BIOGAS COMBUSTION PLANT MAINTENANCE MANUAL

Similar documents
OPTIMA 7 - BIOGAS Calibrating the gas sensors SENSOR ADJUSTMENT. Diamond Scientific 625 Peachtree St., Cocoa, Florida /Tel:

Appendix D: SOP of INNOVA 1412 Photoacoustic Multi-Gas Monitor. Description and Principle of Operation

ACV-10 Automatic Control Valve

Instruction and Maintenance Manual

Continuous Gas Analysis ULTRAMAT 23 Supplement 1 for Operating Instructions C79000-G52xx-C Product Information

Specifications and information are subject to change without notice. Up-to-date address information is available on our website.

Using the UltraRAE. Firmware 2.35

Touch Screen Guide. OG-1500 and OG Part # T011

Portable Gas Monitor GX User Maintenance Manual (H4-0050)

Instruction Manual Dräger MSI P7 and MSI P7 plus

Instruction and Maintenance Manual

Pegas 4000 MF Gas Mixer InstructionManual Columbus Instruments

RAM Operation Manual. Worldwide Manufacturer of Gas Detection Solutions

MASSACHUSETTS STATE POLICE CRIME LABORATORY. Certificate of Calibration Procedure for the Alcotest 9510

RAM 4021-PR. Operation Manual. Worldwide Manufacturer of Gas Detection Solutions

Armfield Distillation Column Operation Guidelines

GA-300 Gas Analyzer. Technical Note. Overview. Front Panel. iworx Systems, Inc. GA-300

JETFIRST 150 RTA SYSTEM OPERATING MANUAL Version: 2 Feb 2012

2. Determine how the mass transfer rate is affected by gas flow rate and liquid flow rate.

KIV-SACS Safe automatic calibration system:

TANK MANAGER FOR TWO TANKS OPERATING MANUAL. 10/31/11 C-More T6C L color touch panel

1)! DO NOT PROCEED BEYOND THIS MARK

RAM Operation Manual

RAM 4021-DPX Operation Manual

Advanced Test Equipment Rentals ATEC (2832)

Continuous gas analysis ULTRAMAT 23 Supplement 2 for Operating Instructions C79000-G52xx- C216-03

Cover Page for Lab Report Group Portion. Head Losses in Pipes

LEGO Engineering Conferences ROBOLAB and MINDSTORMS Education Version 4.5 March 2008

STANDARD OPERATING PROCEDURES. Andersen Instruments Federal Reference Method (FRM) Ambient Particulate (PM 10 /PM 2.

Best Practice Guide, Servomex 2700

OxyCheq Expedition-X Oxygen Analyzer. Operator s Manual

We measure it. For gas and water installers. testo hpa. bar

Met One E-BAM Particulate Monitor

METHOD 21 - DETERMINATION OF VOLATILE ORGANIC COMPOUND LEAKS. 1.2 Scope. This method is applicable for the

USER MANUAL. Intelligent Diagnostic Controller IDC24-A IDC24-AF IDC24-AFL IDC24-F IDP24-A * IDP24-AF * IDP24-AFL * IDP24-F * 1/73

Model 130M Pneumatic Controller

DO NOT PRINT THIS PAGE

Dissolved Oxygen/Temp Waterproof Tester

PREPARED BY: Marshall K. Cheung, Ph.D., Laboratory Director. REVISED BY: Marshall K. Cheung, Ph.D., Laboratory Director

BI-680 Online Dissolved Oxygen Controller Instruction Manual

Columbus Instruments

RAM Operation Manual. Worldwide Manufacturer of Gas Detection Solutions

Gas Absorption Draft Standard Operating Procedure

CircuFlow Quick Setup Guide

5 Channel Calibrator

Burner Management System DEMO Operating instructions

DF-550E PROCESS ANALYSERS APPLICATIONS FEATURES

DPC-30 DPC-100. Reference Manual

Hand-held pressure calibrator with integrated pump Model CPH6600

Cover Page for Lab Report Group Portion. Pump Performance

User manual CF8-D/W-IN

RAM 4021 Operation Manual

User Manual. asense VAV. CO 2 / temperature sensor with built-in general purpose controller

