Condensing pressure regulator, type KVR Differential pressure valve, type NRD

Similar documents
Condensing pressure regulator, type KVR Receiver pressure regulator, type NRD

Evaporator pressure regulator Type KVP

Evaporator pressure regulator Type KVP

Crankcase pressure regulator, type KVL REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Technical leaflet. Pressure and Temperature Regulators. January 1999 RC.4X.B1.22. Danfoss A/S

Water valve Type WVO. Data sheet MAKING MODERN LIVING POSSIBLE

Evaporating Pressure Regulating Valve Type KVQ REFRIGERATION AND AIR CONDITIONING. Technical leaflet

2-step solenoid valve Type ICLX

2-step solenoid valve Type ICLX

Capacity regulator (hot gas bypass)

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Solenoid Valves, one - or two step, on/off ICLX

Differential pressure switch / Lube oil protection control MP 54 and MP 55

Shut-off ball valve Type GBC

Sales Office: Danfoss Expansion Valves. T*2 Range Order valve and orifice separately Range N -40 C to +10 C Without MOP

Differential pressure switch MP 54, MP 55 and MP 55A

MAKING MODERN LIVING POSSIBLE. Pilot operated internal safety valves type POV REFRIGERATION AND AIR CONDITIONING DIVISION.

Differential Pressure Control Types MP 54, MP 55 and MP 55A

Float valves Types SV 1 and SV 3

Solenoid valves, two-step on/off Type PMLX REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Thermostatic Expansion

D A T A S H E E T. Technical Data. Maximum Working Gauge Pressure (bar) Capillary Tube Length (m) 1.5 (5Ft) Burst Gauge Pressure (bar) 234.

Solenoid valve type EVR for Hydrocarbons

Dual position solenoid valve Type ICSH 25-80

Liquid level regulating valves Types PMFL / PMFH and SV

Shut-off ball valve Type GBC

Modulating liquid level regulators, servo-controlled PMFL / PMFH and SV

Series 44 Self-operated Pressure Regulators. Type 44-1 B Pressure Reducing Valve. Type 44-6 B Excess Pressure Valve. ANSI version

CROT-6 CROT-10 CRO-4. for Compressor Overload Protection

Electric expansion valves Types AKV 10, AKV 15 and AKV 20

CHECK VALVES APPLICATIONS

Series 44 Self-operated Pressure Regulators. Type 44-0 B Pressure Reducing Valve. ANSI version

Shut-off ball valve Type GBC

Modulating liquid level regulators, direct-controlled, type SV 1 and 3 REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Safety relief valves, type BSV 8 REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Pressure switch KP-E. Data sheet

Overflow valves Type OFV REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Electric regulating valves Type CCMT 2 - CCMT 8 / CCMT 16 - CCMT 42

Pressure regulating valves Types OFV, OFV-SS

Safety relief valves Type BSV-8

Float valves Types SV 4, SV 5 and SV 6

Pressure relief valve DHV 712 DN 65-80: 0,5-10 bar, DN : 0,3-4 bar, DN 100: 0,5-6 bar

Pilot valves for pilot operated servo valves

Safety relief valves, type SFA 15 REFRIGERATION AND AIR CONDITIONING. Technical leaflet

) for different types of systems Test of contact function The correct pressure control for your system

V43 Pressure Actuated Water Regulating Valve

Pressure controls for hydro carbons, zone II applications, Type KPE

Safety relief valves SFV 20-25

Differential pressure controls/ Lube oil protection controls MP 54 and MP 55 REFRIGERATION AND AIR CONDITIONING. Technical leafl et

Valve Station ICF 15, 20 and 25

Safety relief valves Type SFA 15 and SFA 15-50

Overflow valves Type OFV Type OFV-SS REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Refrigeration and Air Conditioning Technical leaflet

Gas powered stop valves, type GPLX REFRIGERATION AND AIR CONDITIONING. Technical leaflet

T 2523 EN Type 2406 Excess Pressure Valve Self-operated Pressure Regulators ANSI version

