Installation, Operating and Maintenance Manual Overflow Regulator Type 94/ 94 E

Similar documents
GAS PRESSURE CONTROL UNIT TYPE 132

Overflow Regulator TYPe 92-99

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

Mounting and Operating Instructions EB 2558 EN. Self-operated Pressure Regulators. Type Pressure Build-up Regulator

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

Gas Pressure Regulator HON 200

Safety Relief Valve HON 832

WW-730. Pressure Sustaining/Relief Control Valve

Manual Actuated Boiler Blowdown Valves

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

Gas Pressure Regulator HON 300

Pressure relief valve DHV 712 DN 65-80: 0,5-10 bar, DN : 0,3-4 bar, DN 100: 0,5-6 bar

Control Valve with ZK Radial Stage Nozzle ZK 210. Original Installation Instructions English

OPERATING INSTRUCTIONS

WW-720. Pressure Reducing Control Valve

Installation & Operation Manual Proven Quality since 1892

BCV31 DN20 - Blowdown Control Valve

Mounting and Operating Instructions EB 3017 EN. Self-operated Regulators

WW-720. Pressure Reducing Control Valve

Seated valves VRB 3, VRG 3

Operating instructions - Translation of the original -

Model: 43T. Bermad Pressure Relief Valve

Mounting and operating instructions EB 2530 EN. Self-operated Pressure Regulator. Pressure Reducing Valve Type M 44-2

Steam Trap BK 15 (DN40, DN 50) Original Installation Instructions English

64 Series Pressure Reducing Regulators

776 Cryogenic Safety Valve

PV4 and PV6 Piston Valves

SSV-Actuator HON 673 (K 1a, K 2a)

Pilot HON 625. Entwurf. Product information. serving the gas industry worldwide

k valve 2 (50)HF 2½ (65)SF installation guide aylesbury For valve sizes (DN): tel fax

Steam Trap BK BK 212-ASME. Original Installation Instructions English

Type BBS-03, BBS-05, BBS-06, BBS-25

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Type Type Differential Pressure Regulators (opening)

Paul Ladage 26 September 2017 MOVING THINGS AROUND - LATEST TRENDS IN HONEYWELL FLAGSHIP REGULATORS

BCV31 DN40 - Blowdown Control Valve

SCA Series Inverted Bucket Steam Traps

HON 219 Pressure Reducer (D119a)

Universal Charging and Testing Unit FPU-1

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

Mounting and Operating Instructions EB 3009 EN. Self-operated Regulators. Type RS Check Valve (backflow protection)

1200B2 Series Service Regulators. Instruction Manual

756 Safety Relief Valves

Spilt body Flange ball valve. TC-205MFF-PN1640 User Manual English Version. Document No: TC-205MFF-PN1640.Ur-manual. Date: 2007/04/2617. Version: 1.

Water Safety Shut-off Valve HON 790

Pressure Reducing Valve DMV 750 set range: bar

POP Safety Valve. POP Safety Valve INTRODUCTION DEFINITIONS

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

Filling valves AL, ALM Series Automatic filling units ALOMDIW, ALOMDNW Series

Seated valves (PN 6) VL 2 2-way valve, flange VL 3 3-way valve, flange

KBV21i and KBV40i Air Actuated Boiler Blowdown Valves

Crosby style JCE Safety Valve Installation, Maintenance and Adjustment Instructions CROSBY

Product Manual. Description. Specifications. CVS Type 1301F and CVS Type 1301G Regulator. Introduction

Type 3709 Pneumatic Lock-up Valve. Translation of original instructions. Mounting and Operating Instructions EB 8391 EN

Pressure relief valve DHV 716 set range: 0,5-10,0 bar

Ball Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300 DN 40, 50, 65

Atmospheric relief valve type 1100 Installation and maintenance instructions

Ball Float Steam Trap UNA 43 PN 16/CL 125/JIS 10K UNA 46 PN 40/CL 150/CL 300/JIS 10K/JIS 20K DN 80, 100, 150, 3", 4", 6"

SV5 Safety Valve Installation and Maintenance Instructions

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

Seated valves (PN 16) VF 2 2-way valve, flange VF 3 3-way valve, flange

Bermad Model:

Installation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM.

BSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions

Pressure Reducing Valve for Steam Type 2333 A

Mounting and Operating Instructions EB 8546 EN. Type 4708 Supply Pressure Regulators. Translation of original instructions. Type Type

INSTALLATION OPERATION MAINTENANCE

Declaration of Conformity as per Directive 97/23/EC

Engineering Data Sheet

CLASS TLP Pressure Reducing Valve

Operating instructions Two-way / three-way valves for drinking water plants

SRV66 Sanitary Pressure Reducing Valve

Gas Pressure Regulator R 51

Operation and Maintenance Instructions. VAG PICO Pilot Operated Control Valve

Safety Shut-Off Valve HON 720

Mounting and Operating Instructions EB 8546 EN. Supply Pressure Regulator Type Fig. 1 Supply pressure regulators

safety shut-off Valve HON 703 / HON 704

Installation, operation & maintenance manual - original version

RHPS Series RD(H)F40 User Manual. Read the complete manual before installing and using the regulator.

KTM 50 (DN ) Installation, maintenance and operating instructions

DelVal Flow Controls Private limited

TSS21 Sealed Thermostatic Steam Tracer Trap

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

TD45 Thermodynamic Steam Trap Installation and Maintenance Instructions

Telefon (+45) Telefax (+45)

Operating Manual FSV, FSÖV, SSVF

Operating and Maintenance Instructions. VAG BETA 200 Gate Valve

FTGS14 Ball Float Steam Trap DN15 (½") to DN25 (1")

Model GP PRESSURE REDUCING VALVE Installation & Operation Manual

Mounting and Operating Instructions EB 2555 EN. Self-operated Pressure Regulators. Pressure Reducing Valves Type 50 ES Type 50 EM.

Pressure relief valve

Assembly Drawing: W-311B-A01, or as applicable Parts List: W-311B-A01-1, or as applicable Special Tools: , , &

Bermad Pressure Reducing. Model: 42T

Swing Check Valve CB 14 CB 24S CB 26 CB 26A

PRESSURE REDUCING VALVE RP45 (EN)

Actuator HON 670 / 671

RS(H)20, 25 USER MANUAL

ITT RICHTER CHEMIE-TECHNIK

THE MF-400 SERIES. Operating and Service Manual. Series includes all variants of MF-400/401

Transcription:

Installation, Operating and Maintenance Manual Overflow Regulator Type 94/ 94 E Table of content 1. General information on installation, operating and maintenance instructions 1.1 Hazard notices 1.2 Qualified staff 2. Functional description 2.1 Identification 2.2 Sectional drawing / installation example 2.3 Operation 3. Installation, operating instructions 3.1 Installation / assembly 3.2 Commissioning 4. Inspection and maintenance 4.1 Inspection/maintenance 4.2 Special maintenance instructions 4.3 Inspection before commissioning / recurring service inspections 5. Technical documentation 5.1 Spare parts drawing 5.2 Spare parts list 5.3 Technical data sheet 6. Disposal 7. Inspection certificates/certificates/certifications* 8. Documentation of included components *Will be enclosed here depending on the scope of the order - 1 -

1. General on installation, operating and maintenance manual 1.1 Hazard notices These instructions comply with EC safety standards, EC directive 97/23/EC (Pressure Equipment Directive) and the relevant rules and regulations of the Federal Republic of Germany. When the valve is used outside the Federal Republic of Germany, those responsible for the design and operation of the plant must ensure that the relevant standards and national rules and regulations are observed. This manual contains the instructions to install and operate the valve safely and in the prescribed manner. If difficulties or problems arise that cannot be solved with the aid of this manual, further information can be obtained from the manufacturer. Ignoring the above may cause damage to property, environmental damage and personal injury. The manufacturer reserves all rights to make technical changes and improvements at any time. The use of these instructions requires the user to be qualified as described in Section 1.2. The operator has to receive training according to the instructions. 1.2 Qualified staff Qualified staff are persons who from their training and experience are familiar with the installation, mounting, commissioning, operation and maintenance of the regulator apply. They may carry out inspections, functional checks, maintenance and re-commissioning. At plants regulated by the German Association for Gas and Water (DVGW), a second person must be present. - 2 -