High Pressure Chem-SCAN Operating Manual

Instructions for Assembly, Installation, and Operation of the Gas Addition Kit Accessory with the CEM Discover Systems

Operating Instructions Part No

X-dock Software History

Title: Standard Operating Procedure for R&R Environmental Devices Model MFC201 Gas Dilution Calibrator

METHOD 25A - DETERMINATION OF TOTAL GASEOUS ORGANIC CONCENTRATION USING A FLAME IONIZATION ANALYZER

Title: Standard Operating Procedure for Dasibi Model 5008 Gas Dilution Calibrator

OXY Integral. INTERCON ENTERPRISES INC Tel: Fax: Internet:

G200 Analyzer Range. Operating Manual

User Manual 1 P a g e Rev. V1.6-EN 11/08/2014

SL G3. Warning

陕西创威科技有限公司. Shaanxi Creat Wit Technology Co., Ltd. Precision pressure calibrator-cwy300 Operating Manual

Arizona State University Center for Solid State Electronics Research Issue: E Title: Heat Pulse 610 Operating Procedure Page 1 of 7

Bante821 Portable Dissolved Oxygen Meter Instruction Manual

973-SF 6 Analyzer. Precise and Stable SF 6 Gas Analyzer REFLECTING YOUR STANDARDS

CF8-W-Disp-CO. User manual. CO 2 / CO sensor with built-in general purpose controller

GEM-500 OPERATION MANUAL

2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic. Pressure Measurement Engineered solutions for all applications

Instruction Manual. Biogas Analyzer InCa Bio 04

Standard Operating Procedure Inductively Coupled Plasma Optical Emission Spectrometer (ICP-OES) - Thermo Scientific icap 6300

Ultima. X Series Gas Monitor

PRODUCT CONFORMITY CERTIFICATE

Continuous Gas Analysis In situ laser gas analyzers TÜV and MCERTS add-on for LDS 6 operating instructions Compact Operating Instructions

STANDARD OPERATING PROCEDURE

SDM-2012 Docking Station Standalone Configuration Operator s Manual

AUTOMATIC TIRE INFLATOR # MW-60, MW-60-4WAY & MW-64HP

Table of contents. Table of contents 1. Installation 2. Introduction ( Display, monitor ) 3. Introduction ( Operating elements ) 4

WATER CONTROL SYSTEM QUICK START

How to calibrate the formaldehyde sensor within a PPMonitor Wireless Unit:

Digital Piston Standard

Using Modbus Protocol with the ALTUS Net Oil Computer. Instruction Manual

PERFORM Operating Document

Coriolis Mass Flow Meter

INDUSTRIAL HYGIENE GROUP Standard Operating Procedure. TVA-1000 PID/FID Portable Toxic Vapor analyzer. 1 of 9. Contents

CONTROL LOGIC DESCRIPTION DOCUMENT IC-410ND

Optical Dissolved Oxygen Meter

User Manual for the Mars Calibration Bench

Three Lakes Association Hydrolab for Dummies. Table of Contents:

CCT-7320/ROC-2313 Reverse Osmosis Controller

Inert Air (N2) Systems Manual

G100 Range. Operating Manual

Manual Weighingblock VB2 series and Uniscale

G100 RANGE G100, G110, AND G150 OPERATING MANUAL

Ventam 85 Installation & Commissioning Instructions

Control & Maintenance. INT69 Diagnose INT69 TM Diagnose. Protect the heart of your system

Field Instrumentation Training Strategy

MEGAS 2.0. Gas analysis with direct C-Level Calculation and Bus-Connection. Data sheet

Transcription:

BIOGAS COMBUSTION PLANT MAINTENANCE MANUAL (PLANT MAINTENANCE MANUAL) Puente Gallego Landfill, Rosario (Argentina) ARIA.BIZ S.A. Montevideo 589, 7 floor 1019 Capital federal Argentina Tel: +54 11 5171 8200 Fax: +54 11 5171 8201 Pág. 1/8

