Recommended Flexible Pipe Installation For Rental Chillers

Similar documents
ACCU-PULSE Installation and Operation Instructions

Types 749B and R130 Changeover Manifolds

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity

Bray/ VAAS O-Ported Series Knife Gate Valve 770/780 Series Operation and Maintenance Manual

AWG Fittings LLC. Pressure Relief Valve Up to 250 PSI. Product Number Read this instruction manual before use.

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

Bermad Pressure Reducing. Model: 42T

BS Series Basket Strainer

FLANGED TWO-PIECE BALL VALVES

Type 1367 High-Pressure Instrument Supply System with Overpressure Protection

R600 and HSRL Series Instruction Manual

TECHNICAL DATA. TRIMPAC Model B-5 & B-5B

SERIES SAFETY VALVE

Bermad Model:

Cylinder Tilt Saddle Instruction Manual

TECHNICAL DATA. than the water inlet pressure to the concentrate

Pressure Relief Valve Instruction Manual

Hose Manufacturing Data

Safety. April 2018 Supersedes all previous publications 2018 Chevron Phillips Chemical Company LP

HIGH RATE BASKET STRAINER

Model PSI Compressor with 3-Gallon Air Tank 12VDC

Compact Triple Cabinet Outlet Station Model B Installation and Operating Instructions

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

TECHNICAL DATA. Trimpac 251a. Spetember 16, 2013

PumpAgents.com - Click here for Pricing/Ordering Nominal psi (bar) Cut-In Cut-Out

Float Operated Level Controllers

HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS

COMBINATION AIR RELEASE DEGASSING (CARD) VALVES INSTALLATION AND MAINTENANCE MANUAL

TOP VALVE. Pat. #5,857,486 & 5,944,050. Mid-Range Pressure PSIG Back Pressure and Pressure Relief Valves. Instruction Manual

Winter Shut Down Procedure

FM Approved - Automatic Water Control Valve as standard deluge valve. No formal approval available for coating. Foam Concentrate

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

R122H, R222, R232A, and R232E Series Instruction Manual

Rapidmain Installation Guide

Compact Triple Cabinet Outlet Station Model Installation and Operating Instructions

HYGIENIC SIGHT FLOW INDICATORS

REACH COMPLIANT 2500 WEIGEL STREET CADILLAC, MI

MANUAL: IN-LINE PIVOT GAUGE IN-LINE GAUGE

FLANGED TWO-PIECE BALL VALVES

REFER TO AQUATHERM TECHNICAL BULLETIN A-AQTTB FOR ADDITIONAL INFORMATION AND SAFETY PRECAUTIONS

APPENDIX B TESTING PROTOCOLS. Method A: Straight Test Method B: Angular Deflection Test. Method C: Shear Load Test

29 SERIES - SAFETY VALVE

TECHNICAL DATA. Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve.

WW-730. Pressure Sustaining/Relief Control Valve

TITAN FLOW CONTROL, INC.

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE

Hot Tapping Machine. OPERATIONS MANUAL and OPERATING INSTRUCTIONS

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection

TriPod Safety Coupler Installation & Operating Instructions for Models TP4, TP5, TP6, and TP7

Inflatable Stand Up Paddle Board Manual

TECHNICAL DATA Q= C. Table 1 - Specifications

Wet pipe low flow foam/water system

Wilo Triple Duty Valve / Triple Service Valve Installation and operating instructions

Irrigation System Winterization and Pressurization Procedures

Portable Oil Lube Air Compressors

South-Tek Systems - Nitrogen Generation Corrosion Inhibiting System. Designed for: Dry or Preaction Fire Protection Systems (FPS)

INSTALLATION INSTRUCTIONS FOR SSI WIDEBAND DIFFUSER

Installation, Operation and Maintenance Manual for Back Pressure Regulator

TECHNICAL DATA. Trimpac 244a. September 16, 2013

ROPV R40 E Series User Manual

IAPMO GUIDE CRITERIA FOR BALL VALVES IAPMO IGC PURPOSE

RevolveAir / Guardian Breathing Air Cylinder Fill Station Operating Instructions

WHEATLEY Series 822/820 Swing Check Valve

Installation and Operating Instructions

2 GALLON TWIN STACK AIR COMPRESSOR W/ HOSE REEL

Subpart E. Pressure Testing

TOP VALVE. Pat. #5,857,486 & 5,944,050. High Temperature: max. 300 F (149 C) Back Pressure And Pressure Relief Valves. Instruction Manual

