TRANSFORMER SERVICE. Dissolved gas analysis and oil condition testing

Similar documents
Power Transformer Maintenance. Maintenance Practices & Procedures for Substation Class Distribution Power Transformers

MODERN APPROACH FOR CONDITION MONITORING OF POWER TRANSFORMERS USING DISSOLVED GAS ANALYSIS

A REVIEW OF DISSOLVED GAS ANALYSIS AND TRANSFORMER HEALTH CONDITION

Online DGA-monitoring of power transformers

Dissolved Gas Analysis - Past, Present and Future

Dissolved Gas Analysis An Early Identification of Faults in High Voltage Power Equipment using MATLAB GUI

Since the beginning of production of oil for transformers

Understanding Dissolved Gas Analysis (DGA) Techniques and Interpretations

Comparison of Different DGA (Dissolved Gas Analysis) Methods for the Condition Assessment of Power Transformers

EXPERIENCES WITH APPLICATION, DIAGNOSTIC VALUE AND IMPACT ON ASSET MANAGEMENT OF INSULATION OIL ANALYSIS

DISSOLVED GAS ANALYSIS OF NATURAL ESTER FLUIDS UNDER ELECTRICAL AND THERMAL STRESS

Improved Monitoring of Dissolved Transformer Gases on the Basis of a Natural Internal Standard (NIS)

Draft Guide for the Interpretation of Gases in Oil Immersed Transformers

A Revised Framework for the Transformer DGA Guide

Nandkumar Wagh, D.M. Deshpande

DGA Tools: Duval Triangles and Pentagons

* Analysis of TCG ( Total Combustible Gas ) and 6 kinds of Gases * High Sensitivity for C 2

Diagnostics of HV bushings through oil sampling and analysis. Experience with GSU transformers

Transformer fault diagnosis using Dissolved Gas Analysis technology and Bayesian networks

Categorizing Faults via DGA. GE Grid Solutions M&D

FIRE PREVENTION METHOD FOR 275KV OIL-FILLED CABLE IN TEPCO

Research Article. Fault diagnosis of power transformer based on chemical properties of insulation oil

PROPOSAL FOR AN IMPROVEMENT IN TRANSFORMER DIAGNOSIS BY DGA USING EXPERT SYSTEM.

INTERNATIONAL STANDARD

Micafil RIP bushings High-voltage Resin-Impregnated Paper bushings. Power and productivity for a better world TM ABB

Applied Technology and Best Practices in CEE. Conference

Commercial Practice Test Method Internal Vapor Analysis of Hermetic Devices

Gases and welding distributors continue

Micafil RIP bushings High-voltage Resin Impregnated Paper bushings. Power and productivity for a better world TM ABB

Online Publication Date: 19 January, 2012 Publisher: Asian Economic and Social Society

Guide for the Sampling of Oil from Trench COTA Bushings for DGA

Misuse of Combustible Gas Meters

Neil Kane Managing Director EMT UK

Agilent 490 Micro GC Natural Gas Analyzer

Series 6517 Katharometers. The ideal equipment for Process Monitoring and Control. Robust no moving parts. Designed for continuous industrial use

DISSOLVED GAS ANALYSIS OF POWER TRANSFORMERS

Gases&Technology. Measurement of Impurities in Helium Using the Dielectric Barrier Discharge Helium Ionization Detector. FEATURE.

Mathieu Guertin. Morgan Schaffer Inc. Canada. Director Europe, Russia and Africa. A cost effective strategy for smart grid technology adoption

Dynamic Behaviour of Fault Gases and Online Gas Sensors. Germany

Discovery HP-TGA 75/750. Site Preparation Guide

Cambridge Refrigeration Technology

ASTM 3612/TOGA/Dissolved Gas GC Revised October 2013

Multiple Gas#5 GC configuration Jan 2016

ENVIRONMENTAL AND POLLUTANTS GAS ANALYZERS

Instrumental Technique GAS CYLINDER

Zebron Gas Management

Diagnosing EVAP systems By: Bernie Thompson

" High Voltage Switch Yards & How Safe are these really" <Peter Rhodes> <Principal and High Voltage Solution. Com Ltd>

