MT-239-E ENGLISH PRESSURE REGULATOR STAFLUX MINI TECHNICAL MANUAL INSTALLATION, COMMISSIONING AND MAINTENANCE INSTRUCTIONS

Similar documents
Aperflux TECHNICAL MANUAL PRESSURE REGULATOR ENGLISH MT-208-E INSTALLATION, COMMISSIONING AND MAINTENANCE INSTRUCTIONS

CARTRIDGE FILTERS TECHNICAL MANUAL MT 080. Installation, commissioning and maintenance instructions. 08/02 Edition

MT-208-E ENGLISH PRESSURE REGULATOR. Aperflux TECHNICAL MANUAL INSTALLATION, COMMISSIONING AND MAINTENANCE INSTRUCTIONS

HBC/975 TECHNICAL MANUAL MT052/E INSTALLATION START-UP AND MAINTENANCE INSTRUCTION

MT-182-E ENGLISH PRESSURE REGULATOR. Aperval TECHNICAL MANUAL INSTALLATION, COMMISSIONING AND MAINTENANCE INSTRUCTIONS

INSTRUCTIONS FOR THE INSTALLATION, COMMISSIONING AND MAINTENANCE

MANUALLY OPERATED VALVE VLM SYNCROFLUX TECHNICAL MANUAL MT042/E

Un-Pressurized Orefice Fittings FIO EZ. Parts List and Operation Instructions TECHNICAL MANUAL. Dn 2-6 Class Lbs

Pressure Regulators. Aperflux 101

Mounting and Operating Instructions EB 2558 EN. Self-operated Pressure Regulators. Type Pressure Build-up Regulator

PRESSURE REGULATOR NORVAL TECHNICAL MANUAL MT044

PRESSURE REGULATOR APERFLUX 851 TECHNICAL MANUAL MT049

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

Pressure Regulators DIVAL TECHNICAL MANUAL

Pilot HON 625. Entwurf. Product information. serving the gas industry worldwide

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

Types S100K and S102K Pressure Regulators

Manual Actuated Boiler Blowdown Valves

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

299H Series. Introduction. P.E.D. Categories. Specifications. Installation. Warning. Installation Guide English September 2012

64 Series Pressure Reducing Regulators

THE BP-301 SERIES. Operating and Service Manual. Series includes all variants of BP-301 (LF 0.1Cv / MF 0.5Cv)

THE MF-400 SERIES. Operating and Service Manual. Series includes all variants of MF-400/401

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

LRS(H)4 Pressure-Reducing Regulator User Manual

Type HSR Pressure Reducing Regulator for Residential, Commercial, or Industrial Applications

Pressure regulators. Introduction. TR Head. 3 ways body Dival

PRS(TC)4,8 USER MANUAL. Read the complete manual before installing and using the regulator.

THE HF-300 SERIES. Operating and Service Manual. Series includes all variants of HF-300/301

TESCOM 50-4X Series Safety, Installation & Start-Up Procedures

English. Introduction. Safety Instructions. All Products. Inspection and Maintenance Schedules. Parts Ordering. Specifications WARNING WARNING

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves.

Aperval Pressure Regulators

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

CAST IRON SAFETY VALVE TYPE 6301

RHPS Series RD(H)F40 User Manual. Read the complete manual before installing and using the regulator.

ASX 176 Axial Pressure regulator

Mounting and Operating Instructions EB 3009 EN. Self-operated Regulators. Type RS Check Valve (backflow protection)

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Type Type Differential Pressure Regulators (opening)

553 Series.

1305 Series Pressure Reducing Regulators

INSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION

6301 TYPE CAST IRON SAFETY VALVES

Mounting and operating instructions EB 2530 EN. Self-operated Pressure Regulator. Pressure Reducing Valve Type M 44-2

Serie ECO 3F. Flanged back flow preventer with controllable reduced pressure zone. made in. Application fields. Protection

Type ACE97. Introduction. Installation. P.E.D. Categories. Specifications. Overpressure Protection. Installation Guide English May 2002

OPERATING AND MAINTENANCE MANUAL

Type PRX/120, PRX/125, PRX-AP/120, PRX-AP/125, PRX/181, PRX/182, PRX/131 and PRX-AP/131 Pilots

Serie ECO 3T. Threaded end back flow preventer with controllable reduced pressure zone. made in. Application fields. Protection E U R O P E

