VB-7213 Series. Application. Features. Applicable Literature. 1/2" to 2" Screwed NPT Stem Up Open, Two-Way Valves General Instructions

Similar documents
VB-7273 Series. Application. Features. Applicable Literature

VB-7211 Series. Application. Features. Applicable Literature. 1/2" to 1-1/4" Union End NPT Stem Up Open, Two-Way Valves General Instructions

VBS-9263 Series. Application. Features. Applicable Literature

VB-7263 Series. Application. Features. Applicable Literature

VB-7212 Series. Application. Features. Applicable Literature. 5/8" O.D., 45 SAE Flared Stem Up Open, Two-Way Valves General Instructions

VB-7323 Series. Application. Features. Applicable Literature. 1/2 to 2 Screwed NPT Three-Way Diverting Valves General Instructions

A t. VB-7323 Series. Application. Features. Applicable Literature. l/2 to 2 Screwed NPT SIEBE

VB Series. Application. Features. Applicable Literature. 1/2 to l-1/4 Union End NPT Stem Up Open, Two-Way Valves General Ins tructions

TECHNICAL INSTRUCTIONS Iron Body Series 597 SI

Technical Instructions

Pressure Independent Control Series

V43 Pressure Actuated Water Regulating Valve

Application Worksheet

2-port seat valves PN25 with externally threaded connections

MZX. Three-Port Seat Valves SPECIFICIATIONS AND GUIDE TO SELECTION

3-way control valves VK 3

2-port and 3-port valves PN 16

Seated valve for steam (PN 25)

V48 Series 3-Way Pressure-Actuated Water-Regulating Valves With Union Fittings

Seated valves (PN 6) VL 2 2-way valve, flange VL 3 3-way valve, flange

Two-port valves, male threaded, PN25

Seated valves VRB 3, VRG 3

Seated valves (PN 16) VF 2 2-way valve, flange VF 3 3-way valve, flange

TECHNICAL DATA. Page 1 of 12

V46 Series 2-Way Pressure-Actuated Water-Regulating Valves With Union Fittings

2-Port Seat Valves with Flange, PN 16

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

V311. Venta. Three-way Plug Valve, Flanged PN 16

TECHNICAL DATA. Q = C v P S

Simple Set Max. Pressure Independent Control Valves 2 Way 2-1/ /09/18

BGA158 Series CE Approved Class A Shutoff Gas Valve

V146 Series 2-Way Pressure-Actuated Water-Regulating Valves

TECHNICAL DATA CAUTION

2-Port Seat Valves with Flange, PN 16

V248 Series 3-Way Pressure-Actuated. Water-Regulating Valves for High-Pressure

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

Dual Solenoid Gas Valve Installation

TECHNICAL DATA. Q = C v P S

D05 Pressure Regulating Valves

TECHNICAL DATA. Pressure Regulation 531a. April 24, 2009

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

G96 Series BASOTROL Dual Operator Valve

The Shand & Jurs Model Vapor Guard Tank Blanketing Valve

Seated valve for steam (PN 25) VFS 2 2-way valve, flange

TECHNICAL DATA. Q= Cv S

GM-7000 Series CE Approved Gas Control Valve

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

VZL valve - 2/3/4-way

Wafer Check Valve. Contents. User s Manual. (1) Be sure to read the following description of our product warranty 1

Model GP PRESSURE REDUCING VALVE Installation & Operation Manual

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity

Simple Set. Pressure Independent Control Valves 2 Way 1/2-2

CASH VALVE TYPE KP BACK PRESSURE VALVES

TECHNICAL DATA. Q = C v P S

T208VR Series Tank Blanketing Vacuum Regulator

TECHNICAL DATA. Q = C v P S

BGA158, BGA171 and BGA110 Series Shutoff Gas Valve

BGA158 Series CE Approved Class B Shutoff Gas Valve

V248 Series 3-Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants

TECHNICAL DATA. Q = C v P S

Series 44 Self-operated Pressure Regulators. Type 44-0 B Pressure Reducing Valve. ANSI version

2.0 INSTALLATION & SERVICE

D05T Compact Design Pressure Regulating Valves

The valves are used in combination with AMV(E) 130/140, AMV(E) 130H/140H and AMV(E) 13 SU actuators. DN k VS

