Test Report. Test Report Smart Systems Limited Incorporating Smart Extrusions. Page 1 of 78

Similar documents
CONTENTS 1. INTRODUCTION DESCRIPTION OF TEST SAMPLE TEST RIG GENERAL ARRANGEMENT TEST SEQUENCE...7

Technical Report. Title: Product weathertightness testing of a sample of W.G.Ltd 500 series Curtain Walling for The Window Glass Company Limited

Evidence of Performance. Class 4. Class 5A. Class C5 / B5. Test Report No PR01. ift Rosenheim

AAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A STRUCTURAL PERFORMANCE TEST REPORT SUMMARY RENDERED TO:

ETEM S.A. LIGHT METALS COMPANY 1, IROON POLYTEHNIOU STR. GR MAGOULA ATTIKIS GREECE

Intertek Testing Services Building Products. Enterdoor AB ubv

ETEM S.A. LIGHT METALS COMPANY 1, IROON POLYTEHNIOU STR. GR MAGOULA ATTIKIS GREECE

Kestrel Aluminium Systems Limited. Product Manual Section 10 Thermal Framing System. Manual Version

TEST REPORT TS EN : TS EN A1 Windows and doors - Product standard. Testing Reference. : BM 72 Gizli Kanat Pencere (Hidden Vent Window)

LATICRETE International Inc. One LATICRETE Park North Bethany, CT USA

PERFORMANCE TEST REPORT FOR AIR LEAKAGE AND DURABILITY OF BARRIER PRODUCTS ASTM E Rendered to: BAUTEX SYSTEMS

OCEAN - Wellness Line

Opening and closing force guidelines

COBALT BULLETPROOF PRODUCTS. Architect: J.-L. Bonnet Photography: Serge D ly

INSTALLATION INSTRUCTIONS PUSH BAR PULLMAN PANIC BOLT DEVICE TO EN 1125 : 2008

Technical Report. Product testing of 6 mm Graniti Fiandre Maximum panels with support system and fabrication by Telling Architectural

1688 Jean-Berchmans-Michaud Drummondville, Quebec. J2C 8E9. Mr. Marc-Etienne Mathieu,ing.

K13.12 FACE FIXED PANIC EXIT DEVICE K13 DOORS

CFSW. Hinges with built-in safety multiple switch

CE conform applications according to EN Windows without thermal break Systems Forster presto and Forster norm

OS2 F R A M E S E R I E S

IGUMA - IGU Design Limitations

TEST CERTIFICATE THE RESULTS CONCERN ONLY THE SPECIMEN TESTED. THE PRESENT DOCUMENT DOES NOT CONSIST PRODUCT APPROVAL BY E.K.AN.AL.

ENHANCED REQUIREMENTS & TEST METHODS FOR ANTI-LIGATURE HARDWARE

CFSW. Hinges with built-in safety multiple switch

ASTM E1886 and ASTM E1996 TEST REPORT. Report No.: E Rendered to: 3M COMPANY St. Paul, Minnesota 55144

CYCLIC PERFORMANCE PER ASTM E 330 TEST REPORT. Rendered to: TRUSEAL TECHNOLOGIES, LTD. PRODUCT TYPE: Fixed Window

ATHLETICS Track & Field Equipment

SECTION SHOWER AND BATH ENCLOSURES. Display hidden notes to specifier by using Tools / Options / View / Hidden Text.

FLUID - Panic Exit Device

TEST CERTIFICATE PARTIAL REPRODUCTION OF THE PRESENT CERTIFICATE IS PROHIBITED WITHOUT PRIOR WRITTEN PERMISSION BY EKANAL.

FEATURES. Welded Sash and Main Frame. Swiggle or DuraSeal Spacer System on Fixed Units. 3-1/4" Frame Depth. True Sloped Sill. Integral J Channel

TEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina

PRESSURE TANKS HANDLING & INSTALLATION INSTRUCTIONS INSTALLATION MANUAL CONTROL VALVES

MANUAL SEALLESS STEEL STRAPPING TOOL MODEL A

Extension Platform. Base Platform. Crossover. Exit railing. Exit Railing

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

Hatch cover securing and tightness

Testing results for Hose Patch, hydraulic hose repair system

hockey hockey Integral Weighted Goals Aluminium Goals Fence Folding Goals Premier Hockey Goals Folding Wheelaway Goals

Engineering Data Sheet

Order No Projection Backboard

STABILITY AND WATERTIGHT INTEGRITY, CLOSING APPLIANCES

TABLE OF CONTENTS International Racquetball Federation officially approved specifications. Copyright 01/13/1983; rev.

1.0 - OPENING AND CLOSING THE DOOR

FOLD AND ROLL PLAYBACK TABLE TENNIS TABLE

MSA Latchways Ladder System

Plummer Block Housings

Slide and Turn System SF25

Straightaway 130. Sliding & Folding Door Systems. Product Overview. Features. Technical Specifications. Coburn Product Data Sheet

Technical Data Sheet. R&M Closures

Bike-Shell Model 301P

LOAD CHARTS RT890E METRIC DIN / ISO / 75%

KTM OM-2 SPLIT BODY FLOATING BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

Horizontal Bladder Tanks

Contact person Date Reference Page Michael Lindblad F025843A 1 (1) Sustainable Built Environment

10.2. Basketball Single Post System

International Civil Aviation Organization DANGEROUS GOODS PANEL (DGP) MEETING OF THE WORKING GROUP OF THE WHOLE. Montreal, 18 to 22 April 2005

10.2. Basketball Single Post System

CLEANROOM GEL GRID CEILING SYSTEM PRODUCT DATA Division

FOLD AND ROLL PLAYBACK TABLE TENNIS TABLE

Overspeed governors (113 OG Моment 250 MR, 114 OG Moment 250 A3, 115 OG Moment 250 MRL, 119 OG Moment 250 MRL/1)

30T A/Manual Hydraulic Shop Press

SPECIFICATION FOR RAISED PAVEMENT MARKERS

F13.11 PARALLEL HINGES F13 PROJECT-OUT WINDOWS AND TOP HUNG WINDOWS

GV Standard X-Vent. Setup, Commissioning & Installation Guide

SECTION BUTTERFLY VALVES

ST 18 Aluminium Gas Model

Materials : Dichromate zinc plated steel flanges or AISI 316

VENTILATOR OPTIONS. Please visit our web page to view all the available options and for a specification.

Summary of Substantive Changes between the 2012 and 2018 editions of CSA B125.3 Plumbing Fittings

OPENINGS AND REINFORCEMENTS 26

WELL COMPLETION & PROTECTION. www. .com MINERAL EXPLORATION ENVIRONMENTAL GEOTECHNICAL GEOTHERMAL ROTARY SONIC HDD

TEST PROTOCOL VERIFICATION OF THE BEHAVIOUR OF A MECHANICAL COMPRESSION COUPLING DURING SETTLEMENT

The CompacSas BAH airlock is the ideal solution for transforming an existing door into an airlock

Doors in watertight bulkheads of cargo ships and passenger ships

Tex-616-J, Construction Fabrics

Model MTB-ASME Vertical Bladder Tanks

CRYOGENIC TANK SERVICES - CHART RECORDER MANUAL

Model MTB-ASME Horizontal Bladder Tanks

Model MTB-ASME Vertical Bladder Tanks

Vertical Bladder Tanks

Spilt body Flange ball valve. TC-205MFF-PN1640 User Manual English Version. Document No: TC-205MFF-PN1640.Ur-manual. Date: 2007/04/2617. Version: 1.

Technical information for hinges

Summary of Substantive Changes between the 2004 e1 and 2017 editions of ASSE 1011, Hose Connection Vacuum Breakers

Performance Standards for Non-Turf Cricket Pitches Intended for Outdoor Use [TS6] ecb.co.uk

Insulated Door Components. Tension Spring System. High performance hardware door system for residential applications

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

DECLARATION OF PERFORMANCE

Smart Water Application Technologies (SWAT) TM

3 Post Pressure Fit System Owner s Manual

ST 18 Aluminium Gas Model

1.3 LIMITATIONS: The following application limitations must be recognized and considered before using this product:

Slide and Turn System SF35

SET OF EUROLEAGUE BACKSTOP UNITS (Reference PK120)

3190A NEO-ANGLE DOOR INSTALLATION INSTRUCTIONS. Series MODEL NO

Middle East Technical University Department of Mechanical Engineering ME 305 Fluid Mechanics I Fall 2018 Section 4 (Dr.