Safety relief valves, type SFA 15

Pressure and/or Temperature Pilot Operated Steam Regulators Series 2000

for for Industrial Refrigeration

Pressure Reducing Valve DMV 755

Series 44 Self-operated Pressure Regulators. Type 44-1 B Pressure Reducing Valve. Type 44-6 B Excess Pressure Valve

Self-operated Pressure Regulators Type 2405 Pressure Reducing Valve

Series 42 Self-operated Regulators Differential Pressure Regulators with Type 2424/Type 2428 Actuator (closing) Type Type 42-28

Ball Float Steam Trap UNA 43 PN 16/CL 125/JIS 10K UNA 46 PN 40/CL 150/CL 300/JIS 10K/JIS 20K DN 80, 100, 150, 3", 4", 6"

Hand-operated regulating valves in stainless steel Types REG-SA SS and REG-SB SS

Differential pressure controls, Type MP 54, 55 and 55A

Self-operated Pressure Regulators Type Universal Pressure Reducing Valve

Safety relief valves Type SFV 20-25

Ball Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300 DN 40, 50, 65

Series V48. 3-Way Pressure Actuated Modulating Valves. Product Bulletin. Features. Pressure balanced design. Free movement of all parts

Pressure relief valve DHV 716 set range: 0,5-10,0 bar

Capacities Valve Station, type ICF 15, 20, 25

Radiator thermostats type RA2000, valve bodies type RA-FN (series D) and RA-G

Shut-off Liquid level and regulating valves for for Industrial Refrigeration

Technical Instructions Document No. CA2N4721E-P25 Rev. 1, February, Modulating Control Valve for Hot Gas Control.

Instructions. Control Solution ICF 20-4, ICF 25-4, ICF ICF 40-4, ICF 20-6, ICF 25-6, ICF 32-6, ICF 40-6, Direction and position.

Differential pressure and flow controller (PN 16) AVPQ - return mounting, adjustable setting

Pressure switch, Differential pressure switch and Thermostat RT-E

Pressure Reducing Valve DMV 750 set range: bar

DS06D,G Dial Set Pressure Regulating Valve

Regulating valves Type REG 6-65 Type REG-SS REFRIGERATION AND AIR CONDITIONING. Technical leaflet

CASH VALVE TYPE KP BACK PRESSURE VALVES

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves.

Reliable System Performance PM valves

ALE-40. R06 Miniature Brass Body Regulator. Water and Compressed Air Service 1/8" and 1/4" PTF Port Sizes. Air line equipment.

MEGR-1912 Instruction Manual

Self-operated Pressure Regulators for special applications

Pressure reduction controller (PN 16, 25, 40)

Type 1098-EGR. Pilot-Operated Valve Link Regulators. Features. Fisher Controls

R133 HELYON. Brass high pressure regulator, suitable for compressed air, gas and liquid

1200 Series Pressure Regulators

TEK-SUB 4800B. Submersible Level Transmitter. Flow Level Temperature Pressure Valves Analyzers Accessories TekValSys LEVEL

FSW SECTION. Product guide. Shut Off Valves, Vibration Eliminators, Accumulators & Oil Separators D SECTION. 55

CLASS TLP Pressure Reducing Valve

The Discussion of this exercise covers the following points: Pumps Basic operation of a liquid pump Types of liquid pumps The centrifugal pump.

Pressure switch SANHUA PS01/50/15 SERIES. ideas worldwide STANDARD

RA-N radiator valves with integrated presetting and self-sealing tailpiece

STAP. Differential pressure controller DN 15-50

POP Safety Valve. POP Safety Valve INTRODUCTION DEFINITIONS

TBV-CM. Combined control & balancing valves for small terminal units For modulating control NPT threads

Pressure relief valve DHV 725 set range: 0,2-10,0 bar

Transcription:

MAKING MODERN LIVING POSSIBLE Data sheet Condensing pressure regulator, type KVR Differential pressure valve, type NRD The condensing pressure regulator, type KVR can be mounted in either the gas or liquid side of the condenser in refrigeration and air conditioning systems. They are used to maintain a constant and sufficiently high condensing pressure with systems using air-cooled condensers. They can also be used with valve types NRD or KVD to assure that adequate pressure is maintained on the receiver. Features y Accurate, adjustable pressure regulation y Wide capacity and operating range y Pulsation damping design y Stainless steel bellows y Compact angle design for easy installation in any position y Hermetic brazed construction y ¼ in. Schrader valve for pressure gauge connection y Available with flare or ODF solder connections y Can be used as a relief valve from high pressure to suction side y KVR 12-22: Compliant with ATEX hazard zone 2 y NRD: for use with HCFC, HFC and HC refrigerants Approvals UL LISTED, file SA7200 GOST AN30 DKRCC.PD.HC0.B3.22 / 20H8762

Technical data 1 psi = 0.07 bar / 9 (t 1 F -32) = t 2 C HCFC, HFC and HC: KVR 12-22 Refrigerants HCFC and non-flammable HFC: KVR 28-3 Pe = 73.00 24.00 psig Regulation range Factory setting = 14 psig KVR: PS/MWP = 406 psig Maximum working pressure NRD: PS/MWP = 667 psig KVR: Pe = 40 psig Maximum test pressure NRD: Pe = 870 psig Medium temperature range KVR: -49 266 F KVR 12 22: 90 psi P band (full valve stroke) KVR 28 3: 72. psi Start opening: Δp= 20 psi Opening differential pressure for NRD Fully open: Δp = 43 psi Ordering KVR 12, KVR 1, KVR 22, KVR 28, KVR 3, NRD Type Rated liquid capacity 1) [TR] Rated hot gas 1) [TR] Flare connection 2) Code no. Solder connection Code no. R22 R134a R404A/ R07 R407C R22 R134a R404A/ R07 R407C [in.] [in.] KVR 12 12.7 11.8 8.2 13.8 4.13 3.03 3.27 4.0 1 / 2 034L0091 1 / 2 034L0093 KVR 1 12.7 11.8 8.2 13.8 4.13 3.03 3.27 4.0 / 8 034L0092 / 8 034L0097 KVR 22 12.7 11.8 8.2 13.8 4.13 3.03 3.27 4.0 7 / 8 034L0094 KVR 28 32.6 30.2 20.9 3. 10.93 8.04 8.66 11.91 1 1 / 8 034L009 KVR 3 32.6 30.2 20.9 3. 10.93 8.04 8.66 11.91 1 3 / 8 034L0100 NRD 1 / 2 020-1132 1) Rated capacity is based on: evaporating temperature t e = 40 F condensing temperature t c = 110 F pressure drop across the valve p = 3 psi for liquid capacity p = 6 psi for hot gas capacity 2) KVR are delivered without flare nuts. Separate flare nuts can be supplied: 1 / 2 in. code no. 011L1103 / 8 in. code no. 011L1167 The connection dimensions chosen must not be too small, as gas velocities in excess of 130 ft/s at the inlet of the regulator can result in flow noise. 2 DKRCC.PD.HC0.B3.22 / 20H8762