4.2.6 Equipment calibration procedure 4.2.6.1 SCOPE This procedure defines the management, checks and calibration of the equipment used for process control. 4.2.6.2. RESPONSIBILITY PM will be responsible for the management of the pieces of equipment needing regular calibration for the biogas installations. The regular check and calibration will be entrusted to the operators and/or the equipment supplier. The PM will be responsible for checking the equipment s proper working order, as well as check and store up the calibration certificates. 4.2.6.3. OPERATING MODES Fixed methane and oxygen analyzer The biogas analyzer installed at the plant, which measures the concentration of methane and oxygen in the biogas, shall be systematically checked and calibrated. The PM in charge of the plant shall, in collaboration with the local operator, keep the unit conditions and functioning under control, as well as carry out the calibration at least once a month and also make sure that certified, valid gas calibration cylinders will be used for calibration. Moreover, the PM shall verify that the piece of equipment will be properly identified and that the calibration expiry date will be clearly visible. In the event that anomalies are found in equipment operation, the PM may request further checks and additional calibrations (if any) to be carried out by the supplier. The calibration gas shall be procured from certified gas suppliers. All the gas calibration cylinders shall be accompanied by a quality certificate. The operators shall be qualified and aware of the calibration procedures. The fixed analyzers can be calibrated either together or individually. In the following description, it is assumed that both pieces of equipment shall be calibrated simultaneously. Refer to the specific manual available at the plant for more details on the fixed equipment calibration operating modes. Pág. 2/8

Fixed methane analyzer: Siemens ULTRAMAT 23 Fixed oxygen analyzer: Siemens OXIMAT 61 The PM in charge of the plant shall, in collaboration with the local operator, keep the unit conditions and functioning under control, as well as carry out the calibration at least once a month and also make sure that certified, valid decanters will be used for calibration. Below is a description of the operating procedure for manual equipment calibration. To calibrate the Ultramat point 0 (zero) and the Oximat span (20.9% O2): - Open valve 1 and close valve 2 (see diagram) indicated below within the analysis panel (A: open C: closed) C Biogas line inlet N 2: C N 3: C N 1: A Biogas line outlet to the analyzer Air inlet - This will allow atmospheric air to flow in for the calibration of the max. percentage of O2 (20.9%) and 0% methane (CH4). - Then go to the Oxymat equipment and press the second button (not identified) found on the right of the screen. - The following menu will be displayed: a. Diagnostic b. Adjustment c. Measurement margin d. Parameters e. Configuration - Select Adjustment and enter the level 1 code (known only to the PM in charge): to do this, move the direction arrows up or down to change the value of the selected digit, and the right or left arrows to change the location. Then press ENTER. - The following submenus will be displayed in the Adjustment menu: a. Point 0 adjustment b. Sensitivity adjustment c. Point 0/sensitivity nominal values d. Full/individual adjustment e. Self-calibration. Pág. 3/8

- To obtain the maximum O2 (i.e. minimum CH4), select the Point 0 adjustment menu and press ENTER: the equipment will measure a reference value in the top part (20.9) and another one which will be the value measured below the first one. - Verify that the reference value is 20.9%; otherwise, proceed with item c (point 0/sensitivity nominal values) and set the point 0 value by adjusting the same to 20.9%. - The second value will oscillate until it gets stable (note down such value on the module as the detected O2/air value of the Oximat module); if the value differs from 20.xx (set-point), press the MEAS button on the Oximat, then accept the value forced on the calibration by touching the corresponding value (note down such value on the module as the calibrated O2/air value of the Oximat module). - Take note of the value read by the Ultramat (note down this value as the detected O2/air value of the Ultramat module). - Press the Ultramat analyzer CAL key, then wait for the process to be completed (note down this as the calibrated O2/air value of the Ultramat module). To calibrate the Ultramat span: - Press the Ultramat ENTER key: you will access the main menu list: a. Diagnostic b. Adjustment c. Parameters d. Configuration - Select Adjustment by moving around with the direction arrows, then press ENTER. - The equipment will ask you to enter the level 1 code. - Another menu with the options below will be displayed: a. MMIR adjustment b. Pressure sensor adjustment c. Self-calibration. - Select menu a and prepare the calibration decanter in order for the same to be connected when requested. The following will appear on the new screen (MM CH4 Adjustments): a. Nominal values: MM 1 + 2 b. Full adjustment c. Enter self-calibration d. MM 1+2 : 60.2 e. MM 1+2: 60.2 - The nominal value shall be changed in the preceding step, in the event that the MM 1+2 number differs from the calibration cylinder one. To do this, go to the corresponding line (a) and press Pág. 4/8