Operating Manual. R280 Pressure regulator made of brass. 1. Intended Use

AIR-OPERATED DOUBLE DIAPHRAGM PUMP USER S MANUAL

Types S108K and S109K Pressure Reducing Regulators with Integral Slam-Shut Device

Pressure Reducing Valve for Steam Type 2333 A

1200B2 Series Service Regulators. Instruction Manual

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

1805 Series Relief Valves

SLAM-SHUT VALVE. Type OSE CONTENTS INTRODUCTION CHARACTERISTICS. Scope of Manual. Material. Product Description. Connections

Installation, Operation and Maintenance Manual for Back Pressure Regulator

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors

Norval Pressure Regulators

Reduce pressure zone device suitable for high and medium hazard rated applications BSP screwed connections

Regulator from 1800 B series

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

TECHNICAL DATA CAUTION

Dival 500 Pressure Regulators

Slam Shut Valves SBC 782

Welker Sampler. Model GSS-1. Installation, Operation, and Maintenance Manual

RD(H)20/25 Pressure-Reducing Regulator User Manual

Gas Pressure Regulator HON 300

KBV21i and KBV40i Air Actuated Boiler Blowdown Valves

Installation, Operating and Maintenance Manual Overflow Regulator Type 94/ 94 E

627 Series Pressure Reducing Regulators

PRESSURE REGULATOR DIVAL DIVAL DIVAL TECHNICAL MANUAL MT036 INSTALLATION, COMMISSIONING AND MAINTENANCE INSTRUCTIONS

Gas Pressure Regulator HON 502

DN 50 REGULATOR SUTON 5000A1 REGULATOR SUTON 5000D1

Mounting and Operating Instructions EB 8546 EN. Type 4708 Supply Pressure Regulators. Translation of original instructions. Type Type

1. Preface Important Safety Notes Brief Product Information Product Working Principle Installation Guidelines...

Mounting and Operating Instructions EB 3017 EN. Self-operated Regulators

Model: 43T. Bermad Pressure Relief Valve

Anti-flood device Model B-1

OFFICINE OROBICHE S.p.A. 1/9

WW-730. Pressure Sustaining/Relief Control Valve

Installation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM.

Gas Pressure Regulator HON 200

Type 1367 High-Pressure Instrument Supply System with Overpressure Protection

Operating and maintenance manual Filter and reducing station Series / 1.0

VALVCHEQ BACKFLOW PREVENTERS FIGURE RP03

WW-720. Pressure Reducing Control Valve

Norval Pressure regulator

Type CT88 Backpressure Regulator

RB Series Regulating System

TD45 Thermodynamic Steam Trap Installation and Maintenance Instructions

WW-720. Pressure Reducing Control Valve

RTG 25. Introduction

Pressure Reducing Regulator Manual

MAINTENANCE AND OPERATING MANUAL

Installation & Operation Manual Proven Quality since 1892

Preparation and Installation of the Sanitary BDI-FLX Sensor and Connection to the BDI-FLX Interface Cable

MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection

Transcription:

MT-239-E ENGLISH PRESSURE REGULATOR STAFLUX MINI TECHNICAL MANUAL INSTALLATION, COMMISSIONING AND MAINTENANCE INSTRUCTIONS