METHOD 3C - DETERMINATION OF CARBON DIOXIDE, METHANE, NITROGEN, AND OXYGEN FROM STATIONARY SOURCES

Three Columns Gas Chromatograph Analysis Using Correlation between Component's Molecular Weight and Its Response Factor

4/26/16. Section 1 Understanding Solutions. Solutions and Suspensions. Solutions and Suspensions. Solutions and Suspensions. Solvents and Solutes

Portable Gas Analyzers

Protective Atmospheres, Measurement Technologies and Troubleshooting Tools

Gun Vacuum Performance Measurements February 2003

CTB3365x Introduction to Water Treatment

LINEAR TRANSFORMATION APPLIED TO THE CALIBRATION OF ANALYTES IN VARIOUS MATRICES USING A TOTAL HYDROCARBON (THC) ANALYZER

ISO INTERNATIONAL STANDARD. Welding consumables Gases and gas mixtures for fusion welding and allied processes

Power Transformer Fault Diagnosis Based on Dissolved Gas Analysis Using a Fuzzy Neural Network Approach in a Real Data Base

Flare Gas Composition Analysis and QA/QC Lessons Learned and Lessons Lost SPECTRUM ENVIRONMENTAL SOLUTIONS, LLC 1

Session Number: 3 High Voltage Power Transformer Dissolved Gas Analysis, Measurement and Interpretation Techniques

HiQ laboratory gas generators.

Applications Note: Use of "pentane equivalent" calibration gas mixtures

Calibration Requirements for Direct Reading Confined Space Gas Detectors

SUBSTATION MAINTENANCE ELECTRICAL OPERATING PROCEDURE

BPZM-MRD Nitrogen Injection System

CHAPTER 16 %UHDWKLQJ*DV0L[LQJ3URFHGXUHV

acrolein, acetaldehyde and acetone( cm -1 ); methanol (1306 cm -1 ); ethylene (949 cm -1 ); and isoprene (893 cm -1 ).

23.1 Functions, Basic Configuration, and Interfaces

Condition Monitoring of Power Transformer Using Dissolved Gas Analysis of Mineral Oil: A Review

DSC 204 HP Phoenix. High-Pressure Differential Scanning Calorimetry up to 15 MPa Method, Technique and Applications

Learning from Dangerous Occurrences in the Chemical Industries

Department of Physics Standard Operating Procedures (SOP) Approved by: Physics Safety Committee

ASTM WK Standard Test Method for Dissolved Gases. Anne Jurek Applications Chemist

ISO 9539 INTERNATIONAL STANDARD. Gas welding equipment Materials for equipment used in gas welding, cutting and allied processes

Service ISO17025 explained

2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic. Pressure Measurement Engineered solutions for all applications

Working in Gas Hazard Areas

Chapter 7. Coal Cargoes. Properties and Characteristics 7.1

Manual. Online Degasser DDG-75. Manual Degasser DDG-75 April DURATEC Analysentechnik GmbH Rheinauer Strasse 4 DE Hockenheim Germany

ON-LINE MONITORING OF REGULATOR TRANSFORMER AT THE MARGEM DIREITA SS IN ITAIPU. M. E. G. ALVES* Treetech Sistemas Digitais Ltda.

The benefits of the extended diagnostics feature. Compact, well-proven, and flexible

Chapter 5: Comparison of Inspection and Testing Results

ISO INTERNATIONAL STANDARD

Rapid and Reliable Detection of Dissolved Gases in Water

APPLICATION NOTE. Fast Analysis of Coal Mine Gas Using the INFICON 3000 Micro GC ABSTRACT

CHAPTER 5 : THE AIR AROUND US

Mass Spec will not Autotune

Navigator 600 Silica analyzers

Oxygen Measurement in Natural Gas

Automated Determination of Dissolved Gases in Water Anne Jurek. Abstract: Discussion:

NZQA unit standard 7145 version 9 Page 1 of 5. Design and maintain effective ventilation systems for an underground coal mine

Laboratory Hardware. Custom Gas Chromatography Solutions WASSON - ECE INSTRUMENTATION. Engineered Solutions, Guaranteed Results.

