URINAL FLUSHING SYSTEM WITH MICROWAVE SENSOR

Similar documents
BASIN AND WALL MIXER INSTALLATION INSTRUCTIONS

self closing tapware and bubblers AUTOMATIC SHUT-OFF REDUCE WATER WASTE IMPROVE HYGIENE VANDAL RESISTANT Spring Action Series Time Flow Series

PEDESTAL MOUNTED EMERGENCY EYE & EYE/FACE WASH

EMERGENCY WALL MOUNTED HAND OPERATED DELUGE SHOWER

WALL MOUNTED EMERGENCY EYE & EYE/FACE WASH HAND OPERATED

AQUABLEND 2000 THERMOSTATIC MIXING VALVE

AQUABLEND 1500 THERMOSTATIC MIXING VALVE WITH THERMAL FLUSH

Installation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM.

Installation, commissioning and servicing instructions

INSTALLATION, COMMISSIONING AND MAINTENANCE INSTRUCTIONS

AQUABLEND MM THERMOSTATIC MIXING VALVE

REVERSE OSMOSIS INSTALLATION Watermark 4 Stage

Scald Protection Three-Way Thermostatic Mixing Valve

book : t95575.fm Seite 1 Mittwoch, September 20, :10 AM. Avensys. Exposed Single Lever Mixer

3.5 litr es per INSTALLATION INSTRUCTIONS. Avon 21 Self-closing taps (Push button) B0992AA Self-closing basin pillar tap

DB 61 Dolphin TMV3 Integrated Thermostatic Mixing Valve

1200B2 Series Service Regulators. Instruction Manual

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

Installation, commissioning and servicing instructions

INSTALLATION INSTRUCTIONS

Installation, commissioning and servicing instructions

ASSE International Product (Seal) Listing Program

INSTALLATION, OPERATING & MAINTENANCE MANUAL WATER DRAIN VALVE

Instruction & Parts Manual

TMV20 THERMOSTATIC MIXING VALVE

Product Manual B-Safety ClassicLine & PremiumLine Emergency Eyewash and Eye/Face Wash Equipment

SILENTAIRE TECHNOLOGY

AREA VALVE SERVICE UNITS

About. providing superior performance and reliability. Bromic regulators are AGA or UL144 approved.

Mainsflush Troubleshooting Guide

bathrooms.com Concentric Thermostatic Shower Mixers Cleaning and Care Installation Manual Contents

Halsey Taylor Owners Manual

PO Box 370 Phone: Swansea NSW 2281 Fax: AUSTRALIA Mobile: Web:

Installation, commissioning and servicing instructions. General

Speed control assembly model A-1

Deluge Optimo Shower valve and kit 10032CP

1800C and 1800C-HC Series Service Regulators

AcornVac Vacuum Plumbing Systems - Trouble Shooting Guide

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

Safety. Operating instructions Solenoid valve for gas VG 6 VG 15/10 DANGER. Contents WARNING CAUTION. Changes to edition 09.14

AIR HAMMERS MODEL NO: CAT138/CAT139 OPERATING & MAINTENANCE INSTRUCTIONS PART NO: / GC064

Premium Series. Economical Price & Reliable Performance. High Quality. Rust-Resistant. Long Life. Tamper-Resistant locking Screw.

Safety. Operating instructions Solenoid valve for gas VG 10/15 VG 65 DANGER. Contents WARNING CAUTION. Changes to edition 11.14

MANUAL FOR INSTALLATION, COMMISSIONING AND MAINTENANCE FOR

Self-help Temperature Adjustment

Installation, commissioning and servicing instructions

Model 420-HY Pressure Regulating Hydrant Valve

Pressure Dump Valve Service Kit for Series 2300 Units

Thermocirc Installation and Maintenance Instructions

Mounting and Operating Instructions EB 8546 EN. Supply Pressure Regulator Type Fig. 1 Supply pressure regulators

INSTALLATION INSTRUCTIONS 1/2 THERMOSTATIC VALVE AND TRIM

Installation Guide. buoy.ai

Combination Air Valve

TANDEM MODULATOR FOR OUTLET GAS FLOW: STEPPED (836 TANDEM) - CONTINUOUS (837 TANDEM) SERVO-CONTROLLED PRESSURE REGULATOR

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

Mainsboost Installation, Operation & Maintenance Instructions

CARTRIDGE FILTERS. Models: CF50, CF75, CF100, CF150,

Mounting and operating instructions EB 2530 EN. Self-operated Pressure Regulator. Pressure Reducing Valve Type M 44-2

Installation, commissioning and servicing instructions

TECHNICAL DATA. Trimpac 244a. September 16, 2013

SILENTAIRE TECHNOLOGY

Halsey Taylor Owners Manual 4410 Freeze Resistant Tubular Fountain STOP!