Technical manual MT 239-E 1 STAFLUX MINI

Technical manual MT 239-E 2

Technical manual MT 239-E 3 PRECAUTION GENERAL PRECAUTION The apparatus described in this manual is a device subject to pressure installed in systems under pressure. The apparatus in question is normally installed in systems for transporting flammable gases (natural gas, for example). PRECAUTION FOR THE OPERATORS Before proceeding with installation, commissioning or maintenance, operators must: Examine the safety provisions applicable to the installation in which they must work; Obtain the authorisations necessary for working when required; Use the necessary means of individual protection (helmet, goggles, etc.); Ensure that the area in which they operate is fitted with the means of collective protection envisaged and with the necessary safety indications. PACKING The packing for transportation of equipment and of relevant spare parts are designed and shaped to avoid damage to any part during transportation, warehousing and handling activities. Therefore the equipment and spare parts shall be kept into their packing until their installation in the final site. After packing is open, check that no damage occurred to any goods. If damage occurred inform the supplier and keep packing for any verification. INSTALLATION The installation of the pressure regulator has to occur in compliance with the provisions (laws or standards) in force in the place of installation. Natural gas plants have to show features in compliance with the law provisions and standard requirements in force in the place of installation or at lease in compliance with standards EN 12186 or EN 12279. In detail, it is necessary to meet the provisions of paragraphs 6.2, 7.5.2, 7.7, 9.3 of the standard EN 12186 and 6.2, 7.4, 7.6, 9.3 of the EN 12279 standard. The installation in compliance with such standards minimizes the risk of fire hazard and the formation of potentially explosive atmospheres. The valve is not equipped with external pressure limitation devices; therefore, it has to be installed making sure that the operating pressure of the assembly on which it is installed does not exceed the maximum allowable pressure (PS). Therefore, the user, as deemed necessary by the same, shall install on the assembly suitable pressure limitation systems, as well as provide the plant with suitable relief or drain systems in order to discharge the pressure and fluid contained in the plant before proceeding with any inspection and maintenance activity. If the installation of the apparatus requires the application of compression fittings in the field, these must be installed following the instructions of the manufacturer of the fittings themselves. The choice of the fitting must be compatible with the use specified for the apparatus and with the specifications of the system when envisaged. COMMISSIONING Commissioning must be carried out by adequately trained personnel. During the commissioning activities, the personnel not strictly necessary must be ordered away and the no-go area must be properly signalled (signs, barriers, etc.). Check that the settings of the apparatus are those requested; if necessary, reset them to the required values in accordance with the procedures indicated in the manual. When commissioning, the risks associated with any discharges into the atmosphere of flammable or noxious gases must be assessed. In installations in natural gas distribution networks, the risk of the formation of explosive mixtures (gas/air) inside the piping must be considered.

Technical manual MT 239-E 4 - INDEX - 1.0 INTRODUCTION 5 1.1 MAIN FEATURES 6 1.2 OPERATION OF THE PRESSURE REGULATOR STAFLUX MINI 6 2.0 INSTALLATION 8 2.1 GENERAL 8 2.2 CONNECTING THE APPARATUSES 9 3.0 RELIEF VALVES 9 3.1 RELIEF VALVE 9 4.0 START-UP 9 4.1 GENERAL 9 4.2 GAS INPUT, CONTROLL OF EXTERNAL TIGHTNESS AND SETTING 10 4.3 COMMISSIONING THE REGULATOR STAFLUX MINI 11 5.0 TROUBLE-SHOOTING 12 5.1 REGULATOR STAFLUX MINI 12 6.0 MAINTENANCE 13 6.1 GENERAL 13 6.2 STAFLUX MINI REGULATOR MAINTENANCE PROCEDURE 14 6.3 PRESSURIZED CHAMBER INLET VALVE 16 6.4 RELIEF VALVE VS/FI MAINTENANCE PROCEDURE 7.0 FINAL OPERATION 19 7.1 CHECKING THE TIGHTNESS AND SETTING 19 7.2 START UP 19

Technical manual MT 239-E 5 1.0 INTRODUCTION This manual aims to providing essential information for the installation, commissioning and maintenance of the pressure regulator STAFLUX MINI. Moreover, it is deemed suitable to describe in short the main features of the regulator. Fig. 1 contains a functional diagram of the regulator. 1.1 MAIN FEATURES The STAFLUX MINI pressure regulator is a regulator for medium and high pressure. The STAFLUX MINI is a fail close type regulator and therefore closes in the event of: - rupture of the main diaphragm - no feed in the pressurized chamber The main specifications of this regulator are: - Design pressure PS: up to 250 bar - Working temperature range: -20 C + 60 C - Ambient temperature: -20 C + 60 C - Inlet pressure range bpu: 5 to 250 bar - Regulating range possible Wd: 4 75 bar - Minimum differential pressure 1 bar - Precision class AC: up to 10 (depending on the operative conditions) - Closing pressure class SG 10 (depending on the operative conditions)

Technical manual MT 239-E 6 1.2 OPERATION OF THE PRESSURE REGULATOR STAFLUX MINI Refer to figure 1. The pressure regulator STAFLUX MINI is a device which being supplied with a gas at variable pressure, reduces its pressure keeping the downstream value stable also when the requested flow rate changes. The regulator basically consists of: - a body which houses the obturator (1) and the gasket seat (4); - a control head (3) where the control diaphragm (2) connected to the stem (6) are inserted; - a group of calibration valves (8, 9); - one relief valve (5) on the chambers (3). fig. 1 The regulator STAFLUX MINI is a direct action regulator with diaphragm control with "fail close reaction. The operating principle bases on the balance of the forces acting on the diaphragm (2), which is joined to the obturator (1) through the stem (6). These forces are: - On the lower side of the diaphragm: the spring load (7) and the downstream pressure contained in the chamber (10); - On the upper side of the diaphragm: the pressure of the fluid contained in the hood (3) If during operation, due to an increase in the flow rate, a reduction in the downstream regulated pressure occurs, a pressure decrease will occur in the sub-diaphragm chamber (10) and, therefore, also an unbalance of the forces with the following opening of the obturator until the balance condition is restored.