COAL MINES TECHNICAL SERVICES, GAS DETECTION RELATED SERVICES FOR MINES RESCUE

Dissolved Oxygen Guide

Organic Elemental Analysis Series II Nitrogen Analyzer. proven performance. reliable results

Responding to Natural Gas Pipeline Emergencies

Describe Flammable Gas Measurement

LOW-CURRENT INTERRUPTION IN SF 6-ALTERNATIVES

Laboratory Hardware. Custom Gas Chromatography Solutions WASSON - ECE INSTRUMENTATION. Custom solutions for your analytical needs.

Transcription:

TRANSFORMER SERVICE Dissolved gas analysis and oil condition testing

D I S S O LV E D G A S A N A LY S I S A N D O I L C O N D I T I O N T E S T I N G Transformer diagnostic services at ABB perform dissolved gas analysis and supervision of oil condition in power transformers, reactors, instrument transformers, circuit breakers and oil insulated cables.

3 Dissolved gas analysis and oil condition testing This product information is divided into the following sections: 1. Dissolved gas analysis (DGA) 2. Supervision of oil condition 3. Sampling and frequency of analyses 4. Ordering of tests 1. DISSOLVED GAS ANALYSIS (IEC 60599) For many years, analyzing gases dissolved in transformer oil has been used as a diagnostic tool. The method can detect incipient faults, supervise suspect transformers, test a hypothesis, explain reasons behind failures or disturbances that have occurred and ensure new transformers are healthy. In this respect dissolved gas analysis is regarded as a fairly mature technique and it is employed by several ABB transformer companies around the world, either in their own plants or in cooperation with an affiliated or independent laboratory. The idea that supports the value of dissolved gas analysis is the fact that during its lifetime a transformer generates decomposition gases, essentially from its organic insulation, under the influence of various stresses, both normal and abnormal. The gases that are of interest for a DGA analysis are the following: H2 hydrogen CH4 methane C2H4 ethylene C2H6 ethane C2H2 acetylene C3H6 propene C3H8 propane CO carbon monoxide CO2 carbon dioxide O2 oxygen N2 nitrogen TCG total combustible gas content (H2, CH4, C2H4, C2H6, C2H2, CO, C3H6, C3H8) All of these gases, except oxygen and nitrogen, can form as the insulation degrades. The amount and the relative distribution of these gases depend on the type and severity of the degradation and stress. 1.1 Procedure The DGA procedure consists of essentially four steps: Sample oil from the transformer Extract gases from the oil Analyze the gas mixture in a gas chromatography, GC Interpret the analysis according to an evaluation scheme Preferably, the samples should be taken from moving oil so that the gases produced are coming from the point of generation. Suitable locations are valves in the cooler/radiator circuit. To take samples from these locations is not always possible because of design limitations. Other places from which to draw samples are the cover, bottom valve, the conservator and the Buchholz relay. In addition, it is very important that the sampling is carefully done to assure that contamination is kept to a minimum and that gases are not lost during sampling or transportation to the laboratory.

