V48 Series 3-Way Pressure-Actuated Water-Regulating Valves With Union Fittings

Similar documents
V46 Series 2-Way Pressure-Actuated Water-Regulating Valves With Union Fittings

V146 Series 2-Way Pressure-Actuated Water-Regulating Valves

V43 Pressure Actuated Water Regulating Valve

V248 Series 3-Way Pressure-Actuated. Water-Regulating Valves for High-Pressure

Series V48. 3-Way Pressure Actuated Modulating Valves. Product Bulletin. Features. Pressure balanced design. Free movement of all parts

V248 Series 3-Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants

Series V47 Temperature Actuated Modulating Valves

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

V248 Series 3-Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants

G96 Series BASOTROL Dual Operator Valve

Cash Valve TYPE KP PILOT OPERATED BACK PRESSURE VALVE. ISSUED - DECEMBER 2000 CAVMC-0518-US-0208 ISO 9001 Certified

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

TECHNICAL DATA. Q= Cv S

MEGR-1627 Instruction Manual

GM-7000 Series CE Approved Gas Control Valve

P499 Heavy Duty Pressure Transducer

VB-7323 Series. Application. Features. Applicable Literature. 1/2 to 2 Screwed NPT Three-Way Diverting Valves General Instructions

G92 Series BASOTROL Automatic Pilot Gas Valve

TECHNICAL DATA. Q = C v P S

Dual Solenoid Gas Valve Installation

D05 Pressure Regulating Valves

H15 Series BASO 100% Shutoff, Automatic Pilot Valve

P14 Series Pressure Actuated Mechanical Sequencer

TECHNICAL DATA. Page 1 of 12

V246 Series 2-Way Pressure-Actuated Water-Regulating Valves for High-Pressure Refrigerants

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

TECHNICAL DATA. Q = C v P S

DS06D,G Dial Set Pressure Regulating Valve

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Pressure Regulation 531a. April 24, 2009

TECHNICAL DATA. Q = C v P S

VB-7213 Series. Application. Features. Applicable Literature. 1/2" to 2" Screwed NPT Stem Up Open, Two-Way Valves General Instructions

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves.

TECHNICAL DATA CAUTION

Model Series 62 Constant Differential Relay

DS05C,D,G Dial Set Pressure Regulating Valves

VB-7212 Series. Application. Features. Applicable Literature. 5/8" O.D., 45 SAE Flared Stem Up Open, Two-Way Valves General Instructions

CROT-6 CROT-10 CRO-4. for Compressor Overload Protection

Apollo Standard Port, Full Port & One Piece Flanged Ball Valves Installation, Operation, & Maintenance Manual

BGA158 Series CE Approved Class A Shutoff Gas Valve

VB-7211 Series. Application. Features. Applicable Literature. 1/2" to 1-1/4" Union End NPT Stem Up Open, Two-Way Valves General Instructions

BGA158, BGA171 and BGA110 Series Shutoff Gas Valve

TECHNICAL DATA. Q = C v P S

D05T Compact Design Pressure Regulating Valves

BGC258 Series BASOTROL Gas Valve

VB-7263 Series. Application. Features. Applicable Literature

TECHNICAL DATA OBSOLETE

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

VBS-9263 Series. Application. Features. Applicable Literature

Installation, Operation and Maintenance Manual for Back Pressure Regulator

BGA158 Series CE Approved Class B Shutoff Gas Valve

Halsey Taylor Owners Manual STOP!

TECHNICAL DATA CAUTION

VB-7273 Series. Application. Features. Applicable Literature

3/8" Dr. Air Butterfly Impact Wrench

shutoff valves 900 Series psig Manual Shutoff Valves

OPERATING AND MAINTENANCE MANUAL

HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS

INSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION

GM Series Dual-Block Multi-Function Gas Control Valves

PENBERTHY SUBMERSIBLE AUTOMATIC SUMP DRAINER INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

FILTER REGULATORS MODEL NO: CAT155 & CAT156 FITTING & MAINTENANCE INSTRUCTIONS PART NO: & ORIGINAL INSTRUCTIONS

CASH VALVE TYPE KP BACK PRESSURE VALVES

Maximum 0.85 MPa pressure setting Long-life, high flow perfect for balancer applications

Installation Instructions

INSTALLATION INSTRUCTIONS MANUAL ON/OFF SAFETY VALVE/PILOT KIT MODEL GA9050A-1 (F0235)

PRS(TC)4,8 USER MANUAL. Read the complete manual before installing and using the regulator.