Operating Procedure TITON SUBSEA BOLT TENSIONER

Ligature Resistant Head

k valve 2 (50)HF 2½ (65)SF installation guide aylesbury For valve sizes (DN): tel fax

Instruction Manual - Diaframless TM Ejector Chlorine, Sulfur Dioxide and Ammonia

Pressure Independent Control Series

553 Series.

Installation/Care/Use Manual

SEQUENTIAL SHOWER VALVE INSTRUCTION MANUAL PLEASE LEAVE THIS MANUAL WITH THE END USER

TECHNICAL DATA. Trimpac 257a. September 16, 2013

TECHNICAL DATA. Trimpac 251a. Spetember 16, 2013

ACCESSORY KIT INSTALLATION INSTRUCTIONS

Bermad Model:

UltRo Dual Flow Reverse Osmosis Water System

SCA Series Inverted Bucket Steam Traps

TECHNICAL DATA. Trimpac 256a. October 31, 2013

GENO -Flushing Compressor Product Data Sheet F 02

Instruction Manual O-Ring Ejector Chlorine & Sulfur Dioxide to 500 PPD (10 kg/h)

WW-720. Pressure Reducing Control Valve

ATD LB PRESSURE BLASTER INSTRUCTION MANUAL

Presented to the IAPMO Standards Review Committee on March 7, 2016

MZX. Three-Port Seat Valves SPECIFICIATIONS AND GUIDE TO SELECTION

Installation and Use Manual

Model GP PRESSURE REDUCING VALVE Installation & Operation Manual

Scald Protection 3-Way Thermostatic Mixing Valve

RD(H)20/25 Pressure-Reducing Regulator User Manual

TEMPERATURE STABILISED THERMOSTATIC SHOWER PANEL

WW-720. Pressure Reducing Control Valve

Tempering valve for solar and instantaneous applications Installation, commissioning and servicing instructions 2522HP series

Intamix Thermostatic Mixing Valve

Halsey Taylor Owners Manual STOP!

SWIRLFLO Refrigerated fountains with FLEXI-GUARD

2-port seat valves PN25 with externally threaded connections

DESIGN AND PRE - INSTALLATION INFORMATION

Code AWC20HP Air Compressor

Installation of Your SprayMaster System

TECHNICAL DATA. TRIMPAC Model B-5 & B-5B

LRS(H)4 Pressure-Reducing Regulator User Manual

Bar valve with fixed shower head Installation guide

Transcription:

URINAL FLUSHING SYSTEM WITH MICROWAVE SENSOR Installation & Maintenance Instructions EMF303M I00013_Aug 15 Call 1300 369 273 www.enware.com Enware Australia Pty Limited 9 Endeavour Rd Caringbah NSW 2229 Australia Ph: 02 8536 4000 Fax: 02 8556 4055

When tested in accordance with Standard AS/NZS 6400 Sensor Activated Urinal Flushing System Enware s electronic urinal flushing systems provides a neat and reliable flushing solution using concealed microwave activation particularly suited for public access applications. EMF303M The sensor works through low density building materials allowing for a fully concealed installation. FEATURES Microwave sensor control Mains power 24V Shut off valve, filter and airbreak included. 3 Star water efficiency rating 1-year warranty Product Codes EMF303M-3 WELS 3 Star rated* Technical Information Water Supply Connection Minimum Water Supply Line Size Mains Powered 350 kpa Inlet - ½ BSP (15mm) ¾ (20mm) 24V AC transformer 95 130 1/2" FEMALE AIR BREAK 230 25mm SPARGE PIPE 60 90 95 The more stars the more water efficient 55 60 A joint government and industry program Licence No. 0058 Water Consumption 2 litres per flush per stall ATS5200.030 CofC 60042 AGA ATS 5200.020 C of C 40116 Global-Mark 156 Version: Jul 15 Call 1300 369 273 www.enware.com.au Enware Australia Pty Limited 9 Endeavour Rd Caringbah NSW 2229 Australia Ph: 02 8536 4000 Fax: 02 8556 4055

