ORIFICE METERS. WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel.

Similar documents
BVA BUTTERFLY VALVES

GAS LIMITING ORIFICE VALVES LVG SERIES

IPG IGNITION GAS PILOTS BACK-LOADED GAS

PGM PREPIPED GAS MANIFOLD

BBC BETA BURNERS. WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel.

North American Orifice Metering System

OPERATING AND MAINTENANCE MANUAL

BBG BETA BURNER GAS SERIES

Product Manual. Description. Specifications. CVS Type 1301F and CVS Type 1301G Regulator. Introduction

/2004 US/CA

MEGR-1627 Instruction Manual

APCO ARV CLEAN WATER AIR RELEASE VALVES. Model 50A

Installation Instructions

INSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION

MEGR-1912 Instruction Manual

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS

PAPR Flow Tester. instructions. part no WARNING

RHPS Series RD(H)F40 User Manual. Read the complete manual before installing and using the regulator.

VALVES & MEASUREMENT

INSTALLATION INSTRUCTIONS MANUAL ON/OFF SAFETY VALVE/PILOT KIT MODEL GA9050A-1 (F0235)

Noth American 7347 High Pressure Gas Regulators

FUNDAMENTALS OF PRESSURE REGULATORS ROBERT BENNETT MANAGER OF TRAINING ELSTER AMERICAN METER

S300 Series. Valve Link. Features. Fisher Controls

SERIES 500 VARIABLE RANGE PNEUMATIC DIFFERENTIAL PRESSURE TRANSMITTER

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

Design and Application Details MICRO-RATIO Valves

Types S100K and S102K Pressure Regulators

Water Weir Flow Controller. Introduction. Safety Precautions. Mounting the Hardware

ACCESSORY KIT INSTALLATION MANUAL

1800CPB2 Service Regulators Maximum Inlet Pressure 125 PSIG

Types 749B and R130 Changeover Manifolds

For use with select HPC Fire Pits ONLY- refer to product catalog or website. 100K BTU Maximum WARNING: FOR OUTDOOR USE ONLY

R122H, R222, R232A, and R232E Series Instruction Manual

Self-operated Regulators Accessories Differential Pressure and Flow Regulators

GM Series Dual-Block Multi-Function Gas Control Valves

Type HSR Pressure Reducing Regulator for Residential, Commercial, or Industrial Applications

Series MG Mixing Tubes

Industrial Regulator Series 1800/2000

Type R622 Pressure Reducing Regulator

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series

Type ACE97. Introduction. Installation. P.E.D. Categories. Specifications. Overpressure Protection. Installation Guide English May 2002

North American 7337A/B/C-4 High Pressure Gas Regulators

Type 1367 High-Pressure Instrument Supply System with Overpressure Protection

installation instructions

Models 461-S, 461-8S and S Regulators. R-1330 Rev. 7

KTM OM-2 SPLIT BODY FLOATING BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

V5197A. Firing Rate Gas Valve APPLICATION FEATURES PRODUCT HANDBOOK

61 Series Pilots for Pilot-Operated Pressure Reducing Regulators

ACCUMULATOR OPERATING & MAINTENANCE INSTRUCTIONS

ABRASIVE REGULATOR II

299H Series. Introduction. P.E.D. Categories. Specifications. Installation. Warning. Installation Guide English September 2012

1301 Series High-Pressure Regulators

64 Series Pressure Reducing Regulators

Installation Operating Instructions for Duplex Manual Manifolds PX-TMD Series

The conversion of new certified central heating gas appliances must conform to directions outlined in this instruction.

Natural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet)

R600 and HSRL Series Instruction Manual

1800CPB2 Pilot-Loaded Service Regulators

WARNING: Gas Conversion Kit Instructions Applies to: Model UDAP, UDAS, UDBP, and UDBS Unit Heaters. General and Warnings FOR YOUR SAFETY

General. Rugged, Reliable with Value-added Features. Pipe Sizes. Temperature Limits. Spring Ranges. Buried Service. Increased Outlet Pipe Sizes

TESCOM 50-4X Series Safety, Installation & Start-Up Procedures

1800CPB2 Service Regulators

SFC. SKYLINE FLOW CONTROLS INC. The Leader of Accurate and Reliable Flow Measurement DESCRIPTION & APPLICATIONS: ADVANTAGES:

Preparation and Installation of the Sanitary BDI-FLX Sensor and Connection to the BDI-FLX Interface Cable

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

1805 Series Relief Valves

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

Adjustable. Unloader Valve. O&M Manual. Part #

Workhorse 8 Oxygen System Model No 5665, 5673, 5679

1800C and 1800C-HC Series Service Regulators

SIZING AND CAPACITIES OF GAS PIPING

Combination Air Valve Model

MRO Oil-Air Ratio Regulator

KC Series Gas Components and Supply Design Guide

Tri-Tech Medical Inc.

