* * Data Sheet and Operating Manual. Digital manometer ME01 ## # 87 # HL S#### Dust explosion protection Zone 22.

Similar documents
Operating Manual * * Pressure Transmitter. Table of Content. 1 Safety Guidelines. 1.3 Risks due to Non-Observance of Safety Instructions

Instruction Manual Contact Pressure Vacuum Gauge

Instruction Manual Differential Pressure Transmitter

Instruction Manual Differential Pressure Transmitter

Instruction Manual Contact Pressure Gauge

* * Operating manual ME12... R/S. Remotely configurable digital pressure transducer for use in explosive areas

Instruction Manual Differential Pressure Gauge

Installation and Maintenance Instruction Manual

Installation and Maintenance Instruction Manual

Type Operating Instructions. 2/2-way solenoid valve 2/2-Wege Magnetventil Electrovanne 2/2 voies.

VS18/26 with PROFINET and EtherNet/IP Interface. ATEX Installation Instructions

Installation and Maintenance Instructions for F5509/F6509 Differential Pressure Gauges

SITRANS P measuring instruments for pressure

Operating Manual. Diaphragm Seals Models , 107, , 207,

Expert Hydrostatic Level Transmitters

OPTIBAR P 1010 C Technical Datasheet

2 Overview. SITRANS P measuring instruments for pressure. Transmitters for gage and absolute pressure. Z series for gage pressure

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation

Installation and Maintenance Instruction Manual

Pressure Measurement. Transmitters for basic requirements SITRANS P Z for gauge pressure. 2/4 Siemens FI Overview

Pressure Transmitter P41

Operating Instructions

Mounting and Operating Instructions EB 2558 EN. Self-operated Pressure Regulators. Type Pressure Build-up Regulator

Installation and Maintenance Instruction Manual Process gauge with integrated transmitter, model T5500E

Mounting instructions. Strain transducer SLB-700A. B 26.SLB700A.10 e

Pressure Measurement Single-range transmitters for general applications

Compact differential pressure switch Flameproof enclosure Ex d Models DE, DEC

Measurement accessories METPOINT OCV for the measurement in systems up to 40 bar

PRAHER PLC-MP AQUASTAR MANAUL 2009

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI

Type BBS-03, BBS-05, BBS-06, BBS-25

Operating Manual VSA100A. tina29e1 ( )

Differenz-Drucktransmitter Differential pressure transmitter Transmetteur de pression différentielle bar

Operating Instructions for Intrinsically Safe Pressure Transmitters Series DMG/******** for Hazardous Application in Coal Mining Industry

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI US Edition

DK46 - DK800 Supplementary instructions

sitrans p Operating Instructions (de/en) Edition 03/2004

Type 2000 INOX. Quickstart. English Deutsch Français. 2/2-way angle seat valve 2/2-Wege Schrägsitzventil Vanne à siège incliné 2/2 voies

Operating Instructions

better measurement Simply a question of SCHMIDT Flow Sensor SS The cost-effective alternative in pressurised systems up to 10 bars.

* * Operating manual. DE49 ## A BA_EN_DE49_A Rev. ST4-C 01/18. Digital differential pressure transmitter with external sensor

Pressure Measurement Single-range transmitters for general applications

x act i Precision Pressure Transmitter for Food Industry, Pharmacy and Biotechnology Stainless Steel Sensor accuracy according to IEC 60770: 0.

Supplementary Installation and Operating Instructions. Variable Area Flow Meters SGK-1 Ex SGK-2 Ex SGK-3 Ex. Category: II 2G Ex IIC II 3G Ex IIC

SITRANS. Pressure transmitter SITRANS P, Z series for gauge and absolute pressure. Introduction. Safety instructions 2.

Manual Power relay SR853

LTB013EN. Operating Instruction Trimod Besta Level Switch types XA 5, XB 5 for use in potentially explosive atmospheres acc.

Installation and Operating Instructions Bypass Flow Meter DST

x act i Precision- Pressure Transmitter for Food Industry, Pharmacy and Biotechnology Stainless Steel Sensor

Precision pressure sensor Basic version Model CPT6020

Types and approvals. Page 1/6. Data Sheet

Contents. Operating instructions. Pressure switch, heavy-duty version Model PSM-520

ATM.ECO - Analog Pressure Transmitter

ATM.1ST/Ex - High Precision Transmitter

Pressure Switches Application Guideline

Type 0404 / /2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation

Pressure Transmitters 36 F-27839

Operating and maintenance manual Filter and reducing station Series / 1.0

Electro-Pneumatic Converter YT-940 SERIES

Peak Pressure Indicator MSI-3

Air Sensor. SAC Ex. Manual ATEX. AQ Elteknik AB

Pneumatic pressure switch 20DD

1 Overview. Pressure Measurement Transmitters for basic requirements. 1/16 Siemens FI SITRANS P220 for gauge pressure

ED 701 Hygenic Pressure Transmitter

E8AA. Pressure Sensor of Stainless Steel Construction Is Ideal for a Wide Range of Applications. Pressure Sensor (Stainless Steel Diaphragm)