INSTALLATION INSTRUCTIONS Before proceeding with installation ensure all operating & dimensional specifications are suitable for the intended installation. 1.1 INSTALLATION COMPLIANCE REQUIREMENTS IMPORTANT TECHNICAL REQUIREMENTS Enware product s must be installed in accordance with AS/NZS 3500.1 & AS/NZS3500.2 Plumbing and Drainage, the Plumbing Code of Australia as well as imposed Local and State / Territory Legislative requirements and the manufacturers instructions. The following clauses must be observed for a compliant installation and correct operation of Enware tapware: Water Services Plumbing Code of Australia: Part B1 Cold Water Services AS / NZS 3500.1-2003 Water Services; Section 3.3.2 Pressure at outlets (min 200kPa is required for valve to operate) Section 3.3.4 Max. pressure within buildings (500kPa operating) Section 3.4 Velocity Requirement (Max 3.0m/s) Section 16 Testing and Commissioning; Flushing, Hydrostatic testing, cleaning & disinfection of water services. NOTE: Enware s WC flushing units have Watermark License to ATS5200.020 (For Flushing Valves for Water Closets and Urinals - For use with Mains Supply), ATS5200.030 (Solenoid Valves) and WELS registered to AS/NZS 6400 To ensure that the unit works correctly, it is important to ensure that the site and location of installation meets the hydraulic requirements of AS/NZS 3500.1. Also there must be: No more than 1 valve per urinal OR 600mm wall space Minimum 20mm copper supply line for 1 stall or up to 450mm wall space. 600mm of wall space may require 25mm supply Minimum 200kPa for valve to operate NOTE: WELS Flush Volume only achieved at 350kPa Flush valve must be no more than 2m above ground level Flush valve should be installed min 300mm above wall hung urinal and 450mm above continuous wall urinals Pipe work to the valve fixture must be sized according to water service rule calculations and simultaneous demand requirements. To ensure that the pipeline reticulation system for the valve is designed correctly for the satisfactory performance of the valve a Hydraulic services Consultant and/or Engineer (or other personnel appropriately qualified in hydraulic services design) must be engaged. 1.2 INSTALLATION INSTRUCTIONS 1. Separate parts from packaging & check each part (figure 2.1). Parts will separate as shown in figure 1.3. Pay attention to the different models variations. Make sure all parts are accounted for before discarding any packaging material. If any parts are missing, do not attempt to install your flushing system until missing parts are obtained. Flush Valve Sensor GPO 2. Flush water supply lines thoroughly before installing the flush valve. Do not allow dirt, Teflon tape or metal particles to enter the unit. Sparge Pipe 3. Shut off water supply and ensure shut off valve is closed on flushing system. 4. Decide on appropriate position for the sensor. It should be installed directly above the waste channel of the urinal. It is set to suit a ceiling height of between 2.4-2.6m. (Figure 1.1) Note: sensor position can be moved when install is tested to ensure correct positioning. Activation should not occur at approx 300mm past the edge of the urinal 2.4-2.6m Note: power point must be close enough for transformer lead to reach sensor. Note: sensor must be placed directly on plaster board, tile or similar. Metal will interfere with the sensor. No hole in ceiling required. Note: sensor must be installed with LED facing upwards. Take note of installation information on the sensor. Urinal 300mm Approx FIGURE 1.1

