Pneumatic switch module 3/2-way valve (On/Off) Types P Types FP Function tested for use of the float in Ex-zone 0

Similar documents
Pneumatic proportional controller Types M Types FM Function tested for use of the float in Ex-zone 0

LTB013EN. Operating Instruction Trimod Besta Level Switch types XA 5, XB 5 for use in potentially explosive atmospheres acc.

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

Mounting and Operating Instructions EB 2558 EN. Self-operated Pressure Regulators. Type Pressure Build-up Regulator

Steam Trap BK BK 212-ASME. Original Installation Instructions English

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Type Type Differential Pressure Regulators (opening)

Type 2000 INOX. Quickstart. English Deutsch Français. 2/2-way angle seat valve 2/2-Wege Schrägsitzventil Vanne à siège incliné 2/2 voies

Mounting and Operating Instructions EB 3017 EN. Self-operated Regulators

KBV21i and KBV40i Air Actuated Boiler Blowdown Valves

Steam Trap BK 15 (DN40, DN 50) Original Installation Instructions English

AVS32 Stainless Steel Air Vent for Steam Systems Installation and Maintenance Instructions

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

Mounting and Operating Instructions EB 3009 EN. Self-operated Regulators. Type RS Check Valve (backflow protection)

Pressure maintenance valve SDV-P / SDV-P-E

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

OPERATING MANUAL CHEMTRAC 840M MANUAL RETRACTABLE PROCESS HOLDER

V5197A. Firing Rate Gas Valve APPLICATION FEATURES PRODUCT HANDBOOK

Operating instructions - Translation of the original -

Steam trap BK 37 BK 28 BK 29 BK 37 ASME BK 28 ASME BK 29 ASME

OPERATION MANUAL NTF-15

Mounting and operating instructions EB 2530 EN. Self-operated Pressure Regulator. Pressure Reducing Valve Type M 44-2

Instruction Manual Contact Pressure Vacuum Gauge

Mounting and Operating Instructions EB EN. Type Supply Pressure Regulator. with increased air capacity

Type 2080 FALTENBALGVENTIL BELLOWS VALVE VANNE A SOUFFLET. Operating Instructions. Bedienungsanleitung Manuel d utilisation

THE HF-300 SERIES. Operating and Service Manual. Series includes all variants of HF-300/301

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

Type Operating Instructions. 2/2-way solenoid valve 2/2-Wege Magnetventil Electrovanne 2/2 voies.

OPERATING MANUAL. Contents. Bottom outlet ball valve Type ecoline

3-PIECE BALL VALVE, 3600 PSI/ PN 248, WITH ISO DIRECT MOUNTING PAD 306M SERIES/ PED Category II

THE BP-301 SERIES. Operating and Service Manual. Series includes all variants of BP-301 (LF 0.1Cv / MF 0.5Cv)

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators

Type /2-Way Globe Valve 3/2-Wege-Geradsitzventil Vanne à siège droit 3/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation

GESTRA Steam Systems AK 45. Installation Instructions Condensate Drain Valve AK 45

Mounting and Operating Instructions EB EN. Self-operated Pressure Regulators. Type 2335 Excess Pressure Valve with pilot valve

Hand pump type CH. Product documentation. 300 bar 8.3 cm 3 /stroke. Operating pressure p max : Displacement volume V max stroke :

1. Preface Important Safety Notes Brief Product Information Product Working Principle Installation Guidelines...

Pressure booster combination DPA-CRVZS. Operating instructions a [ ]

Bray/ VAAS O-Ported Series Knife Gate Valve 770/780 Series Operation and Maintenance Manual

DCV6 Disc Check Valve

OPERATION MANUAL NTF-60 Plus

Operating Instructions in compliance with Pressure Equipment Directive 2014/68/EU. AWA Change-over Valve

AVC32 Carbon Steel Air Vent for Steam Systems

WHEATLEY WHEATLEY SERIES 500 SWING CHECK VALVE. Installation, Operation and Maintenance Manual

Series 44 Self-operated Pressure Regulators. Type 44-0 B Pressure Reducing Valve. ANSI version

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

A3S Bellows Sealed Stop Valve Installation and Maintenance Instructions

THE MF-400 SERIES. Operating and Service Manual. Series includes all variants of MF-400/401

Installation, Operation and Maintenance Manual for Back Pressure Regulator

SCA Series Inverted Bucket Steam Traps

Declaration of Conformity as per Directive 97/23/EC and Manufacturer s Declaration as per Directive 98/37/EC

Type 0404 / /2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation

CAST IRON SAFETY VALVE TYPE 6301

Mounting and Operating Instructions EB 8546 EN. Type 4708 Supply Pressure Regulators. Translation of original instructions. Type Type

BALL VALVE ASSEMBLY AND MAINTENANCE PROCEDURE. REF. DOC.MMM900N Rev.1 March 2014 SERIES M DIN / ANSI. Page 1 of 17

BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications

Float Operated Level Controllers

Engineering Data Sheet

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS

Materials : Stainless steel ASTM A351 CF8M

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions

WHEATLEY Series 500 Swing Check Valve

HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions

Operating instructions - Translation of the original -

Type BBS-03, BBS-05, BBS-06, BBS-25

MUD 1. Vent check valves. Instruction and maintenance manual.