! WARNING. Model PFC-1-G (direct acting) PFC-1-GR (reverse acting) Modulating Pneumatic Liquid Level Controls INSTRUCTION MANUAL MM-110B

Bermad Pressure Reducing. Model: 42T

DS05C,D,G Dial Set Pressure Regulating Valves

Design and Application Details MICRO-RATIO Valves

BGC258 Series BASOTROL Gas Valve

Tank Blanketing Pressure Regulators RHPS Series

Cash Valve TYPE KP PILOT OPERATED BACK PRESSURE VALVE. ISSUED - DECEMBER 2000 CAVMC-0518-US-0208 ISO 9001 Certified

The Hoffman Specialty Series 2000 consists of main

Instruction Manual 742 5/1/2009. Eclipse Ratio Regulators ES Series Version 1

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

WaterSource Heat Pump Hose Kit Performance Specification-Summary

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves.

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

Ball Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300 DN 40, 50, 65

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

2-port and 3-port seat valves, PN16

Cash Valve TYPE G-4 PILOT OPERATED PRESSURE REDUCING REGULATOR FOR STEAM, AIR AND GASES. ISSUED - MARCH 2001 CAVMC-0512-US-0208 ISO 9001 Certified

Series V48. 3-Way Pressure Actuated Modulating Valves. Product Bulletin. Features. Pressure balanced design. Free movement of all parts

3-port seat valves with externally threaded connection, PN 16

29 SERIES - SAFETY VALVE

TECHNICAL DATA. Page 1 of 8. model f /2 (dn40) & 2 (dn50)

KECKLEY INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS TYPE NO. 7 FLOAT VALVE

Two-port seat valves

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series

DS MZ, MZF, MJF THREE-PORT SEAT VALVES

shutoff valves 900 Series psig Manual Shutoff Valves

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

TECHNICAL DATA OBSOLETE

Operator: Save these instructions for future use!

G92 Series BASOTROL Automatic Pilot Gas Valve

36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS

The valves are used in combination with AMV(E) 130/140, AMV(E) 130H/140H and AMV(E) 13 SU actuators. DN k VS

Pressure Regulator B-95

Operation Manual Piston Sensed Gas Pressure Regulators

94270 Vapor Guard Tank Blanketing Valve Vapor Guard Tank Blanketing Valve What is Tank Blanketing? Features How does it work?

Transcription:

VB-7213 Series 1/2" to 2" Screwed NPT Stem Up Open, Two-Way Valves General Instructions Application VB-7213 series single seat, stem up open, two-way valves control water from 20 to 281 F (-7 to 138 C) or steam to 281 F (138 C) maximum in heating or air conditioning systems. They are used for two-position or proportional control applications. Valve assemblies require an actuator and a valve linkage. A large selection of factory assembled combinations is available. Consult the TAC Valve Products Catalog, F-27384. Danger: Do not use for combustible gas applications. The VB-7213 series valve packings are not rated for combustible gas applications, and if used in these applications, gas leaks and explosions could result. Features Valve sizes 1/2" to 2" 250 psig pressure rating per ANSI Standards (B16.15 1985) for screwed cast bronze bodies Spring-loaded TFE packing American Standard Taper Pipe Thread (NPT) connections Applicable Literature TAC Valve Products Catalog, F-27384 TAC Cross-Reference Guide, F-23638 TAC Reference Manual, F-21683 TAC Application Manual, F-21335 Control Valve Sizing, F-13755 Valve Selection Chart for Steam, F-11366 Valve Selection Chart for Water, F-11080 EN-205 Water System Guidelines, F-26080 Printed in U.S.A. 8-08 Copyright 2008 TAC All Rights Reserved. F-26075-2

