AE30 Automatic Air Eliminators / Air and Gas Vents for Liquid Systems

Similar documents
1. General safety information. 2. General product information. 3. Installation. 4. Commissioning. 5. Operation. 6. Maintenance. 7.

AVC32 Carbon Steel Air Vent for Steam Systems

AE14 Automatic Air Vents for Liquid Systems Installation and Maintenance Instructions

MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap

DF1 and DF2 Diffusers

TSS21 Sealed Thermostatic Steam Tracer Trap

DCV1, DCV3 and DCV3LT Disc Check Valves Installation and Maintenance Instructions

CVS10 Sanitary Check Valves

DCV10 Stainless Steel Disc Check Valve for use with Condensate Pumps

TA10A and TA10P Steam Tracing Temperature Control Valves Installation and Maintenance Instructions

CP10 Sensor Installation and Maintenance Instructions

Dri-Line Mk3 Monnier Compressed Air Drain Trap

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

Dri-Line Mk2 Spirax-Monnier Compressed Air Drain Trap

CA44, CA44S, CA46 and CA46S Air and Gas Traps

Fig 12, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

IFTGS14 Ball Float Steam Trap ½" and ¾" with Integral Spiratec Sensor

Fig 1, Fig 12, Fig 13, Fig 14HP, Fig 16, Fig 16HP and Fig 16L Strainers

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

DCV6 Disc Check Valve

PV4 and PV6 Piston Valves

KBV21i and KBV40i Air Actuated Boiler Blowdown Valves

BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications

AVM7 Stainless Steel Thermostatic Air Vent

FTGS14 Ball Float Steam Trap DN15 (½") to DN25 (1")

TP1 and TP2 Temporary Cone Shaped Strainers

BT6-B Sanitary Balanced Pressure Thermostatic Steam Trap

MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection

Airodyn, BRair and BRoil Compressed Air Drain Traps

BPT13 Balanced Pressure Thermostatic Steam Traps

HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions

CS10-1 Stainless Steel Clean Steam Separator

BTM7, BTS7 and BTS7.1 Stainless Steel Thermostatic Clean Steam Traps

CA16 and CA16S-14 Air and Gas trap Installation and Maintenance Instructions

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Knob Adjustment)

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Dial Adjustment)

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions

M10HTi ISO Tobacco Ball Valve Screwed, SW, BW and Flanged versions

M33F ISO, M33S ISO and M33V ISO Ball Valves Installation and Maintenance Instructions

FV Flash Vessel Installation and Maintenance Instructions

S and SF Inverted Bucket Steam Traps

CA10S, CA14 and CA14S Air and Gas Traps

APT14, APT14HC and APT14SHC Spares 2

SRV66 Sanitary Pressure Reducing Valve

IX1 Spirax-Monnier International Compressed Air Filter Installation and Maintenance Instructions

Fig 3, 7, 33, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers

MF2M Monnier Miniature Compressed Air Filter

AE50S Automatic Air and Gas Vent for Liquid Systems Installation and Maintenance Instructions

Manual Actuated Boiler Blowdown Valves

BCV31 DN40 - Blowdown Control Valve

TW Temperature Control Valve

TDC46M, TDS46M and UTDS46M Thermodynamic Steam Traps with Maintainable Seat Installation and Maintenance Instructions

M70i ISO and M80i ISO Stainless Steel Ball Valves for Sanitary Systems Installation and Maintenance Instructions

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats

Spirax Compact FREME Flash Recovery Energy Management Equipment

FT16 Ball Float Steam Trap Installation and Maintenance Instructions

ML3M Monnier Miniature Compressed Air Lubricator

Fig 7, 33, 33.1, 34, 34HP, 36, 36HP, 37, 3616 and Fig 3716 Flanged Strainers Installation and Maintenance Instructions

SCA Series Inverted Bucket Steam Traps

BRV71 and BRV73 Pressure Reducing Valves

BDV1 and BDV2 Blowdown / Depressurisation Valves

Thermocirc Installation and Maintenance Instructions

PC10HP Pipeline Connector (ASME 600)