ENTER so as to access the number sector, then change the number by means of the direction arrows. Finally, press ENTER again. - After the preceding step is completed, a new screen will appear, which will display the following: a. MM 1 + 2 M1 adjustment start b. MM 1 + 2 M2 adjustment start. - Select option a, then press ENTER. The following will appear on the screen: Nominal value adjustment 60.2 Actual value adjustment (value recorded by the equipment) Enter gas pattern. - Now connect the analysis decanter sleeve to valve 3 shown in the diagram illustrated above. - The equipment will start measuring the gas pattern; when the same has stabilized (note down this value as the detected CH4 value 60.2% of the Ultramat module), press ENTER to accept the measured value (note down this value as the calibrated CH4 value 60.2% of the Ultramat module). - Press ESC, then press MEAS to record the changes; next, select YES and press ENTER again. The methane Maximum calibration will now be concluded. To calibrate the O2 minimum, go to the OXIMAT equipment and proceed as follows. - Press the second button (not identified) found on the right of the screen. - The following menu will be displayed: a. Diagnostic b. Adjustment c. Measurement margin d. Parameters e. Configuration. - Select Adjustment and enter the level 1 code, as described above. - The following submenus will be displayed in the Adjustment menu: a. Point 0 adjustment b. Sensitivity adjustment c. Point 0/sensitivity nominal values d. Full/individual adjustment e. Self-calibration. - To obtain the O2 minimum (0%), select the Sensitivity adjustment menu and press ENTER: the equipment will measure a reference value in the top part (0.00) and another one which will be the value measured below the first one. If the higher value is different from 0, it shall be modified: to do this, go to the corresponding line (b) and press ENTER so as to access the number sector, then change the number by means of the direction arrows. Finally, press ENTER again. Pág. 5/8

- The lower value will oscillate until it gets stable (note down such value as the detected O2 0% value of the Oximat module); if the value differs from 0.00 (set-point), press the MEAS button on the Oximat, then accept the value forced on the calibration (note down such value as the calibrated O2 0% value of the Oximat module). The operator shall complete the analyzer calibration form MCTR008. Innova methane and oxygen portable analyzer The PM in charge of the plant shall, in collaboration with the local operator, keep the unit conditions and functioning under control, as well as carry out the calibration at least once a month and also make sure that certified, valid decanters will be used for calibration. In the event that anomalies are found in equipment operation, the PM may request further checks and additional calibrations (if any) to be carried out by the supplier. Below is a description of the operating procedure for CH4 %V manual calibration. - Switch the equipment on, then wait for the warm-up phase to end. - Press the and buttons together for 3 seconds, until the Menu features message disappears. - When the Begin CAL message is displayed on the screen, press to accept. - Shift from Auto CAL, by pressing or, to Manual CAL, then accept by pressing. - CH4 will be displayed in the top right corner of the screen, referring to the selected sensor. Change by pressing until the letters TC are displayed in the left bottom part. This corresponds to the methane sensor for the % value. - Having accepted the TC calibration, you will have to correct the sensor setting to 60 (by means of the or buttons) and then accept by pressing. - Start the calibration procedure, by first leaving the decanter disconnected and then coupling the same when it reads Apply gas. Wait the necessary time: the Calibration OK message will be displayed. Accept by pressing and take note of the changes. To calibrate the O2 sensor, proceed as follows: - Press the and buttons together for 3 seconds, until the Menu features message disappears. - When the Begin CAL message is displayed on the screen, press or to go to Advanced Features. - Enter by pressing and then press or until Sensor Select is displayed. Enter by pressing. - CH4 O2 (at the top) and OFF OFF (at the bottom) will be displayed on the screen, from right to left. To deactivate CH$ (OFF), press or ; to go to a different location, press until you leave the Sensor Select menu, press or until Exit is displayed, press. Pág. 6/8