SPECIFICATIONS Table-1 Specifications/Models. Specifications Valve Body Series VB-7213-0-4-P Service Chilled or Hot Water and Steam Flow Characteristics (Figure-1) Equal Percentage Action Stem Up Open Sizes 1/2" to 2" Type of End Fitting NPT Body Seat Valve Stem Materials Plug Packing Disc ANSI Pressure Class (Figure-2) Close-off Pressure Rating Bronze Bronze Stainless Steel Brass Spring-loaded TFE EPDM 250 (up to 400 psig below 150 F) a Maximum Inlet Pressure, Steam 35 psig (241 kpa) Allowable Control Media Temperature 20 to 281 F (-7 to 138 C) 35 psi (241 kpa) Max. for Normal Life Allowable Differential Pressure for Water b (refer to Cavitation Limitations on Valve Pressure Drop on page 7) Allowable Differential Pressure for Steam b 20 psi (138 kpa) Valve Size C v Rating k vs Rating c Complete Valve Body Part Number 1/2" 3/4" 0.4 0.3 VB-7213-0-4-1 1.3 1.1 VB-7213-0-4-2 2.2 1.9 VB-7213-0-4-3 4.4 3.8 VB-7213-0-4-4 5.5 4.8 VB-7213-0-4-5 7.5 6.5 VB-7213-0-4-6 1" 10 8.7 VB-7213-0-4-7 14 12 VB-7213-0-4-8 1-1/4" 20 17 VB-7213-0-4-9 1-1/2" 28 24 VB-7213-0-4-10 2" 40 35 VB-7213-0-4-11 a Do not apply above pressure rating to piping system. b Maximum recommended differential pressure in open position. Do not exceed recommended differential pressure (pressure drop) or integrity of parts may be affected. Exceeding maximum recommended differential pressure voids product warranty. c k vs = m 3 /h (ΔP = 100 kpa) C v = k vs x 1.156 The close-off pressure rating is dependent on the size of the valve, valve linkage, and actuator. Consult the TAC Valve Prodcuts Catalog, F-27384, for close-off ratings. 2 Copyright 2008 TAC All Rights Reserved. F-26075-2

Normal Position of Valve Assembly For a valve assembly (valve, linkage, and actuator) to have a normal (spring return) position, the actuator must be of the spring return type. See Table-2 for spring return position of valve assemblies. Table-2 Required Compatible Actuators/Linkages. Actuator Series Required Valve Linkage Normal Position MA-318, MA-418, MA-419 AV-391 N.O. or N.C. MA-5210, MA-5211, MA-5213 AV-7600 a Normally Open MC-351, MC-431, MC-4311, MC5-4311 AV-393 None MF-5413, MF-5513 AV-7600 a Normally Open MF-22203, MF-22303, MF-22323 MF-63103, MF-63123 Included w/actuator None MK-2690 AV-7400 MK-4601, MK-4611, MK-4621 AV-401 Normally Open MK-6601, MK-6611, MK-6621 AV-430 MM-400, MMR-400 AV-630 or None MM-500, MMR-500 AV-630-010 N.O. or N.C. MP-361, MP-367, MP-465, MP5-4651 Normally Closed AV-391 MP-371, MP-377, MP-475, MP5-4751 Normally Open MP-381, MP-382, MP-387, MP-485, MP-486, MP-4851, MP5-4851 AV-393 None MP-5210, MP-5211, MP-5213 AV-7600 a MP-5410, MP-5411, MP-5413 MP-5513 Normally Open AV-7600 & AV-601 MPR-5610, MPR-5611, MPR-5613 MPR-5713 MS-22353 Included w/actuator None a High ambient temperatures with high media temperatures in the valve may require the use of AV-601 in addition to AV-7600. See General Instructions for AV-7600 (F-26235) and AV-601 (F-19069) for details. Flow Characteristics All valves have modified equal percentage flow characteristics. That is, for equal increments of valve stem stroke, the change in flow rate with respect to valve stroke may be expressed as a constant percent of the flow rate at the time of the change. The change of flow rate with respect to valve stroke is relatively small when the valve plug is near the valve seat and relatively high when the valve plug is nearly wide open. See Figure-1 for typical modified equal percentage flow characteristics of VB-7213 series valve bodies. 100% 90% 80% 70% Flow 60% 50% 40% 30% 20% 10% 0% 0% 10% Closed 20% 30% 40% 50% Stroke 60% 70% 80% 90% 100% Open Figure-1 Typical Modified Equal Percentage Flow Characteristics. F-26075-2 Copyright 2008 TAC All Rights Reserved. 3