Model 1800 PFM Series Regulator For Constant Outlet Pressure Precise Fixed Factor Measurement From 0.5 to 30 PSIG

Type 1098-EGR. Pilot-Operated Valve Link Regulators. Features. Fisher Controls

SERVICE MANUAL SALAMANDER BROILERS RADIANT AND INFRARED 36RB 36IRB VULCAN C36RB C36IRB WOLF

GAS FUEL VALVE FORM AGV5 OM 8-03

Operator: Save these instructions for future use!

Engineering Data Sheet

WHEATLEY WHEATLEY SERIES 500 SWING CHECK VALVE. Installation, Operation and Maintenance Manual

FLOMIXERS SELECTION DATA ALL GASES

36H SERIES Combination Gas Valve

North American 7339 High Pressure Gas Regulators

1213B2 Service Regulators Maximum Inlet Pressure 125 PSIG

CLASS D - SENSITIVE LEAK TEST GAS AND BUBBLE METHOD. 1.1 To provide definitive requirements for PNEUMATIC pressure testing of piping systems.

MUELLER GAS. No-Blo Operations Using D-5. Drilling Machine. Reliable Connections. General Information 2

WHEATLEY Series 500 Swing Check Valve

Alkylphosphines. Storage and Handling Recommendations

GAS SUPPLY DESIGN GUIDE

Types S108K and S109K Pressure Reducing Regulators with Integral Slam-Shut Device

Combination Air Valve

Instruction Manual O-Ring Ejector Chlorine & Sulfur Dioxide to 500 PPD (10 kg/h)

ACCESSORY KIT INSTALLATION INSTRUCTIONS

OPERATING INSTRUCTIONS

RE: PROPANE SYSTEM & REGULATOR TESTING/INSPECTION PROCEDURE

Maximum Pressure Differential and Maximum Inlet Pressure for Various Soft-Seated Valve Materials* Introduction. Body Pressure Ratings

T208VR Series Tank Blanketing Vacuum Regulator

Transcription:

INSTRUCTIONS ORIFICE METERS WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components, by unqualified personnel, can result in fire, explosion, severe personal injury, or even death. TABLE OF CONTENTS Subject age A. General Information... 2 B. Receiving and Inspection... 2 C. Installation..... 3 D. Manometer Adjustment.... 3 E. Operation.... 3 F. Maintenance.... 4 Attached: Hauck Orifice Meter Capacity Charts These instructions are intended to serve as guidelines covering the installation, operation, and maintenance of Hauck equipment. While every attempt has been made to ensure completeness, unforeseen or unspecified applications, details, and variations may preclude covering every possible contingency. WARNING: TO REVENT THE OSSIBILITY OF SERIOUS BODILY INJURY, DO NOT USE OR OERATE ANY EQUIMENT OR COMONENT WITH ANY ARTS REMOVED OR ANY ARTS NOT AROVED BY THE MANUFACTURER. Should further information be required or desired or should particular problems arise which are not covered sufficiently for the purchaser's purpose, contact Hauck Mfg. Co. HAUCK MANUFACTURING CO.,.O. Box 90 Lebanon, A 17042-0090 717-272-3051 3/99 www.hauckburner.com Fax: 717-273-9882