BCV31 DN20 - Blowdown Control Valve

SA Control Valve types: BM, BMF, BX, SB, NS, KA, KB, KC (Normally open) BMRA, BMFRA, BXRA, SBRA, NSRA, KX, KY (Normally closed)

Type 130 and HL10 'Safeguard High Limit Control' Installation and Maintenance Instructions

MFP14-PPU (Vented) Automatic Packaged Pump Units

AVS32 Stainless Steel Air Vent for Steam Systems Installation and Maintenance Instructions

TD62LM and TD62M Thermodynamic Steam Traps with Replaceable Seats Installation and Maintenance Instructions

FT53, IFT53, FT54, IFT54, FT57 and IFT57 Ball Float Steam Traps - DIN

LP31 Level Probe. 1. Safety information. 2. General product information. 3. Installation. 4. Wiring. 5. Maintenance

A3S Bellows Sealed Stop Valve Installation and Maintenance Instructions

MPC1M, MPC2M and MPC2AM Monnier High Efficiency Compressed Air Filter / Regulators

SRV2S Pressure Reducing Valve

TD10, TD52M and TD259 Thermodynamic Steam Traps Installation and Maintenance Instructions

BSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions

STERI-TROL Clean Service 'S' Series Two-port Control Valves DN15 (½") to DN100 (4")

Spirax SafeBloc TM DBB3 Double Block and Bleed Bellows Sealed Stop Valve. 1. Safety information. 2. General product information. 3.

Vane Flow Switches Colima FLU Series

FT43, FT44, FT46 and FT47 Ball Float Steam Traps Installation and Maintenance Instructions

BTD52L Thermodynamic Steam Trap Installation and Maintenance Instructions

TD45 Thermodynamic Steam Trap Installation and Maintenance Instructions

QuickHeat TM Packaged Heat Exchanger Solutions

M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions

Fig 1, Fig 12, Fig 13, Fig 14, Fig 16 and Fig 16L Strainers Installation and Maintenance Instructions

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

IP2M, IP2AM and IP2DM Monnier International Compressed Air Filter/ Regulators

FTC62 and FTS62 Ball Float Steam Traps Installation and Maintenance Instructions

UBP32 Sealed Balanced Pressure Thermostatic Steam Trap for use with PC_ Pipeline Connectors Installation and Maintenance Instructions

SRV461S and SRV463S Stainless Steel Direct Acting Pressure Reducing Valves

BSA and BSAT Bellows Sealed Stop Valves Installation and Maintenance Instructions

Colima TOR Magnetic Level Switches

PC3000, PC3001 and PC4000, PC4001 Pipeline Connectors

BCVi43 Blowdown Control Valve

M111 Spiraflo Transducer

BDV60 Blowdown Vessel Installation and Maintenance Instructions

LP10-4 Level Probe. 1. Safety information. 2. General product information. 3. Installation. 4. Wiring. 5. Maintenance IM-P402-92

RJ check valves Installation and Maintenance Instructions

Transcription:

0170651/ 10 IM-P017-08 ST Issue 10 AE30 Automatic Air Eliminators / Air and Gas Vents for Liquid Systems Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning 5. Operation 6. Maintenance 7. Spare parts Printed IM-P017-08 in the ST UK Issue 10 Copyright 2007 1