Rangeability Rangeability is the ratio of rated flow to the minimum controllable flow through a valve. Table-3 lists the rangeability for VB-7213 series valves. Table-3 Rangeability. Valve Body Part Number Nominal Rangeability Valve Body Part Number Nominal Rangeability VB-7213-0-4-1 5:1 VB-7213-0-4-7 60:1 VB-7213-0-4-2 15:1 VB-7213-0-4-8 75:1 VB-7213-0-4-3 25:1 VB-7213-0-4-9 75:1 VB-7213-0-4-4 40:1 VB-7213-0-4-10 75:1 VB-7213-0-4-5 50:1 VB-7213-0-4-11 75:1 VB-7213-0-4-6 60:1 Temperature/Pressure Ratings See Figure-2 for temperature and pressure ratings. Consult the appropriate valve linkage general instruction sheet for the effect of valve body ambient temperatures on specific actuators. Ratings conform with published values and disclaimer. VB-7213-0-4-P (Screwed Cast Bronze Body) Standards: Pressure to ANSI B16.15 Class 250 with 400 psig up to 150 F decreasing to 321 psig at 281 F Materials: Bronze, ASTM B584 300 (149) 321 psig (2218 kpa) Temperature F ( C) 250 (121) 200 (93) 150 (65) 100 (38) 50 (10) Maximum Media Temperature 281 F (138 C) Minimum Fluid Temperature 20 F (-7 C) VB-7213-0-4-P 50 (345) 100 (689) 150 (1034) 200 (1379) 250 (1724) 300 (2068) Pressure psig (kpa) 350 (2458) 400 (2758) Figure-2 Temperature and Pressure Ratings for VB-7213 Series Valve Bodies. 4 Copyright 2008 TAC All Rights Reserved. F-26075-2

VALVE SIZING AND SELECTION Water Two-position Two-position control valves are normally selected line size to keep pressure drop at a minimum. If it is desirable to reduce the valve below line size, then 10% of available pressure (that is, the pump pressure differential available between supply and return mains with design flow at the valve location) is normally used to select the valve. Proportional Proportional control valves are usually selected to take a pressure drop equal to at least 50% of the available pressure. As available pressure is often difficult to calculate, the normal procedure is to select the valve using a pressure drop at least equal to the drop in the coil or other load being controlled (except where small booster pumps are used) with a minimum recommended pressure drop of 5 psi (34 kpa). When the design temperature drop is less than 60 F (33 C) for conventional heating systems, higher pressure drops across the valve are needed for good results (Table-4). Table-4 Conventional Heating System. a Design Temperature Load Drop F ( C) Recommended Pressure Drop a (% of Available Pressure) Multiplier on Load Drop 60 (33) or More 50% 1 x Load Drop 40 (22) 66% 2 x Load Drop 20 (11) 75% 3 x Load Drop Recommended minimum pressure drop = 5 psi (34 kpa). Secondary Circuits with Small Booster Pumps: 50% of available pressure difference (equal to the drop through load, or 50% of booster pump head). Water Capacity See Table-5 for water capacity of VB-7213 series valves. Table-5 Water Capacity in Gallons Per Minute for VB-7213 Series. Valve Body C v Differential Pressure (ΔP in psi) Part Number Rating 1 2 3 4 5 6 7 8 9 10 15 20 35 VB-7213-0-4-1 0.4 0.40 0.57 0.69 0.80 0.89 0.98 1.06 1.13 1.20 1.26 1.55 1.79 2.37 VB-7213-0-4-2 1.3 1.30 1.84 2.3 2.6 2.9 3.2 3.4 3.7 3.9 4.1 5.0 5.8 7.7 VB-7213-0-4-3 2.2 2.2 3.1 3.8 4.4 4.9 5.4 5.8 6.2 6.6 7.0 8.5 9.8 13 VB-7213-0-4-4 4.4 4.4 6.2 7.6 8.8 9.8 11 12 12 13 14 17 20 26 VB-7213-0-4-5 5.5 5.5 7.8 9.5 11 12 13 15 16 17 17 21 25 33 VB-7213-0-4-6 7.5 7.5 11 13 15 17 18 20 21 23 24 29 34 44 VB-7213-0-4-7 10 10 14 17 20 22 24 26 28 30 32 39 45 59 VB-7213-0-4-8 14 14 20 24 28 31 34 37 40 42 44 54 63 83 VB-7213-0-4-9 20 20 28 35 40 45 49 53 57 60 63 77 89 118 VB-7213-0-4-10 28 28 40 49 56 63 69 74 79 84 89 108 125 166 VB-7213-0-4-11 40 40 57 69 80 89 98 106 113 120 126 155 179 237 C v Equation C v = GPM ΔP ΔP= GPM 2 ( ) GPM = C v ΔP C v Where: C v = Coefficient of flow GPM = U.S. gallons per minute (60 F, 15.6 C) ΔP = Differential pressure in psi (pressure drop) F-26075-2 Copyright 2008 TAC All Rights Reserved. 5