Technical manual MT 239-E 7 On the contrary, if the downstream pressure increases due to a reduction in the flow rate, a pressure increase will occur in the sub-diaphragm chamber (10) and, consequently, also an unbalance of the forces with the following closing of the obturator until the balance condition is restored. The regulator is equipped with a valve (8) providing pressure into the chamber (3) (usually, to pressurize such chamber the gas collected upstream of the regulator itself is used) and with a valve (9) draining the chamber (3).These two valves are necessary for the calibration of the regulator. Chamber (3) is protected against any overpressure, by means of a relief valve (5). The calibration of the regulator occurs by means of the gas under pressure contained in chamber 3; ambient temperature changes may lead to changes in the value of the pressure contained in such chamber and, consequently, to changes in the value of the regulated pressure.

Technical manual MT 239-E 8 2.0 INSTALLATION 2.1 GENERALS Pressure regulator does not require any supplementary upstream safety accessory for protection against overpressure compared with its design pressure PS, when upstream reducing station is sized for a max downstream incidental pressure Before installing the regulator it is necessary to ensure that: Pd 1,1 PS - the regulator can be inserted in the space provided and that subsequent maintenance operations will be sufficiently practicable (see dimension in Tab. 2a) - the upstream and downstream piping is at the same level and capable of supporting the weight of the regulator - the inlet/outlet flanges of the piping are parallel - the inlet/outlet flanges of the regulator are clean and the regulator itself has not been subject to damage during transport fig. 2a fig. 2b Overall Dimensions [mm] THREADED CONNECTION FLANGED CONNECTION DIMENSION [mm] 25 Inch 1 s 115 235 a 62 75 b 226 c 77 d 126 e 100 h 270 300 Weight [Kg] Tab. 2a 12 20 Tab. 2b

Technical manual MT 239-E 9 2.2 CONNECTING THE APPARATUSES Pressure Regulator Vent Valve Pressure Gauge Vent Valve Vent Valve On/Off Valve fig. 3 On/Off Valve The regulator must be installed in the line with the arrow on the body pointing in the gas flow direction. When the regulator is used in gas pressure reduction stations it must be installed at least according to the requirements envisaged in EN 12186 or EN 12279 standards. Any possible gas leakage at any point, due to diaphragm or sensor malfunction or breakage, must be channelled according to EN 12186 standards. or EN 12279. The following is recommended so as to prevent the accumulation of impurities and condensate in the lines of the pressure take-off: a) the lines themselves must slope down towards the downstream piping connectors with a slope of about 5-10%; b) the connectors on the piping must always be welded on the top of the piping itself and there must be no burr or inward protrusions in the hole in the piping. 3.0 RELIEF VALVES 3.1 RELIEF VALVE VS/FI Please consult the correspondant table VS/FI x STAFLUX MINI in table TT673 4.0 START-UP 4.1 GENERAL After installation, check that the inlet/outlet on/off valves, any by-pass and the bleed valves are closed. Before commissioning, you must ensure that the conditions of use comply with the characteristics of the apparatuses. These characteristics are recalled by the symbols on the specification plates applied to each apparatus (fig. 4). We recommend actuating the opening and closing valves very slowly. The regulator could be damaged by too fast valve operations.

Technical manual MT 239-E 10 APPARATUS SPECIFICATION PLATES fig. 4 The list of symbols used and their meanings are listed below: = According to 97/23/CE PED Directive Pumax= maximum operating pressure at the inlet of the apparatus. bpu= range of variability of the inlet pressure of the pressure regulator in normal operating conditions. PS= maximum pressure for which the body and its inner metallic partition walls are designed in accordance with the strength requirements in this document. Cg and KG = experimental coefficient of critical flow. AC= regulation class. SG= closing pressure class. Fail safe mode= fail open regulator o fail closed regulator. Strength type= strength class (IS o DS). 4.2 GAS INPUT, CONTROL OF EXTERNAL TIGHTNESS AND SETTING The pressurization of the equipment shall be performed very slowly. Should not any stabilization procedure be carried out, it is recommended to keep gas speed in the feeding piping at a value equal to 5 m/sec during pressurization. To protect the apparatus from damage, the following operations must never be carried out: Pressurization through a valve located downstream from the apparatus itself. Depressurization through a valve located upstream from the apparatus itself. External tightness is guaranteed if no bubbles are visible when a foam medium is applied on the element under pressure. The regulator is normally supplied with the pressostatic chamber already drained. Only the relief valve VS/FI is set. It is possible for various reasons (e.g., vibration during transport) for the settings to be changed while remaining within the values allowed by the spring installed. In installation consisting of two lines, we suggest commissioning one line at a time, starting from the one with the lover setpoint, known as the stand-by line. Before commissioning the regulator you must check that all the on/off valves (inlet, outlet, any by-pass) are closed and that the gas is at a temperature which will not lead to malfunction.