Pressure Sensing Valve - Model 4023

Hydraulic Piston Accumulators

Bermad Pressure Reducing. Model: 42T

I T T Pressure Reducing Valve WARNING INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

Model 40H Nullmatic Pressure Regulators

A28 Series Two-Stage Temperature Controls with NEMA 1 Enclosure

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

INSTRUCTIONS PARTS LIST

INDUSTRIAL VALVES MODELS: C62-A; C62-D. INSTRUCTION MANUAL Installation Operation Parts Service DIAPHRAGM BYPASS PRESSURE REGULATING VALVES

Medical Gas Control Panel

Halsey Taylor Owners Manual 4410 Freeze Resistant Tubular Fountain STOP!

VOLUMATIC WATER REGULATOR

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

Model GP PRESSURE REDUCING VALVE Installation & Operation Manual

UL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function Gas Control Valves

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

MZX. Three-Port Seat Valves SPECIFICIATIONS AND GUIDE TO SELECTION

INSTALLATION INSTRUCTIONS

Instruction Manual Pressure Relief Valve and Rupture Disc Chlorine or Sulfur Dioxide, Series 869

627 Series Pressure Reducing Regulators

29 SERIES - SAFETY VALVE

Product Manual. Description. Specifications. CVS Type 1301F and CVS Type 1301G Regulator. Introduction

Back Pressure Regulator

ELKHART BRASS MANUFACTURING COMPANY

GS-20/25 and GS-40/45 Series Single-block Multi-function Gas Control Valves

A t. VB-7323 Series. Application. Features. Applicable Literature. l/2 to 2 Screwed NPT SIEBE

MUELLER GAS. No-Blo Operations Using D-5. Drilling Machine. Reliable Connections. General Information 2

Introduction. Description. Series P48 Pressure Controls for Steam, Air or (hot) Water. Feature and Benefits

TECHNICAL DATA. Page 1 of 8. model f /2 (dn40) & 2 (dn50)

Pressure Dump Valve Service Kit for Series 2300 Units

Transcription:

Installation Instructions V48 Issue Date 08/30/01 V48 Series 3-Way Pressure-Actuated Water-Regulating Valves With Union Fittings Application IMPORTANT: The V48 Series 3-Way Pressure-Actuated Water-Regulating Valves are intended to control water flow under normal equipment operating conditions. Where failure or malfunction of the V48 valves could lead to an abnormal operating condition that could cause personal injury or damage to the equipment or other property, other devices (limit or safety controls) or systems (alarm or supervisory) intended to warn of, or protect against, failure or malfunction of the V48 valve must be incorporated into and maintained as part of the control system. Dimensions Port 1 A Port 2 C D E B The V48 direct-acting models open on an increase in pressure. The V48 valves with Union fittings are available in 1/2-in. through 1-1/4-in. sizes and may be used with standard non-corrosive refrigerants. Installation IMPORTANT: If these valves are installed on equipment that contains hazardous or regulated materials, such as refrigerants or lubricants, the installer and user should observe all regulations governing the handling and containment of those materials. Port 3 Plugged Pressure connection and capillary as specified Figure 1: V48 Valve Dimensions for Models With Union Fittings F IMPORTANT: It is recommended to apply a non-hardening, pliable sealant (Loctite 567 or equivalent) to the face of the copper tailpiece to compensate for slight piping misalignments and surface imperfections on union ends. Table 1: V48 Valve Dimensions, inches (millimeters) Product Code Number Nominal Valve Size A B C D E F V48AJ-2C 1/2 in. 4-9/16 (115) 1-13/16 (47) 7-7/8 (200) 3-3/4 (96) 1-1/2 (38) V48EK-2C 3/4 in. 5-3/8 (136) 2 (52) 8-9/16 (218) 4-3/16 (106) 1-3/4 (44) 2-5/8 (67) V48AL-2C 1 in. 7-1/16 (179) 11-5/8 (295) 5-15/16 (151) 2 (51) 3-11/16 (94) 2-5/8 (67) V48AM-2C 1-1/4 in. 7-3/16 (182) 12-7/16 (319) 6-3/16 (160) 2-3/8 (60) 3-7/8 (99) 2001 Johnson Controls, Inc. 1 Part No. 24-7664-2160, Rev. www.johnsoncontrols.com

