COOPER POWER SERIES. 600 A 15, 25 and 35 kv class bushing adapter installation instructions. Deadbreak Apparatus Connectors MN650058EN

Similar documents
COOPER POWER SERIES. 600 A 15, 25, and 35 kv class PUSH-OP bushing adapter cap installation instructions. Deadbreak Apparatus Connectors MN650050EN

COOPER POWER SERIES. 200 A 15, 25, and 35 KV class insulated standoff bushing installation instructions. Loadbreak Apparatus Connectors MN650039EN

COOPER POWER SERIES. 200 A 15, 25, and 35 kv class portable feedthru installation instructions. Loadbreak Apparatus Connectors MN650037EN

200 A, 15 and 25 kv class loadbreak bushing insert installation instructions

COOPER POWER SERIES. 600 Ampere Deadbreak Grounded Standoff Bushing 15 & 25 kv and 35 kv Class Installation Instructions. Bushings MN650045EN

DT400/436 Tee Connector Installation Instructions

COOPER POWER SERIES. QD8 Quik-Drive tap-changer VR or VL reversing switch stationary contact assembly kit number A48 installation instructions

COOPER POWER SERIES. Series winding ratio test procedure instructions. Voltage Regulators MN225060EN. 120 Vac VOLTMETER

COOPER POWER SERIES. Manual or Hostick Operable, Padlockable 150 A Tap-Changer Switch Installation Instructions. Tap-Changer Switch MN800015EN

Effective May 2017 Supersedes July 2009 (S ) 600 A 35 kv Class T-OP II connector assembly installation instructions 200 A PROTECTIVE CAP LRTP

COOPER POWER SERIES. D-73P3 bypass switches installation instructions. Switches MN008005EN. Effective April 2016 Supersedes S June 2013

COOPER POWER SERIES. EL Bay-O-Net Current-Limiting Fuse Installation Instructions. Fusing Equipment MN132023EN

COOPER POWER SERIES. UltraSIL Polymer-Housed Distribution-Class MOV Surge Arrester Installation Instructions. Surge Arresters MN235006EN

COOPER POWER SERIES. Under-oil arrester disconnector installation/operation instructions. OEM Equipment MN800010EN

DAI630TB2669 Dead Front Arrester Installation Instruction

Effective March 2015 Supersedes S August 2002

COOPER POWER SERIES. VariSTAR Storm Trapper high energy MOV arrester installation instructions. Surge Arresters MN235017EN

COOPER POWER SERIES. 200 A 15/25 kv class deadbreak straight connector installation instructions. Deadbreak Apparatus Connectors MN650043EN

COOPER POWER SERIES. 200 A 15/25 kv class elbow installation instructions. Deadbreak Apparatus Connectors MN650042EN

COOPER POWER SERIES. DS250 deadbreak straight connector installation instructions interface A. Connectors MN650027EN

COOPER POWER SERIES. DE250 deadbreak elbow connector installation instructions interface A. Screened Separable Connectors MN650025EN

COOPER POWER SERIES. 600 A 35 kv class PUSH-OP deadbreak connector installation instructions. Deadbreak Apparatus Connectors MN650052EN

COOPER POWER. SERIES VariSTAR type composite light-duty under-oil (CLU) MOV arrester installation instructions. Surge Arresters MN235023EN

COOPER POWER SERIES. 600 A, 15, 25, and 35 kv Class Cleer Grounding Elbow Installation Instructions. Loadbreak Apparatus Connectors MN650056EN

COOPER POWER SERIES. UltraSIL polymer-housed VariSTAR surge arrester IEC for MV systems to 36 kv installation instructions

COOPER POWER SERIES. 50 A 2:1 series multiple (dual voltage) switch cap/wrench, lever or hotstick operable handles installation instructions

600 A 35 kv class PUSH-OP deadbreak connector installation instructions

COOPER POWER SERIES. Operation Counter Replacement Instructions. Reclosers MN280047EN. Effective May 2016 Supersedes S December 2003

COOPER POWER SERIES. 200 A 35 kv class LE series elbow installation instructions. Loadbreak Apparatus Connectors MN650010EN

COOPER POWER. SERIES VariSTAR type AZE station class surge arresters installation and maintenance instructions. Surge Arresters MN235022EN 0.

