SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Knob Adjustment)

Similar documents
SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Dial Adjustment)

Dri-Line Mk3 Monnier Compressed Air Drain Trap

Dri-Line Mk2 Spirax-Monnier Compressed Air Drain Trap

TA10A and TA10P Steam Tracing Temperature Control Valves Installation and Maintenance Instructions

DF1 and DF2 Diffusers

TP1 and TP2 Temporary Cone Shaped Strainers

TSS21 Sealed Thermostatic Steam Tracer Trap

PV4 and PV6 Piston Valves

Fig 12, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

DCV10 Stainless Steel Disc Check Valve for use with Condensate Pumps

Fig 1, Fig 12, Fig 13, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

MF2M Monnier Miniature Compressed Air Filter

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators

BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications

CP10 Sensor Installation and Maintenance Instructions

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

DCV1, DCV3 and DCV3LT Disc Check Valves Installation and Maintenance Instructions

FV Flash Vessel Installation and Maintenance Instructions

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions

Type 130 and HL10 'Safeguard High Limit Control' Installation and Maintenance Instructions

KBV21i and KBV40i Air Actuated Boiler Blowdown Valves

APT14, APT14HC and APT14SHC Spares 2

IX1 Spirax-Monnier International Compressed Air Filter Installation and Maintenance Instructions

CVS10 Sanitary Check Valves

ML3M Monnier Miniature Compressed Air Lubricator

DCV6 Disc Check Valve

Manual Actuated Boiler Blowdown Valves

MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection

AVM7 Stainless Steel Thermostatic Air Vent

AVC32 Carbon Steel Air Vent for Steam Systems

BCV31 DN40 - Blowdown Control Valve

Spirax Compact FREME Flash Recovery Energy Management Equipment

IFTGS14 Ball Float Steam Trap ½" and ¾" with Integral Spiratec Sensor

SA Control Valve types: BM, BMF, BX, SB, NS, KA, KB, KC (Normally open) BMRA, BMFRA, BXRA, SBRA, NSRA, KX, KY (Normally closed)

SRV66 Sanitary Pressure Reducing Valve

AE14 Automatic Air Vents for Liquid Systems Installation and Maintenance Instructions

AE30 Automatic Air Eliminators / Air and Gas Vents for Liquid Systems

HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions

FTGS14 Ball Float Steam Trap DN15 (½") to DN25 (1")

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors

Airodyn, BRair and BRoil Compressed Air Drain Traps

TW Temperature Control Valve

Fig 3, 7, 33, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers

BTM7, BTS7 and BTS7.1 Stainless Steel Thermostatic Clean Steam Traps

MPC1M, MPC2M and MPC2AM Monnier High Efficiency Compressed Air Filter / Regulators

M33F ISO, M33S ISO and M33V ISO Ball Valves Installation and Maintenance Instructions

S and SF Inverted Bucket Steam Traps

IP2M, IP2AM and IP2DM Monnier International Compressed Air Filter/ Regulators

BCV31 DN20 - Blowdown Control Valve

CS10-1 Stainless Steel Clean Steam Separator

Vane Flow Switches Colima FLU Series

BT6-B Sanitary Balanced Pressure Thermostatic Steam Trap

BRV71 and BRV73 Pressure Reducing Valves

M10HTi ISO Tobacco Ball Valve Screwed, SW, BW and Flanged versions

SRV2S Pressure Reducing Valve

BPT13 Balanced Pressure Thermostatic Steam Traps

CA44, CA44S, CA46 and CA46S Air and Gas Traps

PC10HP Pipeline Connector (ASME 600)

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats

MFP14-PPU (Vented) Automatic Packaged Pump Units

Fig 7, 33, 33.1, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers Installation and Maintenance Instructions

QuickHeat TM Packaged Heat Exchanger Solutions

M70i ISO and M80i ISO Stainless Steel Ball Valves for Sanitary Systems Installation and Maintenance Instructions

BDV1 and BDV2 Blowdown / Depressurisation Valves

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats Installation and Maintenance Instructions

Spirax SafeBloc TM DBB3 Double Block and Bleed Bellows Sealed Stop Valve. 1. Safety information. 2. General product information. 3.