Preliminary filter Precision measurement chamber Flow meter Instruction manual

PV4 and PV6 Piston Valves

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

Modular valve block. Operating manual Series MVB 100/200. Version BA EN Print-No TR MA DE Rev001

Ball Float Steam Trap UNA 43 PN 16/CL 125/JIS 10K UNA 46 PN 40/CL 150/CL 300/JIS 10K/JIS 20K DN 80, 100, 150, 3", 4", 6"

Universal Charging and Testing Unit FPU-1

Declaration of Conformity as per Directive 97/23/EC

Declaration of Conformity as per Directive 97/23/EC

INSTRUCTION MANUAL Pressure Relief Device LPT

MF2M Monnier Miniature Compressed Air Filter

Instruction Manual. Alfa Laval SB Membrane Sample Valve ESE02963-EN Original manual

PGN. Application example. Pneumatic 2-Finger Parallel Grippers Universal Grippers. Gripping force 100 N N. Sizes

INSTRUCTIONS AND MAINTENANCE MANUAL SERIES: RT

Seated valves VRB 3, VRG 3

6-way characterised control valves DN15 and DN 20

Installation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM.

Flow controller Type ED/CCB311 Instruction manual

Manual Actuated Boiler Blowdown Valves

Ball Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300 DN 40, 50, 65

MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection

Declaration of Conformity as per Directive 97/23/EC

TD45 Thermodynamic Steam Trap Installation and Maintenance Instructions

Installation, Operation, and Maintenance Manual

Installation & Operation Manual Proven Quality since 1892

Type 3709 Pneumatic Lock-up Valve. Translation of original instructions. Mounting and Operating Instructions EB 8391 EN

FT53, IFT53, FT54, IFT54, FT57 and IFT57 Ball Float Steam Traps - DIN

Operating Instructions in compliance with Pressure Equipment Directive 2014/68/EU. FAS Manual Brass Shut-Off Valve DN10 through DN22

GM Series Dual-Block Multi-Function Gas Control Valves

Pressure Relief Valve DHV 718

FTGS14 Ball Float Steam Trap DN15 (½") to DN25 (1")

Wafer Check Valve. Contents. User s Manual. (1) Be sure to read the following description of our product warranty 1

Magnetic level switch type MR783 Instruction Manual

Instruction Manual. Alfa Laval SB Pressure Exhaust Valve ESE02965-EN Original manual

Double valves for biogases and recycling gases

KTM OM-2 SPLIT BODY FLOATING BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

Transcription:

Operating Manual LTIA3E Pneumatic switch module 3/2-way valve (On/Off) Types P Types FP Function tested for use of the float in Ex-zone 0 Contents 1. Safety Instructions 2. Conformity to standards 3. Technical data 4. Installation and initial start-up 5. Maintenance 6. Replacement of the switch module 7. Fire protection 8. Disposal Legend Information: Application hints and important information. To be followed for optimal function. Attention: Requirements and prohibitions to prevent damages, especially to material and the environment. Danger: Dangerous situation that can lead to injury and death if instructions are not followed. www.besta.ch page 1 of 6 LTIA3E / 2010.01

1. Safety Instructions The operating manual must be read and understood before installation. If you are uncertain on any point, please contact Besta AG. During work in potentially explosive atmospheres at the operator s site, please ensure that you always observe the special regulations applicable to work on Exdevices (applies to type series FP ). Every Trimod Besta level switch must be selected by qualified personnel in accordance with the specifications stipulated by the customer. These specifications must be kept by the operator in a safe place, together with the operating manual, the customer-specific designation and the type number (see type plate). In the event of any deviation of the physical quantities (pressure, temperature, density, etc.) from the original specification, the suitability of the level switch must be checked again by qualified, trained personnel or by the manufacturer, with regard to the new specifications. Process vessels / float chambers must be brought to atmospheric pressure and appropriately vented before work is carried out. The Trimod Besta level switches must under no circumstances be used as a support aid or as a security fixture for equipment structures or persons. 2. Conformity to standards The Trimod Besta level switches of the type series P correspond to the requirements of the Machine Directive 98/37/EC. In addition, the Trimod Besta level switches of type series FP correspond to the requirements of the standards according to EN 50284:1999, EN 50014:1997 +A1 +A2 3. Technical data Pneumatic connection Supply air (compressed air quality) : Quality class 4 to ISO 8571 (max. particle size 15 μm, max. particle density 8 mg/m³) Max. control pressure : 10 bar Test pressure : 12 bar Internal opening at 10 bar : 1.5 mm Kv factor : 1 Internal leakage rate : Max. 1 cm³/min Flow rate : 90 Nl/min at 6 bar Pressure drop : 1 bar The connection of the type series FP should be carried out in accordance with the rules and safety regulations for Ex-devices. www.besta.ch page 2 of 6 LTIA3E / 2010.01