Installation, commissioning and servicing instructions

CAISSON SHAFT SYSTEM

PERSONAL FALL PROTECTION

Transcription:

Test Report 8365614. Smart Systems Limited Incorporating Smart Extrusions Page 1 of 78

Introduction. This report has been prepared by Adam Pearce and relates to the activity detailed below: Job/Registration Details Job number: 8365614 Job type: Testing Samples Submitted Start Date: 05/09/2016 Test type: Type Sample ID: 10156882 Registration: KM 530838 Scheme: BS 4873 / PAS24 Protocol: PP519 Scheme Mgr: Lorraine Balch Quality system: ISO 9001:2008 Client Details Smart Systems Limited Incorporating Smart Extrusions Arnolds Way Yatton BS49 4QN United Kingdom The report has been approved for issue by Mark Manito Team Manager Approved For Issue Approver Name: Issue Date:17 March 2017 Objectives. Type test for product certification. Product Scope. Visofold 1000 Aluminium Bi-fold Doors Report Summary. The samples were received on 31 August 2016 and the testing was started on 7 September 2016. The samples submitted complied with the requirements of the test work conducted. Page 2 of 78

Description of Test Sample. Outer Frame width 2700 & 3740 Outer Frame Material Aluminium Outer Frame height 2570 Outer Frame Gasket Outer Frame Part Numbers Gasket Type Epdm Top DV14 Manufacturer Bottom DV14 Product Name Lock Side DV14 Product Code ACDV272, 244 Hinge Side DV14 Threshold Outer Frame section dimensions Manufacturer Smart Width 51.5 Product name Depth 70 Product Code DV14, 171, 271 Reinforcing: N/A Materials Aluminium Manufacturer Outer Frame Joint Method Product Name Head Corner Cleat Product code Foot Corner Cleat /Screwport Material Leaf Leaf Material: Leaf Width: 1200 Leaf Gasket Leaf Height: 2510 Gasket type: Epdm Leaf Part Numbers: Manufacturer: Top: DV23 Product Name: Bottom: DV23 Product Code ACDV272 Lock side: DV23 Leaf Midrail: N/A Hinge Side DV23 Manufacturer: Leaf section size Product name: Width: 60.5 Product code: Depth: 74.5 Material: Reinforcing N/A Leaf joint method Manufacturer: Head: Corner Cleat Product Name: Foot: Corner Cleat Product Code: Material: Bead Manufacturer: Smart Product Name: Product Code: DV67 Material: Aluminium Bead Size: 22 x 17 Page 3 of 78

Description of Test Sample.(continued) Glazing Unit Glazing Gasket Manufacturer: Gasket Type: Epdm Inner Thickness: 6 Manufacturer: Spacer Material: 16 Product Name: Outer Thickness: 6 Product Code ACVDV31 ACVG34 Unit Sizes: Glazing Clip N/A Glazing Tape Details N/A Manufacturer: Manufacturer: Product Name: Product Name: Product Code Product Code Hardware Fixings Quantity Hinges: ACDV331 Refer to Fabrication Manual Hinge Protectors: N/A Lock: ACDV722/723 Cylinder: ACDV258 (with handle ACDV480) Security Cylinder: ACCCY50/50S3 (with handle ACDV251) Handle: ACDV251, 480 Cylinder Support: N/A Cylinder Escutcheon: N/A Keeps: Full height Included in lock kits above Drip Bar N/A Additional Hardware Top Guide ACDV333/381 Roller ACDV332/380 Run-up block ACDV080 Anti-lift block ACDV081 Page 4 of 78

PAS24:2012 Type Test. Product Description (Security Testing) 1 off three leaf glaze in open out hinged bi-fold door assembly with one master leaf and two folding sliding leaves, full glass infill and standard threshold Note: An additional cylinder test was conducted, see sample description for details. (Sample ID No 10156882) Date samples received: 31 August 2016 Test Results. 1. Manipulation Test sample met the requirements of the Specification in respect of B.4.3 2. Infill removal Test sample met the requirements of the Specification in respect of B.4.4 3. Mechanical loading Test sample met the requirements of the Specification in respect of B.4.5 4. Manual check test Test sample met the requirements of the Specification in respect of B.4.6 5. Soft body impact Test sample met the requirements of the Specification in respect of B.4.8 6. Hard body impact Test sample met the requirements of the Specification in respect of B.4.9.2.2 7. Security hardware Test sample met the requirements of the Specification in and cylinder test respect of Annex A 8. Additional hardware Test sample met the requirements of the Specification in Security and cylinder respect of Annex A test 9. Letter plate None fitted Page 5 of 78

Sample Selection. The sample submitted for tests were selected using the PCP Scheme Document Specification. The sample was submitted for test mounted in a 75mm x 100mm timber subframe in accordance with the manufacturer s installation requirements. Sample manufactured by the client. Clause 5 Sequence of Tests. The sequence of testing the sample followed that detailed in Clause 5 of BS 6375-1:2015. Clause 5 Performance Requirements. The performance of the sample was assessed against the requirements detailed in Table 1 Exposure categories and classifications Page 6 of 78

Description of Sample. (Sample 1) Sample type - A three leaf glaze in open out hinged bi-fold door assembly with one master leaf and two folding sliding leaves, full glass infill and standard threshold Material - Aluminium Finish - Painted Fittings - Handle and Cylinder - Handle and Cylinder - Fittings - Master door A five point (D KT) locking (two hook bolts, two cams, one dead bolt) Fuhr espagnolette system with four pin hinges. ACDV258 cylinder, key locking Mila Pro Secure handle Yale ACCY50/503S 3* cylinder, key locking standard handle Two Sliding leaves A two point locking (two shoot bolts), twelve pin hinges and two rollers Weathersealing - Doubled sealed plastic weather strips Glass - Double glazed with 4-20-4 mm toughened glass sealed units Glass retention system - Internal beads and gaskets Sample dimensions - Overall - Length: 2700mm Height: 2570mm Master Leaves - Length: 880mm Height: 2510mm Salve Leaves - Length: 850mm Height: 2510mm Date of test - 06 September 2016 Laboratory temperature - 25.3 C Laboratory humidity - 73.3% Page 7 of 78

Elevation Drawing of Door Assembly. Master Leaf Bifold Leaf Bifold Leaf - Handle - Hinge - Cylinder - Cam - Shoot Bolt - Dead Bolt - Hook Bolt Page 8 of 78

Test Results. CLAUSE 7 PERFORMANCE REQUIREMENTS ASSESSMENT B.4.3 Manipulation Test The sample was mounted, vertically and square, in the test rig as described in B.3.1. The test was carried out in accordance with the given objective of this Annex using the procedure detailed in B.4.3.1 and the tools described in Group A and B where applicable. The sample was closed and locked and the key removed. Although there is no overall time limit no one technique was used for more than 3 minutes. No tools were effective by any technique after 3 minutes B.4.4 Cutting and Infill medium removal test B.4.4.2 Infill Manual Test The sample was mounted, vertically and square, in the test rig as described in B.3.1. The test was carried out in accordance with the requirements of this Annex using the tools described tools in Group A and B where applicable. A craft knife was used to cut a V in the profile. No entry was gained. No entry could be effected within 3 minutes B.4.4.3 Infill Mechanical Test The sample was mounted, vertically and square, in the test rig as described in B.3.1. The test was carried out with a perpendicular to plane load of 2.0kN applied to each corner of the glazing and each corner of the boundaries of components in turn as specified. No evidence of bead failure No entry could be effected B.4.4.4 Manual Cutting Test Not applicable Page 9 of 78

Test Results (Continued). PERFORMANCE REQUIREMENTS B.4.5 Mechanical Loading Test The sample was mounted, vertically and square, in the test rig. The test was carried out in accordance with the procedures detailed in B.4.5, Using loading cases B.1 to B.6 and Figures B.12 for loading sequence and using the test apparatus detailed in Figures B.6 to B.9. Diagram of points of application of loads 1 9 10 13 20 8 2 14 19 7 3 6 11 15 18 5 4 12 16 17 Page 10 of 78

Test Results (Continued). PERFORMANCE REQUIREMENTS ASSESSMENT B.4.5 Mechanical Loading Test B.4.5.2 Loading Procedures Point of application of load First Sequence 1. Hinge (head of left jamb) Standard loading case used: 1 Load applied in plane: 1.5kN at right angles to the edge and towards the opposite edge Load applied perpendicular to plane: 4.5kN applied for 10 seconds 2. Hinge (upper left jamb) Standard loading case used: 1 Load applied in plane: 1.5kN at right angles to the edge and towards the opposite edge Load applied perpendicular to plane: 4.5kN applied for 10 seconds 3. Hinge (lower left jamb) Standard loading case used: 1 Load applied in plane: 1.5kN at right angles to the edge and towards the opposite edge Load applied perpendicular to plane: 4.5kN applied for 10 seconds 4. Hinge (threshold of left jamb) Standard loading case used: 1 Load applied in plane: 1.5kN at right angles to the edge and towards the opposite edge Load applied perpendicular to plane: 4.5kN applied for 10 seconds 5. Cam (lower false mullion) Standard loading case used: 8 Load applied in plane: 1.5kN along edge in a direction to disengage the cam Load applied perpendicular to plane: 4.5kN applied for 10 seconds Load applied in plane: 1.5kN at right angles to the edge and towards the opposite edge 1.5kN at the mullion to oppose the above load Load applied perpendicular to plane: 4.5kN applied for 10 seconds Page 11 of 78