2. Functional description The Type 94 overflow regulator protects against rising operating pressure upstream. It consists of a control regulator (I) and an actuator (II) (see sectional drawing). The regulator cannot be used not as a check valve. The angle design version of the regulator is called Type 94 E. The function and mode of operation remain the same (see figure below). Type 94E Type 94 Optionally, a vent silencer to reduce noise (see spare parts drawing 4) can be supplied or an external control nozzle (see spare parts drawing 5) can be installed. This does not have any influence on the function. - 3 -

2.1 Identification The component is identified with a hard stamp on the valve body and nameplate. Valve body: Factory number Material, possibly according to APZ, DN PN, material and standard of the flanged joints Nameplate: PS: Pressure Stage OPu: Operating Pressure Upstream OPd: Operating Pressure Downstream DN: Nominal Width PN: Rated Pressure W ds : Specific Set Input Range (Adjustment Range) - 4 -

2.2 Sectional drawing/installation example Type 94 E overflow regulator - 5 -

2.3 Function (according to the sectional drawing) The operating pressure upstream (OPu) is present at the bottom of the cone valve 5 and on the upstream pipe 4 on the compensation diaphragm 3 and under the working diaphragm 1; also over the control nozzle 2 in the top diaphragm chamber. When the compressor starts, that is, with rising upstream pressure the overflow regulator opens, as the pressure above the working diaphragm 1 increases more slowly than in the lower diaphragm chamber because of the control nozzle 2. The cone valve 5 closes again when the pressure in the two diaphragm chambers has been equalised. If the upstream pressure which passes via the control line 8 to the control regulator the set point of the set-point spring 13, the control valve 7 and opens and releases the gas from the top diaphragm chamber through the control line 6. This creates a pressure difference on the working diaphragm 1, which causes the valve cone 5 top open. The discharge pressure is adjusted by the handwheel 10. Right turn increases the pressure. 3. Installation, operating instructions 3.1 Installation/assembly The overflow regulator can be installed horizontally or vertically. In horizontal installations, the control regulator is mounted upright next to the actuator. The control regulator is available in UH or UN versions. The Type UH is rated for operating pressures up to 7.5 bar, the Type UN is used under 1 bar. It has a larger diaphragm and thus a larger diaphragm housing, although this does not affect the function. Outlet pressure range [bar] Drawing number Control regulator UN 0.01-0.12 4-St-12/DN/4 5/2.5 0.12-0.30 4-St-12/DN/5 2.5 0.30-0.60 4-St-12/DN/6 1 0.60-0.75 4-St-12/DN/7 1 0.75-1.00 4-St-12/DN/8 1 Control regulator UH 0.05-0.30 4-St-12/DH/4 2.5 0.30-1.00 4-St-12/DH/5 2.5 1.00-1.90 4-St-12/DH/6 2.5 1.90-2.90 4-St-12/DH/7 1 2.90-4.30 4-St-12/DH/8 1 4.30-7.50 4-St-12/DH/9 1 Other adjustment ranges on request Control group (CG) The control group according to DIN 3380 refers to the permissible deviation from the set point in percentage. CG 5 means that it may deviate by 5% up or down. An on-site pressure test with water is not possible. - 6 -

