Installation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM.

Similar documents
WW-730. Pressure Sustaining/Relief Control Valve

WW-720. Pressure Reducing Control Valve

WW-720. Pressure Reducing Control Valve

Model 420-HY Pressure Regulating Hydrant Valve

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

Bermad Pressure Reducing. Model: 42T

Model: 43T. Bermad Pressure Relief Valve

Bermad Model:

INSTALLATION OPERATION MAINTENANCE

Operation & Maintenance Manual Place this manual with valve or person responsible for maintenance of the valve

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

BERMAD Waterworks. Level Control Valve with Altitude Pilot. 700 Series. Model X. Features and Benefits. Major Additional Features

I T T Pressure Reducing Valve WARNING INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

SUBMITTAL NOTES PROJECT: Ross Model 50RWR-A Pilot Operated Surge Relief Valve with Hydraulic Anticipation. Size: inch / mm

Pressure Reducing Valve for Steam Type 2333 A

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

TD45 Thermodynamic Steam Trap Installation and Maintenance Instructions

CAST IRON VALVES FLOAT VALVE

TECHNICAL DATA. Page 1 of 12

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

PRS(TC)4,8 USER MANUAL. Read the complete manual before installing and using the regulator.

TECHNICAL DATA CAUTION

Model GPR Primary Pressure Regulating Valve. Instruction Manual

553 Series.

TECHNICAL DATA. Pressure Regulation 531a. April 24, 2009

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

DS05C,D,G Dial Set Pressure Regulating Valves

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

Installation and operation Manual. Bermad Surge Anticipation Valve. Model No 435

OPERATING AND MAINTENANCE MANUAL

Model GP PRESSURE REDUCING VALVE Installation & Operation Manual

End Connection. Thread x Thread N/A N/A N/A N/A Flange x Flange N/A

299H Series. Introduction. P.E.D. Categories. Specifications. Installation. Warning. Installation Guide English September 2012

1. Preface Important Safety Notes Brief Product Information Product Working Principle Installation Guidelines...

GREIG FILTERS, INC. OPERATION MANUAL

Reduce pressure zone device suitable for high and medium hazard rated applications Flanged end connections

Installation, Operation and Maintenance Manual for Back Pressure Regulator

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats

WHEATLEY Series 500 Swing Check Valve

Reduce pressure zone device suitable for high and medium hazard rated applications BSP screwed connections

DOUBLE ACTING ALTITUDE VALVE. INSTRUCTIONS Installation - Operation - Inspection - Maintenance

Operation Manual. Diaphragm Sensed Gas Pressure Regulators

Installation Troubleshooting Maintenance Instructions Installation / Start-up

TECHNICAL DATA CAUTION

Operation Manual Air Saver Unit ASV5000 Series

Mounting and operating instructions EB 2530 EN. Self-operated Pressure Regulator. Pressure Reducing Valve Type M 44-2

WHEATLEY WHEATLEY SERIES 500 SWING CHECK VALVE. Installation, Operation and Maintenance Manual

Installation and operating manual. Pneumatic control station LK product no: PCS 1-10

Pressure Reducing Control Valve w/ Hydraulic Check Feature

MODEL 200 KNIFE GATE VALVES INSTALLATION & MAINTENANCE MANUAL

TECHNICAL DATA. the Viking Pilot Pressure Regulating Valve 1 Model A-1 Speed Control Assembly: OBSOLETE. the Viking Speed Control Assembly 1

1800C and 1800C-HC Series Service Regulators

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves.

MWEA MAINTENANCE SEMINAR SPECIALTY VALVES POWER GLOBES

SRV66 Sanitary Pressure Reducing Valve

VALVCHEQ BACKFLOW PREVENTERS FIGURE RP03

Pressure Dump Valve Service Kit for Series 2300 Units

Regulator from 1800 B series

Halsey Taylor Owners Manual STOP!

Halsey Taylor Owners Manual 4410 Freeze Resistant Tubular Fountain STOP!

Apollo Standard Port, Full Port & One Piece Flanged Ball Valves Installation, Operation, & Maintenance Manual

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats Installation and Maintenance Instructions

RS(H)20, 25 USER MANUAL

Testing Procedures & Trouble Shooting Guide Reduced Pressure Zone Assembly (1/2, 3/4", 1, 1 1/4, 1 1/2" & 2 )

LRS(H)4 Pressure-Reducing Regulator User Manual

KBV21i and KBV40i Air Actuated Boiler Blowdown Valves

VALVCHEQ BACKFLOW PREVENTERS FIGURE RP03

RHPS Series RD(H)F40 User Manual. Read the complete manual before installing and using the regulator.