Test Results (Continued). PERFORMANCE REQUIREMENTS ASSESSMENT B.4.5 Mechanical Loading Test B.4.5.2 Loading Procedures Point of application of load 6. Hook Bolt (lower false mullion) Standard loading case used: 8 Load applied in plane: 1.5kN along edge in a direction to disengage the bolt Load applied perpendicular to plane: 4.5kN applied for 10 seconds Load applied in plane: 1.5kN at right angles to the edge and towards the opposite edge 1.5kN at the mullion to oppose the above load Load applied perpendicular to plane: 4.5kN applied for 10 seconds 7. Dead bolt (centre false mullion) Standard loading case used: 9 Loads applied in plane: 1.5kN at right angles to the edge and away from the opposite edge 1.5kN at the mullion to oppose the above load Load applied perpendicular to plane: 4.5kN applied for 10 seconds 8. Hook Bolt / Hinge (upper false mullion) Standard loading case used: 8 / 2 Load applied in plane: 1.5kN along edge in a direction to disengage the bolt Load applied perpendicular to plane: 4.5kN applied for 10 seconds Load applied in plane: 1.5kN at right angles to the edge and towards the opposite edge 1.5kN at the mullion to oppose the above load Load applied perpendicular to plane: 4.5kN applied for 10 seconds 9. Cam (upper false mullion) Standard loading case used: 8 Load applied in plane: 1.5kN along edge in a direction to disengage the cam Load applied perpendicular to plane: 4.5kN applied for 10 seconds Load applied in plane: 1.5kN at right angles to the edge and towards the opposite edge 1.5kN at the mullion to oppose the above load Load applied perpendicular to plane: 4.5kN applied for 10 seconds Page 12 of 78

Test Results (Continued). PERFORMANCE REQUIREMENTS ASSESSMENT B.4.5 Mechanical Loading Test B.4.5.2 Loading Procedures Point of application of load 10. Roller / Hinge (upper false mullion) Standard loading case used: 11/2 Load applied in plane: 1.5kN along edge in a direction to disengage the roller Load applied perpendicular to plane: 1.5kN applied for 10 seconds Load applied in plane: 1.5kN at right angles to the edge and towards the opposite edge 1.5kN at the mullion to oppose the above load Load applied perpendicular to plane: 4.5kN applied for 10 seconds 11. Hinge (lower false mullion) Standard loading case used: 1 Load applied in plane: 1.5kN at right angles to the edge and towards the opposite edge Load applied perpendicular to plane: 4.5kN applied for 10 seconds 12. Roller / Hinge (lower false mullion) Standard loading case used: 11/2 Load applied in plane: 1.5kN along edge in a direction to disengage the roller Load applied perpendicular to plane: 1.5kN applied for 10 seconds Load applied in plane: 1.5kN at right angles to the edge and towards the opposite edge Load applied perpendicular to plane: 4.5kN applied for 10 seconds 13. Shoot / Hinge (lower false mullion) Standard loading case used: 5/2 Load applied in plane: 1.5kN along edge in a direction to disengage the shoot bolt Load applied perpendicular to plane: 4.5kN applied for 10 seconds Load applied in plane: 1.5kN at right angles to the edge and towards the opposite edge Load applied perpendicular to plane: 4.5kN applied for 10 seconds 14. Hinge (lower false mullion) Standard loading case used: 1 Load applied in plane: 1.5kN at right angles to the edge and towards the opposite edge Load applied perpendicular to plane: 4.5kN applied for 10 seconds Page 13 of 78

Test Results (Continued). PERFORMANCE REQUIREMENTS ASSESSMENT B.4.5 Mechanical Loading Test B.4.5.2 Loading Procedures Point of application of load 15. Hinge (upper false mullion) Standard loading case used: 1 Load applied in plane: 1.5kN at right angles to the edge and towards the opposite edge Load applied perpendicular to plane: 4.5kN applied for 10 seconds 16. Shoot / Hinge (upper false mullion) Standard loading case used: 5/2 Load applied in plane: 1.5kN along edge in a direction to disengage the shoot bolt Load applied perpendicular to plane: 4.5kN applied for 10 seconds Load applied in plane: 1.5kN at right angles to the edge and towards the opposite edge Load applied perpendicular to plane: 4.5kN applied for 10 seconds 17. Hinge (head of right jamb) Standard loading case used: 1 Load applied in plane: 1.5kN at right angles to the edge and towards the opposite edge Load applied perpendicular to plane: 4.5kN applied for 10 seconds 18. Hinge (upper right jamb) Standard loading case used: 1 Load applied in plane: 1.5kN at right angles to the edge and towards the opposite edge Load applied perpendicular to plane: 4.5kN applied for 10 seconds 19. Hinge (lower right jamb) Standard loading case used: 1 Load applied in plane: 1.5kN at right angles to the edge and towards the opposite edge Load applied perpendicular to plane: 4.5kN applied for 10 seconds 20. Hinge (threshold of right jamb) Standard loading case used: 1 Load applied in plane: 1.5kN at right angles to the edge and towards the opposite edge Load applied perpendicular to plane: 4.5kN applied for 10 seconds No entry effected Page 14 of 78

Test Results (Continued). PERFORMANCE REQUIREMENTS B.4.8 Soft Body Impact Test ASSESSMENT The sample was mounted, vertically and square, in the test rig as described in B.3.1. The test was carried out in accordance with the requirements, objectives and procedures detailed in B.4.8.1 using the impact point and procedure described in B.4.8.2 and B.4.8.3 and Figure B.10 Diagram of points of application of loads 9 10 11 12 8 7 6 5 1 2 3 4 Page 15 of 78

Test Results (Continued). PERFORMANCE REQUIREMENTS B.4.8 Soft Body Impact Test ASSESSMENT Impact point Position from Effect floor level 1 0.80m None 2 0.80m None 3 0.80m None 4 0.80m None 5 1.25m None 6 1.25m None 7 1.25m None 8 1.25m None 9 1.70m None 10 1.70m None 11 1.70m None 12 1.70m None No entry effected Page 16 of 78

Test Results (Continued). PERFORMANCE REQUIREMENTS B.4.9 Hard body impact test The sample was mounted, vertically and square, in the test rig as described in B.3.1. The test was carried out in accordance with the requirements, objectives and procedures detailed in B.4.9.1, B.4.9.2.1, B.4.9.2.2, B.4.9.2.3 using procedure B.4.9.3, using the test apparatus detailed in B.11 using the impact sequence in figure B.14. Diagram of points of application of loads 1 12 13 11 2 10 9 8 3 7 6 4 5 14 Page 17 of 78

Test Results (Continued). PERFORMANCE REQUIREMENTS B.4.9 Hard body impact test (continued) ASSESSMENT Impact point Position Effect 1 Corner/Hinge None 2 Hinge None 3 Hinge None 4 Corner Hinge None 5 Corner/ Hinge / Roller None 6 Cam None 7 Hook None 8 Cylinder None 9 Dead Bolt/ Hinge None 10 Hook Bolt/Hinge None 11 Cam None 12 Corner/ Roller/ Hinge None 13 Shoot Bolt None 14 Shoot bolt None No entry effected Page 18 of 78

Test Results (Continued). PERFORMANCE REQUIREMENTS ASSESSMENT B.4.6 Manual Check Test The sample was mounted, vertically and square, in the test rig as described in B.3.1. The test was carried out in accordance with the given objective of this Clause using the procedure detailed in B.4.6.3 and the tools described in B.4.6.2. No one technique was used for more than 3 minutes. No alternative method of entry could be effected within 3 minutes B.4.7 Additional Loading Test Not applicable as an alternative method of entry was not identified Page 19 of 78

Test Results (Continued). PERFORMANCE REQUIREMENTS ASSESSMENT Hardware - ACDV258 cylinder with key locking Mila Pro Secure handle Annex A Security Hardware and Cylinder Test and Assessment Annex A.3.2 (Part 1) The sample was mounted, vertically and square, in the test rig as described in Clause 3.1. The test was carried out in accordance with the given objective of this Annex using the procedure detailed in Annex A.3.1 and the tools described in A.2. The sample was closed and locked and the key removed. Mole grips were used to snap the cylinder The total attack time was 3 minutes and the total rest time was 7 minutes No entry could be effected within 3 minutes Annex A.3.2 (Part 2) The sample was mounted, vertically and square, in the test rig as described in Clause 3.1. The test was carried out in accordance with the given objective of this Annex using the procedure detailed in Annex A.3.1 and the tools described in A.2 The sample was closed and locked and the key removed. The total attack time was 3 minutes and the total rest time was 7 minutes No entry could be effected within 3 minutes Page 20 of 78

Test Results (Continued). PERFORMANCE REQUIREMENTS ASSESSMENT Hardware Yale ACCY50/503S 3* cylinder with key locking standard handle Annex A Security Hardware and Cylinder Test and Assessment Annex A.3.2 (Part 1) The sample was mounted, vertically and square, in the test rig as described in Clause 3.1. The test was carried out in accordance with the given objective of this Annex using the procedure detailed in Annex A.3.1 and the tools described in A.2. The sample was closed and locked and the key removed. Mole grips were used to snap the cylinder The total attack time was 3 minutes and the total rest time was 7 minutes No entry could be effected within 3 minutes Annex A.3.2 (Part 2) The sample was mounted, vertically and square, in the test rig as described in Clause 3.1. The test was carried out in accordance with the given objective of this Annex using the procedure detailed in Annex A.3.1 and the tools described in A.2 The sample was closed and locked and the key removed. The total attack time was 3 minutes and the total rest time was 7 minutes No entry could be effected within 3 minutes B.4.3 Letter Plates None fitted Page 21 of 78