Steam Two-position Two-position zone valves and direct radiation valves are normally sized using a minimum of 10% of inlet pressure (psig). Proportional Proportional control valves are normally sized using: For low pressure (15 psig or less), use ΔP of 80% of gauge inlet pressure. For steam pressures greater than 15 psig, use ΔP of 42% of absolute (gauge plus 14.7) inlet pressure. When the C v required is between two valve sizes, select the larger size. Do not size steam valves using a pressure drop greater than 42% of the absolute inlet pressure. Steam Capacity See Table-6 for steam capacity of VB-7213 series valves. Table-6 Steam Capacity in Pounds Per Hour for VB-7213 Series. Valve Body Part Number a C v Rating C v Equation Differential Pressure (ΔP in psi) a 2 psig Inlet 5 psig Inlet 10 psig Inlet 15 psig Inlet 20 psig Inlet 25 psig Inlet 30 psig Inlet 35 psig Inlet 0.2 1.6 0.5 4 1 8 1.5 12 2 14 2.5 16 3 18 3.5 20 VB-7213-0-4-1 0.4 2.2 5.9 3.7 9.5 5.8 13.9 7.8 17.5 9.7 20.4 11.6 23.4 13.4 26.3 15.3 29.2 VB-7213-0-4-2 1.3 7.1 19.2 12.1 30.9 19.0 45.1 25.4 56.8 31.5 66.4 37.6 75.9 43.6 85.5 49.6 95.1 VB-7213-0-4-3 2.2 12.0 32.4 20.4 52.3 32.1 76.3 42.9 96.2 53.4 112 63.6 129 73.8 145 83.9 161 VB-7213-0-4-4 4.4 24.0 64.9 40.9 105 64.3 153 85.9 192 107 225 127 257 148 289 168 322 VB-7213-0-4-5 5.5 30.0 81.1 51.1 131 80.3 191 107 240 133 281 159 321 185 362 210 402 VB-7213-0-4-6 7.5 40.9 111 69.7 178 110 260 146 328 182 383 217 438 252 493 286 548 VB-7213-0-4-7 10 54.5 147 93 238 146 347 195 437 243 511 289 584 336 658 381 731 VB-7213-0-4-8 14 76.3 206 130 333 204 485 273 612 340 715 405 818 470 921 534 1024 VB-7213-0-4-9 20 109 295 186 475 292 694 390 874 485 1021 579 1168 671 1315 763 1462 VB-7213-0-4-10 28 153 413 260 666 409 971 546 1224 679 1430 810 1636 939 1841 1068 2047 VB-7213-0-4-11 40 218 590 372 951 584 1387 780 1749 970 2043 1157 2337 1342 2631 1526 2925 Values are for saturated steam (K = 1). Left column under each inlet pressure is for two-position control, and right column is for proportional control. C v = 3 QK ΔP P2 Q = 3C v ΔP P2 K Where: C v = Coefficient of flow Q = Lbs. per hour of steam ΔP = Differential pressure in psi (pressure drop) P2 = Outlet pressure in psia (absolute) (P2 = Inlet pressure + 14.7 ΔP) K = 1 + (0.0007 x F superheat) (K = 1 for saturated steam) 6 Copyright 2008 TAC All Rights Reserved. F-26075-2

