COOPER POWER SERIES. 600 A 15, 25, and 35 kv class PUSH-OP bushing adapter cap installation instructions. Deadbreak Apparatus Connectors MN650050EN

Similar documents
COOPER POWER SERIES. 600 A 15, 25 and 35 kv class bushing adapter installation instructions. Deadbreak Apparatus Connectors MN650058EN

COOPER POWER SERIES. 200 A 15, 25, and 35 KV class insulated standoff bushing installation instructions. Loadbreak Apparatus Connectors MN650039EN

COOPER POWER SERIES. 600 Ampere Deadbreak Grounded Standoff Bushing 15 & 25 kv and 35 kv Class Installation Instructions. Bushings MN650045EN

COOPER POWER SERIES. 200 A 15, 25, and 35 kv class portable feedthru installation instructions. Loadbreak Apparatus Connectors MN650037EN

200 A, 15 and 25 kv class loadbreak bushing insert installation instructions

COOPER POWER SERIES. D-73P3 bypass switches installation instructions. Switches MN008005EN. Effective April 2016 Supersedes S June 2013

DT400/436 Tee Connector Installation Instructions

COOPER POWER SERIES. Manual or Hostick Operable, Padlockable 150 A Tap-Changer Switch Installation Instructions. Tap-Changer Switch MN800015EN

Effective March 2015 Supersedes S August 2002

COOPER POWER SERIES. VariSTAR Storm Trapper high energy MOV arrester installation instructions. Surge Arresters MN235017EN

COOPER POWER SERIES. EL Bay-O-Net Current-Limiting Fuse Installation Instructions. Fusing Equipment MN132023EN

COOPER POWER SERIES. QD8 Quik-Drive tap-changer VR or VL reversing switch stationary contact assembly kit number A48 installation instructions

COOPER POWER SERIES. Series winding ratio test procedure instructions. Voltage Regulators MN225060EN. 120 Vac VOLTMETER

COOPER POWER SERIES. 600 A, 15, 25, and 35 kv Class Cleer Grounding Elbow Installation Instructions. Loadbreak Apparatus Connectors MN650056EN

COOPER POWER SERIES. UltraSIL Polymer-Housed Distribution-Class MOV Surge Arrester Installation Instructions. Surge Arresters MN235006EN

DAI630TB2669 Dead Front Arrester Installation Instruction

COOPER POWER SERIES. Under-oil arrester disconnector installation/operation instructions. OEM Equipment MN800010EN

COOPER POWER SERIES. 200 A 15/25 kv class deadbreak straight connector installation instructions. Deadbreak Apparatus Connectors MN650043EN

COOPER POWER SERIES. 600 A 35 kv class PUSH-OP deadbreak connector installation instructions. Deadbreak Apparatus Connectors MN650052EN

COOPER POWER. SERIES VariSTAR type composite light-duty under-oil (CLU) MOV arrester installation instructions. Surge Arresters MN235023EN

COOPER POWER SERIES. 50 A 2:1 series multiple (dual voltage) switch cap/wrench, lever or hotstick operable handles installation instructions

COOPER POWER SERIES. DS250 deadbreak straight connector installation instructions interface A. Connectors MN650027EN

COOPER POWER SERIES. DE250 deadbreak elbow connector installation instructions interface A. Screened Separable Connectors MN650025EN

600 A 35 kv class PUSH-OP deadbreak connector installation instructions

Effective May 2017 Supersedes July 2009 (S ) 600 A 35 kv Class T-OP II connector assembly installation instructions 200 A PROTECTIVE CAP LRTP

COOPER POWER SERIES. 200 A 15/25 kv class elbow installation instructions. Deadbreak Apparatus Connectors MN650042EN

COOPER POWER SERIES. UltraSIL polymer-housed VariSTAR surge arrester IEC for MV systems to 36 kv installation instructions

COOPER POWER SERIES. 200 A 35 kv class LE series elbow installation instructions. Loadbreak Apparatus Connectors MN650010EN

COOPER POWER SERIES. Operation Counter Replacement Instructions. Reclosers MN280047EN. Effective May 2016 Supersedes S December 2003

COOPER POWER. SERIES VariSTAR type AZE station class surge arresters installation and maintenance instructions. Surge Arresters MN235022EN 0.