Photograph of Sample. Page 22 of 78

BS4873:2009 Type Test. Product Description (Weather Test) 1 off three leaf glaze in open out hinged bi-fold door assembly with one master leaf and two folding sliding leaves, full glass infill and low threshold (Sample 2) 1 off three leaf glaze in open in hinged bi-fold door assembly with one master leaf and two folding sliding leaves, full glass infill and low threshold (Sample 3) 1 off three leaf glaze in open out hinged bi-fold door assembly with one master leaf and two folding sliding leaves, full glass infill and standard threshold (Sample 4) 1 off three leaf glaze in open in hinged bi-fold door assembly with one master leaf and two folding sliding leaves, full glass infill and standard threshold (Sample 5) (Sample ID No 10156882) Date samples received: 31 August 2016 Test Results. 1. Air permeability Test samples 2, 3, 4 and 5 met the requirements of the Specification, in respect of Clause 13, for Test Pressure Class 1. 2. Watertightness Test sample 2 met the requirements of the Specification, in respect of Clause 13, for Test Pressure Class 2A. Test sample 3 met the requirements of the Specification, in respect of Clause 13, for Test Pressure Class 3A. Test sample 4 met the requirements of the Specification, in respect of Clause 13, for Test Pressure Class 4A. Test sample 5 met the requirements of the Specification, in respect of Clause 13, for Test Pressure Class 8A. 3. Wind resistance Test samples 2, 3 and 4 met the requirements of the Specification, in respect of Clause 8, for Exposure Category Class A2. Classification for Wind Resistance. Test sample 3 Exposure Category 800Pa 4. Operational Test sample 3 met the requirements of the Specification Strength in respect of BS 6375-2 Page 23 of 78

Classification for Operational strength. Operating forces Class 1 Vertical load Class 2 Resistance to Static torsion Class 2 Soft and Heavy body Impact Load bearing Class 2 Hard body impact Class 2 Load bearing capacity of safety devices N/A Closure against obstruction 5. Basic security Test sample 3 met the requirements of BS6375-3 Sample Selection. The sample submitted for tests were selected using the PCP Scheme Document Specification. The sample was submitted for test mounted in a 75mm x 100mm timber subframe in accordance with the manufacturer s installation requirements. Sample manufactured by the client. Clause 5 Sequence of Tests. The sequence of testing the sample followed that detailed in Clause 5 of BS 6375-1:2015. Clause 5 Performance Requirements. The performance of the sample was assessed against the requirements detailed in Table 1 Exposure categories and classifications Page 24 of 78

Methods Of Test. 1. Operating Forces The operating forces acting on the sample were determined by the methods given in standard BS EN 12046 2. 2. Air Permeability The air permeability of the sample was determined by the method given in BS 6375-1:2015. 3. Watertightness The watertightness of the sample was determined by the method given in BS 6375-1:2015. 4. Wind Resistance The wind resistance of the samples was determined by the methods (P1 and P2) given in BS 6375-1:2015. 5. Repeat Tests After testing for resistance to wind loading (P1 and P2) the air permeability test was repeated. 6. Wind Resistance The wind resistance of the samples was determined by the method (P3) given in BS 6375-1:2015. 7. Resistance to Vertical Loads The resistance to vertical loads test was carried out using the method given in standard BS EN 947. 8. Resistance to Static Torsion The resistance to static torsion test was carried out using the method given in standard BS EN 948. 9. Soft and heavy body impact The resistance to soft and heavy body impact was carried out using the method given in standard BS EN 949. 10. Hard body impact The resistance to hard body impact was carried out using the method given in standard BS EN 950. 11. Closure against obstruction The Closure against obstruction was carried out using the method given in BS 6375-3 Page 25 of 78

Methods Of Test (Continued). 12. Basic security The basic security test was carried out using the method given in standard BS 6375:3. Note. Basic Security not UKAS accredited to BS6375-3 Page 26 of 78

Description of Sample. (Sample 2) Sample type - A three leaf glaze in open out hinged bi-fold door assembly with one master leaf and two folding sliding leaves, full glass infill and low threshold Material - Aluminium Finish - White Fittings - Master door A five point locking (two hook bolts, two cams, 1 dead bolt) Fuhr espagnolette system, ACDV258 cylinder, key locking Mila Pro Secure handle and four pin hinges. Two Sliding leaves A two point locking (two shoot bolts), twelve pin hinges and two rollers Weathersealing - Doubled sealed plastic weather strips Glass - Double glazed with 4-20-4 mm toughened glass sealed units Glass retention system - Internal beads and gaskets Sample dimensions - Overall - Length: 3740mm Height: 2570mm Master Leaves - Length: 1200mm Height: 2500mm Slave Leaves - Length: 1200mm Height: 2500mm Date of test - 06 September 2016 Laboratory temperature - 22.4 C Laboratory humidity - 69.7% Laboratory Atmospheric Pressure - 100.1kPa Page 27 of 78

Elevation Drawing of Door Assembly. 8365614-Test Report. Master Leaf Bifold Leaf Bifold Leaf - Handle Water Leakage Points - Hinge - Cylinder - Cam Transducer Placement - - Shoot Bolt - Dead Bolt - Hook Bolt Page 28 of 78

Air permeability [m³/h.m² of overall area] Air permeability [m³/h.m of opening joints] Graph of Air Permeability Before Gusting. 8365614-Test Report. 100 90 80 70 60 50 40 Exfiltration 25.0 22.5 20.0 17.5 15.0 12.5 10.0 30 7.5 20 Class 1 Infiltration [m³/h.m] 5.0 10 9 Class 2 2.5 2.25 8 7 Exfiltration 2.0 1.75 6 1.5 5 1.25 4 Class 3 Infiltration [m³/h.m²] 1.0 3 0.75 2 0.5 Class 4 1 10 50 100 150 300 600 1000 Differential pressure [Pa] 0.25 Page 29 of 78

Table of Air Permeability Before Gusting. 8365614-Test Report. AIR PERMEABILITY TEST RESULTS - BS 6375-1:2015 / BS EN 1026:2000 Clause 6.3 - Before resistance to wind tests Three positive pressure pulses of 660Pa were applied prior to testing Air Pressure [Pa] Average rate of air leakage [m³/h] Average rate of air leakage per meter length of opening joint [m³/h.m] Average rate of air leakage relative to area of sample [m³/h.m²] 50 35.1 2.05 3.66 100 64.4 3.76 6.71 150 89.7 5.24 9.33 200 - - - 250 - - - 300 - - - 450 - - - 600 - - - Note: The figures in the table above give the leakage as an average of the leakage at positive pressure and the leakage at negative pressure Total opening perimeter = 17.12m Overall area = 9.61m² BS 6375-1:2015 Clause 6.3 - Joint class = 1 BS 6375-1:2015 Clause 6.3 - Area class = 1 BS 6375-1:2015 Clause 6.3 - Overall class = 1 Page 30 of 78

Air permeability [m³/h.m² of overall area] Air permeability [m³/h.m of opening joints] 8365614-Test Report. Graph of Average Air Permeability Before Gusting. 100 90 80 70 60 50 Class 1 25.0 22.5 20.0 17.5 15.0 12.5 40 10.0 30 Class 2 7.5 20 Average Leakage [m³/h.m²] 5.0 10 9 8 7 6 5 Class 3 Average Leakage [m³/h.m] 2.5 2.25 2.0 1.75 1.5 1.25 4 1.0 3 Class 4 0.75 2 0.5 1 10 50 100 150 300 600 1000 Differential pressure [Pa] 0.25 Page 31 of 78

Watertightness Test Results. BS EN 1027:2000 Clause 7 Watertightness before resistance to wind loads TABLE 2 - Spraying method 1A Pressure (Pascals) Point and time at which water leakage occurred 0 No leakage 50 No leakage 100 Water leaked from threshold opening joint onto sill at 1 minutes and 10 seconds 150-200 - 250-300 - 450-600 - 750-900 - 1050 - WIND LOAD RESISTANCE TEST RESULTS - BS EN 12211:2000 Clause 8 Resistance to wind load P1 DEFLECTION TEST Three positive pressure pulses at 880Pa were applied No visible failures or functional defects to the test sample were observed after wind loads applied at a positive air pressure of 800Pa. Actual deflection 10.36mm (maximum deflection allowed 15.66mm) Deflection/span ratio 1/226 (maximum ratio allowed 1/150) Three negative pressure pulses at 880Pa were applied No visible failures or functional defects to the test sample were observed after wind loads applied at a negative air pressure of 800Pa. Actual deflection 7.23mm (maximum deflection allowed 15.66mm) Deflection/span ratio 1/325 (maximum ratio allowed 1/150) Page 32 of 78

P2 REPEATED PRESSURE TEST No visible failures or functional defects to the test sample were observed after 50 cycles of repeated wind loads applied at a positive air pressure of 400Pa. No visible failures or functional defects to the test sample were observed after 50 cycles of repeated wind loads applied at a negative air pressure of 400Pa. In accordance with BS 6375-1:2015 Clause 6.5, as the classification after the resistance to wind load tests is the same as the classification before the resistance to wind load tests, the resulting classification for the sample is Class 1. (see following Table). Page 33 of 78

