No N/A Pressure reading at control valve Yes No N/A Detection system response time sec Yes No N/A Detection system tested in accordance with NFPA 72 Yes No N/A Ventilation system interlocks tested Yes No N/A Fuel/lubrication system interlocks tested Yes No N/A Cylinders hydrostatic test every 5-½ years Maintenance Semi-annual Yes No N/A Air supply filters and moisture traps cleaned Yes No N/A Water recirculation tank filters, strainers and cyclone separator cleaned Pump System Lubricate bearings Check pump shaft end play Pressure gauge/sensors (check accuracy) Pump coupling alignment Electrical System Trip circuit breaker Operate manual starting means Operate emergency manual starting means Tighten electrical connections (as necessary) Lubricate mechanical moving parts (except starters and relays) Calibrate pressure Switch settings Lubricate motor bearings Check Change Clean Test NFPA Water-Based Fire Protection Systems Forms 4 of 5

Comments Company DFS-P# Technician Name Phone Fax Signature Date Business Representative Phone Signature Date NFPA Water-Based Fire Protection Systems Forms 5 of 5