MJK Expert 700 / 800 / 900 / 7070 / 7060 MJK Expert 1400 / 3400

ATM.ECO/IS - Analog Transmitter with Temperature compensation

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/16 Siemens FI US Edition

ATM.1ST. Pressure transmitters CUSTOMER BENEFITS

Type 3709 Pneumatic Lock-up Valve. Translation of original instructions. Mounting and Operating Instructions EB 8391 EN

Electronic relative and differential pressure switch type 616

PULSAR 5000 SERIES OPERATING & INSTALLATION INSTRUCTIONS SERIES 5000 PLEASE READ CAREFULLY BEFORE INSTALLING

3-port seat valves with externally threaded connection, PN 16

Gas density monitor With integrated transmitter Model GDM-100-TI

Instruction Manual AD 1000 / BA 1000 Absolute Pressure Sensor

Proportional pressure regulators VPPE

Type C-CUT. Quickstart. English Deutsch Français

Mounting and operating instructions EB 2530 EN. Self-operated Pressure Regulator. Pressure Reducing Valve Type M 44-2

2-Port Seat Valves with Flange, PN 16

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

Operating Instructions Melt Pressure Sensor

DMK 458. Pressure Transmitter for Marine and Offshore. Ceramic Sensor. accuracy according to IEC 60770: standard: 0.25 % FSO option: 0.

OPERATING INSTRUCTIONS MANUAL FOR QACV PNEUMATIC DOSING PUMP

FPD20 Series. Gear wheel flow sensor

Note: the lock-out circuit must be in accordance with Section 8.7 of DIN/VDE Twin thermostats ATH.-SW-2020 ATH.-SW-2070 ATH.

Pilot HON 625. Entwurf. Product information. serving the gas industry worldwide

ATH-EXx. B Operating Instructions

Gas Pressure Regulator HON 300

2-Port Seat Valves with Flange, PN 16

3G Operating instructions. Digital Purge Gas Valve 3G Type: Document no.: D0001 Version: 01. July 2011/Rev.

Magnetic level switch type MR783 Instruction Manual

Bourdon tube pressure gauge for diaphragm seals

Pressure Measurement Single-range transmitters for general applications

P499 Heavy Duty Pressure Transducer

Self-operated Pressure Regulators for special applications

Installation, operating and maintenance Instructions for Seemag bypass level indicator

PLEASE READ CAREFULLY BEFORE INSTALLING OR USING MEGA POOL SAVER MPS 1100

Operating instructions - Translation of the original -

SPD310/SPD360 Air Differential

2/2-Way Solenoid Control Valve

Transcription:

*09005087* DB_BA_EN_ME01_S Rev.A 12/16 *09005087* d e v e l o p i n g s o l u t i o n s Data Sheet and Operating Manual ME01 Digital manometer Table of Contents ME01 ## # 87 # HL S#### Dust explosion protection Zone 22 1 Safety guidelines 2 Application purpose 3 Product and function description 4 Installation and assembly 5 Commissioning 6 Maintenance 7 Transportation 8 Service 9 Accessories 10 Waste disposal 11 Technical Data 12 Dimensional drawings 13 Order Codes 14 Attachments 1 Safety guidelines 1.1 General Information This operating manual contains instructions fundamental to the installation, operation and maintenance of the device that must be observed unconditionally. It must be read by the assembler, operator and the specialized personnel in charge of the instrument before it is installed and put into operation. This operating manual must always be accessible at the place of installation. The subsequent sections on general safety instructions 1.2-1.7 as well as the following special instructions ranging from intended use to disposal 2-10 contain important safety instructions the nonobservance of which can cause danger to persons, animal and physical objects. 1.2 Personnel Qualification The instrument may only be installed and commissioned by specialized personnel familiar with the installation, commissioning and operation of this product. Specialized personnel are persons who can assess the work they have been assigned and recognize potential dangers by virtue of their specialized training, their skills and experience and their knowledge of the pertinent standards. For explosion-proof models the specialized personnel must have received special training or instruction or be authorized to work with explosion-proof instruments in explosion hazard areas. 1.3 Risks due to Non-Observance of Safety Instructions Non-observance of these safety instructions, the intended use of the device or the limit values given in the technical specifications can be hazardous or cause harm to persons, the environment or the plant itself. The supplier of the equipment will not be liable for damage claims if this should happen. 1.4 Safety Instructions for the Operating Company and the Operator The safety instructions governing correct operation of the instrument must be observed. The operating company must make them available to the installation, maintenance, inspection and operating personnel. Dangers arising from electrical components, energy discharged by the medium, escaping medium and incorrect installation of the instrument must be eliminated. The particulars can be found in the respective regulations such as DIN, EN, explosion hazard,