Air permeability [m³/h.m² of overall area] Air permeability [m³/h.m of opening joints] Graph of Air Permeability After Gusting. 8365614-Test Report. 100 90 80 70 60 50 Class 1 25.0 22.5 20.0 17.5 15.0 12.5 40 10.0 30 Class 2 7.5 20 5.0 Exfiltration [m³/h.m] Infiltration [m³/h.m] 10 9 8 7 6 5 4 Exfiltration [m³/h.m²] Class 3 Infiltration [m³/h.m²] 2.5 2.25 2.0 1.75 1.5 1.25 1.0 3 Class 4 0.75 2 0.5 1 0.25 10 50 100 150 300 600 1000 Differential pressure [Pa] Page 34 of 78

Table Average Air Permeability After Gusting. 8365614-Test Report. AIR PERMEABILITY TEST RESULTS - BS 6375-1:2015 / BS EN 1026:2000 Clause 6.5 - After resistance to wind tests Three positive pressure pulses of 660Pa were applied prior to testing Air Pressure [Pa] Average rate of air leakage [m³/h] Average rate of air leakage per meter length of opening joint [m³/h.m] Average rate of air leakage relative to area of sample [m³/h.m²] 50 35.8 2.09 3.73 100 65.1 3.80 6.78 150 91.3 5.33 9.50 200 - - - 250 - - - 300 - - - 450 - - - 600 - - - Note: The figures in the table above give the leakage as an average of the leakage at positive pressure and the leakage at negative pressure Total opening perimeter = 17.12m Overall area = 9.61m² BS 6375-1:2015 Clause 6.5 - Joint class = 1 BS 6375-1:2015 Clause 6.5 - Area class = 1 BS 6375-1:2015 Clause 6.5 - Overall class = 1 In accordance with BS 6375-1:2015 Clause 6.5, as the classification after the resistance to wind load tests is the same as the classification before the resistance to wind load tests, the resulting classification for the sample is Class 1. Page 35 of 78

Air permeability [m³/h.m² of overall area] Air permeability [m³/h.m of opening joints] 8365614-Test Report. Graph of Average Air Permeability After Gusting. 100 90 80 70 60 50 Class 1 25.0 22.5 20.0 17.5 15.0 12.5 40 10.0 30 Class 2 7.5 20 5.0 Average leakage [m³/h.m²] 10 9 8 7 6 5 4 Class 3 Average leakage [m³/h.m] 2.5 2.25 2.0 1.75 1.5 1.25 1.0 3 Class 4 0.75 2 0.5 1 10 50 100 150 300 600 1000 Differential pressure [Pa] 0.25 Page 36 of 78

Air permeability [m³/h.m² of overall area] Air permeability [m³/h.m of opening joints] 8365614-Test Report. Graph of Average Air Permeability After Gusting Including +20% Lines for Each Class. 100 90 80 70 60 50 Class 1 25.0 22.5 20.0 17.5 15.0 12.5 40 10.0 30 Class 2 7.5 20 5.0 Average leakage [m³/h.m²] 10 9 8 7 Class 3 2.5 2.25 2.0 1.75 6 5 Average leakage [m³/h.m] 1.5 1.25 4 1.0 3 Class 4 0.75 2 0.5 1 10 50 100 150 300 600 1000 Differential pressure [Pa] 0.25 Page 37 of 78

Wind Load Resistance Test Results - BS EN 12211:2000. P3 SAFETY TEST 8365614-Test Report. No parts of the test sample became detached and the test sample remained closed after a wind load safety test applied at a positive air pressure of 1200Pa. No parts of the test sample became detached and the test sample remained closed after a wind load safety test applied at a negative air pressure of 1200Pa Page 38 of 78

BS 6375-2:2009. Clause 6 Performance characteristics and requirements for pedestrian doorsets Assessment Clause 6.2 Operating Forces: EN12046-2 and EN12217 The sample was tested three times, closing the leaf, handle, locking the key, unlocking the key, handle opening and maintaining the leaf to stay open, and highest of the three results were then recorded. Closing leaf force 38.65N (maximum 75N) Handle closing 60.45N (maximum 100N) Key torque to lock 0.10Nm (maximum 20N) Key torque to unlock 0.10Nm (maximum 20N) Handle opening 63.05 (maximum 100N) Force to maintain opening 42.30N (maximum 75N) Clause 6.3.1 Vertical Load. All loads were applied and removed in increments of maximum 100N. The diagonal measurement of door was measured to the nearest 1mm (hinge bottom to lockside top corner) A pre-load of 200± 4N using weights vertically to the top of the lock side corner of the door leaf, at 50± 5mm from the opening edge, and maintained for 60± 5s, then removed and left to rest for a further 60± 5s. The gauge was zeroed then to the same loading point (Class 2) 600N was applied for 300s ± 5s, a maximum deformation measurement was taken The load was removed and after 180± 5s the residual deflection measurement was taken, along with the diagonal measurement. Pre diagonal measurement - Maximum deformation Residual measurement Diagonal measurement 2655mm 0.20mm 0.00mm 2655mm For the door to pass, the residual deformation must not exceed 1.0mmass Page 39 of 78

BS 6375-2:2009. Clause 6 Performance characteristics and requirements for pedestrian doorsets Assessment Clause 6.3.2 Resistance to static torsion. All loads were applied and removed in increments of maximum 100N. The door leaf was opened to 90 then fixed at the top lockside corner, 50± 5mm from the edge. A pre-load of 200± 4N was applied horizontally and normally to the plane of the leaf, at the lower lockside corner, at 50± 5mm from the edge, then maintained for 60± 5s. After 1 minute the gauge was zeroed and loaded to (Class 2) 250N for 300s ± 5s, the maximum deformation was taken, the load was taken off and left to rest for 180s ± 5s, the residual measurement was then taken. Maximum deformation Residual measurement 34.30mm 0.00mm For the door to pass the residual deformation must not exceed 2.0mm Clause 6.3.3 Soft and Heavy body Impact. The door was closed to its normal operating mode and the sample was marked at the centre of the door leaf. The deviation across the width of the door was measured at the impact point. A 30±0.6Kg leather impactor was raised to the required drop height and impacted to the exterior face, then the deviation was measured again For the door to achieve the required class it shall not exceed 2mm Residual measurement across face of impacted side. The sample was impacted in the centre of the active leaf and from the outside Residual measurement 0mm Page 40 of 78

BS 6375-2:2009. Clause 6 Performance characteristics and requirements for pedestrian doorsets Assessment Clause 6.3.4 Hard body Impact. The door leaf was mounted horizontally with rigid supports under the long edges of the leaf and pattern 2 was selected. Glazed impact points were omitted, and the exterior side was impacted. If permanent damage is left after impact measurements were taken after 30 minutes. Mean of the Diameter 3.00mm Mean of the depth 0.10m The mean to qualify for a class shall not exceed 20mm, and the mean for the depth shall not exceed 1.0mm Clause 6.4 Load bearing capacity of safety devices. Not assessed due to no safety device being fitted Closure against obstruction. The objective of this test is to determine the resistance of a doorset to closure of the door leaf against small objects such as small toys, which may be accidentally trapped between the frame and leaf. A 50 x 50 x 10mm aluminium block was placed in the gap between the leaf and the bottom of the hinge side jamb. A 200N force was applied to the lock side of the leaf and held for 15 ±5 seconds The leaf was then opened and closed 5 times and the operating forces were taken Page 41 of 78

BS 6375-2:2009. Clause 6 Performance characteristics and requirements for pedestrian doorsets Assessment Clause 6.2 Operating Forces: EN12046-2 and EN12217 The sample was tested three times, closing the leaf, handle, locking the key, unlocking the key, handle opening and maintaining the leaf to stay open, and highest of the three results were then recorded. Closing leaf force 40.50N (maximum 75N) Handle closing 61.60N (maximum 100N) Key torque to lock 0.10Nm (maximum 20N) Key torque to unlock 0.10Nm (maximum 20N) Handle opening 66.60N (maximum 100N) Force to maintain opening 41.25N (maximum 75N) Basic security (Annex A). BS 6375: Part 3: 2009 - Performance of Doors The objective of this test is to establish from if from the outside entry can be gained by defeating the glazing or locking system. The force used did not result in permanent set or plastic deformation of any tool. Damaged tools shall be replaced and the test did not exceed the maximum 3 minute time period. The screwdriver was used to no effect No entry could be effected Page 42 of 78

Description of Sample. (Sample 3) Sample type - A three leaf glaze in open in hinged bi-fold door assembly with one master leaf and two folding sliding leaves, full glass infill and low threshold Material - Aluminium Finish - White Fittings - Master door A five point locking (two hook bolts, two cams, 1 dead bolt) Fuhr espagnolette system, ACDV258 cylinder, key locking Mila Pro Secure handle and four pin hinges. Two Sliding leaves A two point locking (two shoot bolts), twelve pin hinges and two rollers Weathersealing - Doubled sealed plastic weather strips Glass - Double glazed with 4-20-4 mm toughened glass sealed units Glass retention system - Internal beads and gaskets Sample dimensions - Overall - Length: 3740mm Height: 2570mm Master Leaves - Length: 1200mm Height: 2500mm Slave Leaves - Length: 1200mm Height: 2500mm Date of test - 7 September 2016 Laboratory temperature - 22.4 C Laboratory humidity - 69.7% Page 43 of 78