TECHNICAL DATA. than the water inlet pressure to the concentrate

TECHNICAL DATA. Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve.

Installation Instructions

BUTTERFLY VALVES Series 800

Anderson Greenwood Series 93 Positive Pressure POSRV Installation and Maintenance Instructions

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

OWNER S TECHNICAL MANUAL

TECHNICAL DATA Q= C. Table 1 - Specifications

Speed control assembly model A-1

A3S Bellows Sealed Stop Valve Installation and Maintenance Instructions

SRV2S Pressure Reducing Valve

Types S100K and S102K Pressure Regulators

TECHNICAL DATA. Q = C v P S

Filling valves AL, ALM Series Automatic filling units ALOMDIW, ALOMDNW Series

RD(H)20/25 Pressure-Reducing Regulator User Manual

64 Series Pressure Reducing Regulators

Hi-Force Limited Prospect Way Daventry Northants NN11 8PL United Kingdom Tel: +44(0) : Fax: +44(0) : Website:

Product Manual. Description. Specifications. CVS Type 1301F and CVS Type 1301G Regulator. Introduction

DS06D,G Dial Set Pressure Regulating Valve

TEST SPECIFICATION NYT-909-C

D05T Compact Design Pressure Regulating Valves

Combination Air Valve

Type ACE95jr Tank Blanketing Valve

D05 Pressure Regulating Valves

Float Operated Level Controllers

1200B2 Series Service Regulators. Instruction Manual

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

Pressure Dump Valve Service Kit for Series 3000 Units

TESCOM 50-4X Series Safety, Installation & Start-Up Procedures

TECHNICAL DATA ACCELERATOR MODEL E-1

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model 50 Systems Outfitted with ABM-725 Monitor C O M P A N Y

Transcription:

Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow Model: FP 450-80 Installation Operation Maintenance PAGE 1 OF 5

1. Safety First BERMAD believes that the safety of personnel working with and around our equipment is the most important consideration. Please read all safety information below and from any other relevant source before attempting to perform any maintenance function. Comply with all approved and established precautions for working with your type of equipment and/or environment. Authorized personnel should perform all maintenance tasks. Prior to performing a procedure, read it through to the end and understand it. If anything is not clear, ask the appropriate authority. When performing a procedure, follow the steps in succession without omission 2. Description The Model 450-80 Level Control Valve, One Way Flow is an automatic control valve designed to control the high water level in reservoirs and tanks without the need for external control devices such as floats, etc. It is a pilot controlled, hydraulically operated, diaphragm actuated globe valve design. The valve diaphragm is line pressure activated, controlled by a 3-way Level pilot valve to open or close. 3. Approvals BERMAD 400 Valve is Lloyd s Register and ABS approved when installed with specific components & accessories. Refer to the current Directory. Consult the manufacturer for any component approval recently to appear in the fire protection equipment directory. 4. Installation Installation Instructions 4.1 Allow enough room around the valve assembly for any adjustments and future maintenance/disassembly work. 4.2 Thoroughly flush the pipeline to remove any dirt, scale, debris etc. Failure to do this may result in the valve being inoperable. 4.3 Isolation valves A and B should be installed upstream and downstream of the main valve to allow maintenance. Figure 1: Installation Drawing B A PAGE 2 OF 5