Effective January 2017 Supersedes July 2011 (I ) VariSTAR Type AZG4 Surge Arresters Installation and Maintenance Instructions

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with optional integral jacket seal installation instructions. Loadbreak Connectors MN650008EN

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with integral jacket seal* for use on tape and wire shielded cable installation instructions

COOPER POWER SERIES. Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions. Reclosers MN280051EN

COOPER POWER SERIES. VFI SF6-insulated vacuum fault interrupter installation, operation and maintenance instructions. Switchgear MN285004EN

S Surge Arresters

Installation Instructions for the Walking Beam Interlock for Eaton EHD, FDB, FD, HFD, FDC, FW, HFW, FWC, Circuit Breakers and Molded Case Switches

S Loadbreak Apparatus Connectors WARNING: WARNING:

Effective May 2017 Supersedes August 2005 (S )

Operation Manual Enabling Pole-Top Communication Via the TripSaver II Magnet Tool

COOPER POWER SERIES. Type VFI, Fluid-insulated Switchgear; Installation, Operation and Maintenance Instructions

DEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers

Inspection Recommendations

Medium voltage standard-duty, heavyduty, and extreme-duty single-phase, unfused capacitor units and accessories

Norrsken Family Booklet

S Surge Arresters. Handling and Storage. Standards. Acceptance and Initial Inspection

SIX R (P ) AND SEVEN R (P ) POSITION CYLINDERS Service Information

S Vacuum Switches. Contents. Type VCS-1 Single-Phase Vacuum Capacitor Switch Installation and Operation Instructions

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

Media-Isolated Mag Plus Probe Low Pressure-ISO Kit

OPERATOR'S & PARTS MANUAL

2000 lb manual winch

This document to be used with Hurley traditional Davits

INSTRUCTION MANUAL MP4AR Remote Convection Gauge Range: 1 x 10-3 Torr to 1 x 10+3 Torr

Instruction manual. Type Vector manual group-operated switch. Answers for infrastructure and cities.

Type Vector manual group-operated switch instruction manual. Installation operation maintenance E50001-F710-A420-X-4A00. Answers for energy.

Permanent Roof Anchors

Acid- Rite ph Adjustment System 2500 by Axiall, a Westlake Company

BS Series Basket Strainer

Cocoa Patio Pond with Lit Spillway

Model No Product Name Handpiece Only Complete System

Accu-Tab Systems 1000 Series by Axiall Corporation

Remington 700. Disclaimer Limited Warranty Satisfaction Guarantee Installation Instructions

Index Table. Model 794. Installation, Operating and Maintenance Instructions

User s Guide Temperature Sensor Converter TSC-599

GETZ EQUIPMENT INNOVATORS PART NO.: 9G59554 MODEL: MS 36 SC-R HYDROSTATIC TEST PUMP

Booster Pump PB4-60 Replacement Kits

Operating Instructions for BAIR22-6 AIR-POWERED CRIMPING TOOL

Teledyne Oil & Gas North Williamson Blvd. Daytona Beach, FL USA (phone) (fax)

AIR INLINE METAL SHEAR

Pressure Dump Valve Service Kit for Series 2300 Units

Triple Tine Mechanical Grapple

ACCESSORY KIT INSTALLATION INSTRUCTIONS

USER MANUAL FLOW SELECTOR PM1000 SAVE THESE INSTRUCTIONS. Federal (USA) law restricts this device to sale by or on the order of a physician.

Model ASSEMBLY and OPERATING INSTRUCTIONS

VOLLEYBALL SPIKE TRAINER. Assembly Instructions. Owner s Manual. Model # VST-400. Club Volleyball Gear

60 farm jack. Distributed exclusively by Harbor Freight Tools Mission Oaks Blvd., Camarillo, CA 93011