Elevation Drawing of Door Assembly. 8365614-Test Report. Master Leaf Bifold Leaf Bifold Leaf - Handle Water Leakage Point - Hinge - Cylinder - Cam Transducer Placement - - Shoot Bolt - Dead Bolt - Hook Bolt Page 44 of 78

Air permeability [m³/h.m² of overall area] Air permeability [m³/h.m of opening joints] Graph of Air Permeability Before Gusting. 8365614-Test Report. 100 90 80 70 60 50 Class 1 25.0 22.5 20.0 17.5 15.0 12.5 40 Exfiltration [m³/h.m] 10.0 30 7.5 Class 2 20 Infiltration [m³/h.m] 5.0 10 9 8 7 Class 3 2.5 2.25 2.0 1.75 6 5 Exfiltration [m³/h.m²] 1.5 1.25 4 1.0 3 Infiltration [m³/h.m²] Class 4 0.75 2 0.5 1 10 50 100 150 300 600 1000 Differential pressure [Pa] 0.25 Page 45 of 78

Table of Average Air Permeability Before Gusting. AIR PERMEABILITY TEST RESULTS - BS 6375-1:2015 / BS EN 1026:2000 Air Pressure [Pa] Clause 6.3 - Before resistance to wind tests Three positive pressure pulses of 660Pa were applied prior to testing Average rate of air leakage [m³/h] Average rate of air leakage per meter length of opening joint [m³/h.m] Average rate of air leakage relative to area of sample [m³/h.m²] 50 35.1 7.04 3.66 100 59.1 11.83 6.14 150 79.7 15.98 8.30 200 - - - 250 - - - 300 - - - 450 - - - 600 - - - Note: The figures in the table above give the leakage as an average of the leakage at positive pressure and the leakage at negative pressure Total opening perimeter = 4.99m Overall area = 9.61m² BS 6375-1:2015 Clause 6.3 - Joint class = 1 BS 6375-1:2015 Clause 6.3 - Area class = 1 BS 6375-1:2015 Clause 6.3 - Overall class = 1 Page 46 of 78

Air permeability [m³/h.m² of overall area] Air permeability [m³/h.m of opening joints] 8365614-Test Report. Graph of Average Air Permeability Before Gusting. 100 90 25.0 22.5 80 20.0 70 17.5 60 15.0 50 40 Average Leakage [m³/h.m²] Class 1 12.5 10.0 30 Class 2 7.5 20 5.0 10 9 Class 3 2.5 2.25 8 2.0 7 1.75 6 1.5 5 1.25 4 1.0 3 Average Leakage [m³/h.m] Class 4 0.75 2 0.5 1 10 50 100 150 300 600 1000 Differential pressure [Pa] 0.25 Page 47 of 78

Watertightness Test Results. BS EN 1027:2000 Clause 7 Watertightness before resistance to wind loads TABLE 2 - Spraying method 1A Pressure (Pascals) Point and time at which water leakage occurred 0 No leakage 50 No leakage 100 No Leakage 150 Water leaked from threshold opening joint onto sill at 2 minutes and 10 seconds 200-250 - 300-450 - 600-750 - 900-1050 - WIND LOAD RESISTANCE TEST RESULTS - BS EN 12211:2000 Clause 8 Resistance to wind load P1 DEFLECTION TEST Three positive pressure pulses at 880Pa were applied No visible failures or functional defects to the test sample were observed after wind loads applied at a positive air pressure of 800Pa. Actual deflection 7.47mm (maximum deflection allowed 15.66mm) Deflection/span ratio 1/314 (maximum ratio allowed 1/150) Three negative pressure pulses at 880Pa were applied No visible failures or functional defects to the test sample were observed after wind loads applied at a negative air pressure of 800Pa. Actual deflection 13.43mm (maximum deflection allowed 15.66mm) Deflection/span ratio 1/174 (maximum ratio allowed 1/150) Page 48 of 78

P2 REPEATED PRESSURE TEST No visible failures or functional defects to the test sample were observed after 50 cycles of repeated wind loads applied at a positive air pressure of 400Pa. No visible failures or functional defects to the test sample were observed after 50 cycles of repeated wind loads applied at a negative air pressure of 400Pa. In accordance with BS 6375-1:2015 Clause 6.5, as the classification after the resistance to wind load tests is the same as the classification before the resistance to wind load tests, the resulting classification for the sample is Class 1. (see following Table). Page 49 of 78

Air permeability [m³/h.m² of overall area] Air permeability [m³/h.m of opening joints] Graph of Air Permeability After Gusting. 8365614-Test Report. 100 90 25.0 22.5 80 20.0 70 17.5 60 50 Exfiltration [m³/h.m] Class 1 15.0 12.5 40 10.0 30 7.5 Class 2 20 Infiltration [m³/h.m] 5.0 10 9 8 Class 3 2.5 2.25 2.0 7 6 Exfiltration [m³/h.m²] 1.75 1.5 5 1.25 4 1.0 3 Infiltration [m³/h.m²] Class 4 0.75 2 0.5 1 0.25 10 50 100 150 300 600 1000 Differential pressure [Pa] Page 50 of 78

Table of Average Air Permeability After Gusting. AIR PERMEABILITY TEST RESULTS - BS 6375-1:2015 / BS EN 1026:2000 Air Pressure [Pa] Clause 6.5 - After resistance to wind tests Three positive pressure pulses of 660Pa were applied prior to testing Average rate of air leakage [m³/h] Average rate of air leakage per meter length of opening joint [m³/h.m] Average rate of air leakage relative to area of sample [m³/h.m²] 50 35.8 7.18 3.73 100 59.9 12.01 6.24 150 81.3 16.29 8.46 200 - - - 250 - - - 300 - - - 450 - - - 600 - - - Note: The figures in the table above give the leakage as an average of the leakage at positive pressure and the leakage at negative pressure Total opening perimeter = 4.99m Overall area = 9.61m² BS 6375-1:2015 Clause 6.5 - Joint class = 1 BS 6375-1:2015 Clause 6.5 - Area class = 1 BS 6375-1:2015 Clause 6.5 - Overall class = 1 In accordance with BS 6375-1:2015 Clause 6.5, as the classification after the resistance to wind load tests is the same as the classification before the resistance to wind load tests, the resulting classification for the sample is Class 1. Page 51 of 78

Air permeability [m³/h.m² of overall area] Air permeability [m³/h.m of opening joints] 8365614-Test Report. Graph of Average Air Permeability After Gusting. 100 90 25.0 22.5 80 20.0 70 17.5 60 15.0 50 40 Average leakage [m³/h.m²] Class 1 12.5 10.0 30 7.5 Class 2 20 5.0 10 9 8 Class 3 2.5 2.25 2.0 7 1.75 6 5 Average leakage [m³/h.m] 1.5 1.25 4 1.0 3 Class 4 0.75 2 0.5 1 10 50 100 150 300 600 1000 Differential pressure [Pa] 0.25 Page 52 of 78

Air permeability [m³/h.m² of overall area] Air permeability [m³/h.m of opening joints] 8365614-Test Report. Graph of Average Air Permeability After Gusting Including +20% Lines for Each Class. 100 90 25.0 22.5 80 20.0 70 17.5 60 15.0 50 40 Average leakage [m³/h.m²] Class 1 12.5 10.0 30 7.5 Class 2 20 5.0 10 9 8 Class 3 2.5 2.25 2.0 7 1.75 6 1.5 5 1.25 4 1.0 3 Average leakage [m³/h.m] Class 4 0.75 2 0.5 1 10 50 100 150 300 600 1000 Differential pressure [Pa] 0.25 Page 53 of 78

Wind Load Resistance Test Results - BS EN 12211:2000. P3 SAFETY TEST 8365614-Test Report. No parts of the test sample became detached and the test sample remained closed after a wind load safety test applied at a positive air pressure of 1200Pa. No parts of the test sample became detached and the test sample remained closed after a wind load safety test applied at a negative air pressure of 1200Pa Page 54 of 78

BS 6375-2:2009. Clause 6 Performance characteristics and requirements for pedestrian doorsets Assessment Clause 6.2 Operating Forces: EN12046-2 and EN12217 The sample was tested three times, closing the leaf, handle, locking the key, unlocking the key, handle opening and maintaining the leaf to stay open, and highest of the three results were then recorded. Closing leaf force 37.18N (maximum 75N) Handle closing 59.96N (maximum 100N) Key torque to lock 0.10Nm (maximum 20N) Key torque to unlock 0.10Nm (maximum 20N) Handle opening 60.93(maximum 100N) Force to maintain opening 42.73N (maximum 75N) Basic security (Annex A). BS 6375: Part 3: 2009 - Performance of Doors The objective of this test is to establish from if from the outside entry can be gained by defeating the glazing or locking system. The force used did not result in permanent set or plastic deformation of any tool. Damaged tools shall be replaced and the test did not exceed the maximum 3 minute time period. The screwdriver was used to no effect No entry could be effected Page 55 of 78