Cavitation Limitations on Valve Pressure Drop A valve selected with too high a pressure drop can cause erosion of discs and/or wire drawing of the seat. In addition, cavitation can cause noise, damage to the valve trim (and possibly the body), and choke the flow through the valve. Do not exceed the maximum differential pressure (pressure drop) for the valve selected. The following formula can be used on higher temperature water systems, where cavitation could be a problem, to estimate the maximum allowable pressure drop across the valve: Pm = 0.5 (P 1 Pv) Where: Pm = Maximum allowable pressure drop (psi) P 1 = Absolute inlet pressure (psia) Pv = Absolute vapor pressure (psia) (refer to Table-6 or Table-7) Note: Add 14.7 psi to gauge supply pressure to obtain absolute pressure value. For example, if a valve is controlling 200 F water at an inlet pressure of 18 psig, the maximum pressure drop allowable would be: Pm = 0.5 [(18 + 14.7) 11.53] = 10.6 psi (Vapor pressure of 200 F water is 11.53 psia.) If the pressure drop for this valve is less than 10.6 psi, cavitation should not be a problem. Systems where cavitation is shown to be a problem can sometimes be redesigned to provide lower inlet velocities. Valves having harder seat materials should be furnished if inlet velocities cannot be lowered. Table-7 Vapor Pressure of Water Table. Water Temp. ( F) Vapor Pressure (psia) Water Temp. ( F) Vapor Pressure (psia) Water Temp. ( F) Vapor Pressure (psia) Water Temp. ( F) Vapor Pressure (psia) 40 0.12 90 0.70 140 2.89 190 9.34 50 0.18 100 0.95 150 3.72 200 11.53 60 0.26 110 1.28 160 4.74 210 14.12 70 0.36 120 1.69 170 5.99 220 17.19 80 0.51 130 2.22 180 7.51 230 20.78 Additional Valve Sizing Information For additional valve sizing information, see: CA-28 Control Valve Sizing, F-13755 Valve Selection Chart Water, F-11080 Valve Selection Chart Steam, F-11366 Valve Sizing Slide Rule, TOOL-150 F-26075-2 Copyright 2008 TAC All Rights Reserved. 7

INSTALLATION Inspection Inspect the package for damage. If damaged, notify the appropriate carrier immediately. If undamaged, open the package and inspect the device for obvious damage. Return damaged products. Requirements Tools (not provided): Pipe wrenches Training: Installer must be a qualified, experienced technician Appropriate accessories Caution: Install the valve with the flow in the direction of the flow arrow ( A port is the inlet and AB port is the outlet). Do not exceed the ratings of the device. Avoid locations where excessive moisture, corrosive fumes, or vibration are present. Mounting 1. The valve should be mounted in a weather-protected area in a location that is within the ambient limits of the actuator. When selecting a location, allow sufficient room for valve linkage, actuator, and other accessories and for service of the product. 2. The preferred mounting position for the valve is with the valve stem vertical above the valve body. Avoid mounting the valve so that the valve stem is below horizontal. 3. On steam applications where the ambient temperature approaches the limit of the actuator, the valve stem should be mounted 45 from vertical. 4. The valves must be piped with the A port as the inlet and the AB port as the outlet. Screwed Valve Bodies The VB-7213-0-4 series screwed valve bodies conform to American Standard Taper Pipe Threads (NPT). 1. Apply pipe dope sparingly to all but the last two threads of a properly threaded, reamed, and cleaned pipe. Make sure that pipe chips, scale, etc. do not get into the pipe since this material may lodge in the valve seat and prevent proper closing and opening of the valve. 2. Start the joint by hand screwing the pipe into the valve. If the thread engagement feels right, turn the pipe by hand as far as it will go. 3. Use a pipe wrench to fully tighten the valve to the pipe. Do not over tighten or strip threads. See Table-8 and Figure-3 for the normal engagement length of the threads. Figure-4 shows a means of tightening the pipe so that the valve is not twisted or crushed. Table-8 Normal Thread Engagement Between Male Pipe Thread and Valve Body. Valve Size Inches (NPT) Normal Engagement Valve Size Inches (NPT) Normal Engagement 1/2" 1/2" 1-1/4" 11/16" 3/4" 9/16" 1-1/2" 11/16" 1" 11/16" 2" 3/4" 8 Copyright 2008 TAC All Rights Reserved. F-26075-2

Pipe threads too long. Pipe interferes with seat. Wrong Right Figure-3 Normal Thread Engagement. Valve Assembly Tighten pipe using this pipe wrench. Use pipe wrench to prevent valve from turning. Figure-4 Installation of Screwed End Valves. F-26075-2 Copyright 2008 TAC All Rights Reserved. 9