3.2 Commissioning After the regulator has been properly installed, commissioning can proceed as follows: - Slacken the set-point spring of the control regulator, that is, the controller opens when excess pressure is applied. - Close the gate valve on the pressure side. - Start the blower. - Slowly tension the set-point spring of the control regulator until the desired discharge pressure is reached. - Secure the handwheel with lock nut. The overflow regulator is ready for operation. Slowly reopen the pressure side gate valve. To achieve the preset pressure, the spindle must be screwed in after dismantling until it stops. Only then the preset value specified in the enclosed documentation is reached. 4. Inspection and maintenance tasks 4.1 Inspection / maintenance Special maintenance of the Type 94 overflow regulator is not required. Malfunctions can occur only through dirt or damage to individual components. The maintenance intervals depend on the operating conditions and the nature of the gas used. Rigid maintenance intervals are therefore not specified, the responsibility lies with the operator. 4.2 Special maintenance instructions The actuator (as per spare parts drawing 1) must be checked during maintenance to ensure that the cone valve 13 does not leak; the diaphragms 3, 18 must also be checked for wear and external leakage. The cone valve 13 is tight if during plant operation no significant rise in temperature occurs, or no audible overflow occurs (preset set-point value is not reached). To remove the cone valve 13, first loosen the screws 25 and remove the diaphragm housing. Now the working diaphragm 3 can be unscrewed. Once the screws 19 have been loosened, the compensation diaphragm 18 can be removed as a unit with the valve suspension 9, the valve guide 7 and the cone valve 13. All the wear parts can be replaced after dismantling. During installation, make sure that the items 4, 11, 12 and 20 are also replaced. The cone valve 13 must be centred on the valve seat so that the compensation diaphragm 18 is automatically centred in the lower diaphragm housing 23 during installation. When installing the working diaphragm 3, make sure that the maximum preset valve travel is reached again. For this purpose, the following equation can be used as a rule of thumb: Valve travel [mm] = valve Ø [mm] x 0.25. The valve travel is measured between the membrane suspension 27 and top diaphragm housing 1. - 7 -

The control regulator Type UH / UN (as per spare parts drawings 2, 3) must be dismantled from the main unit for maintenance purposes. Before every disassembling of the control regulator the set point spring 12 must be released with the palm grip 17. During maintenance, the diaphragm 8, the control regulator insert (2, 3, 4) and the control valve 1 in particular must be checked for wear. By loosening the screws 19, the diaphragm 8 can be taken out along with the suspension 7 and checked. By unscrewing the spring cap 6 and loosening the screws 21 and 27 as well as the nut 28, the control valve 1 can be unscrewed from the control regulator insert (2, 3, 4), the insert removed and checked. To maintain its general operational reliability, the insert should be replaced at least every 3 years. When assembling, make sure that: - The control valve 1 is screwed to about a ¼ turn before the stop on the control regulator insert (2, 3, 4). - The spring cap 6 on the control regulator insert (2, 3, 4) is screwed on only to the extent that when pressing down the spring cap 6, the loosely connected regulator foot 26 is lifted about 2 mm from the seat of the regulator body 24 by the control valve 1. 4.3 Inspection before commissioning / recurring service inspections The operator must do and document service inspections before commissioning and at regular time intervals. Inspections relating to, among other, compliance with the construction requirements, equipment integration, leaks and function. - 8 -

5. Technical documentation 5.1 Spare parts drawing 1 Actuator Type 94E/ Type 94-9 -

Spare parts drawing 2 Control regulator Type UH Spare parts drawing 3 Control regulator Type UN

Spare parts drawing 4 Vent silencer Venting noises by the overflow regulators discharging gas into the atmosphere when opened can effectively be reduced with a flange mounted silencer. The absorption silencer only generate a low back pressure and act in a relatively wide frequency spectrum. They are designed for the specific application and dampen sound up to 20 db. Outlet flange L ABS [mm] Di [mm] Da [mm] DN 50-150 1500 200 360 From DN 200 Design according to requirement Spare parts drawing 5 External control nozzle The external control nozzle is used when: - Dirt and blockage are expected or when wet gas is present. - Easier and faster access to the control nozzle is required. 10L Ermeto fittings are used standard to connect the control nozzle. - 11 -

