pressure regulator Zero pressure regulator Proportional pressure regulator Compressed air-controlled

Similar documents
Pressure regulator FRS

Pressure regulator FRS

GasMultiBloc Combined regulator and safety valve Infinitely variable air/ gas ratio control mode MBC-300-VEF MBC-700-VEF MBC-1200-VEF

Old documentation - Only for your information! Product is not available anymore!

GasMultiBloc Combined regulating and safety valve Infinitely variable air/gas ratio control mode MB-VEF B01

GasMultiBloc Combined regulator and safety shut-off valves Two-stage function Integrated bypass valve MB-ZRD(LE) B07

GasMultiBloc Combined regulator and safety shut-off valves Single-stage function MB-D(LE) B01

Ratio Regulator Zero Governor. FRG/6 Series

SAV. Safety Shut-off Valve. Safety Shut-off Valve Type SAV

WhirlWind Combined fully integrated gas/air control and safety system GB-WND 055 D01

GasBloc Multifunctional gas control Combined regulator and safety shut-off valves Electrically modulating GB-M(P) 055 D01

Old documentation - Only for your information! Product is not available any more!

FRM. Medium Pressure Regulator. Medium pressure regulator Type FRM

GasMultiBloc Combined regulator and safety shut-off valves Two-stage function MB-ZRD(LE) B01

Gas Appliance Pressure Regulators and. Line Pressure Regulator. FRS 7../6 Series FRS 5... Series

Compact pressure switches for gas and air

GasBloc Multifunctional gas control Combined regulator and safety shut-off valves Integrated gas-air system GB-GD 057 D01

Gas Appliance Pressure Regulators with integrated gas filter. FRI/6 Series

Gas Appliance Pressure Regulators with integrated gas filter. FRI/6 Series

GasBloc Multifunctional gas control Combined regulator and safety shut-off valves single-stage atmospheric operating mode GB-(LEP) 057 D01

Old documentation - Only for your information! Product is not available any more!

Line Pressure Regulator. Class I or Class II. FRS 7../6 Series

Line Pressure Regulators Class I or Class II. FRS 7../6 Series

WhirlWind Multifunctional gas control Fully integrated gas-air system with control and safety function GB-WND 055 D01

SV - Safety Shutoff Valve with Proof of Closure 1/2" NPT - 2" NPT. SV/614 Series SV-DLE/614 Series

Pressure Switch for gas and air GGAO-A4

Pressure regulator with solenoid valve VAD Air/gas ratio control with solenoid valve VAG Variable air/gas ratio control with solenoid valve VAV

Gas Pressure Regulator HON 300

Gas Pressure Regulator R 51

Dual Modular Safety Shutoff Valves with Two-stage operation and Proof of Closure DMV-ZRD/612 Series DMV-ZRDLE/612 Series

Dual Modular Safety Shutoff Valves with Two-stage operation and Proof of Closure. DMV-ZRD/612 Series DMV-ZRDLE/612 Series

Gas Pressure Regulator HON 502

Pressure Switch for gas and air

Gas Filters DN15 DN300. elektrogas.com EE151 06/13

safety shut-off Valve HON 703 / HON 704

Pilot HON 625. Entwurf. Product information. serving the gas industry worldwide

Gas Pressure Switch for DMV safety shutoff valves

Dual Modular Safety Shutoff Valves with Two-stage operation. DMV-ZRD/602 Series DMV-ZRDLE/602 Series

Dual Modular Safety Shutoff Valves with Two-stage operation. DMV-ZRD/602 Series DMV-ZRDLE/602 Series

Valve Proving System VDK 200 A S02

Valve Proving System VDK 200 A S06*

Pressure switch for gas and air

Series 42 Self-operated Regulators Differential Pressure Regulators with Type 2424/Type 2428 Actuator (closing) Type Type 42-28

Governor with solenoid valve VAD Air/gas ratio control with solenoid valve VAG

Dual Modular Safety Shutoff Valves with NEMA 4x Enclosure DMV-D 704/604 DMV-DLE 704/604

Dual Modular Safety Shutoff Valves. DMV-D/11 Series DMV-DLE/11 Series

Pressure regulator with solenoid valve VAD Air/gas ratio control with solenoid valve VAG

VGG... VGF... VGH... Gas Valves. Building Technologies HVAC Products VGG... VGF... VGH...