INSTALLATION INSTRUCTIONS 5. Prepare the inlet pipe for installation. (FIGURE 1.2) Note: 20mm (min) inlet pipe with 1/2 BSP (male) adaptor required for install. 6. Connect the shut off valve and upper section of the union (as shown) (FIGURE 1.3 & 1.4) Note: If using EMFS10-Air Gap refer to image 1.7 on page 4. 7. Connect lower half of flush valve to union and spreader pipe (connection to sparge to suit urinal) (FIGURE 1.3 & 1.4) 8. Place the transformer near to electrical outlet and thread its lead to the sensor. Fit the leads from the transformer to the blue plug on the sensor. Hand tighten screws to complete connection, ensure screws are not over tightened. (Figure 1.5) Note: transformer MUST be accessible after installation. 10. Turn on water supply and check that there are no leaks. Ensure shut off valve is off again after test. 12. Plug microwave sensor spade connectors onto solenoid (FIGURE 1.6) 13. Plug in transformer. Turn on to test the operation of the valve. Sensor LED will glow yellow when sensor is triggered. If the valve clicks and resets, it is working. Ensure the transformer is turned off until after final connection. 14. Turn on water supply and test. Note: sensor will operate 50 seconds after being triggered. It will not re-trigger until 20 seconds after the start of each flush. Note: ensure unit does not trigger more than 300mm away from the edge of the urinal. Reposition if required. Note: sensor angle can be adjusted if required, see sticker on unit for details. CUTOUT DETERMINED BY CONNECTIONS FIGURE 1.2 UPPER SECTION OF FLUSH VALVE LOWER SECTION OF FLUSH VALVE SPARGE CONNECTION (ADAPTOR OR AIR GAP) FIGURE 1.3 FIGURE 1.4 FIGURE 1.5 FIGURE 1.6 4 Call 1300 369 273 EMF303M www.enware.com.au

INSTALLATION INSTRUCTIONS Figure 1.7: INSTALLATION OF AIR GAP EMFS10 Flush Valve Air Gap Flush Valve Air Gap - Air gap must be installed vertically to prevent leakage - Fit air gap to solenoid (use thread tape or similar to seal) - Fit sparge 25mm pipe to air gap. SINGLE STALL 600 MAX TROUGH Solenoid Air Gap Sparge Nut O-Ring Sparge Pipe www.enware.com.au EMF303M Call 1300 369 273 5

PRODUCT COMPONENTS AND SPARE PARTS LIST 2.1 EXPLODED VIEW Shut off Valve Transformer Sensor Union Filter Connection Nipple Solenoid FIGURE 2.1 2.2 SPARE PARTS EMS804 ENMS123 EMFS304 EMFS10 Solenoid 3/8 24V AC 1/2 Strainer Shut off valve 1/2 Air Gap 6 Call 1300 369 273 EMF303M www.enware.com.au

SERVICE AND MAINTENANCE 3.1 SERVICE INSTRUCTIONS Refer to trouble shooting chart to help determine specific problems. Spare part kits should be on hand before servicing the unit. 3.2 TROUBLE SHOOTING Refer to the following trouble shooting chart for specific problems and solutions. Service instructions are supplied with spare part kits FAULT / SYMPTOM CAUSE RECTIFICATION Sensor Activates - water does not flow Loose connection on leads Reconnect electrical connections Water supply not turned on Dirty Filter Supply pressure issue Ensure water supply is on and shut off valve is open Turn off shut off valve. Open union and remove lower section of valve. Clean or replace filter. Ensure pressure delivered to unit is above 200kpa and below 500kPa (dynamic) Water does not stop flowing Debris or scale in the solenoid Remove solenoid, pull out plunger and spring & clean them. Use scale remover if required. When replacing plunger, ensure spring is in vertical position Dirty Filter Supply pressure issue Turn off shut off valve. Open union and remove lower section of valve. Clean or replace filter. Ensure pressure delivered to unit is above 200kpa and below 500kPa (dynamic) Flush pattern not fully covering bowl Supply pressure issue Ensure pressure delivered to unit is above 200kpa and below 500kPa (dynamic) Supply pipe inadequate size Ensure supply is 20mm (minimum) Too little water delivered Supply pressure issue Ensure pressure delivered to unit is above 200kpa and below 500kPa (dynamic) Supply pipe inadequate size Trying to flush too large an area Ensure supply is 20mm (minimum) Ensure no more than 450 wall space or 1 stall is being serviced by valve (25mm supply if covering 600mm of wall space) 3.3 FILTER CLEANING This flush valve is provided with a stainless steel filter preventing foreign particles from entering the lines. If the water flow has decreased, this may be because the filter is clogged. They can be cleaned as follows: 1. Turn-off the water shut off valve 2. Disconnect flush valve at union and separate from spreader pipe 3. Remove the filter & wash it under running water. It may be necessary to replace the filter (spare parts can be ordered from Enware) 4. Reinsert the filter and refit the flush valve 6. Turn on the water shut off valve 7. Make sure that there is no water leakage www.enware.com.au EMF303M Call 1300 369 273 7