Description of Sample. (Sample 4) Sample type - A three leaf glaze in open out hinged bi-fold door assembly with one master leaf and two folding sliding leaves, full glass infill and standard threshold Material - Aluminium Finish - White Fittings - Master door A five point locking (two hook bolts, two cams, 1 dead bolt) Fuhr espagnolette system, ACDV258 cylinder, key locking Mila Pro Secure handle and four pin hinges. Two Sliding leaves A two point locking (two shoot bolts), twelve pin hinges and two rollers Weathersealing - Doubled sealed plastic weather strips Glass - Double glazed with 4-20-4 mm toughened glass sealed units Glass retention system - Internal beads and gaskets Sample dimensions - Overall - Length: 3740mm Height: 2570mm Master Leaves - Length: 1200mm Height: 2500mm Slave Leaves - Length: 1200mm Height: 2500mm Date of test - 7 September 2016 Laboratory temperature - 19.7 C Laboratory humidity - 35.4% Laboratory Atmospheric Pressure - 99.7kPa Page 56 of 78

Elevation Drawing of Door Assembly. Master Leaf Bifold Leaf Bifold Leaf - Handle Water Leakage Point - Hinge - Cylinder - Cam Transducer Placement - - Shoot Bolt - Dead Bolt - Hook Bolt Page 57 of 78

Air permeability [m³/h.m² of overall area] Air permeability [m³/h.m of opening joints] Graph of Air Permeability Before Gusting. 8365614-Test Report. 100 90 25.0 22.5 80 20.0 70 17.5 60 15.0 50 Class 1 12.5 40 10.0 30 7.5 Class 2 20 5.0 10 9 8 Infiltration [m³/h.m] Class 3 Infiltration [m³/h.m²] 2.5 2.25 2.0 7 1.75 6 1.5 5 Exfiltration [m³/h.m] 1.25 4 Exfiltration [m³/h.m²] 1.0 3 Class 4 0.75 2 0.5 1 10 50 100 150 300 600 1000 Differential pressure [Pa] 0.25 Page 58 of 78

Table of Average Air Permeability Before Gusting. AIR PERMEABILITY TEST RESULTS - BS 6375-1:2015 / BS EN 1026:2000 Clause 6.3 - Before resistance to wind tests Three positive pressure pulses of 660Pa were applied prior to testing Air Pressure [Pa] Average rate of air leakage [m³/h] Average rate of air leakage per meter length of opening joint [m³/h.m] Average rate of air leakage relative to area of sample [m³/h.m²] 50 32.8 1.92 3.57 100 52.3 3.05 5.68 150 76.3 4.45 8.29 200 - - - 250 - - - 300 - - - 450 - - - 600 - - - Note: The figures in the table above give the leakage as an average of the leakage at positive pressure and the leakage at negative pressure Total opening perimeter = 17.12m Overall area = 9.2m² BS 6375-1:2015 Clause 6.3 - Joint class = 1 BS 6375-1:2015 Clause 6.3 - Area class = 1 BS 6375-1:2015 Clause 6.3 - Overall class = 1 Page 59 of 78

Air permeability [m³/h.m² of overall area] Air permeability [m³/h.m of opening joints] 8365614-Test Report. Graph of Average Air Permeability Before Gusting. 100 90 80 70 60 50 40 Class 1 25.0 22.5 20.0 17.5 15.0 12.5 10.0 30 Class 2 7.5 20 5.0 Average Leakage [m³/h.m²] 10 9 8 Class 3 2.5 2.25 2.0 7 1.75 6 1.5 5 1.25 4 1.0 3 Average Leakage Class 4 0.75 2 0.5 1 10 50 100 150 300 600 1000 Differential pressure [Pa] 0.25 Page 60 of 78

Watertightness Test Results. BS EN 1027:2000 Clause 7 Watertightness before resistance to wind loads TABLE 2 - Spraying method 1A Pressure (Pascals) Point and time at which water leakage occurred 0 No leakage 50 No leakage 100 No Leakage 150 No Leakage 200 Water leaked from threshold opening joint onto sill at 58 seconds. 250-300 - 450-600 - 750-900 - 1050 - WIND LOAD RESISTANCE TEST RESULTS - BS EN 12211:2000 Clause 8 Resistance to wind load P1 DEFLECTION TEST Three positive pressure pulses at 880Pa were applied No visible failures or functional defects to the test sample were observed after wind loads applied at a positive air pressure of 800Pa. Actual deflection 15.57mm (maximum deflection allowed 15.66mm) Deflection/span ratio 1/150 (maximum ratio allowed 1/150) Three negative pressure pulses at 880Pa were applied No visible failures or functional defects to the test sample were observed after wind loads applied at a negative air pressure of 800Pa. Actual deflection 8.31mm (maximum deflection allowed 15.66mm) Deflection/span ratio 1/282 (maximum ratio allowed 1/150) Page 61 of 78

P2 REPEATED PRESSURE TEST No visible failures or functional defects to the test sample were observed after 50 cycles of repeated wind loads applied at a positive air pressure of 400Pa. No visible failures or functional defects to the test sample were observed after 50 cycles of repeated wind loads applied at a negative air pressure of 400Pa. In accordance with BS 6375-1:2015 Clause 6.5, as the classification after the resistance to wind load tests is the same as the classification before the resistance to wind load tests, the resulting classification for the sample is Class 1. (see following Table). Page 62 of 78

Air permeability [m³/h.m² of overall area] Air permeability [m³/h.m of opening joints] Graph of Air Permeability After Gusting. 8365614-Test Report. 100 90 80 70 60 50 Class 1 25.0 22.5 20.0 17.5 15.0 12.5 40 10.0 30 Class 2 7.5 20 Exfiltration [m³/h.m] 5.0 Infiltration [m³/h.m] 10 9 8 7 6 5 Exfiltration [m³/h.m²] Class 3 Infiltration [m³/h.m²] 2.5 2.25 2.0 1.75 1.5 1.25 4 1.0 3 Class 4 0.75 2 0.5 1 0.25 10 50 100 150 300 600 1000 Differential pressure [Pa] Page 63 of 78

Table of Average Air Permeability After Gusting. AIR PERMEABILITY TEST RESULTS - BS 6375-1:2015 / BS EN 1026:2000 Air Pressure [Pa] Clause 6.5 - After resistance to wind tests Three positive pressure pulses of 660Pa were applied prior to testing Average rate of air leakage [m³/h] Average rate of air leakage per meter length of opening joint [m³/h.m] Average rate of air leakage relative to area of sample [m³/h.m²] 50 47.8 2.79 5.20 100 73.9 4.32 8.03 150 102.6 5.99 11.15 200 - - - 250 - - - 300 - - - 450 - - - 600 - - - Note: The figures in the table above give the leakage as an average of the leakage at positive pressure and the leakage at negative pressure Total opening perimeter = 17.12m Overall area = 9.2m² BS 6375-1:2015 Clause 6.5 - Joint class = 1 BS 6375-1:2015 Clause 6.5 - Area class = 1 BS 6375-1:2015 Clause 6.5 - Overall class = 1 In accordance with BS 6375-1:2015 Clause 6.5, as the classification after the resistance to wind load tests is the same as the classification before the resistance to wind load tests, the resulting classification for the sample is Class 1. Page 64 of 78

Air permeability [m³/h.m² of overall area] Air permeability [m³/h.m of opening joints] 8365614-Test Report. Graph of Average Air Permeability After Gusting. 100 90 80 70 60 50 Class 1 25.0 22.5 20.0 17.5 15.0 12.5 40 10.0 30 Class 2 7.5 20 5.0 Average leakage 10 9 8 7 6 5 Class 3 2.5 2.25 2.0 1.75 1.5 1.25 4 Average leakage 1.0 3 Class 4 0.75 2 0.5 1 10 50 100 150 300 600 1000 Differential pressure [Pa] 0.25 Page 65 of 78

Air permeability [m³/h.m² of overall area] Air permeability [m³/h.m of opening joints] 8365614-Test Report. Graph of Average Air Permeability After Gusting Including +20% Lines for Each Class. 100 90 80 70 60 50 Class 1 25.0 22.5 20.0 17.5 15.0 12.5 40 10.0 30 Class 2 7.5 20 Average leakage [m³/h.m²] 5.0 10 9 8 7 6 5 Class 3 2.5 2.25 2.0 1.75 1.5 1.25 4 Average leakage [m³/h.m] 1.0 3 Class 4 0.75 2 0.5 1 10 50 100 150 300 600 1000 Differential pressure [Pa] 0.25 Page 66 of 78

Wind Load Resistance Test Results - BS EN 12211:2000. P3 SAFETY TEST 8365614-Test Report. No parts of the test sample became detached and the test sample remained closed after a wind load safety test applied at a positive air pressure of 1200Pa. No parts of the test sample became detached and the test sample remained closed after a wind load safety test applied at a negative air pressure of 1200Pa Page 67 of 78