4 DISSOLVED GAS ANALYSIS AND OIL CONDITION TESTING The removal of the gases from the oil can be accomplished by various methods: Partial degassing (single-cycle vacuum extraction) Total degassing (multi-cycle vacuum extraction) Stripping by flushing the oil with another gas The headspace technique in which gases are "equalized" between free gas volume and oil volume. ABB Transformers Diagnostic Services in Ludvika uses the headspace method (figure 1). 1.2 Interpretation There are several different ways to explain and interpret the analyzed gas composition and to diagnose the condition of the transformer. Essentially the following methods are at hand: Identify the key gas to ascertain a particular problem, e.g. H2 indicates partial discharges (PD) Determine gas ratios, normally between gas levels Determine gas levels in ppm or ml Determine rates of gas increase or "production rates" in ppm/day or ml gas/day Around the world and over the years several different evaluation schemes have been proposed for DGA. The most commonly known include one proposed by Rogers, which forms the ANSI method, and another described in IEC Publication 60599. Both methods use ratios between gas concentrations. In order to get a feeling for DGA interpretation, the key-gas method is appropriate (figure 3). 01 Headspace gas chromatography instrument analyzes gases in insulation oil. The extracted gas mixture is fed into adsorption columns in a GC where the different gases are adsorbed and separated to varying degrees and consequently reach the detector after different periods of time. The gas mixture is separated into individual chemical compounds, identified and their concentrations in volume gas STP/volume oil are calculated and expressed in ppm. (STP=standard temperature and pressure). It should be emphasized that extraction and analysis may involve analytical errors, making it difficult to directly compare the results from two different laboratories. ABB advises working with just one highly reputable lab. You are looking for the most prominent gas the one that differs most from a tacitly expected "normal" level (or change). For instance when cellulose overheats, the main decomposition gases are CO and CO 2. With a partial corona discharge, is formed (PD in cellulose involves the formation of carbon oxides). With a more severe electrical discharge, such as arcing, is formed (normally also is formed with smaller amounts of methane and ethane. If CO is present, cellulose is involved). Lastly, overheated oil produces saturated hydrocarbons ( H 6 ) at lower temperatures and unsaturated hydrocarbons ( ) at higher temperatures. The presence of acetylene indicates very high temperatures. This scheme can also be used to understand the evaluation schemes based on ratios. For instance, the IEC method uses three ratios: C H 6 C / is used to discriminate between a thermal fault and an electrical fault. / indicates the presence of a strong discharge or very severe electrical problem and / H 6 is an indication of oil temperatures.

DISSOLVED GAS ANALYSIS AND OIL CONDITION TESTING 5 02 Characteristic key gases, principal layout 03 Breakdown voltage measurement cell 04 Apparatus for measurement of dielectric dissipation factor (tan δ) 02 1. Overheating of cellulose CO, CO 2 2. Overheating of oil increasing temperature H 6 C C C 3. Partial discharges (PD) increasing intensity 4. Discharges, 1.3 Application Oil sampling frequency depends on the importance of the transformer. A suspected fault (e.g. abnormal sounds) Signals from gas or pressure relay Directly after, or within some weeks, a short circuit When an essential transformer is put into operation, followed by further tests after a few months Following an obvious overloading of the transformers 2. Supervision of oil condition Even though it is generally acknowledged that dissolved gas analysis is normally the most powerful tool for diagnostic purposes, and for detecting incipient faults in a transformer, it is also very important to monitor the general status of the insulating oil. The oil may become contaminated with water, particles and other foreign substances. There is also a continuous aging of the oil and the solid insulation through the formation of water, acids and sludge. Apart from impairing the insulating properties, these oxidizing byproducts also cause accelerated degradation of the cellulose insulation. There are a number of different tests devised for detecting changes in the electrical properties and chemical composition of the oil. Some are done to order to obtain information about the status of the oil itself, while others are done mainly to assess the status of the cellulose insulation. Only the most commonly used and important measurements are discussed here. 2.1 Electrical properties 2.1.1 Breakdown voltage (IEC 60156) The ability of the oil to withstand electrical stress is obviously an important parameter in itself. A lowering of the breakdown voltage is usually due to the presence of particles in the oil, in particular in combination with a large water content (figure 3). 03 The analysis results are documented in reports that are sent to the customer. All recent and historical results and recommendations are also available online (itrafo). 04 2.1.2 Dielectric dissipation factor, tan δ (IEC 60247) This is a measure of the oil's dielectric losses (figure 4), mostly due to its conductivity. As such, it is not a very important parameter for the transformer's operation (unless the value is extremely high), but it is a good indicator of the presence of any dissolved ions and acids.