Effective January 2017 Supersedes July 2011 (I ) VariSTAR Type AZG4 Surge Arresters Installation and Maintenance Instructions

S Surge Arresters

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with optional integral jacket seal installation instructions. Loadbreak Connectors MN650008EN

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with integral jacket seal* for use on tape and wire shielded cable installation instructions

COOPER POWER SERIES. Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions. Reclosers MN280051EN

Installation Instructions for the Walking Beam Interlock for Eaton EHD, FDB, FD, HFD, FDC, FW, HFW, FWC, Circuit Breakers and Molded Case Switches

COOPER POWER SERIES. VFI SF6-insulated vacuum fault interrupter installation, operation and maintenance instructions. Switchgear MN285004EN

S Loadbreak Apparatus Connectors WARNING: WARNING:

Effective May 2017 Supersedes August 2005 (S )

Operation Manual Enabling Pole-Top Communication Via the TripSaver II Magnet Tool

FLANGED TWO-PIECE BALL VALVES

FLANGED TWO-PIECE BALL VALVES

GRAVITY BIKE RACK ASSEMBLY & OPERATING INSTRUCTIONS

Pressure Dump Valve Service Kit for Series 2300 Units

INTRODUCTION BILL OF MATERIALS SPECIFICATIONS & TOOLS PROCEDURES OPERATION OF SEATPOST GIANT LIMITED WARRANTY

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

MAVERICK FOOSBALL TABLE

JBR Ford Focus ST Heavy Shift Knob Installation Instructions

DEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers

3M Liqui-Cel EXF-14x28 and 14x40 Series Membrane Contactor

Booster Pump PB4-60 Replacement Kits

BS Series Basket Strainer

Medium voltage standard-duty, heavyduty, and extreme-duty single-phase, unfused capacitor units and accessories

DISASSEMBLING & REASSEMBLING CARTRIDGE INSTALLING SEATPOST ON BIKE

3" UC Ultra-Chuck Durable Lightweight Air Inflated Bladder Chuck Operation/Repair Manual. (76.2 mm) DOUBLE E COMPANY, INC.

Teledyne Oil & Gas North Williamson Blvd. Daytona Beach, FL USA (phone) (fax)

Pressure Dump Valve Service Kit for Series 3000 Units

Acid- Rite ph Adjustment System 2500 by Axiall, a Westlake Company

Media-Isolated Mag Plus Probe Low Pressure-ISO Kit

Instruction Manual. PE Pipe Squeeze-off Tool Model TR650

Inspection Recommendations

Sunset Swings By Health in Motion, LLC

60 farm jack. Distributed exclusively by Harbor Freight Tools Mission Oaks Blvd., Camarillo, CA 93011

TITAN FLOW CONTROL, INC.

3M Liqui-Cel EXF-10x28 Series Membrane Contactor

Norrsken Family Booklet

Hygienic Bubble Trap Installation and Operations Manual

COOPER POWER SERIES. Type VFI, Fluid-insulated Switchgear; Installation, Operation and Maintenance Instructions

ROPV R40 E Series User Manual

USER MANUAL FLOW SELECTOR PM1000 SAVE THESE INSTRUCTIONS. Federal (USA) law restricts this device to sale by or on the order of a physician.

Model No Product Name Handpiece Only Complete System

PARK AVENUE 7' POOL TABLE WITH TABLE TENNIS & BENCHES ASSEMBLY INSTRUCTIONS

S Vacuum Switches. Contents. Type VCS-1 Single-Phase Vacuum Capacitor Switch Installation and Operation Instructions

AIR INLINE METAL SHEAR

FLANGED MULTI-PORT BALL VALVES

Angled Sign Light with Shade

This document to be used with Hurley traditional Davits

Operating Instructions for BAIR22-6 AIR-POWERED CRIMPING TOOL

COMPACT METAL bender 99826

Caliber Sled Wheels Assembly Instructions for PN and 13579

User Instruction Manual

INSTRUCTION MANUAL MP4AR Remote Convection Gauge Range: 1 x 10-3 Torr to 1 x 10+3 Torr