GAS SUPPLY DESIGN GUIDE

Guide for Evaluating Your Hose Assembly Supplier

SERVICE MANUAL SALAMANDER BROILERS RADIANT AND INFRARED 36RB 36IRB VULCAN C36RB C36IRB WOLF

Owner s Guide. ElevateSUP.com

Sterile Visual Flow Indicator

FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS

SINGER MODEL 106/206-RPS-L&H

FLANGED MULTI-PORT BALL VALVES

September 2018 Pressure Test

Installation, Operating and Maintenance Instructions. V914 Cast Iron Flanged Swing Check Valve V914

HAYWARD FLOW CONTROL TFS SERIES FLOW METER INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

HPB25 Hydraulic Paving Breaker

Instruction Manual. PE-25/32/37 Tapping Machines. POLYTAPP Valves

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series

DC5A. Cyclone Separator Trap for Air. Copyright 2015 by TLV Co., Ltd. All rights reserved ISO 9001/ ISO MA-03 (DC5A) 19 June 2015

SECTION PRESSURE TESTING OF PIPING

Wafer Check Valve. Contents. User s Manual. (1) Be sure to read the following description of our product warranty 1

DB 61 Dolphin TMV3 Integrated Thermostatic Mixing Valve

Type 1 - Nitrogen Generation System. Designed for: Dry or Pre-Action Fire Protection Systems (FPS) with a total capacity up to 750 gallons

SPECIFICATIONS Type: Twin stack, single phase Tank: 4 gallon Air Output: PSI; PSI Max PSI: 125 PSI HP: 1.

RG3100 and RG3100Ice Regulator System

Installation, Operation, and Maintenance Manual

OWNER S MANUAL. This manual contains; IMPORTANT SAFETY INFORMATION INSTALLATION INSTRUCTIONS MAINTENANCE FACTORY SERVICE REPAIR PARTS WARRANTY

PLEASE NOTE: Pressures for 200mm (8ins) and 250mm (10ins) are based on the use of METALFLEX Braided Braid

Gemini Owner s Manual

2 GAL AIR COMPRESSOR OPERATOR S MANUAL 1/3HP/2-GALLON IMPORTANT: READ THIS OPERATOR S MANUAL BEFORE USING

INSTALLATION INSTRUCTIONS FOR THE SSI TUBE DIFFUSER General

REL-46 WARNING NOTICE 15 TON SINGLE ACTING REMOTE HYDRAULIC CRIMPING HEAD. Compatible with RELIABLE R15 and P Style dies. REL-46 Manual

Installation Instructions and valve Maintenance Rev. 0 of 29/09/15

TECHNICAL DATA. Trimpac 257a. September 16, 2013

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE

Model PRS-07i. Stainless Steel Low Pressure, In-Line Pressure Regulator (Reducing Valve)

Model: 43T. Bermad Pressure Relief Valve

Transcription:

Installation, Operation and Maintenance Manual IOM 1159 Group: MQFS Chiller Rental Effective: June 2012 Supersedes: New Recommended Flexible Pipe Installation For Rental Chillers Angus Super Aquaduct flexible hose in blue 2012 McQuay International

Introduction This Installation, Operation and Maintenance Manual (IOM) advises McQuay Service or contractors acting on the behalf of a McQuay Service as to the proper installation of flexible hose when used with rental chillers from McQuay International. Note: The specified hose for use with McQuay Rental Chillers is Angus Super Aquaduct flexible hose in blue. Hose is manufactured by; Kidde Fire Fighting Angus Hose, 180 Sheree Blvd, STE 3900, Exton, PA 19341. It is critical that this IOM is followed to minimize premature or catastrophic failure of this hose. McQuay disclaims liability for damages and costs resulting from third party failure to follow the instructions in this bulletin. General Hazard Identification Information DANGER Dangers indicate a hazardous situation that will result in death or serious injury if not avoided. WARNING Warnings indicate potentially hazardous situations, which can result in property damage, severe personal injury, or death if not avoided. CAUTION Cautions indicate potentially hazardous situations, which can result in personal injury or equipment damage if not avoided. Specific Hazard Identification for the procedures in this manual. CAUTION Hose must never be pressurized over 150 psi to avoid damage to the hose. If higher pressures are required, hard pipe must be utilized. WARNING Hose must always be used in a pressurized application. If a negative pressure application is required, hard pipe must be utilized; otherwise hose may collapse, causing total system failure. DANGER These guidelines MUST be followed to avoid leaking, coupling failure, catastrophic hose failure or serious injury or death to workers in the immediate area of the failing pressurized hose. Do not support the hose ONLY by its couplings. Support over half of the hose s length by ground or other supporting surface otherwise coupling clamps may fail. Do not run hose vertically more than 7 feet, otherwise coupling clamps may fail. Do not cut hose to custom fit pieces this will affect the integrity of the hose. Bleed all air from the system prior to pressurizing hose to avoid couplings separating from the hose. IOM 1159 (06/12) 2