Manually Flushing the Valve Manually flush the valve and fluid piping before and after installing, repairing, or replacing a valve to remove filings, chips, or other foreign matter. Insert screwdrivers under both sides of the valve spring guide and lift upwards to flush the valve. See Figure 2. Manual flushing does not affect valve adjustment. Range Spring Valve Spring Guide Top Retainer Range Adjustment Screw Figure 2: Manual Flushing Insert screwdrivers underneath the valve spring guide. Location Considerations Install the valve vertically with the range adjustment screw on the top and the bellows and pressure connection line on the bottom to allow drainage of oil and refrigerant away from valve bellows. Do not mount the valve in any position other than vertical unless specified by the manufacturer of the equipment on which the valve is installed. Follow the manufacturer's installation instructions. Install the V48 valve as shown in Figure 3. Port 1 is for the inlet connection from the tower. Port 2 is for the outlet connection to the condenser inlet. Port 3 is the bypass connection. Install the valve on the inlet side of the condenser. If it is necessary to keep the condenser flooded with water, the valve may be installed on the outlet side of the condenser. If the system is located in an area with high ambient temperatures, refrigerant head pressures may remain high enough during Off cycles to prevent the valve from closing completely. In such instances, the opening point pressure of the valve should be raised just enough to cause the valve to stop flow to the condenser during compressor standby periods. When used on a single condenser system, adjust the balancing valve in the bypass with the compressor shut off and the tower pump operating. Adjust the balancing valve so that the amount of water through the bypass is just sufficient to provide the minimum recommended nozzle pressure. See Figure 3. On a multiple condenser system, adjust the balancing valves in the bypasses evenly with the compressors Off and the tower pump On. The total flow through all the bypasses should be just sufficient to provide the minimum recommended nozzle pressure. IMPORTANT: After installing the valve, evacuate bellows and pressure connection lines, in accordance with EPA and other regulations, to remove air, moisture and other contaminants. From Cooling Tower V48 Valve Port 1 Port 2 Port 1 = Inlet (From Cooling Tower) Port 2 = To Condenser Port 3 = Bypass Condenser to Cooling Tower To Cooling Tower Port 3 Condenser Flow From Bellows to Refrigerant Pressure Tap Connection To Other Condensers (if used) Bypass Balancing Valve Flow From Other Condensers (if used) Figure 3: Recommended Piping Arrangement for V48 Valves 2 V48 Series 3-Way Pressure-Actuated Water-Regulating Valves With Union Fittings Installation Instructions

Pressure Connections! WARNING: Risk of Personal Injury. Contents of liquid lines could be under pressure. Avoid possible personal injury by shutting off the liquid supply and relieving the pressure before servicing the valve. Connect the refrigerant-side flare connector to the appropriate high-side pressure tap point. If additional capillary tubing is necessary, use 1/4-in. copper tubing. Follow the guidelines below when making pressure connections: Use Pressure Tap Points Located on the Top Side of the Refrigerant Lines This reduces the possibility of oil, liquids, or sediment accumulating in the pressure connection line or valve bellows, which could cause valve malfunction. Avoid Sharp Bends in the Capillary Tubes Sharp bends can weaken or kink capillary tubes, which may result in refrigerant leaks or restrictions. Allow for Slack in the Capillary Tubes to Dampen Vibration Mechanical vibration can weaken or damage the capillary tubes. Avoid Contact Between the Capillary Tubing and Sharp or Abrasive Objects Vibration or rubbing of sharp or abrasive objects in contact with capillary tubes can cause leaks. Coil and Secure Excess Capillary Tubing Away from Contact with Sharp or Abrasive Objects or Surfaces Carefully loop any excess capillary tube into smooth, circular coils (minimum 2 in. [5 cm] diameter). Securely fasten the coiled capillary tube. Do Not Overtighten Flare Nuts on Pressure Connection Line Fittings Overtightening flare connections may damage the threads and result in refrigerant leaks. Do not exceed 9 lb ft (12 N m) of torque when tightening brass flare connections. Avoid Severe Pressure Pulsation at Pressure Tap Points Install pressure connection lines to pressure tap points away from the compressor discharge, to minimize the affects of pressure pulsation from reciprocating compressors. Table 2: Pressure Specifications for V48 Series Valves with Union Fittings Product Code Number Nominal Valve Size Maximum Refrigerant Pressure at Bellows V48AJ-2C 1/2 in. 320 psi (2206 kpa) V48EK-2C 3/4 in. 370 psi (2551 kpa) 320 psi V48AM-2C 1-1/4 in. (2206 kpa) Opening Point Adjustment Range 70 to 260 psi (483 to 1793 kpa) Factory-Set Opening Point (Port 1 to Port 2) 165 psi (1138 kpa) Throttling Range 190 psi (1310 kpa) Pressure Connection Style Shipping Weight lb (kg) 45 3.3 (1.5) 4.3 (2.0) V48AL-2C 1 in. 9.3 (4.0) 10.0 (4.5) 46 Style 45 Style 46 Copper Capillary with 1/4-in. SAE Female Flare Connector (Includes Valve Stem Depressor.) Copper Capillary with 1/4-in. SAE Female Flare Connector (Includes Valve Stem Depressor.) Figure 4: Pressure Connection Styles V48 Series 3-Way Pressure-Actuated Water-Regulating Valves With Union Fittings Installation Instructions 3