Installation, Operation and Maintenance Manual

Cocoa Patio Pond with Lit Spillway

INSTRUCTION MANUAL. Includes: OPERATION SETUP USE & CARE SERVICE. SPORTS ATTACK LLC

CP-D/CP-M Circular Polarizer for Phoroptor. User s Guide

Pressure Relief Valve Instruction Manual

7 FOOT POOL TABLE WITH TABLE TENNIS TOP ASSEMBLY INSTRUCTIONS

1/2 Twin Hammer Composite. Air Impact Wrench ASSEMBLY AND OPERATING INSTRUCTIONS

Permanent Roof Anchors

COSASCO MODEL 60 RETRACTABLE 1500 PSI SYSTEM RETRACTOR KIT Work Instruction

60 Drum Style Spike Aerator

GETZ EQUIPMENT INNOVATORS PART NO.: 9G59554 MODEL: MS 36 SC-R HYDROSTATIC TEST PUMP

Accu-Tab Systems 1000 Series by Axiall Corporation

S Surge Arresters. Handling and Storage. Standards. Acceptance and Initial Inspection

2-1- Shipping Receiving Lifting Location on Site Installation Stages 6

Remington 700. Disclaimer Limited Warranty Satisfaction Guarantee Installation Instructions

WHEATLEY Series 500 Swing Check Valve

SIX R (P ) AND SEVEN R (P ) POSITION CYLINDERS Service Information

APCO ARV CLEAN WATER AIR RELEASE VALVES. Model 50A

Transcription:

Deadbreak Apparatus Connectors MN650058EN Effective May 2017 Supersedes July 2009 (S600-59-1) 600 A 15, 25 and 35 kv class bushing adapter installation instructions COOPER POWER SERIES

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. INSTALLATION INSTRUCTIONS MN650058EN May 2017 i

Contents DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY... I SAFETY FOR LIFE... III SAFETY INFORMATION... III Safety instructions... iii PRODUCT INFORMATION.... 1 Introduction...1 Read this manual first...1 Additional information...1 Acceptance and initial inspection...1 Handling and storage...1 Standards...1 INSTALLATION INSTRUCTIONS.... 1 Equipment required...1 ii INSTALLATION INSTRUCTIONS MN650058EN May 2017

! SAFETY FOR LIFE Safety for life Eaton s Cooper Power series products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high-voltage lines and equipment and support our Safety For Life mission.! SAFETY FOR LIFE Safety information The instructions in this manual are not intended as a sub stitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians, who are familiar with this equipment should install, operate and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high- and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as flash clothing, safety glasses, face shield, hard hat, rubber gloves, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates a hazardous situation which, if not avoided, will result in death or serious injury. Indicates a hazardous situation which, if not avoided, could result In death or serious injury. CAUTION Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. CAUTION Indicates a hazardous situation which, if not avoided, could result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with high voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high- and low-voltage lines and equipment. Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply may result in death, severe personal injury and equipment damage. Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. INSTALLATION INSTRUCTIONS MN650058EN May 2017 iii