6 digital caliper with case

Accu-Tab Systems 2000 P Series by Axiall Corporation

Parts & Operators Manual

Pressure Relief Valve Instruction Manual

J Air and Water Kit Instructions Part# 02584

FLANGED TWO-PIECE BALL VALVES

Installation and Operation

Interface Devices, Inc. Hydraulic Mini Mule

INSTRUCTION MANUAL. Includes: OPERATION SETUP USE & CARE SERVICE. SPORTS ATTACK LLC

Hygienic Bubble Trap Installation and Operations Manual

INTRODUCTION BILL OF MATERIALS SPECIFICATIONS & TOOLS PROCEDURES OPERATION OF SEATPOST GIANT LIMITED WARRANTY

Installation Instructions JATCO Environmental Protection Tank Model J-7000

ROPV R40 E Series User Manual

D Series Air and Water Kit Part# 02550

FLANGED TWO-PIECE BALL VALVES

92831 TEL: (714) FAX:

GE Oil & Gas Model. Masoneilan* Air Lock-up Valve Instruction Manual. GE Data Classification : Public

3M Liqui-Cel EXF-14x28 and 14x40 Series Membrane Contactor

For ELECTRIC ANCHOR WINCH Models: T Pontoon 35 T sw Salt Water Series Coastal 35

Operation Manual. Hand tool for AMP DUOPLUG Customer Manual PN: en (Translation of the original German version)

GRAVITY BIKE RACK ASSEMBLY & OPERATING INSTRUCTIONS

ASG-SD2500 ASG-SD2500

INSTALLATION & OPERATION MANUAL. Dual Duct VAV Terminals. Redefine your comfort zone.

Transcription:

Deadbreak Apparatus Connectors MN650050EN Effective May 2017 Supersedes January 2010 (S600-19-1) COOPER POWER 600 A 15, 25, and 35 kv class PUSH-OP bushing adapter cap installation instructions SERIES

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. ii 600 A 15, 25, AND 35 KV CLASS PUSH-OP BUSHING ADAPTER CAP INSTALLATION INSTRUCTIONS MN650050EN May 2017

Contents SAFETY INFORMATION Safety Information...iv PRODUCT INFORMATION Introduction...1 Acceptance and Initial Inspection....1 Handling and Storage...1 Standards...1 INSTALLATION INSTRUCTIONS Bushing adapter cap kit contents....2 Equipment required...2 Installation steps...2 BUSHING ADAPTER CAP REMOVAL PROCESS...3 600 A 15, 25, AND 35 KV CLASS PUSH-OP BUSHING ADAPTER CAP INSTALLATION INSTRUCTIONS MN650050EN May 2017 iii

! SAFETY FOR LIFE Safety for life! SAFETY FOR LIFE Eaton meets or exceeds all applicable industry standards relating to product safety with its Cooper Power series products. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment, and support our Safety For Life mission. Safety information The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equipment should install, operate, and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as arc flash clothing, safety glasses, face shield, hard hat, rubber gloves, clampstick, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around highand low-voltage lines and equipment. G103.3 Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. G101.0 This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage. G102.1 Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. G122.3 iv 600 A 15, 25, AND 35 KV CLASS PUSH-OP BUSHING ADAPTER CAP INSTALLATION INSTRUCTIONS MN650050EN May 2017

PUSH PLATE LATCH HANDLE FIRST NOTCHES LOCKING TEETH BAIL BRACKET SHROUD PIN 200 A INTERFACE LOCKING SLOT OPERATING EYE Figure 1. Line drawing showing 15 kv 600 A PUSH-OP bushing adapter cap. The 600 A 15, 25 and 35 kv PUSH-OP bushing adapter cap is designed to be operated in accordance with normal safe operating procedures. These instructions are not intended to supersede or replace existing safety and operating procedures. Terminators must be de-energized during operation or maintenance. Visible break and adequate grounding must be provided before cable work proceeds. (Ensure that the component is rated for the intended application before it is installed.) The bushing adapter cap should be installed and serviced only by personnel familiar with good safety practice and the handling of high-voltage electrical equipment. Failure to comply may result in death, severe personal injury or equipment damage. Product Information Introduction Eaton's Cooper Power series 600 A, 15, 25, and 35 kv PUSH-OP bushing adapter cap is a factory assembled load reducing tap plug (LRTP) and bushing extender unit. It is used to convert a 600 A deadbreak interface to a 200 A loadbreak interface* allowing for safe testing and grounding. It has electrical characteristics identical to those of the LRTP. Used with Eaton's Cooper Power series 200 A insulated protective cap, M.O.V.E. arrester, grounding elbow or loadbreak elbow connector, a bushing adapter provides a fully shielded, submersible unit that meets the requirements of IEEE Std 386-2006 standard. All associated apparatus must be de-energized during installation and/or maintenance. Failure to comply may result in death, severe personal injury or equipment damage. * Switching rating limited to single-phase 21.1 kv. 600 A 15, 25, AND 35 KV CLASS PUSH-OP BUSHING ADAPTER CAP INSTALLATION INSTRUCTIONS MN650050EN May 2017 1