5.2 Spare parts list x: Keep wear parts in stock for maintenance. The storage requirements of the respective manufacturers apply. Spare parts list 1 Actuator Type 94 / Type 94E Item Quantit Unit Designation Standard / drawing number Material / remarks 1 y 1 Piece Diaphragm housing, top 4-132-1/ GGG 40 / St 2 1 Piece Diaphragm plate, working 4-132-2/ St, chromated x3 1 Piece diaphragm Working diaphragm 4-132-3/ Perbunan/Viton x4 1 Piece Control nozzle seal 8 x 12 x 6 Perbunan 5 1 Piece Control nozzle/ external Control 4-132-5 / 4-94-5 VA 6 1 Piece nozzle Diaphragm disc, top 4-132-20 Al 7 1 Piece Valve guide St, chromated x8 1 Piece Hexagon nut DIN 439, M16 St, galvanised 9 1 Piece Valve suspension 4- VA x10 1 Piece Closing spring 4-132-29 Spring steel C, x11 2 Piece Sealing ring DIN 7603 A,16x24x1.5 Cu x12 1 Piece O-ring 16 x 5 Perbunan x13 1 Piece Cone valve 4-132-13/ St, Perbunan/ Viton x14 1 Piece Locknut DIN 985, M16 St, galvanised 15 1 Piece Spring cup 4-94 Al/VA 16 1 Piece Body 4-94 St 17 1 Piece Diaphragm disc, bottom 4-132-20 Al x18 1 Piece Compensation diaphragm Perbunan/Viton 19 8/12 Piece Allen screw DIN 912, M12x35/40 8.8, galvanised x20 8/12 Piece Sealing ring DIN 7603 A, 12x18x1,5 Cu 21 1 Piece Body flange 4-132-32/ C22.8 x22 1 Piece Round packing cord/o-ring ~ 5 / ~ 168x5 Perbunan 23 1 Piece Diaphragm housing, bottom GGG 40 / St 24 1 Piece Hexagon nut DIN 431, G3/4 St, galvanised 25 12 Piece Allen screw DIN 912, M10x35/40 8.8, galvanised 26 1 Piece Membrane disc, working diaphragm 4-132-34 St, galvanised 27 1 Piece Membrane suspension, working G 3/4 Al 28 2 Piece diaphragm Allen screw DIN 912, M8x16 8.8, galvanised - 12 -

Spare parts list 2, 3 Control regulator Type UH/ UN Item QuantityUnit Designation Standard / drawing number Material / remarks x1 1Piece Control valve 4-St-1/D//a Ms x2 1Piece Spring body 4-St-2 Bronze x3 1Piece Valve suspension 4-St-3/D VA x4 1Piece Solder flange 4-St-4 VA 5 1Piece Closing spring 4-St-5 VA spring steel 6 1Piece Spring cap 4-St-6 VA 7 1Piece Diaphragm suspension 4-St-7 VA x8 1Piece Diaphragm 4-St-8/... Perbunan 9 1Piece Diaphragm plate 4-St-9/... Al 10 1Piece Disc DIN 125; 10.5x2.5; Form B St, galvanised 11 1Piece Hexagon nut DIN 439; M10; St, galvanised 12 1Piece Set point spring 4-St-1 2/... Spring steel C, 13 1Piece Spring cup 4-St-13 chromated St, chromated 14 1Piece Stem seal 4-St-14 Perbunan 15 1Piece Press ring 4-St-15 Ms 16 1Piece Hexagon nut DIN 431; G1/4; St, galvanised 17 1Piece Palm grip with spindle 4-St-1 7 Ms; Duroplast 18 1Piece Diaphragm housing, top 4-St-18/... Al 19 8Piece Allen screw DIN 912; M6x20; 8.8, galvanised 20 1Piece Diaphragm housing, bottom 4-St-20/... Al 21 4Piece Allen screw DIN 912; M6x25; 8.8, galvanised x22 1Piece O-ring 48 x 4 Perbunan x23 1Piece O-ring 26 x 2 Perbunan 24 1Piece Regulator body 4-St-24/D Al x25 1Piece O-ring 26 x 2 Perbunan 26 1Piece Regulator foot 4-St-26/D//a Al 27 4Piece Allen screw DIN 912; M6x50; 8.8 8.8, galvanised 6. Disposal Environmental damage can occur during disposal when the equipment still contain poisonous fluid residues. It is therefore essential to ensure that the equipment is cleaned and free of fluid residues before disposal. After that, all materials can be disposed of according to the regulations applicable at the operating site. - 13 -