accident prevention regulations and also in the industry guidelines issued by the DVWG, GL, etc. and the VDE as well as the local EVUs. The instrument must be decommissioned and secured against inadvertent re-operation if a situation arises in which it must be assumed that safe operation is no longer possible. Reasons for this assumption could be: evident damage to the instrument failure of the electrical circuits long storage in temperatures over 85 C considerable strain due to transport Repairs may be carried out by the manufacturer only. A professional single conformity inspection as per DIN EN 61010, section 1, must be carried out before the instrument can be re-commissioned. This inspection must be performed at the manufacturer's location. Correct transport and storage of the instrument are required. 1.5 Unauthorised Modification Modifications of or other technical alterations to the instrument by the customer are not permitted. This also applies to replacement parts. Any modifications/alterations required will be carried out by Fischer Mess- und Regeltechnik GmbH only. 1.6 Impermissible modes of operation The operational safety of this instrument can only be guaranteed if it is used as intended. The instrument model must be suitable for the medium used in the system. The limit values given in the technical data may not be exceeded. 1.7 Safe working practices for maintenance and installation work The safety instructions given in this operating manual, any nationally applicable regulations on accident prevention and any of the operating company's internal work, operating and safety guidelines must be observed. The operating company is responsible for ensuring that all required maintenance, inspection and installation work is carried out by qualified specialized personnel. 1.8 Explanation of symbols WARNING! indicates a potentially dangerous situation, non-observance of which could endanger persons, animals, the environment or objects. INFORMATION! highlights important information efficient and smooth operation. TIP! indicates recommendations that are not specifically necessary in certain situations but which could be useful. 2 Application purpose Electronic manometer for measuring over-pressure and under-pressure of fluid and gas-like measuring substances. The device is to be exclusively used for the applications agreed between the manufacturer and the user. Explosion hazard area classification The digital manometers ME01 are suitable for use as 'Electrical equipment for use in areas with combustible gases', zone 22 - dry dusts. Designation as per guideline 2014/34/EU II 3D Ex tc IIIB T125 C IP65 3 Product and function description 3.1 Design and mode of operation A ceramic measuring cell acts as the pressure transducer. The high resistance of the ceramic materials that are used allow use even for aggressive media. There is a resistance measuring bridge attached to the side of the measuring diaphragm that faces away from the medium. When pressure is exerted, the membrane distorts in the elastic range. t the same time, the resistance values of the bridge change proportionally to the measuring pressure. These values are implemented and displayed by the installed electronics. There are electrical uniform signals 0/4 20 ma and 0 10 V in a 3-wire system available for remote transmission.

4 Installation and assembly As standard, the device with the connecting port for connection to pipes and other connection parts, such as the welding sleeve, union nut with soldering and welding nipples, is equipped with soldering and welding nipples (see data sheet MZ...). It can be mounted to a wall using the wall bracket (see data sheet MZ...). Manometer screw connections for 10, 8, 6 mm dia. pipes can be supplied for connection to pipes.the enclosure protection type IP 65 is only guaranteed, if a suitable power supply cable is used. 4.1 Process connection By authorized and qualified specialized personnel only. Only for the designated mechanical process connection - for the model, see the order code on the device type plate. The pipes need to be depressurized when the device is being connected. Do not mount the device against existing water columns, and secure suitably against pressure surges. Use only with media suitable for operation. Observe the maximum pressure. Check that the pressure connections do not leak before commissioning. 4.2 Electrical connection By authorized and qualified specialized personnel only. Disconnect the system from the mains before connecting the device. Do not take out the connecting plug while energized Explosion protection instructions To guarantee safe operation of the instrument, the supply circuit must satisfy the requirements for zone 2, category 3, and the locally applicable regulations and guidelines for the installation and operation of electrical systems in explosion hazard areas (e.g. EN 60079-0). The supply voltage may not exceed 30 V DC. The supply circuit must be protected by a slow 200 ma fuse. Only a CE-compliant power supply unit may be used as a power supply. 4.3 Wiring diagram Static electricity Do not take out the connecting plug while energized Three-conductor circuit output Signal The case must be equipped with an earth connection to reduce the surface resistance. 5 Commissioning Operating voltage All electrical supply, operating and measuring lines, and the pressure connections must have been correctly installed before commissioning. All supply lines are arranged so that there are no mechanical forces acting on the device. If liquid measuring media are used the pressure connection line must be vented, as liquid columns of different heights in the pipes can cause measuring errors. The instrument must be protected against frost if water is used as a medium. The pressure sensing lines must be installed on an incline so that no condensation pools can form. The pressure sensing lines need to be kept as short as possible and installed without sharp bends to avoid interfering delay times. Appropriate shutoff valves must be provided to ensure safety during installation, maintenance and inspection