1.Safety information Safe operation of these products can only be guaranteed if they are properly installed, commissioned, used and maintained by qualified personnel (see Section 1.11) in compliance with the operating instructions. General installation and safety instructions for pipeline and plant construction, as well as the proper use of tools and safety equipment must also be complied with. 1.1 Intended use Referring to the Installation and Maintenance Instructions, name-plate and Technical Information Sheet, check that the product is suitable for the intended use/application. The products listed below comply with the requirements of the European Pressure Equipment Directive 97/23/EC and carry the mark when so required. It should be noted that products rated as 'SEP' are required by the Directive not to carry the mark. The products fall within the following Pressure Equipment Directive categories: Group 1 Group 2 Group 1 Group 2 Product Gases Gases Liquids Liquids AE30 (all versions) - SEP - SEP i) The product has been specifically designed for use on steam, air or water/ condensate which are in Group 2 of the above mentioned Pressure Equipment Directive. The products use on other fluids may be possible but, if this is contemplated, Spirax Sarco should be contacted to confirm the suitability of the product for the application being considered. ii) Check material suitability, pressure and temperature and their maximum and minimum values. If the maximum operating limits of the product are lower than those of the system in which it is being fitted, or if malfunction of the product could result in a dangerous overpressure or overtemperature occurrence, ensure a safety device is included in the system to prevent such over-limit situations. iii) Determine the correct installation situation and direction of fluid flow. iv) Spirax Sarco products are not intended to withstand external stresses that may be induced by any system to which they are fitted. It is the responsibility of the installer to consider these stresses and take adequate precautions to minimise them. v) Remove protection covers from all connections and protective film from all name-plates, where appropriate, before installation on steam or other high temperature applications. 1.2 Access Ensure safe access and if necessary a safe working platform (suitably guarded) before attempting to work on the product. Arrange suitable lifting gear if required. 1.3 Lighting Ensure adequate lighting, particularly where detailed or intricate work is required. 2 IM-P017-08 ST Issue 10

1.4 Hazardous liquids or gases in the pipeline Consider what is in the pipeline or what may have been in the pipeline at some previous time. Consider: flammable materials, substances hazardous to health, extremes of temperature. 1.5 Hazardous environment around the product Consider: explosion risk areas, lack of oxygen (e.g. tanks, pits), dangerous gases, extremes of temperature, hot surfaces, fire hazard (e.g. during welding), excessive noise, moving machinery. 1.6 The system Consider the effect on the complete system of the work proposed. Will any proposed action (e.g. closing isolation valves, electrical isolation) put any other part of the system or any personnel at risk? Dangers might include isolation of vents or protective devices or the rendering ineffective of controls or alarms. Ensure isolation valves are turned on and off in a gradual way to avoid system shocks. 1.7 Pressure systems Ensure that any pressure is isolated and safely vented to atmospheric pressure. Consider double isolation (double block and bleed) and the locking or labelling of closed valves. Do not assume that the system has depressurised even when the pressure gauge indicates zero. 1.8 Temperature Allow time for temperature to normalise after isolation to avoid the danger of burns. If parts made from Viton have been subjected to a temperature approaching 315 C (599 F) or higher, it may have decomposed and formed hydroflouric acid. Avoid skin contact and inhalation of any fumes as the acid will cause deep skin burns and damage the respiratory system. If parts made from PTFE have been subjected to a temperature approaching 260 C (500 ) or higher, they will give off toxic fumes, which if inhaled are likely to cause temporary discomfort. It is essential for a no smoking rule to be enforced in all areas where PTFE is stored, handled, or processed as persons inhaling the fumes from burning tobacco contaminated with PTFE particles can develop 'polymer fume fever'. 1.9 Tools and consumables Before starting work ensure that you have suitable tools and/or consumables available. Use only genuine Spirax Sarco replacement parts. 1.10 Protective clothing Consider whether you and/or others in the vicinity require any protective clothing to protect against the hazards of, for example, chemicals, high/low temperature, radiation, noise, falling objects, and dangers to eyes and face. IM-P017-08 ST Issue 10 3