Dual Modular Safety Shutoff Valves DMV-D 525/11 DMV-DLE 525/11

SPECIFICATIONS FRS. 2 1/2 DN (ISO) Flanged. FRS DN (ISO) Flanged

Commonwealth of Massachusetts Approved Product Approval code G

Dual Modular Safety Shutoff Valves. DMV-D/602 Series DMV-DLE/602 Series

Pressure regulators with solenoid valve VAD, VAG, VAV, VAH Flow rate regulator VRH Pressure regulators with double solenoid valve VCD, VCG, VCV, VCH

Dual Modular Safety Shutoff Valves. DMV-D/602 Series DMV-DLE/602 Series

Self-operated Regulators Accessories Differential Pressure and Flow Regulators

Dual Modular Safety Shutoff Valves with Proof of Closure and NEMA Type 4x Enclosure DMV-D 704/624 DMV-D 704/634 DMV-DLE 704/624 DMV-DLE 704/634

Gas Pressure Regulator HON 505

Dual Modular Safety shutoff Valves with Proof of Closure and NEMA Type 4x Enclosure DMV-D 704/624 DMV-D 704/634 DMV-DLE 704/624 DMV-DLE 704/634

VGG... VGF... VGH... Gas Valves. Siemens Building Technologies HVAC Products VGG... VGF... VGH...

Dual Safety Shutoff Valves with Proof of Closure and NEMA 4x Enclosure. DMV-D/624L Series DMV-DLE/624L Series

Pressure Regulator 133 / 233

Dual Modular Safety Shutoff Valves with Proof of Closure. DMV-D/622 Series DMV-DLE/622 Series

T 2523 EN Type 2406 Excess Pressure Valve Self-operated Pressure Regulators ANSI version

Safety Relief Valve HON 832

Gas Pressure Switch for DMV safety shutoff valves

Self-operated Pressure Regulators Type 2405 Pressure Reducing Valve

Commonwealth of Massachusetts Approved Product Approval code G

Dual Modular Safety Shutoff Valves DMV-D 525/11 DMV-DLE 525/11

OPERATING INSTRUCTIONS

safety Shut-Off Valve HON 721

Tightness control TC. Product brochure GB 3 Edition AGA

Self-operated Pressure Regulators Type 2405 Pressure Reducing Valve

Butterfly Control Valve. DMK/6 Series

Gas pressure regulator RSP 254 / RSP 255. Product information. Regulator R / R / R Actuator AS 254 / AS 255

Old documentation - Only for your information! Product is not available anymore!

Dual Safety Shutoff Valves with Proof of Closure and NEMA 4x Enclosure. DMV-D/624L Series DMV-DLE/624L Series

VGG... VGF... VGH... Gas Valves. Building Technologies HVAC Products VGG... VGF... VGH...

Safety Shut-Off Valve HON 720

Gas Pressure Regulator HON 200

Safety. Operating instructions Gas pressure regulators 60DJ, J78R, GDJ DANGER WARNING. Contents CAUTION Edition 12.10

Type 4708 Supply Pressure Regulator

Modulating Valves for Atmospheric, Infrared, and Direct Fired Burners

DIAPHRAGM PUMPS WITH KNF STABILIZATION SYSTEM

Safety Relief Valve HON 835

Differential pressure control and flow limiter AVPB/AVPB-F, PN 16

Differential pressure and flow controller (PN 16) AVPQ - return mounting, adjustable setting

GAS PRESSURE CONTROL UNIT TYPE 132

Gas Filters DN15 DN300. delta-elektrogas.com EE151 03/17

M/MR Modulating Valves TABLE OF CONTENTS DESCRIPTION SPECIFICATIONS. For Atmospheric, Infrared, and Direct Fired Burners

AVP-F. p setting range (bar) Code No. 003H6200

AVPQ/AVPQ-F, PN 16. Application

TANDEM MODULATOR FOR OUTLET GAS FLOW: STEPPED (836 TANDEM) - CONTINUOUS (837 TANDEM) SERVO-CONTROLLED PRESSURE REGULATOR

Safety Shutoff Valves MVD/6 Series MVDLE/6 Series

Safety shut-off valve S 50. Product information

Safety. Operating instructions Solenoid valve for gas VG 6 VG 15/10 DANGER. Contents WARNING CAUTION. Changes to edition 09.14