CHECKOUT 1. Make sure the valve stem operates smoothly before installing the valve linkage and the actuator. 2. If the stem does not operate smoothly, it may indicate that the valve was twisted or crushed during installation or that the stem was bent by rough handling. These conditions may require that the valve be replaced. 3. After the piping is under pressure, check the valve body and the connections for leaks. 4. After the valve linkage and the actuator are installed, check their operation. a. Power the actuator and run the valve to the stem down position. Make sure the linkage and valve stem move freely. At the stem down position, the valve should shut off tightly. b. For spring return actuators, allow the actuator to spring return to the stem up position. Again, the valve stem and linkage should operate smoothly. At the stem up position, the valve should be in its full open position. MAINTENANCE & FIELD REPAIR Regular maintenance of the total system is recommended to assure sustained performance. See for maintenance kit part numbers. Table-9 Maintenance Kits for VB-7213 Valves Valve Body Part Number VB-7213-0-4-1 VB-7213-0-4-2 VB-7213-0-4-3 VB-7213-0-4-4 VB-7213-0-4-5 VB-7213-0-4-6 VB-7213-0-4-7 VB-7213-0-4-8 VB-7213-0-4-9 VB-7213-0-4-10 VB-7213-0-4-11 Replacement Packing Assembly YBA-622-1 a Kit includes replacement packing and stem & plug assembly. Packing Wrench TOOL-20-1 Valve Repair Kit a RYB-721-1 RYB-721-2 RYB-721-3 RYB-721-4 RYB-721-5 RYB-721-6 RYB-721-7 RYB-721-8 RYB-721-9 RYB-721-10 RYB-721-11 Water System Maintenance All heating and cooling systems are susceptible to valve and system problems caused by improper water treatment and system storage procedures. These guidelines are provided to help avoid valve and water system problems resulting from improperly treated water or storage procedures in cooling and hot water systems, and to obtain maximum life from TAC valves. Durability of valve stems and packings is dependent on maintaining non-damaging water conditions. Inadequate water treatment or filtration, not in accordance with chemical supplier/ashrae handbook recommendations, can result in corrosion, scale, and abrasive particle formation. Scale and particulates can result in stem and packing scratches and can adversely affect packing life and other parts of the hydronic system. To maintain non-damaging conditions, follow these guidelines: Clean the system prior to start up. Use a nitrite or molybdate-based treatment program. Use filtration equipment where needed. Properly store off-line systems and monitor water treatment results using corrosion test coupons. Follow the advice of a water treatment professional. Consult EN-205, Water System Guidelines Engineering Information, F-26080, for further details. 10 Copyright 2008 TAC All Rights Reserved. F-26075-2

DIMENSIONAL DATA Table-10 Dimensions for VB-7213 Series Valve (Figure-5). Part Number VB-7213-0-4-1 VB-7213-0-4-2 VB-7213-0-4-3 VB-7213-0-4-4 Valve Size 1/2" 3-1/16 (78) A B C Dimensions in Inches (mm) 1-1/16 (27) 1-11/16 (43) VB-7213-0-4-5 VB-7213-0-4-6 3/4" 3-5/8 (92) VB-7213-0-4-7 1" 1-1/8 (29) VB-7213-0-4-8 4-5/8 (118) 2-3/8 (60) VB-7213-0-4-9 1-1/4" 1-3/8 (35) VB-7213-0-4-10 1-1/2" 5-3/8 (137) 1-1/2 (38) 2-7/16 (57) VB-7213-0-4-11 2" 6-1/8 (156) 1-9/16 (40) 2-3/4 (70) D (Stem Down) E a (Stroke) 3/4 (19) 7/16 (11) a Stroke for rated flow. Add up to 1/16 inch (1.6 mm) for disc seating and compression. E D C B A Figure-5 Typical of VB-7213-0-4-P Valve Bodies. F-26075-2 Copyright 2008 TAC All Rights Reserved. 11

Copyright 2008, TAC All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice. F-26075-2 TAC 1354 Clifford Avenue P.O. Box 2940 Loves Park, IL 61132-2940 www.tac.com