TDC46M, TDS46M and UTDS46M Thermodynamic Steam Traps with Maintainable Seat Installation and Maintenance Instructions

CA10S, CA14 and CA14S Air and Gas Traps

FT53, IFT53, FT54, IFT54, FT57 and IFT57 Ball Float Steam Traps - DIN

M111 Spiraflo Transducer

STERI-TROL Clean Service 'S' Series Two-port Control Valves DN15 (½") to DN100 (4")

LP31 Level Probe. 1. Safety information. 2. General product information. 3. Installation. 4. Wiring. 5. Maintenance

BDV60 Blowdown Vessel Installation and Maintenance Instructions

Thermocirc Installation and Maintenance Instructions

Colima TOR Magnetic Level Switches

BCVi43 Blowdown Control Valve

BSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions

LP10-4 Level Probe. 1. Safety information. 2. General product information. 3. Installation. 4. Wiring. 5. Maintenance IM-P402-92

SRV461S and SRV463S Stainless Steel Direct Acting Pressure Reducing Valves

AE50S Automatic Air and Gas Vent for Liquid Systems Installation and Maintenance Instructions

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

A3S Bellows Sealed Stop Valve Installation and Maintenance Instructions

AVS32 Stainless Steel Air Vent for Steam Systems Installation and Maintenance Instructions

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

PC3000, PC3001 and PC4000, PC4001 Pipeline Connectors

FT43, FT44, FT46 and FT47 Ball Float Steam Traps Installation and Maintenance Instructions

TD45 Thermodynamic Steam Trap Installation and Maintenance Instructions

RJ check valves Installation and Maintenance Instructions

BTD52L Thermodynamic Steam Trap Installation and Maintenance Instructions

Fig 1, Fig 12, Fig 13, Fig 14, Fig 16 and Fig 16L Strainers Installation and Maintenance Instructions

SCA Series Inverted Bucket Steam Traps

FT16 Ball Float Steam Trap Installation and Maintenance Instructions

CA16 and CA16S-14 Air and Gas trap Installation and Maintenance Instructions

UBP32 Sealed Balanced Pressure Thermostatic Steam Trap for use with PC_ Pipeline Connectors Installation and Maintenance Instructions

1. General safety information. 2. General product information. 3. Installation. 4. Commissioning. 5. Operation. 6. Maintenance. 7.

FTC62 and FTS62 Ball Float Steam Traps Installation and Maintenance Instructions

STD Spray Type Desuperheater

Standard Pressure Powered Pump Packaged Units to Size 3 x 2 Type PPEC, PTC & PTF with vented and ASME coded receivers

Transcription:

3810050/5 IM-P381-01 CH Issue 5 SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Knob Adjustment) Installation and Maintenance Instructions 1. Safety information 2. Use 3. Installation 4. Pre-commissioning checks 5. Display adjustment 6. Commissioning 7. Decommissioning 8. Maintenance and spare parts IM-P381-01 Printed in the CH UK Issue 5 Copyright 2006 1

1. Safety information Safe operation of these products can only be guaranteed if they are properly installed, commissioned, used and maintained by qualified personnel (see Section 1.11) in compliance with the operating instructions. General installation and safety instructions for pipeline and plant construction, as well as the proper use of tools and safety equipment must also be complied with. These product are designed and constructed to withstand the force encountered in normal use. Use of these products for any purpose other than as temperature controllers could cause injury or fatality to personnel. 1.1 Intended use Referring to the Installation and Maintenance Instructions, name-plate and Technical Information Sheet, check that the product is suitable for the intended use/application. The products comply with the requirements of the European Pressure Equipment Directive 97 / 23 / EC and fall within category 'SEP'. It should be noted that products within this category are required by the directive not to carry the mark. i) The products have been specifically designed for use on steam, water, compressed air and other non-hazardous fluids which are in Group 2 of the above mentioned Pressure Equipment Directive. The products use on other fluids may be possible but, if this is contemplated, Spirax Sarco should be contacted to confirm the suitability of the product for the application being considered. ii) Check material suitability, pressure and temperature and their maximum and minimum values. If the maximum operating limits of the product are lower than those of the system in which it is being fitted, or if malfunction of the product could result in a dangerous overpressure or overtemperature occurrence, ensure a safety device is included in the system to prevent such over-limit situations. iii) Determine the correct installation situation and direction of fluid flow. iv) Spirax Sarco products are not intended to withstand external stresses that may be induced by any system to which they are fitted. It is the responsibility of the installer to consider these stresses and take adequate precautions to minimise them. v) Remove protection covers from all connections and protective film from all name-plates, where appropriate, before installation on steam or other high temperature applications. 1.2 Access Ensure safe access and if necessary a safe working platform (suitably guarded) before attempting to work on the product. Arrange suitable lifting gear if required. 1.3 Lighting Ensure adequate lighting, particularly where detailed or intricate work is required. 1.4 Hazardous liquids or gases in the pipeline Consider what is in the pipeline or what may have been in the pipeline at some previous time. Consider: flammable materials, substances hazardous to health, extremes of temperature. WARNING: The sensor must not be subjected to mercury or ammonium salts. 2 IM-P381-01 CH Issue 5