Dual Modular Safety Shutoff Valve with NEMA 4x Enclosure. DMV-D/604L Series DMV-DLE/604L Series

Tightness controls TC 1 3 and TC 4

MULTIFUNCTIONAL CONTROL FOR GAS BURNING APPLIANCE

Double gas valves for biogases and recycling gases

Safety shut-off valve S 100. Product information

Transcription:

Pressure regulator FRNG Zero pressure regulator Proportional pressure regulator Compressed air-controlled pressure regulator 4.14 Printed in Germany Edition 01.18 Nr. 219 570 Technical description The DUNGS pressure regulator, type FRNG, has an adjustable setpoint spring and defined counterspring. The pressure regulator complies with EN 88-1 and DIN 3380: - Input pressures up to 50 mbar (5 kpa) for zero pressure applications - Input pressures up to 200 mbar (20 kpa) for proportional pressure applications - Bypass prepared, Rp 3/8 to R - Sturdy, precise and sensitive regulation of regulator output pressure - Inlet pressure compensation diaphragms - Safety diaphragms - Internal pulse for regulator output pressure as standard, external pulse connection prepared - Connection for blower pressure as standard Application The DUNGS pressure regulator, type FRNG, is suitable for gases of families 1, 2, 3 and other neutral gaseous media. Does not contain any non-ferrous metals, suitable for gases of up to max. 0.1 vol.% H 2 S, dry. Approval EC type testing certificate as per: EC-Gas Appliances Regulation Approvals in other important gas consuming countries. 1 8

FRNG Spring-loaded pressure regulator with adjustable setpoint spring and defined counterspring. Internal tap of regulator output pressure, external pulse and blower pressure connections prepared. Suitable for controlling regulator output pressure via a pneumatic command variable. Specifications Nominal diameters Pipe thread as per ISO 7/1 Flange Max. operating pressure Pressure regulator Input pressure range Zero pressure regulator Proportional pressure regulator Compressed air-controlled pressure regulator Output pressure range Materials of gas-conveying parts Ambient temperature Installation position Measuring/ignition gas connections Measurement opening Bypass Pulse connection Ventilation line / pressure connection for blower pressure Blower pressure command variable DN 40 50 65 80 100 125 150 Rp 3/8 1/2 3/4 1 11/2 2 Connection flange (PN 16) per DIN EN 1092-1 up to mbar (50 kpa) Pressure regulator as per EN 88-1, Class A, Grou, DIN 3380 RG 10, EN 12078 5 to 50 mbar (0.5 to 5 kpa) 5 to 200 mbar (0.5 to 20 kpa) to mbar (50 kpa) Zero pressure regulator - 3 to 5 mbar (-0.3 to 0.5 kpa) Proportional pressure regulator -10 to 150 mbar (-1 to 15 kpa) Pressure with compressed air up to max. 350 mbar (35 kpa). Housing: aluminium, steel, no non-ferrous metals Seals and diaphragms: NBR 15 C to +70 C Regulator dome from vertically upright to lying horizontally Rp 1/2 - DN 100 Regulator dome in vertical position DN 125, DN 150 ISO 228 on both sides in inlet section G 1/8 ISO 228 in the baseplate (option DN 125, DN 150) Reclosable opening for setting system-specific valuas when the system is put into operation, e. g. gas motor Bypass prepared: Rp 3/8 to R on right of housing Internal in outlet section, externally prepared on housing: Rp 3/8 to Rp 1 left, G 1/8; on both sides from Rp 1 1/2, DN 40 ; internal pulse lockable Ventilation line needs no routing, use existing connection as pressure connection for command variable (blower pressure). Connection: to Rp 1; from Rp 1 1/2, DN 40: For proportional pressure applications and gas-air ratio applications at pressure ratio of approx. 1:1 and in compressed-air controlled operation: p max = 150 mbar (15 kpa) 2 8