Installation Guidelines Possible hose rupture at the hose-coupling interface can be avoided with careful installation of the hose. Proper hose installation guidelines that should be followed are: Install elbows for a smooth hose transition on all vertical hose installations. Never exceed a 7' vertical run of hose. Hose must be supported by more than half its total length on the ground. Never have the hose completely supported by the couplings. Never cut hose to "custom" fit lengths. Never pressurize hose above 150 psi. Bleed all air from the system before pressurizing the hose. Horizontal Hookup Application The following figures illustrate the correct and incorrect methods for installing hose in a horizontal hookup application. Figure 1 shows a correct hose installation. In this configuration either a 45 or 90 elbow can be installed. This elbow prevents stretching and crimping of the hose at the hose coupling connection. This elbow also directs the hose to the ground at an appropriate angle to minimize the crimping of the hose at the ground or supporting surfaces. Figure 1 - Correct Horizontal Hose Installation Couplings Rental Chiller 90 Elbow Couplings 90 Elbow Figure 2 shows an incorrect hose installation. Elbows are not installed. IOM 1159 (04/12) 3

This causes the top of the hose to be in tension, which stretches the hose out of the coupling; and the bottom of the hose to be in compression, which causes it to crimp. It also causes the hose to crimp at the ground. Figure 2 - lncorrect Horizontal Hose Installation Stretching Rental Chiller Crimping Crimping Vertical Hookup Installation The following figures illustrate the correct and incorrect methods for installing hose in a vertical hookup application. Figure 3 shows a correct vertical hose installation. In this configuration, the hose is installed with an elevation less than 7 feet off the ground. A 45 elbow is installed to reduce the stress in the hose coupling connection. This elbow also directs the hose to the ground at an appropriate angle to minimize the crimping of the hose at the ground or supporting surface. IOM 1159 (06/12) 4

Figure 3 - Correct Vertical Hose Installation Existing Hard Pipe 45 Elbow Coupling Coupling 7' Flexible Hose Ground Figure 4 shows an incorrect hose installation. In this configuration the hose is installed without an elbow and with an elevation greater than seven feet off the ground. This creates excessive stress at the hose coupling connection, causing the hose to stretch and separate from the coupling. It also causes the hose to crimp at the ground. Figure 4 - lncorrect Vertical Hose Installation Existing Hard Pipe Stretching Coupling Flexible Hose > 7' Hose Crimping Ground IOM 1159 (04/12) 5

Combined Horizontal and Vertical Hookup Installation The following figures illustrate the correct and incorrect methods for installing hose in a horizontal and vertical combination. Figure 5 shows a correct vertical/horizontal hose installation. In this configuration, correct installation techniques followed are: the hose is installed with elbows at both connection ends the vertical run of hose is less than 7 feet The hose is adequately supported by more than half its total length on the ground. These items minimize the stretching and separation at the hose-coupling interface and also the crimping of the hose at the ground. Figure 5 - Correct Vertical/Horizontal Hose Installation Hard Pipe Rental Chiller Couplings 90 Elbow 45 Elbow 7' Couplings Ground Figure 6 shows an incorrect vertical/horizontal hose installation. In this configuration, a number of improper installation techniques can be noted: elbows are not installed the hose is completely supported by the couplings the vertical run of hose is greater than 7 feet the hose is not adequately supported by the ground These items cause excessive stress to be generated at the hose-coupling interface, causing the hose to stretch and separate from the coupling. IOM 1159 (06/12) 6

Figure 6 - Incorrect Vertical/Horizontal Hose Installation Hard Pipe Coupling Coupling Stretching Rental Chiller > 7' Hose Crimping Ground Figure 7 illustrates a correct horizontal hose installation where there is a section of unsupported hose. The length of unsupported hose should be less than 7 feet. Also, the hose must be adequately supported by having more than half its total length on the ground. Figure 7 - Correct Unsupported Horizontal Installation Chiller 45 Elbow Existing Hard Pipe 45 Elbow <7' Ground IOM 1159 (04/12) 7