1.5 Hazardous environment around the product Consider: explosion risk areas, lack of oxygen (e.g. tanks, pits), dangerous gases, extremes of temperature, hot surfaces, fire hazard (e.g. during welding), excessive noise, moving machinery. 1.6 The system Consider the effect on the complete system of the work proposed. Will any proposed action (e.g. closing isolation valves, electrical isolation) put any other part of the system or any personnel at risk? Dangers might include isolation of vents or protective devices or the rendering ineffective of controls or alarms. Ensure isolation valves are turned on and off in a gradual way to avoid system shocks. 1.7 Pressure systems Ensure that any pressure is isolated and safely vented to atmospheric pressure. Consider double isolation (double block and bleed) and the locking or labelling of closed valves. Do not assume that the system has depressurised even when the pressure gauge indicates zero. 1.8 Temperature Allow time for temperature to normalise after isolation to avoid the danger of burns. 1.9 Tools and consumables Before starting work ensure that you have suitable tools and/or consumables available. Use only genuine Spirax Sarco replacement parts. 1.10 Protective clothing Consider whether you and/or others in the vicinity require any protective clothing to protect against the hazards of, for example, chemicals, high / low temperature, radiation, noise, falling objects, and dangers to eyes and face. 1.11 Permits to work All work must be carried out or be supervised by a suitably competent person. Installation and operating personnel should be trained in the correct use of the product according to the Installation and Maintenance Instructions. Where a formal 'permit to work' system is in force it must be complied with. Where there is no such system, it is recommended that a responsible person should know what work is going on and, where necessary, arrange to have an assistant whose primary responsibility is safety. Post 'warning notices' if necessary. 1.12 Handling Manual handling of large and/or heavy products may present a risk of injury. Lifting, pushing, pulling, carrying or supporting a load by bodily force can cause injury particularly to the back. You are advised to assess the risks taking into account the task, the individual, the load and the working environment and use the appropriate handling method depending on the circumstances of the work being done. IM-P381-01 CH Issue 5 3

1.13 Residual hazards In normal use the external surface of the product may be very hot. If used at the maximum permitted operating conditions the surface temperature of some products may reach temperatures of 215 C (419 F). Many products are not self-draining. Take due care when dismantling or removing the product from an installation (refer to 'Maintenance instructions'). WARNING: This product contains kerosene which is highly inflammable. 1.14 Freezing Provision must be made to protect products which are not self-draining against frost damage in environments where they may be exposed to temperatures below freezing point. 1.15 Disposal Unless otherwise stated in the Installation and Maintenance Instructions, this product is recyclable and no ecological hazard is anticipated with its disposal providing due care is taken. 1.16 Returning products Customers and stockists are reminded that under EC Health, Safety and Environment Law, when returning products to Spirax Sarco they must provide information on any hazards and the precautions to be taken due to contamination residues or mechanical damage which may present a health, safety or environmental risk. This information must be provided in writing including Health and Safety data sheets relating to any substances identified as hazardous or potentially hazardous. 2. Use It is important that these self-acting temperature control systems are only used with Spirax Sarco control valves as indicated in Table 1: Table 1 Self-acting temperature control system Control valve size Control valve type SA121, SA123 SA128, SA122 All 2-port ¾" to 2" TW ½" to 1" 2-port ¾" and 1" TW SA1219 3" and 4" TW 4 IM-P381-01 CH Issue 5