Spring selection The output pressure is provided by the force of the installed adjustable spring, the counterspring and the the blower pressure applied. The pressure regulator is equipped with the brown spring No. 1 as standard. By exchanging the adjustable spring, it is possible to achieve larger positive zero point shifts (offsets) of the output pressure (refer to Fig. Compressed air-controlled pressure regulator). Setpoint spring range Spring colour Nominal diameter Rp/DN Rp 3/8, Rp 1/2 Rp 3/4 Rp 1 Rp 1 1/2, DN 40 R, DN 50 DN 65, 80 DN 100 DN 125 DN 150 2.5 +9 Spring 1 brown Standard 229 817 229 833 229 842 229 851 229 874 229 883 229 892 229 901 229 909 5 13 Spring 2 white 229 818 229 834 229 843 229 852 229 875 229 884 229 893 229 902 229 910 5 20 Spring 3 orange 10 30 Spring 4 blue 25 55 Spring 5 red 30 70 Spring 6 yellow 60 110 Spring 7 black 100 150 Spring 8 pink Spring 2 to 9 for compressed air applications only 229 820 229 835 229 844 229 853 229 876 229 885 229 894 229 903 229 911 229 821 229 836 229 845 229 854 229 877 229 886 229 895 229 904 229 912 229 822 229 837 229 846 229 869 229 878 229 887 229 896 229 905 229 913 229 823 229 838 229 847 229 870 229 879 229 888 229 897 229 906 229 914 229 824 229 839 229 848 229 871 229 880 229 889 229 898 229 907 229 915 229 825 229 840 229 849 229 872 229 881 229 890 229 899 229 908 229 916 140 200 Spring 9 grey 229 826 229 841 229 850 229 873 229 882 229 891 229 900 243 416 243 417 Standard Offset 5 mbar (Closing force of counterspring in closed position) Dimensions Type Order No. p max. Rp / DN Dimensions [mm] a b c d e f g h Weight [kg] FRNG 503 FRNG 505 FRNG 507 FRNG 510 FRNG 515 FRNG 520 220 967 220 968 220 969 220 970 209 064 209 065 Rp 3/8 Rp 1/2 Rp 3/4 Rp 1 Rp 1 1/2 R 77 77 100 110 150 170 115 115 130 145 195 250 24 24 28 33 40 47 143 143 165 190 250 310 G 1/8 G 1/8 G 1/8 G 1/8 225 225 245 310 365 450 0.60 0.60 1.00 1.20 2.50 3.50 FRNG 5040 FRNG 5050 FRNG 5065 FRNG 5080 FRNG 5100 FRNG 5125 FRNG 5150 159 350 209 067 209 068 209 069 214 422 220 758 224 212 DN 40 DN 50 DN 65 DN 80 DN 100 DN 125 DN 150 200 230 290 310 350 400 480 195 250 285 285 350 400 480 75 82.5 92.5 100 110 125 142.5 280 340 405 405 495 635 780 395 480 590 590 760 1000 1180 3.50 5.00 7.50 10.00 16.00 28.00 38.00 3 8 Bypass restrictor Rp 3/8 - Rp2 225 256

Functional description Functions according to the force comparison principle between the force of: - the adjustable setpoint spring - the defined counterspring - the differential pressure at the working diaphragm and - the force due to weight of the moving parts The counterspring acts against the adjustable spring and the weight due to force of the moving parts. Depending on the pretension of the adjustable spring and the installation position, the force of the counterspring is compensated. Overcompensation leads to positive regulator output pressures, partial compensation leads to negative regulator output pressures. Instructions Gas-conveying lines, pulse and connection lines must be made of steel and at least PN 1, DN 6. The lines must be resistant to thermal, chemical and mechanical loads. The lines must be durable and deformation- and crackproof. Do not route condensate from lines into the pressure regulator. Do not apply burning gas or combustion gas air mixtures to the installation chamber of the adjustable spring. FRNG 515 sectional drawing Pressure regulator in closed position 11 10 9 8 7 5 6 4 p 1 3 2 1 12 13 1 Housing 2 Regulating cup 3 Pulse tap, internal 4 Compensation diaphragm 5 External pulse 6 Diaphragm disk 7 Working diaphragm 8 Safety diaphragm 9 Breathing plug 10 Setpoint spring 11 Adjustment device 12 Counterspring 13 Option DN 125, DN 150 Measurement opening with screw plug G 1/8 4 8