6 DISSOLVED GAS ANALYSIS AND OIL CONDITION TESTING 2.2 Chemical properties 2.2.1 Water content (IEC 60814) Some buildup of water content is inevitable, due to the aging processes mentioned above. Water leakage into the transformer by a variety of mechanisms can also occur. Measuring the oil's water content helps to estimate the amount of water in the solid insulation, which is where most of the water is bound. High water content in the oil may lower the breakdown voltage, while the main problem with high water content in the solid insulation is the increased aging rate of the paper (figure 6). Note, however, that the oil and solid insulation water content is strongly linked, and as the temperature changes, water is redistributed between the two. reaction in which oxidizing agents promote further oxidation. Inhibited oils of good quality normally age very slowly as long as any inhibitor is still present. However, when the inhibitor is spent the oxidation will proceed relatively rapidly. For this reason it is important to monitor the inhibitor content, so that preventive maintenance actions can be taken before the onset of rapid oxidation (figure 6). 2.3 Physical properties 2.3.1 Color (ASTM D1500) Color is not a very important property of insulating oil. However, it indicates the degree of aging and, when combined with the chemical analyses, it has some diagnostic value. 05 Apparatus for determining the water content in oil using Karl Fischer titration. 2.2.2 Acidity (IEC 62021) Acids are a product of the oxidizing oil. This is a process involving reactions very similar to those causing wine to turn into vinegar, or butter or vegetable oil becoming rancid. The acidity, which is the amount of potassium hydroxide needed to neutralize the acids in the oil, is an indicator of the degree of aging. 2.2.3 Inhibitor content (IEC 60666) Inhibitors are added to the oil in order to slow oxidation. They react with certain intermediates in the oxidation process, thus preventing a chain 2.3.2 Interfacial tension (IFT) (ASTM D971-99) The interfacial tension between oil and water is a measure of the amount of polar contaminants and degradation agents. It is a useful indicator of aging, and a good complement to the acidity, because, as opposed to the latter, it is also influenced by non-acidic oxidation agents (figure 7). 2.3.3 Corrosive sulphur (IEC 62535) In recent years there have been a significant number of failures, in different types of equipment, due to the formation of copper sulphide in the cellulosic insulation. Also, due to the corrosive action of sulphur compounds in oil, other problems have been reported. It was realized that the tests for corrosive sulphur used in oil specifications, mostly ASTM D1275 (copper strip) or DIN 51353 (silver strip) were not adequate. Several oils passing these tests have caused copper sulphide formation on the site, in some cases resulting in failure. New tests have been developed that have higher sensitivity or are more relevant for the failure mechanisms involved. A new more severe copper strip test has been introduced (ASTM D1275 method B), and a covered conductor deposition test (CCD) was developed to identify oils that may cause copper sulphide precipitation in cellulosic insulation. A simplified version of the latter test is described in IEC 62535. Although the phenomenon of copper sulphide formation has attracted most of the attention in the last few years, the risk of sulphide formation on silver coated selector contacts should not be forgotten. The DIN 51353 silver strip test may be useful to detect this problem.

DISSOLVED GAS ANALYSIS AND OIL CONDITION TESTING 7 07 06 06 Gas chromatography mass spectrometer (GC-MS) for analysis of inhibitor content in oil. 07 Apparatus for measurement of interfacial tension (IFT). 3. Sampling and frequency of analysis (IEC 60567, IEC 60475) It is recommended to perform the oil sampling according to IEC 60567. The sampling procedure for oil condition supervision is describe in IEC 60475. ABB provides the appropriate test vessels and sampling instructions (figure 1). Sampling for DGA should be performed annually or as recommended by the laboratory. Oil supervision sampling should take place every 5 years for transformers up to 15 years of age, then every 3 years as recommended by the laboratory. 4. Ordering of tests Contact the laboratory at diagnostics@se.abb.com, or tel. +46 240 783307. We will provide the required sampling containers. Carefully follow the instructions in documents 1ZSE 209 001-4 and 1ZSE 209 001-6, which are provided with the sampling vessels. It is very important to indicate in your order if this is for a routine test. or if anything special has occurred in the transformer. Please also provide the name and telephone number of a contact person.

ABB Inc. Transformer Services (TRES) www.abb.com/transformerservice Additional information We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB. Copyright 2018 ABB. All rights reserved. 1LAB000628 04.2018