Technical manual MT 239-E 11 4.3 COMMISSIONING THE REGULATOR (fig.5) If there is also a relief valve in the line, refer to par. 3.1 to check it.. fig. 5 1) Open the inlet on-off valve V1 very slowly. 2) Partially open the bleed valve 6 checking the outlet pressure value by mean of the pressure gauge 5 3) Adjust the setting value by means of the pressurized chamber inlet valve. 4) Close the bleed valve 6 and check the lock up pressure. 5) Using a foam substance, check the tightness of all the items and joints between the on-off valves V1and V2. 6) Very slowly open the downstream on-off valve V2 to obtain the complete filling of the pipe line.

Technical manual MT 239-E 12 5.0 TROUBLE-SHOOTING The problems of various kinds that could arise over time are highlighted below. They derive from phenomena associated with the conditions of the gas as well as the natural ageing and wear of the materials. It must be remembered that all operations on the apparatuses must be carried out by highly qualified personnel with appropriate knowledge of the subject. Tampering of the apparatuses by unsuitable personnel relieves us from all responsibility of any kind. 5.1 REGULATOR STAFLUX MINI (FIG. 6) PROBLEM POSSIBLE CAUSES REMEDY No tightness at Q=0 Pumping Pd pressure increases with Q>0 Valve seat [11] damaged Obturator [13] damaged O-ring [12] damaged O-ring [22] damaged O-ring [17] damaged O-ring [15] damaged Diaphragm [7] damaged Obturator of pressurized chamber inlet valve damged Dirt or foreign bodies in the sealing area Stem locked by dirt or foreign bodies Unusual friction of obturator stem group Reduced downstream volumes Brocken diaphragm [7] Stem locked by dirt or foreign bodies Obturator of pressurized chamber inlet valve damaged Clean Clean Celan and in case replace sealing and/or guide elements Volume increases Clean Pd pressure decreases with Q>0 Obturator of pressurized chamber inlet valve damaged Stem locked by dirt or foreign bodies Excessive flow rate Inlet pressure decreases Celan Reduce flow rate Check filter

Technical manual MT 239-E 13 6.0 MAINTENANCE 6.1 GENERALS Before carrying out any operation is important to ascertain that the regulator has been cut off both upstream and downstream and that the pressure has been discharged in the sections of piping between the regulator and the on/off valves. Furthermore it is important to ascertain that the pressostatic chamber is completely drained. The maintenance operations are closely associated with the quality of the gas transported (impurities, humidity, gasoline, corrosive substances) and with the efficiency of the filtering. Preventive maintenance should be carried out at intervals which, if not established by regulations, depend on: - the quality of the gas transported - the cleanliness and conservation of the piping upstream from the regulator. In general, for example, when starting the equipment for the first time, more frequent maintenance is required because of the precarious state of cleanliness inside the piping - the level of reliability required from the regulation system Before starting the disassembly operations on the apparatus you should check that: - a set of recommended spares is available. The spares must be original Fiorentini, bearing in mind that the more important such as diaphragms are marked - a set of wrenches is available For a proper maintenance the recommended spare parts are unequivocally identified by the assembly drawing of the apparatus contained in the package of the kit. It is suggestable to replace all rubber parts; fot this aim use the relative spare parts kit. N.B. The use of non-original components relieves Pietro Fiorentini S.p.A. of all responsibility. The depressurization operation has to be carried out paying attention to discharge the bleed valves to the drains in a safe area. To avoid the risk of generating sparks due to bumps of impurity particles within the discharge lines, it is recommended to keep the fluid speed lower than 5 m/sec. Moreover, it is suggested to perform reference marks, before disassembling the equipment, on the parts that may show problems of mutual orientation or positioning during re-assembly. Finally, it shall be underlined that the O-rings and the mechanical sliding parts (stems, etc.) must be lubricated, before reassembling them, with a thin layer of silicone grease. Before commissioning, the external tightness of the equipment has to be tested at a suitable pressure in order to assure the absence of external leaks. Such tests are essential to assure the safe use under the foreseen operating conditions. They have in any case to comply with the national regulations in force.