4.4 Install the valve in the pipeline with the valve flow arrow on the body casting in the proper direction. Use the lifting eye provided on the main valve cover for raising and lowering the valve. It is highly recommended to install a strainer upstream from the 450-80 valve, for best performance, install the valve horizontally with the cover up. 4.5 Prepare a 1" female threaded "Hydrostatic level sensing port"; consist of a full-port block valve, at a "stillpoint" at the bottom of the reservoir. Note: The drainage pipe might provide this "still-point". 4.6 A sensing line with at least ½ tube of stainless steel should be connected from the "level sensing port" at the bottom of the reservoir to the altitude pilot valve sensing port which is located on the lower side of the sensing diaphragm see (2) on figure 2. 4.7 This placement will ensure accurate static pressure sensing. If possible, the sense line should be sloped upwards from the altitude pilot valve toward the reservoir to minimize air pockets from forming in the pilot. 4.8 After installation, carefully inspect/correct any damaged accessories, piping, tubing, or fittings. 5. Startup 5.1 Confirm that the supply ball valve is open and that selector valve [4] is directing the pilots to valve control chamber (according to the flow arrow on the handle). 5.2 Open fully the upstream and the downstream isolating valves & confirm that the supply pressure is typical. 5.3 Fill up the reservoir until the level reaches its desired shut-off level. 5.4 Vent air from the valve's control loop & the pilot sensing chamber by loosening tube fittings at the highest points, allowing all air to bleed. Retighten the tube fittings eyebolts. 5.5 The valve is factory calibrated, the closing setting level is marked on a sticker placed on the pilot valve. 5.6 Allow the valve to open by ensuring reservoir level is approx 1 meter lower then the setting. Confirm the valve closes as level reaches the closing set level. 5.7 Note: the altitude change can be simulate by connecting an accurate gauge to the sensing line, close the sensing block valve (para. 4.5) and open connecting fitting on the sensing line to bleed the water column. The valve shall remains closed until water level drop approx one meter (three foot) below the closing set level. Figure 2: Operation Drawing C C PAGE 3 OF 5

6. Calibration 6.1 For changing the closing level setting, perform the below procedure: 6.2 Turn selector valve [4] to "Close" position (flow arrow on the handle directing valve upstream to the valve control chamber), verify that the valve is now closed. 6.3 Slowly turn the pilot valve adjusting screw Clock-Wise to the maximum spring compression. 6.4 Simulate reservoir level to 30cm (1 foot) below the desired upper (closing) level. 6.5 Disconnect the tube connected to the pilot port [C]. 6.6 Unlock the pilot valve-locking nut and turn slowly the adjusting screw Counter-Clock-Wise until water starts draining through port [C]. Re-turn the pilot adjusting screw Clock-Wise until draining is stopped. 6.7 Raise (or simulate) the reservoir level to the desired closing level. The drain from port [C] should restart. 6.8 Re-connect the tube to the pilot port [C] & rotate selector valve [4] to "Open" position. 6.9 Lock the pilot valve locking nuts. 6.10 To increase opening speed turn the pilot integral needle valve Counter-Clock-Wise. 7. Maintenance and Inspection Test 7.1 Maintenance Schedule The following procedure suggestions are a maintenance guide. These procedure suggestions will vary depending on the type of fluid and operation conditions. Description Clean filter Seat inspection Seal inspection Indicator Stem freedom of rotation Valve freedom of movement Sealing Needle valve operation Pressure gauge Seat damage Inspect and/or replace diaphragm heavy duty Inspect and/or replace diaphragm light duty Norm Biannually or longer Semi 3 years 5 years 7.2 Field Maintenance Instructions Bermad valves require no lubrication, no packing tightening, and require a minimum of maintenance. A periodic inspection schedule should be established to determine how the flow, the erosion, the dissolved minerals and the suspended particles are affecting the valve. After about three years of operation, replacement of important parts and diaphragm is recommended. Remove the valve cover, clean the valve body from sediments, clean the control tubing entry holes, and install a new main valve diaphragm and replace pilot valve other Elastomers. Filter cleaning - The filter should be cleaned manually every time the valve is opened for internal inspection. PAGE 4 OF 5

8. Trouble-Shooting Symptom Probable Cause Action Valve Fails To Open Insufficient inlet pressure 3-way Selector valve closed Reservoir is full. Compression. Check/create inlet pressure. Turn the 3-way valve to automat position. Open Check reservoir water level. Insufficient pilot spring Turn the adjusting screw CW on pilot. Valve Fails To Close Valve Fails To Regulate (Not Accurate) Filter (4) blocked Debris trapped in main valve. Diaphragm in main valve is leaking Altitude Pilot valve is not well calibrated Filter (4) blocked Sensing line blocked. Level Pilot valve not properly adjusted Remove filter cap and screen to clean. Open ball. Inspect valve interior. Remove the cover. Check the seat and disc seal. Refer also to Model FP 400 data. Test for leakage. Close main isolating valve. Open valve cover and check diaphragm elastomer. Readjust according to paragraph 6 Remove filter cap and screen to clean. Open ball. Check and clean. Readjust pilot valve according to paragraph 6. PAGE 5 OF 5