1.11 Permits to work All work must be carried out or be supervised by a suitably competent person. Installation and operating personnel should be trained in the correct use of the product according to the Installation and Maintenance Instructions. Where a formal 'permit to work' system is in force it must be complied with. Where there is no such system, it is recommended that a responsible person should know what work is going on and, where necessary, arrange to have an assistant whose primary responsibility is safety. Post 'warning notices' if necessary. 1.12 Handling Manual handling of large and/or heavy products may present a risk of injury. Lifting, pushing, pulling, carrying or supporting a load by bodily force can cause injury particularly to the back. You are advised to assess the risks taking into account the task, the individual, the load and the working environment and use the appropriate handling method depending on the circumstances of the work being done. 1.13 Residual hazards In normal use the external surface of the product may be very hot. If used at the maximum permitted operating conditions the surface temperature of some products may reach temperatures of 100 C (212 F). Many products are not self-draining. Take due care when dismantling or removing the product from an installation (refer to 'Maintenance instructions'). 1.14 Freezing Provision must be made to protect products which are not self-draining against frost damage in environments where they may be exposed to temperatures below freezing point. 1.15 Disposal Unless otherwise stated in the Installation and Maintenance Instructions, this product is recyclable and no ecological hazard is anticipated with its disposal providing due care is taken, except: Viton: - Can be landfilled, when in compliance with National and Local regulations. - Can be incinerated, but a scrubber must be used to remove Hydrogen Flouride, which is evolved from the product and with compliance to National and Local regulations. - Is insoluble in aquatic media. PTFE: - Can only be disposed of by approved methods, not incineration. - Keep PTFE waste in a separate container do not mix it with other rubbish, and consign it to a landfill site. 1.16 Returning products Customers and stockists are reminded that under EC Health, Safety and Environment Law, when returning products to Spirax Sarco they must provide information on any hazards and the precautions to be taken due to contamination residues or mechanical damage which may present a health, safety or environmental risk. This information must be provided in writing including Health and Safety data sheets relating to any substances identified as hazardous or potentially hazardous. 4 IM-P017-08 ST Issue 10

2. General product information 2.1 General description The AE30 automatic air eliminator/air vent range is designed for use on hot and cold water installations. The body and cap are of a special brass alloy which is dezincification resistant (DZR). The range is available as follows: AE30 Standard air eliminator/ air vent AE30A Standard air eliminator/air vent with check valve * AE30B Standard air eliminator/air vent with lockshield valve * AE30C Standard air eliminator/air vent with check valve and lockshield valve ** AE30LV Standard air eliminator/air vent with a lightweight float ** AE30LVA Standard air eliminator/ air vent with a lightweight float and check valve * The fitted lockshield valve (versions AE30B and AE30C) has a unique 3-way locking system enabling the valve to be either locked open or locked closed or used as a conventional ball valve. Operation of the valve is by using a lockshield valve key which is available (at extra cost) from Spirax Sarco. ** The lightweight float is suitable for use on liquids with a minimum specific gravity of 0.7 and has a Viton valve cone as standard for chemical resistance. Note: For further information see the following Technical Information Sheets, TI-P017-07 and TI-P017-16. 2.2 Sizes and pipe connections AE30, AE30A, AE30LV and AE30LVA: Inlet ½" female, Outlet ¼" male both BSP or NPT AE30B and AE30C: Inlet ½" male, Outlet ¼" male both BSP AE30A AE30LVA AE30 AE30LV AE30B AE30C Fig. 1 AE30C shown Lockshield key (available at extra cost) IM-P017-08 ST Issue 10 5

2.3 Pressure/ temperature limits Temperature C Pressure psi g Pressure bar g Temperature F The product should not be used in this region as damage to the internals will occur. Body design conditions PN10 PMA Maximum allowable pressure 10 bar g @ 120 C (145 psi g @ 248 F) TMA Maximum allowable temperature 120 C @ 10 bar g (248 F @ 145 psi g) Minimum allowable temperature -10 C (14 F) PMO Maximum operating pressure TMO Maximum operating temperature (at all pressures) PMX Maximum differential pressure AE30 10 bar g @ 110 C (145 psi g @ 230 F) AE30LV 10 bar g @ 110 C (145 psi g @ 230 F) 110 C (230 F) AE30 8 bar g @ 110 C (116 psi g @ 230 F) AE30LV 3 bar g @ 110 C (43.5 psi g @ 230 F) Minimum operating temperature 0 C (32 F) Note: For lower operating temperatures consult Spirax Sarco. Designed for a maximum cold hydraulic test pressure of: Minimum specific gravity of water AE30 0.926 Minimum specific gravity of liquid AE30LV 0.7 15 bar g (217 psi g) 6 IM-P017-08 ST Issue 10