A. GENERAL INFORMATION age 2 The Hauck Orifice Metering System is a family of assemblies of threaded or welded design used for measuring the flow of either combustion air or any industrial gas. These meters may be used in the main gas and air lines or in the gas and air lines of individual burners. The former configuration allows the monitoring of total flow while the latter method allows precise setting of each burner. B. RECEIVING AND INSECTION Upon receipt, check each item on the bill of lading/and or invoice to determine that all equipment has been received. A careful examination of all parts should be made to ascertain if there has been any damage in shipment. IMORTANT If the installation is delayed and the equipment is stored outside, provide adequate protection as dictated by climate and period of exposure. Special care should be given to all motors and bearings, if applicable, to protect them from rain or excessive moisture. C. INSTALLATION 1. Install the orifice meter in any position in the appropriate line. Most orifice meters are available in either of two configurations: one designed specifically for a welded connection, the other for a threaded female connection. The location chosen for installation should permit easy access to both pressure cocks and allow sufficient space to remove the orifice plate, if required. When used in the gas and air lines of individual burners, mount the orifice meter between a flow control valve and the burner. NOTE For maximum accuracy provide 10 pipe diameters of straight piping without fittings immediately preceding the orifice meter and 5 pipe diameters downstream of the orifice. 2. Insert and loosely tighten the three (3) connecting bolts not required to hold the orifice plate in position. 3. Insert the orifice plate and secure it in place by insertion of the fourth connecting bolt.

age 3 4. Firmly tighten all bolts. 5. Insert a threaded plug in the unused cock openings. D. MANOMETER ADJUSTMENT 1. lace the manometer on a rigid support. 2. Insert the proper amount of fluid into the manometer and adjust the fluid height until a 0.0" manometer reading is obtained. 3. Connect the orifice meter pressure cocks to the manometer, using EQUAL lengths of vinyl tubing, such as Tygon, or equivalent. E. OERATION The orifice metering system is designed so that the specific water column (wc) differential observed on the manometer corresponds to a specific flow rate through the orifice (for the specific plate being used). 1. Fully open the orifice meter pressure cocks.

age 4 2. Read the water column differential in inches and tenths of an inch. If the reading differs from the desired reading, adjust the flow control valve until the manometer coincides with the desired reading. 3. Fully close the orifice meter pressure cocks (and tubing clips if applicable). 4. Disconnect the connecting tubing, if desired. F. MAINTENANCE NOTE To reduce the risk of "blowing" the manometer (forcing the fluid out of the manometer into the tubing) tubing clips or valves can be located in the vinyl tubing lines near the manometer. The clips or valves are first closed and then the orifice meter cocks are opened. The clips or valves are then opened. Locating the shutoff near the manometer minimizes the gas volume being compressed when the opposite leg of the manometer is opened to system pressure. Reducing this volume limits movement of fluid in the manometer. The design of the orifice plate and brackets requires no service or maintenance. If it ever becomes necessary to change the orifice plate: 1. Loosen all four (4) connecting bolts. 2. Completely remove the plate positioning bolt. 3. Remove the old plate and insert the new one. 4. Securely tighten all connecting bolts. eriodically check the quantity of fluid in the manometer and refill as required.

age 5 OMG SERIES ORIFICE METERS ipe OMG Model Number 3/8" 103 1/2" 105 3/4" 107/207 110/210 1 ¼" 112/212 1 ½" 115/215 AIR & NATURAL GAS FLOW CAACITY (SCFH) 100 200 Series Threaded / Weld-In 3/8" Through 1 ½" ipe Orifice Bore Air Natural Gas 0.197 24 33 57 73 30 43 73 94 0.232 33 46 80 103 42 60 103 132 0.266 44 62 107 137 57 80 137 177 0.307 61 85 147 189 78 110 189 244 0.350 84 118 203 261 108 152 262 336 0.232 32 45 78 100 41 58 100 129 0.266 42 60 103 133 55 77 133 171 0.317 61 86 149 191 79 111 192 247 0.368 85 120 206 265 109 154 266 342 0.423 118 166 286 368 152 214 369 475 0.273 44 62 107 137 57 80 137 177 0.324 62 87 151 194 80 113 194 250 0.379 86 121 208 268 110 156 269 346 0.437 116 163 282 363 149 211 363 468 0.508 162 228 394 507 208 294 508 654 0.585 221 322 555 714 294 415 716 921 0.324 61 86 149 192 79 111 192 247 0.384 86 122 210 270 111 157 271 349 0.452 120 170 293 378 155 219 378 487 0.523 163 230 398 513 211 297 513 661 0.613 231 326 562 724 297 420 725 935 0.715 331 467 806 1039 427 602 1040 1340 0.456 120 170 294 379 155 219 379 488 0.533 165 233 403 520 213 301 520 671 0.630 233 330 570 734 301 425 735 947 0.735 324 457 790 1018 418 590 1020 1314 0.850 447 632 1092 1407 577 815 1409 1816 0.986 641 905 1564 2015 827 1168 2018 2600 0.533 164 232 400 516 212 299 517 666 0.635 234 331 572 737 302 427 738 951 0.744 325 459 794 1023 419 593 1024 1320 0.867 450 636 1100 1417 581 821 1419 1829 1.005 626 885 1530 1972 808 1142 1974 2544 1.156 881 1245 2151 2771 1137 1607 2776 3576 Notes: 1. Orifice Bore Equals The Orifice late Inside Diameter. All Bore s In Inches. ipe Equals Schedule 40 ipe. 2. Capacity Based On 60 F @ 1 psig Upstream ressure. Natural Gas Specific Gravity At 0.60; Air Specific Gravity At 1.0. 3. 1 Model Number Designates NT Threaded Connection. 2 Model Number Designates Weld-In Connection. 4. All Flow Rates At Standard Barometric ressure: 29.92" Hg (Sea Level). 5. Design Capacity Is Based On W.C.Δ. Continued 9/98