Hard Pipe Installation Certain installations may require the use of hard pipe (steel or PVC). Hard pipe is typically recommended for (1) indoor installations, (2) semi-permanent installations (three months or more) and/or (3) installations with space limitations. When installing hard pipe: Construct and install the piping according to local and national codes. Isolate and support the piping as required to prevent stress on the unit and vibration to building piping. Routine Maintenance Care, Maintenance, and Service Test The unique construction features of Angus hose make it virtually maintenance free. However, the following basic care and maintenance tips should be considered. 1. CLEAN UP Although Angus Hose requires no routine washing and drying, it is recommended that accumulations of mud, sand, ash, etc. be rinsed or brushed off. These materials will ultimately find their way to your hose bed floor and could cause future problems. 2. DAMAGE Damaged hose can be dealt with in two ways: Cover damage (cosmetic repair) can be repaired by applying Angus Coverseal to the affected area. Because there is no inner tube, Angus hose will not burst, even if punctured under most circumstances. Punctures, cuts and tears are repaired both inside and out by a unique vulcanizing process that returns the hose to 100% of its annual service test pressure. 3. COUPLINGS Angus grooved couplings require little maintenance; however, we recommend the following: Sand, mud, ash, etc., should be rinsed off after each use. Visual inspection of the seal area will prevent leakage of coupling. 4. ANNUAL HYDROSTATIC SERVICE TESTS All Angus Water Supply and Distribution System components should be hydrostatically tested annually. Hose Test - In accordance with NFPA 1962 (latest edition). Fittings, Appliances and Accessories - All Angus hose, fittings, appliances and accessories are safety tested before leaving the factory. Angus recommends annual testing of all parts of the system to ensure top performance. Test all fittings and appliances to 250 psi for five minutes or to the limits of the relief valve settings. Pressure Rating of Hose Service Test - One third of burst rating of hose. Proof or Acceptance Test - Two thirds of burst rating of hose. Burst Test Example - Hose that has a service test of 250 psi, proof or acceptance of 500 psi and burst of 750 psi. This allows a 3 times safety factor. IOM 1159 (06/12) 8

IOM 1159 (04/12) 9

This information is only a general guideline. Angus Flexible Pipeline reserves the right to change any portion of this information without notice. Terms and conditions of sale apply and are available on request. Kidde Fire Fighting - Angus. (n.d.). Angus Fire INTRODUCTION TO FIRE HOSE. Retrieved April 13, 2012, from Angus Technical Information: http://www.kidde-fire.com/utcfs/ws- 465/Assets/angus%20introduction%20to%20fire%20hose.pdf Kidde Fire Fighting - Angus. (n.d.). Care, Maintenance, and Service Test. Retrieved April 13, 2012, from Kidde Fire Fighting - Angus Technical Information: http://www.kidde-fire.com/utcfs/ws- 465/Assets/Care_and_Maintenance.pdf Kidde Fire Fighting - Angus. (n.d.). Chemical Resistance Chart for Fire Hose. Retrieved April 13, 2012, from Kidde Fire Fighting - Angus Technical Information: http://www.kidde-fire.com/utcfs/ws- 465/Assets/angus%20chemical%20resistance%20chart.pdf Kidde Fire Fighting - Angus. (n.d.). Pressure Rating of Fire Hose. Retrieved April 16, 2012, from Angus Technical Information: http://www.kidde-fire.com/utcfs/ws-465/assets/pressure_rating.pdf Kidde Fire Fighting - Angus. (n.d.). Super Aquaduct. Retrieved April 13, 2012, from Kidde Fire Fighting - Angus Flexible Pipe: http://www.kidde-fire.com/utcfs/ws-465/assets/super%20aquaduct%20new.pdf Replacement of Hose Hose sections are available through McQuay Parts. These items are not stocked and will drop ship to your office. Lead-times will be quoted by McQuay Parts at time of order. The part numbers are as follows: McQuay Part Number Description 300049268 6 10 hose with grooved ends 300049269 6 15 hose with grooved ends 300049270 6 25 hose with grooved ends 300049271 6 50 hose with grooved ends IOM 1159 (06/12) 10

Limited Warranty Consult your local Daikin McQuay Representative for warranty details. Refer to Form 933-43285Y. To find your local Daikin McQuay Representative, go to www.daikinmcquay.com. Notice 2012 McQuay International, Minneapolis MN. All rights reserved throughout the world. McQuay International reserves the right to change any information contained herein without prior notice. This document contains the most current product information as of this printing. For the most current product information, please go to www.daikinmcquay.com. All equipment is sold pursuant to McQuay International Standard Terms and Conditions of Sales and Limited Warranty. IOM 1159 (04/12) 11