3. Installation Note: Before actioning any installation observe the 'Safety information' in Section 1. Referring to the Installation and Maintenance Instructions, name-plate and Technical Information Sheet, check that the product is suitable for the intended installation: 3.1 Check materials, pressure and temperature and their maximum values. If the maximum operating limit of the product is lower than that of the system in which it is being fitted, ensure that a safety device is included in the system to prevent overpressurisation. 3.2 Determine the correct installation situation and the direction of fluid flow. 3.3 Remove protection covers from all connections and protective film from all name-plates, where appropriate, before installation on steam or other high temperature applications. 3.3 The automatic air eliminator/air vent should be installed vertically with the inlet at the bottom. We recommend piping the discharge from the air eliminator/air vent to a suitable safe point. To enable this to be done the outlet is provided with a ¼" BSP or NPT male thread. See Figure 2 for a typical application. Discharge to safe visual point Air bottle Fig. 2 Typical application 4. Commissioning After installation or maintenance ensure that the system is fully functioning. Carry out tests on any alarms or protective devices. IM-P017-08 ST Issue 10 7

5. Operation At start-up the air eliminator/air vent is open allowing air to pass through the main valve. As soon as water reaches the vent the float is raised and the lever mechanism closes the valve. When more air reaches the vent it displaces water and the float falls thus opening the valve. After the air is discharged the valve is closed, as the water level rises to replace the air. The check valve is essential where there is a possibility of the system operating under negative head conditions. It will prevent air being drawn into the system. The lockshield valve is a standard ball valve fitted with a lockshield. It has a unique feature that offers 3 modes of operation: - Normal operation. - Locked in open position. - Locked in closed position. In normal operation the ball valve can be adjusted using a lockshield key. In the open or closed position the valve can be locked. If the plastic cover and screw are removed the valve stem can be rotated to lock the ball valve in the open or closed position. 6. Maintenance Note: Before actioning any maintenance programme observe the 'Safety information' in Section 1. 6.1 General information All work must be carried out by a suitably competent person. Before starting work ensure that suitable tools are available. Use only Spirax Sarco replacement parts. Before attempting to work on the air vent ensure that it is isolated from the rest of the pressurised system. Allow time for the temperature of the air vent to normalise. The unit has a long service life and the only maintenance that would normally be required is the occasional cleaning of the valve and seat. 6.2 How to clean/replace the valve and seat: - Unscrew the cap from (1) the body. - The float (4) can then be detached from the lever and the mechanism removed by undoing the screw (8) in the centre of the cap. - The valve cone (5) is easily changed once the float has been removed. - Refitting of the mechanism is straight forward, the float can then be hooked back onto the lever and the whole assembly screwed back into the body (see Table 1 for the recommended tightening torque). - The set of internals are supplied with a check valve ball and circlip. - The check valve is only required for the AE30A, AE30LVA and AE30C. - The check valve should be fitted into the outlet port and held loosely by the circlip, which is fitted 1.6 mm below the level of the outlet as shown in Figure 3. After maintenance ensure that the system is fully functioning. 1.6 mm Fig. 3 8 IM-P017-08 ST Issue 10

1 AE30A AE30C and AE30LVA only 8 5 4 Fig. 4 AE30A shown Table 1 Recommended tightening torques Item No. or N m (lbf ft) mm 1 30 A/F 10-12 (7.0-8.6) 8 Cheesehead M4 x 6 2.5-2.8 (1.8-2.0) IM-P017-08 ST Issue 10 9

7. Spare parts The spare parts available are shown in solid outline. Parts drawn in broken lines are not supplied as spares. Available spares Maintenance kit - comprising: Cap 'O' ring, float, valve cone, check valve ball and check valve circlip. 2, 4, 5, 9, 10 Important note If you have earlier versions of the AE30 designated AE30 and AE30CV which operate over the range 0-3 bar then the spares set for the AE30, A, B and C can be used (but this will not convert it to operate over the range 0-8 bar). However, if you have the AE30H and AE30HCV which operate over the range 3-8 bar then the earlier spares set should be used. How to order spares Always order spares by using the description given in the column headed 'Available spares' and state the size and type of automatic air eliminator/ air vent. Example: 1 - Maintenance kit for a ½" Spirax Sarco AE30A automatic air vent. 10 IM-P017-08 ST Issue 10

AE30A, AE30C and AE30LVA only 10 9 5 4 2 AE30B and AE30C only Fig. 5 IM-P017-08 ST Issue 10 11