age 6 ipe OMG Model Number 2" 120/220 2 ½" 125/225 130/230 4" 140/240 6" 160/260 Orifice Bore OMG SERIES ORIFICE METERS AIR & NATURAL GAS FLOW CAACITY (SCFH) 100 200 Series Threaded / Weld-In 2" Through 6" ipe Air Natural Gas 0.640 238 335 577 743 307 432 744 958 0.754 334 470 808 1039 430 605 1041 1339 0.875 455 640 1100 1415 586 824 1417 1823 1.034 650 914 1568 2016 836 1175 2019 2597 1.203 911 1278 2192 2817 1170 1644 2822 3629 1.375 1250 1753 3003 3858 1605 2253 3865 4967 0.754 330 465 800 1030 425 599 1031 1328 0.890 464 652 1123 1445 597 840 1447 1863 1.048 651 916 1576 2027 838 1180 2030 2613 1.236 926 1302 2237 2877 1191 1676 2881 3707 1.423 1266 1778 3053 3925 1628 2288 3932 5056 1.625 1730 2428 4164 5353 2223 3123 5362 6894 0.894 462 651 1122 1444 595 839 1446 1863 1.056 649 914 1575 2027 836 1178 2030 2614 1.252 923 1300 2237 2879 1188 1674 2884 3712 1.452 1262 1776 3056 3932 1625 2287 2938 5068 1.688 1753 2466 4238 5452 2256 3174 5460 7026 1.963 2483 3489 5993 7706 3193 4491 7719 9929 1.261 919 1295 2234 2877 1184 1670 2881 3710 1.470 1258 1773 3056 3935 1621 2285 3941 5075 1.722 1748 2462 4242 5461 2251 3173 5468 7041 2.029 2479 3491 6009 7734 3192 4497 7746 9971 2.345 3418 4810 8275 10648 4400 6195 10665 13725 2.691 4731 6655 11440 14716 6088 8568 14741 18966 1.735 1729 2439 4211 5425 2229 3146 5432 6998 2.067 2470 3484 6011 7743 3184 4493 7754 9988 2.437 3468 4890 8434 10863 4469 6305 10878 14011 2.879 4924 6941 11965 15408 6344 8947 15429 19870 3.314 6685 9420 16231 20897 8611 12140 20928 26946 3.850 9423 13272 22856 29419 12135 17101 29466 37931 4.388 13055 18381 31638 40712 16809 23679 40781 52484 Notes: 6. Orifice Bore Equals The Orifice late Inside Diameter. All Bore s In Inches. ipe Equals Schedule 40 ipe. 7. Capacity Based On 60 F @ 1 psig Upstream ressure. Natural Gas Specific Gravity At 0.60; Air Specific Gravity At 1.0. 8. 1 Model Number Designates NT Threaded Connection. 2 Model Number Designates Weld-In Connection. 9. All Flow Rates At Standard Barometric ressure: 29.92" Hg (Sea Level). 10. Design Capacity Is Based On W.C.Δ.