Read This Manual First Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment. Additional Information These instructions cannot cover all details or variations in the equipment, procedures, or process described nor provide directions for meeting every possible contingency during installation, operation, or maintenance. For additional information, contact your Eaton representative. Acceptance and Initial Inspection Each PUSH-OP bushing adapter cap is in good condition when accepted by the carrier for shipment. Upon receipt, inspect the shipping container for signs of damage. Unpack the PUSH-OP bushing adapter cap and inspect it thoroughly for damage incurred during shipment. If damage is discovered, file a claim with the carrier immediately. Handling and Storage Be careful during handling and storage of the PUSH-OP bushing adapter cap to minimize the possibility of damage. If the PUSH-OP bushing adapter cap is to be stored for any length of time prior to installation, provide a clean, dry storage area. Standards ISO 9001 Certified Quality Management System Installation instructions PUSH-OP bushing adapter cap kit Each kit contains: Bushing Adapter Silicone Lubricant Installation Instructions 200 A Loadbreak Protective Cap (Optional) Equipment required Tools: Torque Wrench (Catalog Number 15/25 kv - TQHD625, 35 kv - TQHD635) T-Wrench (Catalog Number T-WRENCH) O & T Tool (Catalog Number 15 kv - OT615, 25 kv - OT625, 35 kv - OT635) Combined O & T/Torque Tool (Catalog Number 15 kv - OTTQ615, 25 kv - OTTQ625, 35 kv - OTTQ635) NNote: Step 1. If Combined O & T Tool is used, a separate O & T tool and torque wrench is not required. Clean and lubricate Clean and lubricate 600 A and 200 A interfaces of PUSH-OP bushing adapter cap with lubricant supplied or approved equivalent. Clean and lubricate mating surface of PUSH-OP bushing. Step 2. Ground Attach drain wire to system ground bus. 2 600 A 15, 25, AND 35 KV CLASS PUSH-OP BUSHING ADAPTER CAP INSTALLATION INSTRUCTIONS MN650050EN May 2017

Step 3. Assemble to apparatus bushing Grasp operating eye on bushing adapter with hotstick and pull eye completely into hotstick. Place bushing adapter cap on PUSH-OP apparatus bushing, engaging shroud pins in bail bracket locking slots, and push until latch plate engages first notches. Release operating eye from hotstick. Push forward on push plate until a bump is felt and latch plate engages locking teeth. Pull on push plate with hotstick to ensure latch plate is engaged. Use hotstick to hook catch strap on push plate slots. Step 4 Install mating apparatus Clean and lubricate 200 A interface of mating apparatus (e.g. insulated protective cap, grounding elbow, M.O.V.E. arrester). Bushing adapter cap removal process Remove mating apparatus from bushing adapter using a hotstick. Test for voltage by fuzzing or by using voltage detector. Do not proceed until bushing is de-energized. Failure to comply may result in death, severe personal injury or equipment damage. Ensure that catch strap is hooked on push plate. Grasp latch handle of PUSH-OP bushing using hotstick and pull backward until bushing adapter is completely unsealed. Remove bushing adapter cap by unhooking catch strap ring with hotstick. Place bushing adapter in clean protected area. 600 A 15, 25, AND 35 KV CLASS PUSH-OP BUSHING ADAPTER CAP INSTALLATION INSTRUCTIONS MN650050EN May 2017 3

! SAFETY FOR LIFE Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No. MN650050EN May 2017 Eaton is a registered trademark. All trademarks are property of their respective owners. For Eaton's Cooper Power series product information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.