3. Installation These product are designed and constructed to withstand the force encountered in normal use. Use of these products for any purpose other than as temperature controllers could cause injury or fatality to personnel. WARNING: The sensor must not be subjected to mercury or ammonium salts. Check that the control system supplied is of the temperature range required. It is important that the whole of the temperature sensing area of the sensor is fully immersed in the fluid being controlled, see Figure 1. The sensors can be held in a screwed nipple by means of a compression ring. Screw the nipple into the boss provided on the plant, thread the union nut and compression ring over the sensor. Insert the sensor fully into the nipple and tighten up the nut and compression ring. Do not overtighten. Where the sensors are used in conjunction with a pocket, either to allow easy withdrawal or as a protection against corrosion, the separate screwed nipple is dispensed with and the union nut and compression ring attached directly to the top of the pocket. Therefore insert the pocket in place of the screwed nipple. When using a special long pocket with the SA122 or SA123 sensor, the screwed nipple, compression ring and nut are dispensed with and a rubber sealing bung provided, which is fitted over the capillary and slid into place to secure the sensor into the pocket. Screw the pocket into place, then feed the sensor bulb to the bottom of the pocket, using the rubber bung to seal the top. When using a pocket it is advisable to fill the gap between the pocket and the sensor with a heat conducting medium such as oil, but when using a special long pocket in conjuction with the SA122 or SA123 sensors it should not be filled above the top of the sensor. The adjustment mechanism should not be subjected to an ambient temperature above 50 C (122 F) or below -35 C (-31 F). The capillary tube between the sensor and the valve must be run and supported in such a way that it will not become damaged. Avoid all sharp bends. See Sections 5 and 6 'Display adjustment' and 'Commissioning'. Fig. 1 Correct installation Incorrect installation IM-P381-01 CH Issue 5 5

4. Pre-commissioning checks These temperature control systems have been designed and manufactured to the highest industrial standards. In order that they function correctly, please observe the following points and then proceed with the 'Display adjustment' in Section 5 for adjusting to the desired set temperature. Factory temperature setting In order to avoid accidental damage due to exposure of extreme temperatures, the unit is factory adjusted to its highest set temperature. This value will vary according to the data shown in Table 2. Overtemperature protection In the event that the overtemperature protection is exceeded by the values shown, serious damage will occur and the warranty will be invalidated. Before commissioning this unit, please ensure that the system temperature cannot exceed the overtemperature protection value. Table 2 Metric Self-acting temperature control system Range no. Temperature adjustment range ( C) Factory setting 1-15 to +50 50 C Overtemperature protection SA121, SA1219 and SA123 2 +40 to +105 105 C 55 C over set 3 +95 to +160 160 C value to 190 C SA122 1-20 to +120 120 C maximum 2 +40 to +170 170 C (215 C maximum SA128 Imperial Self-acting temperature control system 1-20 to +110 110 C for the SA123) 2 +40 to +170 170 C Range no. Temperature adjustment range ( F) Factory setting 1 +5 to +125 125 F Overtemperature protection SA121, SA1219 and SA123 2 +105 to +225 225 F 130 F over set 3 +205 to +325 325 F value to 374 F SA122 1-5 to +240 240 F maximum 2 +106 to +340 340 F (420 F maximum SA128 1-5 to +230 230 F for the SA123) 2 +106 to +340 340 F 6 IM-P381-01 CH Issue 5

5. Display adjustment The adjustment head provided (Figure 2), enables the set temperature to be raised or lowered, once the drive screw 'C' has been engaged. To make any adjustment the blue knob is turned clockwise to lower the temperature, and anticlockwise to increase it. After setting, if desired, the drive screw can be disengaged by prising out the black plastic cap 'B' with a small flat bladed screw driver, via the slot provided, remove the 3 mm A / F allen headed drive screw 'C' and stow in the knob, then replace the black cap. The adjustment knob will now spin freely without changing the temperature setting. Fig. 2 Adjustment head (knob) B C 6. Commissioning Reference Figure 3, opposite, for the following instructions:- Adjust to the desired setting by turning the knob clockwise to lower the temperature and anticlockwise to increase it. After setting the plant to work, compare the thermometer reading with the scale reading on the temperature control reading. This may be found to differ by a few degrees. If precise indication is required it can be adjusted by resetting the scale as follows:- 1. Loosen the screw holding the sleeve scale in place and adjust the sleeve by rotating it until the scale reading matches the actual temperature. 2. Tighten the screw until it holds the scale firmly in place without over tightening (it only needs a light touch as it is for location only). Knob Sleeve scale Screw Fig. 3 IM-P381-01 CH Issue 5 7

7. Decommissioning As a safety precaution, if the unit is to be decommissioned, it is important to reset the unit to its maximum (factory) setting before reinstalling. 8. Maintenance and spare parts There are no serviceable parts. 8 IM-P381-01 CH Issue 5