Application of zero pressure regulator (standard design) The FRNG regulates a gas flow proportional to the consumer vacuum for gas motors and self-intaking gas equipment. The regulator is adjusted within the setting range at the setpoint spring. V min. = V max. x 0.1 KH GF FRS DMV FRNG Gas motor +5 Air filter Mixer For V max, see volumetric flow pressure drop characteristic. Pressure Vacuum +1-1 -3 Resulting output pressure Vmax. Setting range p2-3 mbar +5 mbar V [m 3/h] Application with compressed aircontrolled pressure regulator (standard design) For externally controlled gas equipment. Blower M Compressed air regulator Pulse P L Control air In connection with a selected setpoint spring, the regulator output pressure can be controlled depending on the blower pressure (compressed air). The command variable can be up to +150 mbar. V min. = V max. x 0.05 For V max, see volumetric flow pressure drop characteristic. Sequential variable Regulator output pressure KH GF DMV FRNG Command variable 1 Blower pressure p L 0 +1 or compressed air P 2 Burner Pretension of setpoint spring e.g. spring No. 6 (yellow) 30-70 bar p L Pressure taps Pulse and blower connection 1 Breathing plug or connection for ventilation line. Only route ventilation line in special cases or connection for air pulse line 1 2 Connection for external gas pulse. Internal pulse must be closed. 3 Pressure connection in inlet section ISO 228 screw plug, Rp 3/8 to R with bypass cover prepared for mounting adjustable bypass restriction. 2 3 Option FRNG 503-520 V1 + 225 256 5 8

Application of proportional pressure regulator (standard design) As proportional pressure regulator for gas-air ratio regulators with fixed efficiency pressure ratio V = 1:1 on gas equipment operated with differential pressure. The offset range of the counterspring can be set by the setpoint spring. The moving parts are compensated by the force due to weight. Gas supply or air supply are adjustable at full load and partial load. Basic load is adjustable via bypass restrictor. The command variable can be up to +150 mbar. V min. = V max. x 0,05 For V max, see volumetric flow pressure drop characteristic. Blower M Air Valve Pulse KH GF DMV FRNG Adjustable bypass restrictor FRNG 503-520 V1 + 225 256 P L P 2 Industrial burner 100 % 95 % Regulator output pressure 1 : 1 Offset range for regulator characteristic 0,95 : 1 Actual pressure ratio Blower pressure p L p L 6 8

Volumetric flow pressure difference characteristic Bypass restrictor 100 80 60 50 40 Recommended operating range 30 p 20 10 8 6 5 4 3 Bypass restrictor adjustable for FRNG 503 FRNG 505 FRNG 507 FRNG 510 FRNG 515 FRNG 520 Order-No. 225 256 + 2 1 Basis + 15 C, 1013 mbar, trocken Based on + 15 C, 1013 mbar, dry Base + 15 C, 1013 mbar, sec Base + 15 C, 1013 mbar, secco 0,1 0,2 0,3 0,4 0,5 0,6 0,8 1 2 3 4 5 6 7 8 9 10 Vn [m 3/h] Luft / Air / Aria dv = 1,00 0,2 0,3 0,4 0,5 0,6 0,8 1 2 3 4 5 6 7 8 910 Vn [m 3/h] Erdgas/Natural gas/gaz Naturel/Gas metano dv = 0,65 7 8

Pressure regulator FRNG Zero pressure regulator Proportional pressure regulator Compressed air-controlled pressure regulator Volumetric flow pressure loss characteristic Rp 3/8 Rp 1/2 Rp 3/4 Rp 1 DN 40, Rp 1 1/2 DN 50, R DN 65 DN 80 DN 100 DN 125 DN 150 100 90 80 70 60 50 40 Recommended operating range 30 20 Δp 10 9 8 7 6 5 4 3 2 1,0 Basis + 15 C, 1013 mbar, trocken Based on + 15 C, 1013 mbar, dry Base + 15 C, 1013 mbar, sec Base + 15 C, 1013 mbar, secco 1 2 4 6 8 10 20 40 60 80 100 200 400 600 800 1000 2000 4000 3 Vn [m /h] Luft / Air / Aria dv = 1,00 1 2 4 6 8 10 20 40 60 80 100 200 400 600 800 1000 2000 4000 3 Vn [m /h] Erdgas/Natural gas/gaz Naturel/Gas metano dv = 0,65 We reserve the right to make any changes in the interest of technical progress. Head Offices and Factory Karl Dungs GmbH & Co. KG Karl-Dungs-Platz 1 D-73660 Urbach, Germany Telephone +49 (0)7181-804-0 Fax +49 (0)7181-804-166 Postal address Karl Dungs GmbH & Co. KG Postfach 12 29 D-73602 Schorndorf, Germany e-mail info@dungs.com Internet www.dungs.com 8 8