Principles of use Depending on the required function, the supply air can be connected to the 3/2-way valve optionally at A or B, according to whether the filling process (Fig. 1) or the emptying process (Fig. 2) or the actuator is fail-safe to close or fail-safe to open. This means that the pressurization occurs via A-C and the venting via C-B or vice versa, pressurization via B-C and venting via C-A. Connection diagram (Fig. 1) Filling (Fig. 2) Emptying Special conditions for safe use Temperature application ranges Type series Housing material Operating temperature T 0 (of medium) P, PV untreated 2P, 2PV chromated (Alodine) 5P, 5PV stainless steel 1 C 250 C 1 C 250 C 1 C 380 C Ambient temperature T A 1 C 80 C 1 C 80 C 1 C 80 C Type series Housing material Operating temperature T 0 (of medium) FP, FPV untreated F2P, F2PV chromated (Alodine) F5P, F5PV stainless steel 1 C 250 C 1 C 250 C 1 C 380 C Ambient temperature T A 1 C 80 C 1 C 80 C 1 C 80 C www.besta.ch page 3 of 6 LTIA3E / 2010.01

4. Installation and initial start-up During installation (see Fig. 3), the correct operating position must be observed. For side mounting, observe the Top arrow on the type plate. The float must be able to move freely over the whole range of movement and must not be restricted by the tank walls or (Fig. 3) by fittings in the tank. Applications where turbulence is present (e.g. stirring apparatus) can interfere with the function and should, in all cases, be avoided. Process connection flange - industrial series For switches of the industrial series with flanges according to DIN, ANSI, etc., the gaskets 1) and connecting stud bolts 1) used must correspond to the industry standard as regards material, pressure class and type of gasket and must be tightened to the corresponding tightening torques. In the case of uncertainty on any point, refer to the corresponding standard or consult the manufacturer. Process connection flange - standard series For switches of the standard series PN 25 (360 psi), corresponding gaskets are supplied with the unit. Minimum tightening torques and tightening sequence Flange D Gasket 01 / 011 92 mm Garlock Blue Gard 3000 Stud bolts carbon steel Stud bolts stainless steel 18 Nm 2) 22 Nm 2) Connecting 1. Remove protective plugs from the valve body 2. Assemble the hose or pipe screwed connection and check that it is seated correctly. 3. Carefully allow the control pressure (supply air) to build up. Caution: Use only clean control air; if necessary, install a filter! 1) Not included in the scope of supply 2) Data refer to lubricated stud bolts www.besta.ch page 4 of 6 LTIA3E / 2010.01

5. Maintenance Level switches must be periodically (min. 1x annually) tested and cleaned. Procedure: 1. Loosen the flange connection and remove the switch. 2. Check the float and mechanism for damage and contamination. 3. Remove deposits and metal particles by means of suitable and approved methods. Care must be taken to ensure that no mechanical damage occurs as a result of the cleaning. 4. In the case of floats with protective bellows, the bellows must be removed before cleaning and should be cleaned separately, both internally and externally. 5. Inspect the float and mechanism for complete deflection, as well as for smooth and unrestricted operation. 6. In the event that it becomes necessary to replace individual components, please note that only original spare parts, split pins, float, switch module, etc. may be installed. 7. After completion of the cleaning / inspection work, the switch module must be checked for correct function by means of simultaneous complete deflection of the float, followed by recording in the inspection log book. 8. In order to guarantee the absence of leaks between process vessel / float chamber, the flange gasket must be replaced after each dismantling. 9. After carrying out the inspection work, the device is re-assembled at the intended location. Adjustment screws in the interior of the housing must not be adjusted! 6. Replacement of the switch module Defective switch modules must be replaced with new, works-tested units. In order that the complete type designation can be stamped on the type plate, the complete designation of the existing switch must be specified at the time of ordering. If a complete identification of the switch is not possible, then the manufacturer should be consulted before dispatching the complete device. In the case of uncertainty on any point, please contact the local Trimod Besta agent or the manufaturer. www.besta.ch page 5 of 6 LTIA3E / 2010.01

Replacing the switch module Important notes: The level switch does not have to be removed from the process vessel in order to replace the switch module. Procedure: 1. Observe Chapter 1 Safety instructions. 2. Detach the hose or pipe screwed connection from the valve body. 3. Remove socket head cap screws from housing with Allen key (5 mm). 4. Carefully remove the switch module from the flange. 5. Fit a new gasket on the flange and check that it is correctly seated. 6. Place the replacement switch module (incl. gasket) on the flange and tighten the socket head cap screws with the Allen key. 7. Assemble the hose or pipe screwed connection in the valve body and check that it is seated correctly. 8. Carefully allow the supply air (pressure) to build up. 7. Fire protection Trimod Besta level switches must be protected against external fire hazard. 8. Disposal Trimod Besta level switches are free of any asbestos-containing or otherwise hazardous materials. Disposal must be carried out in an environmentally-friendly manner and in accordance with the local regulations. Besta AG, Ackerstrasse 45, CH-8610 Uster / Switzerland Phone +41 43 399 15 15, Fax +41 43 399 15 00 Email info@besta.ch, www.besta.ch With reservation of technical modification www.besta.ch page 6 of 6 LTIA3E / 2010.01