BS 6375-2:2009. Clause 6 Performance characteristics and requirements for pedestrian doorsets Assessment Clause 6.2 Operating Forces: EN12046-2 and EN12217 The sample was tested three times, closing the leaf, handle, locking the key, unlocking the key, handle opening and maintaining the leaf to stay open, and highest of the three results were then recorded. Closing leaf force 35.77N (maximum 75N) Handle closing 61.12N (maximum 100N) Key torque to lock 0.10Nm (maximum 20Nm) Key torque to unlock 0.10Nm (maximum 20N) Handle opening 64.08 (maximum 100N) Force to maintain opening 42.42N (maximum 75N) Basic security (Annex A). BS 6375: Part 3: 2009 - Performance of Doors The objective of this test is to establish from if from the outside entry can be gained by defeating the glazing or locking system. The force used did not result in permanent set or plastic deformation of any tool. Damaged tools shall be replaced and the test did not exceed the maximum 3 minute time period. The screwdriver was used to no effect No entry could be effected Page 68 of 78

Description of Sample. (Sample 5) Sample type - A three leaf glaze in open in hinged bi-fold door assembly with one master leaf and two folding sliding leaves, full glass infill and standard threshold Material - Aluminium Finish - White Fittings - Master door A five point locking (two hook bolts, two cams, 1 dead bolt) Fuhr espagnolette system, ACDV258 cylinder, key locking Mila Pro Secure handle and four pin hinges. Two Sliding leaves A two point locking (two shoot bolts), twelve pin hinges and two rollers Weathersealing - Doubled sealed plastic weather strips Glass - Double glazed with 4-20-4 mm toughened glass sealed units Glass retention system - Internal beads and gaskets Sample dimensions - Overall - Length: 3740mm Height: 2570mm Master Leaves - Length: 1200mm Height: 2500mm Slave Leaves - Length: 1200mm Height: 2500mm Date of test - 7 September 2016 Laboratory temperature - 20.0 C Laboratory humidity - 34.8% Laboratory Atmospheric Pressure - 99.8kPa Page 69 of 78

Elevation Drawing of Door Assembly. Master Leaf Bifold Leaf Bifold Leaf - Handle Water Leakage Point - Hinge - Cylinder - Cam - Shoot Bolt - Dead Bolt - Hook Bolt Page 70 of 78

Air permeability [m³/h.m² of overall area] Air permeability [m³/h.m of opening joints] 8365614-Test Report. Graph of Air Permeability. 100 90 25.0 22.5 80 20.0 70 17.5 60 15.0 50 Class 1 12.5 40 10.0 30 7.5 Exfiltration [m³/h.m] Class 2 20 5.0 Infiltration [m³/h.m²] 10 9 8 7 Infiltration [m³/h.m] Class 3 2.5 2.25 2.0 1.75 6 1.5 5 Exfiltration [m³/h.m²] 1.25 4 1.0 3 Class 4 0.75 2 0.5 1 10 50 100 150 300 600 1000 Differential pressure [Pa] 0.25 Page 71 of 78

Table of Average Air Permeability. 8365614-Test Report. AIR PERMEABILITY TEST RESULTS - BS 6375-1:2015 / BS EN 1026:2000 Clause 6.3 - Before resistance to wind tests Three positive pressure pulses of 660Pa were applied prior to testing Air Pressure [Pa] Average rate of air leakage [m³/h] Average rate of air leakage per meter length of opening joint [m³/h.m] Average rate of air leakage relative to area of sample [m³/h.m²] 50 47.0 2.75 4.89 100 65.4 3.82 6.81 150 81.9 4.79 8.52 200 - - - 250 - - - 300 - - - 450 - - - 600 - - - Note: The figures in the table above give the leakage as an average of the leakage at positive pressure and the leakage at negative pressure Total opening perimeter = 17.12m Overall area = 9.6118m² BS 6375-1:2015 Clause 6.3 - Joint class = 1 BS 6375-1:2015 Clause 6.3 - Area class = 1 BS 6375-1:2015 Clause 6.3 - Overall class = 1 Page 72 of 78

Air permeability [m³/h.m² of overall area] Air permeability [m³/h.m of opening joints] Graph of Average Air Permeability. 8365614-Test Report. 100 90 80 70 60 50 40 Class 1 25.0 22.5 20.0 17.5 15.0 12.5 10.0 30 Class 2 7.5 20 Average Leakage [m³/h.m²] 5.0 10 9 8 7 6 5 4 Class 3 Average Leakage [m³/h.m] 2.5 2.25 2.0 1.75 1.5 1.25 1.0 3 Class 4 0.75 2 0.5 1 10 50 100 150 300 600 1000 Differential pressure [Pa] 0.25 ftfgjfj Page 73 of 78

Watertightness Test Results. BS EN 1027:2000 Clause 7 Watertightness before resistance to wind loads TABLE 2 - Spraying method 1A Pressure (Pascals) Point and time at which water leakage occurred 0 No leakage 50 No leakage 100 No Leakage 150 No Leakage 200 No Leakage 250 No Leakage 300 No Leakage 450 No Leakage 600 Water leaked from threshold opening joint onto sill at 0 minutes and 10 seconds. 750-900 - 1050 - BS 6375-2:2009. Clause 6 Performance characteristics and requirements for pedestrian doorsets Assessment Clause 6.2 Operating Forces: EN12046-2 and EN12217 The sample was tested three times, closing the leaf, handle, locking the key, unlocking the key, handle opening and maintaining the leaf to stay open, and highest of the three results were then recorded. Closing leaf force 41.22N (maximum 75N) Handle closing 59.03N (maximum 100N) Key torque to lock 0.10Nm (maximum 20Nm) Key torque to unlock 0.10Nm (maximum 20Nm) Handle opening 63.13N (maximum 100N) Force to maintain opening 46.88N (maximum 75N) Page 74 of 78

Basic security (Annex A). BS 6375: Part 3: 2009 - Performance of Doors The objective of this test is to establish from if from the outside entry can be gained by defeating the glazing or locking system. The force used did not result in permanent set or plastic deformation of any tool. Damaged tools shall be replaced and the test did not exceed the maximum 3 minute time period. The screwdriver was used to no effect No entry could be effected Page 75 of 78

Photograph of Sample. Page 76 of 78

Test Samples. Sample Id ER Number Description 1 10156882 Aluminium Bi-Fold Doors Test Requirements. PAS 24/BS4873 Type Test Clause Results table Requirements Actual test results See Table A - PAS 24/BS4873 Type Test Summary of Test Results (Table A). Sample Id Description Air Permeability Watertightness Wind Resistance 1 Open out standard (PAS24) 2 Open Out Low Threshold Class 1 2A A2 ( at 800Pa) 3 Open In Low Threshold Class 1 3A A2 ( at 800Pa) 4 Open Out Standard Threshold Class 1 4A A2 ( at 800Pa) 5 Open In Standard Threshold Class 1 8A Not Assessed Description of Test Samples. Sample Description 1 off three leaf glaze in open out hinged bi-fold door assembly with one master leaf and two folding sliding leaves, full glass infill and low threshold (Sample 2) 1 off three leaf glaze in open in hinged bi-fold door assembly with one master leaf and two folding sliding leaves, full glass infill and low threshold (Sample 3) 2 off three leaf glaze in open out hinged bi-fold door assemblies with one master leaf and two folding sliding leaves, full glass infill and standard threshold (Samples 1 and 4) 1 off three leaf glaze in open in hinged bi-fold door assembly with one master leaf and two folding sliding leaves, full glass infill and standard threshold (Sample 5) Page 77 of 78

Glossary of Terms. PASS: Complies. Tested by BSI engineers at BSI laboratories. PASS1: Complies. Witnessed by BSI engineers in manufacturers laboratory. PASS2: Complies. Tests carried out by third party lab; results accepted by BSI. PASS*: Report resulted in uncertainty and states that Compliance is more probable than non-compliance. FAIL: Non compliance Product does not meet the requirements of this clause. FAIL*: Report resulted in uncertainty and states that Non-compliance is more probable than compliance. N/A: Not applicable to design under consideration. N/T: Not tested due to similarity to previously tested item; reference earlier test report. Conditions of Issue. This Test Report is issued subject to the conditions stated in current issue of 'BSI Terms of Service'. The results contained herein apply only to the particular sample(s) tested and to the specific tests carried out, as detailed in this Test Report. The issuing of this Test Report does not indicate any measure of Approval, Certification, Supervision, Control or Surveillance by BSI of any product. No extract, abridgement or abstraction from a Test Report may be published or used to advertise a product without the written consent of BSI, who reserve the absolute right to agree or reject all or any of the details of any items or publicity for which consent may be sought. Should you wish to speak with BSI in relation to this report, please contact Customer Services on +44 (0)8450 80 9000. BSI Kitemark House Maylands Avenue Hemel Hempstead Hertfordshire HP2 4SQ Opinions and Interpretations expressed herein are outside the scope of our UKAS accreditation. Unless otherwise stated, any results not obtained from testing in a BSI laboratory are outside the scope of our UKAS accreditation *** End of Report *** Page 78 of 78