Setup and Adjustments The V48 valves are factory adjusted for the settings shown in Table 2. The opening point pressure is the refrigerant pressure (at the valve s bellows) necessary to just lift the valve disc off of the valve seat and allow water to flow through the valve body. Turning the adjustment screw changes the opening point pressure. The throttling pressure range is the difference between the opening point pressure and the pressure necessary to fully open the valve and allow maximum flow. The throttling range is a fixed pressure value. Turning the range adjustment screw to adjust the opening point pressure also moves the fixed throttling pressure range. Use a standard service valve wrench or screwdriver to adjust the opening point pressure. Turn the range adjustment screw clockwise to lower the opening point pressure (and throttling range). Use a refrigerant pressure gauge to adjust the opening point pressure. Operate the system at normal load conditions and adjust the valve s opening point to the desired pressure. See Table 2 for refrigerant pressure specifications. Repairs and Replacement Replacement of the sensing element, internal parts, and the rubber diaphragm can be made. For a replacement valve or replacement parts kit, contact the nearest Johnson Controls/PENN distributor. For replacement kit part numbers, refer to Table 3. Turn the range adjustment screw counter-clockwise to raise the opening point pressure (and throttling range). Table 3: Repair and Replacement Kits Valve Product Code Number Nominal Size Shipping Weight Seat Repair Kit Product Code Nu mber For replacement kit instructions and details, refer to the following bulletin: V46, V47, V48, and V49 Sensing Element Replacement Technical Bulletin LIT-121700. Sensing Element Replacement Kit Product Code Number V48AJ-2C 1/2 in. 3.3 lb (1.5kg) STT15A-605R SEP91A-602R, SEC99AB-48C V48EK-2C 3/4 in. 4.3 lb (2.0kg) STT16A-604R SEP91A-601R, SEC99AB-48C V48AL-2C 1 in. 9.3 lb (4.0kg) STT17A-616R SEP91A-603R, SEC99AB-48C V48AM-2C 1-1/4 in. 10.0 lb (4.5kg) STT17A-617R SEP91A-603R, SEC99AB-48C 4 V48 Series 3-Way Pressure-Actuated Water-Regulating Valves With Union Fittings Installation Instructions

Flowchart 70 60 50 40 30 1-1/4-in. Valve 1-in. Valve Water Flow (gpm) 20 10 9 8 7 6 5 4 3 3/4 -in. Valve 1/2-in. Valve 2 1 50 Water Pressure Drop Through Valve (psi) 7 10 15 40 Refrigerant Head Pressure Above Valve Opening Point (psi) 30 20 10 0 Valve Opening Point Figure 5: Water Flow Related to Valve Size and Water Pressure V48 Series 3-Way Pressure-Actuated Water-Regulating Valves With Union Fittings Installation Instructions 5

Technical Data Product Body Material Extension Sleeve, Disc, Stud, Disc Holder Material Valve Seat Material Valve Disc Diaphragm Water Supply Pressure Water Supply Temperature V48 Series Pressure-Actuated Water-Regulating Valves 1/2-and 3/4-in. Sizes - Cast Brass Bodies, 1-in. and 1-1/4-in. Sizes - Cast Iron Bodies with Rust-Resisting Finish Brass Aluminum Bronze Buna-N Nylon-Reinforced Buna-N 150 psig (1034 kpa) Maximum 170 F (77 C) Maximum Water Flow See Figure 5. Sensing Element Pressure Range See Table 3. Shipping Weight See Table 3. Brass and Phosphor Bronze Bellows in Brass Cup The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult local Johnson Controls/PENN Application Engineering at (800) 275-5676. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Refer to the V48 Series 3-Way Pressure-Actuated Water-Regulating Valves for Cooling Tower Systems Product Bulletin (LIT-121705) for necessary information on operating and performance specifications of this product. Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI 53201 Printed in U.S.A. www.johnsoncontrols.com 6 V48 Series 3-Way Pressure-Actuated Water-Regulating Valves With Union Fittings Installation Instructions