- Press the and buttons together for 3 seconds, until the Menu features message disappears. - When the Begin CAL message is displayed on the screen, press to accept. - Shift from Auto CAL, by pressing or, to Manual CAL, then accept by pressing. - After accepting, you will be asked to adjust the sensor calibration value by means of the or buttons (you will set 0%). Once the correct number has been entered, press to continue. - The analyzer will request that N2 shall be connected to calibrate the equipment zero (0): you will set the calibration decanter. - Wait until the process is ended, then accept by pressing. If the calibration has been concluded successfully, start again without selecting Abort. Refer to the manual for more details. The operator shall complete the analyzer calibration form MCTR008. Flow meter The Rosemount 285 Annubar flow meters installed on the torch line and the motor line require calibration to be carried out once a year. The two meters can be calibrated by making use of the portable, differential switch MAGNEHELIC CAT n 2000-50 (available at the plant) as well as the pipes needed for its connection. Each of the two flow meters is connected with an ABB pressure transmitter (series 2600T) on which the calibration operations will be carried out. The calculation sheets indicating the calibration values are included in the technical documents of the Rosemount meter, available at the plant. Calibration procedure for the ABB pressure transmitter (series 2600T): - Verify, by means of the portable pressure meter, that the value detected on the torch pressure line corresponds to the value indicated in the software. - If the pressure indicated on the meter display exceeds by +/- 2% the pressure measured by the transmitter on the PC monitor, the same shall be replaced with a new transmitter. - The out-of-calibration transmitter shall be forwarded to a specialized service centre in order to be calibrated (manufacturer). The operator shall complete the Flow meter calibration form MCTR012. Calibration procedure for the Rosemount 285 Annubar flow meters installed on the torch line and the motor line: - Undo one of the two screws of the meter identification plate: by rotating the plate, you can access the two calibration buttons identified by letters Z and S. Pág. 7/8

- Disconnect the plastic pipes that connect the ABB meter with the Rosemount 285 Annubar. - Now you can press the Z button to calibrate the instrument zero, by verifying that the volume displayed on the supervision system is equal to 0. - Connect the differential pressure meter plastic pipe with the pressure transmitter HIGH input, then fix, by blowing into the pressure meter feed plastic pipe and closing the meter shut-off valve, the desired pressure value (155.97 mmh 2 O for the torch line flow meter; 231.56 mmh 2 O for the future motor line). Once you have certified that the fixed value is correct, press the S button to calibrate the meter span. - Before disconnecting the pressure meter, verify that the volume displayed on the supervision system is equal to 2,000 Nm 3 /h (torch line) or 200 Nm 3 /h (motor line), depending on the meter that has been calibrated. - Disconnect the pressure meter, close the transmitter plate and reconnect the plastic pipes running from the Rosemount, taking care that the pipe running from the line corresponds to the High inlet. The operator shall complete the Flow meter calibration form MCTR012. Procedure for checking the calibration of the ELSI temperature sensor ( S and PT100 types). The thermocouples cannot be calibrated in the plant, but only through special equipment, by specialized service centres or the manufacturer themselves. For this reason, the description below refers to the control procedure needed to calibrate the sensor by means of the HDT-18833 infrared pyrometer. - Insert the measuring probe in direct contact with the gas flow to be measured in the lower part of the thermometer. - Insert the probe inside the measuring point fitted on the torch biogas inlet line near the thermocouple installed for continuous temperature control. - If the temperature shown on the meter display exceeds by +/- 1.5% the temperature measured by the thermocouple and read on the PC monitor, the same shall be replaced with a new thermocouple. - The out-of-calibration thermocouple shall be forwarded to a specialized service centre in order to be calibrated (manufacturer). - The infrared thermometer shall be calibrated at a specialized centre (manufacturer) on an annual basis, and the calibration certificates shall be kept and made available at the plant. The operator shall complete the Flow meter calibration form MCTR012. Pág. 8/8