6 Maintenance The instrument is maintenance-free. We recommend checking the instrument at regular intervals to ensure reliable operation and a long service life. Inspecting the output signal. Check the leak-tightness of the pressure connection lines. Check the electrical connection (cable clamp connections). The precise test cycles and operating and ambient conditions need to be adjusted. If various instrument components interact, the operating instructions of all the other instruments also need to be observed. 7 Transportation The measuring device must be protected against impacts. It may only be transported in packaging specifically intended for transport. 8 Service All defective or faulty devices should be sent directly to our repair department. We would ask you to please coordinate all return shipments with our sales department so that we can ensure careful processing of all faulty devices for our customers. Measuring residues in and on dismantled devices can be a hazard to people, animals and the environment. Take adequate preventive measures. If required, the devices must be cleaned thoroughly. 9 Accessories Manometer accessories acc. to data sheet MZ... 10 Waste disposal For the sake of the environment... Please help to protect our environment and dispose of or recycle used instruments as stipulated by the applicable regulations.

11 Technical Data Measuring range in bar 0-1.6 0-2.5 0-4 0-6 0-10 0-16 0-25 0-40 0-60 Overpressure-proof in bar 3.2 5 8 12 20 32 50 80 120 Measuring range in bar - 1..0-1..0.6-1..1.5-1..3-1..5-1..9-1..15 0...-1 Overpressure-proof in bar 2 3 3 8 12 20 32 2 Permissible ambient temperature -10 C 60 C Admissible medium temperature Max. 60 C Pressure connection Electrical connection Connection ports with external thread G½ B stainless steel, rustproof Standardised plug DIN EN 175 301-803-A Protection class: IP 65 acc. to DIN EN 60529 Parts in contact with the medium AISI 316L (1.4404), Seal: Viton Casing AISI 304 (1.4305) Electrical data Power supply Rated voltage Allowed operating voltage U b inner effective capacity C i effective inner inductivity L i Only CE-compliant power supply units with a slow 200 ma fuse may be used. 24V DC 15...30 V DC max. 270nF max. 980 H Electrical connection type Output signal Load at rated voltage Current/voltage limit Zero-point, temperature drift Measuring range, temperature drift Linearity Hysteresis Three-conductor 0..20 ma / 4..20 ma / 0..10 V 450 for output 0..10V: ca. 10.5 V for output 0/4..20 ma: ca. 24 ma 0.4 % FS/10 K 0.05 % FS/10 K < 1 % of the measuring range < 0.5 % of the measuring range Identification acc. to ATEX guideline 2014/34/EU II 3D Ex tc IIIB T125 C IP65

12 Dimensional drawings (all dimensions in mm unless otherwise specified) SW22 M16 x 1.5 Manometer connection port G1/2 acc. to DIN EN 837

13 Order Codes Digital manometer Type ME01 8 7 H L S#### Measuring range 0... 1 bar... > 0 2 0...1.6 bar... > 0 3 0...2.5 bar... > 0 4 0... 4 bar... > 0 5 0... 6 bar... > 0 6 0... 10 bar... > 0 7 0... 16 bar... > 0 8 0... 25 bar... > 0 9 0... 40 bar... > 1 0 0... 60 bar... > 1 1-1... 0 bar... > 3 1-1...0.6 bar... > 3 2-1...1.5 bar... > 3 3-1... 3 bar... > 3 4-1... 5 bar... > 3 5-1... 9 bar... > 3 6-1... 15 bar... > 3 7 Measurement accuracy Characteristic curve dev. Relative pressure 1.0...> M Characteristic curve dev. Absolute pressure 1.0...> S Discharge port Connection ports with external thread G½ B bottom, Stainless steel... > 8 7 Electrical output signal 0 20 ma 3-wire (STANDARD)... > A 0 10 V DC 3-wire (STANDARD)... > C 4 20 ma 3-wire (STANDARD)... > P Electrical connection Plug 4-pin, standardised plug DIN EN 175 301-803-A... > H Operating voltage 24 V DC / AC... > L Customer-specific no. Code for use in Zone 22 - Danger due to dry dusts:` II 3D Ex tc IIIB T125 C IP65... > S####

14 Attachments Technische Änderungen vorbehalten Subject to change without notice Changements techniques sous réserve Fischer Mess- und Regeltechnik GmbH Bielefelder Str. 37a D-32107 Bad Salzuflen Tel. +49 5222 9740 Fax +49 5222 7170 email: info@fischermesstechnik.de www.fischermesstechnik.de