Technical manual MT 239-E 14 6.2 STAFLUX MINI MAINTENANCE PROCEDURE Procedure for disassembling, complete replacing of spare parts and reassembly of the gas pressure regulator STAFLUX MINI (fig. 6). PRELIMINARY OPERATION 1) Put the regulator in safety conditions 2) Ensure that upstream, downstream and pressostatic chamber pressure are 0 3) Perform a reference mark between cover and body DISASSEMBLY AND REASSEMBLY OF THE UPPER PART 1) Remove the screws (4) and remove the cover (3). 2) Remove the diaphragm (7) and the diaphragm protection disk (8). 3) Pull out the stem (10), clean and cover it with a fine layer of silicon grease. 4) Reposition the stem (10) 5) Insert the diaphragm protection disk (8) and the new diaphragm (7) 6) Reassembly the cover (3) taking care to respect the matching of the reference mark previously performed 7) Position the screws (4) and cross them according to a cross schem. DISASSEMBLY AND REASSEMBLY OF THE LOWER PART 1) Unscrew the plug (2). While removing this component, OR (18) and the obturator group (41, 13, 14 and 16) will be pulled out. 2) Pull out the piston (16) and replace the or OR (18) e (17) 3) Remove the screw (14), unscrew the ring nut (41) from the piston (16) and replace OR (15) and the gasket (13). 4) Screw the nut ring (41) and the screw (14) on the piston (16) 5) Insert the piston (16) in the plug (2) 6) Remove the filter (23) and the filter support (21) 7) By mean of the apposite tool, remove the OR (12) 8) Remove the seat (11) and the OR (22) 9) the or (12) and (22) and reassemble them in the body with the seat (11) 10) Reassemble the filter support (21) and the new filter (23) 11) Reassemble the plug (2) with the obturator group (41, 13, 14 and 16) Before re-installing the tightness elements elements (o-rings, diaphragm, etc ), it is necessary to check their integrity. Pay attention to handle the obturator group and the valve seat in order to avoid to damage the seal edges.

Technical manual MT 239-E 15 fig. 6

Technical manual MT 239-E 16 6.3 PRESSURIZED CHAMBER INLET VALVE MAINTENANCE PROCEDURE Procedure for disassembling, complete replacing of spare parts and reassembly of the pressurized chamber inlet valve (fig. 7 and fig. 8). PRELIMINARY OPERATION 1) Put the regulator in safety conditions 2) Ensure that upstream, downstream and pressostatic chamber pressure are 0 DISASSEMBLY AND REASSEMBLY 1) Remove the screws (31) 2) Remove and replace the OR (33) e (34). 3) Unscrew each tap (+) and (-) and replace the OR (36) and (40) 4) Remove and replace the gasket (38) To reassemble the pressurized chamber inlet valve you can run the other way the operations described for the disassembling process. 6.4 RELIEF VALVE VS/FI MAINTENANCE PROCEDURE Refer to the technical manual MT159 of the valve VS/FI.

Technical manual MT 239-E 17 fig. 7

Technical manual MT 239-E 18 fig. 8

Technical manual MT 239-E 19 7.0 FINAL OPERATION 7.1 CHECKING THE TIGHTNESS AND SETTING 1) Very slowly open the on/off valve upstream from the regulator 2) Open a bleed cock the atmosphere downstream from the regulator to create a small gas flow. 3) Act on the pressurized chamber inlet valve until the desired set-point value is reached. 4) Close the bleed valve to the atmosphere. 5) Check the tightness of the regulator (internal tightness). 6) Using a foam solution or the like, check the tightness of the external surfaces of the regulator 7.2 START UP Very slowly open the downstream valve and, if necessary, adjust the regulator setting by adjusting the pressure on the pressostatic chamber by means of the pressurized chamber inlet valve.

Pietro Fiorentini S.p.A. via E.Fermi 8/10 I-36057 Arcugnano (VI) Italy Tel. +39 0444 968.511 Fax. +39 0444 960.468 www.fiorentini.com via Rosellini 1 I-20124 Milano Italy Tel. +39 02 696.14.21 Fax. +39 02 688.04.57 MT239-E September 2015