600 A 15, 25 and 35 kv class bushing adapter installation instructions Hazardous Voltage Terminators must be de-energized during operation or maintenance. Visible break and adequate grounding must be provided before cable work proceeds. (Ensure that the component is rated for the intended application before it is installed.) Failure to comply could result in death or serious injury. The Bushing Adapter should be installed and serviced only by personnel familiar with good safety practice and the handling of high-voltage electrical equipment. Product information Introduction The Eaton Cooper Power series 600 A Bushing Adapter is a factory assembled Loadbreak Reducing Tap Plug (LRTP) and bushing extender unit. It is used to convert a 600 A deadbreak interface to a 200 A loadbreak interface* allowing for safe testing and grounding. It has electrical characteristics identical to those of the LRTP. Used with a 200 A insulated protective cap, M.O.V.E. arrester, grounding elbow or loadbreak elbow connector, a bushing adapter provides a fully shielded, submersible unit that meets the requirements of IEEE Std 386 standard. Read this manual first Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment. Additional information These instructions cannot cover all details or variations in the equipment, procedures, or process described nor provide directions for meeting every possible contingency during installation, operation, or maintenance. For additional information, contact your representative. Figure 1. 15 kv 600 A Bushing Adapter, including Loadbreak Reducing Tap Plug (LRTP) and bushing extender Acceptance and initial inspection Each bushing adapter is in good condition when accepted by the carrier for shipment. Upon receipt, inspect the shipping container for signs of damage. Unpack the bushing adapter and inspect it thoroughly for damage incurred during shipment. If damage is discovered, file a claim with the carrier immediately. Handling and storage Be careful during handling and storage of the bushing adapter to minimize the possibility of damage. If the bushing adapter is to be stored for any length of time prior to installation, provide a clean, dry storage area. Standards ISO 9001 Certified Quality Management System Installation instructions Equipment required Choose one of the following: Tools Torque Tool & T-Wrench Combination: 15 and 25 kv - Torque Tool Catalog Number TQHD625 35 kv - Torque Tool Catalog Number TQHD635 5/16 T-Wrench - Catalog Number TWRENCH or O & T Tool & Torque Tool Combination: 15 kv - Catalog Number OT615 25 kv - Catalog Number OT625 35 kv - Catalog Number OT635 15 and 25 kv - Torque Tool Catalog Number TQHD625 35 kv - Torque Tool Catalog Number TQHD635 1 INSTALLATION INSTRUCTIONS MN650058EN May 2017

600 A 15, 25 and 35 kv class bushing adapter installation instructions or Combined O & T/Torque Tool: 15 kv - Catalog Number OTTQ615 25 kv - Catalog Number OTTQ625 35 kv - Catalog Number OTTQ635 NNote: If Combined O & T/Torque Tool is used, a separate O & T tool and torque wrench is not required. Place a screwdriver or the T-wrench through the hotsitck operating eye of the torque tool and tighten the bushing adapter until the tool ratchets. (20-25 ft.-lbs.) NNote: If 5/16 hex rod (HD625) is used with customer suppled torque wrench, tighten to 20-25 ft.-lbs. Remove torque tool. Step 1 Install stud into apparatus bushing NNote: Ensure unit is de-energized. Thread the shorter threaded end of the extended stud into the apparatus bushing until hand tight. (Refer to Figure 2). Engage the flats on the stud with a 1/2 wrench and thread the stud into the bushing an additional 1/4 revolution past hand tight. Remove any shavings that may have been raised during the threading procedure. SHORT THREADS INTO BUSHING Figure 3. Installing the bushing adapter onto the apparatus bushing Step 3 CLEAN AND LUBRICATE Cap the 200 A Interface Clean and lubricate the 200 A interface of LRTP and mating apparatus (i.e. protective cap, grounding elbow, M.O.V.E. arrester) with lubricant supplied. (Refer to Figure 4.) To cap interface, follow installation instructions supplied with the separable insulated connector used. APPARATUS BUSHING EXTENDED STUD (STUD-T) Figure 2. Line illustration of bushing stud installation Step 2 Install the bushing adapter assembly on the apparatus bushing Clean and lubricate mating 600 A interfaces of the apparatus bushing and bushing adapter with the lubricant supplied. Figure 4. Installation of protective cap CLEAN AND LUBRICATE Remove shipping cap from 200 A interface of the bushing adapter. Push the bushing adapter onto the apparatus bushing until the extended length stud makes contact with the rotating nut in the LRTP. Insert the 5/16 torque tool into the 200 A tap and engage the rotating nut. (Refer to Figure 3.) INSTALLATION INSTRUCTIONS MN650058EN May 2017 2

600 A 15, 25 and 35 kv class bushing adapter installation instructions Step 4 Attach drain wire Connect apparatus drain wire to common ground point leaving adequate slack for hotstick operation. (Refer to Figure 5.) BUSHING ADAPTER 200 A INSULATED PROTECTIVE CAP DRAIN WIRE Figure 5. Drain wire connection 3 INSTALLATION INSTRUCTIONS MN650058EN May 2017

! SAFETY FOR LIFE Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No. MN650058EN May 2017 Eaton is a registered trademark. All trademarks are property of their respective owners. For Eaton s Cooper Power series product information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.