Liquid capacity Max. regulator capacity Q e 1) Type Condensing temperature t c Liquid capacity [TR] Offset 4 psi Hot gas capacity [TR] Offset 4 psi Pressure drop p [psi] Pressure drop p [psi] [ F] 1. 3 6 10 2 1. 3 6 10 2 R22 KVR 12 KVR 1 KVR 22 R22 0 13.1 17.6 2.2 32.9 2.6 1.81 2.47 3.2 4.1 6.86 70 11.9 16.0 23.0 30.0 48.0 1.92 2.62 3.7 4.83 7.44 90 10.6 14.4 20.8 27.0 43.2 2.04 2.76 3.96.12 7.94 110 9.2 12.7 18.4 23.9 38.2 2.13 2.89 4.13.36 8.34 130 7.8 11.0 16.0 20.7 33.1 2.20 2.98 4.27.4 8.64 0 33. 4.0 64.4 84.2 134.6 4.77 6.0 9.31 11.9 18.1 KVR 28 KVR 3 70 30.4 41.1 8.9 76.8 122.8.11 6.93 9.92 12.79 19.66 90 27.1 37.0 3.2 69.2 110.6.42 7.34 10.48 13.4 20.98 110 23.6 32.6 47.2 61.3 97.8.67 7.6 10.93 14.16 22.06 130 20.0 28.0 40.9 3.0 84.6.79 7.83 11.23 14.60 22.8 R134a KVR 12 KVR 1 KVR 22 R134a 0 12.0 16.9 24.0 31.0 49.1 1.40 1.97 2.7 3.0.1 70 11.9 16.0 23.0 30.0 48.0 1.92 2.62 3.7 4.83 7.44 90 9.6 13.6 19.2 24.8 39.3 1.0 2.12 2.97 3.80.7 110 8.4 11.8 16.7 21.6 34.2 1.3 2.1 3.03 3.87.92 130 7.1 10.0 14.2 18.3 29.0 1.2 2.14 3.01 3.86.9 0 30.7 43.4 61.3 79.2 126.0 3.72.24 7.31 9.26 13.60 1 psi = 0.07 bar / 9 (t 1 F -32) = t 2 C 1 TR = 3. kw 1 in. = 2.4 mm KVR 28 KVR 3 70 27.6 39.1.3 71.4 113.0 3.87.44 7.63 9.71 14.49 90 24. 34.7 49.1 63.4 100.0 3.99.62 7.89 10.07 1.22 110 21.4 30.2 42.8.3 87. 4.06.71 8.04 10.28 1.69 130 18.1 2.6 36.3 46.9 74.2 4.03.68 8.00 10.2 1.77 1) The capacities are based on: Evaporating temperature t e = 40 F. For other evaporating temperatures see table below. Correction factors (evaporating temperature) t e [ F] -40-20 0 20 40 0 R22 1.12 1.09 1.0 1.03 1.0 0.98 R134a 1.22 1.16 1.10 1.04 1.0 0.96 System capacity x correction factor = table capacity. DKRCC.PD.HC0.B3.22 / 20H8762 3

Liquid capacity (continued) Maximum regulator capacity Q e 1) Type Condensing temperature t c Liquid capacity [TR] Offset 4 psi Hot gas capacity [TR] Offset 4 psi Pressure drop p [psi] Pressure drop p [psi] [ F] 1. 3 6 10 2 1. 3 6 10 2 R404A/R07 R404A/R07 0 9.2 12.4 17.6 23.0 37.0 1.63 2.09 2.99 3.84.87 KVR 12 KVR 1 KVR 22 70 8.1 10.9 1.7 20.4 32.7 1.60 2.17 3.10 4.00 6.17 90 7.0 9.6 13.8 17.9 28.7 1.6 2.2 3.21 4.1 6.4 110.9 8.2 11.8 1.4 24. 1.68 2.28 3.27 4.24 6.60 130 4.8 6.8 10.0 13.0 20.6 1.69 2.31 3.34 4.34 6.78 0 23.6 31.7 4.2 9.0 94. 4.06.2 7.89 10.1 1.48 KVR 28 KVR 3 70 20.8 27.9 40.1 2.2 83.6 4.24.74 8.20 10.8 16.32 90 17.9 24. 3.2 4.9 73.4 4.41.96 8.0 10.99 17.06 110 1.1 20.9 30.3 39.3 62.7 4.88 6.06 8.66 11.22 17.49 130 12.3 17.4 2.7 33.1 2.7 4.49 6.12 8.82 11.4 17.92 R407C KVR 12 KVR 1 KVR 22 R407C 0 4.2 19.0 27.2 3. 6.8 1.96 2.67 3.80 4.87 7.41 70 12.9 17.3 24.8 32.4 1.8 2.07 2.83 4.0.22 8.04 90 11. 1.6 22. 29.2 46.7 2.20 2.98 4.28.3 8.8 110 10.0 13.8 20.1 26.1 41.6 2.32 3.1 4.0.84 9.09 130 8.6 12.1 17.6 22.8 36.4 2.42 3.28 4.70 6.09 9.0 0 36.2 48.6 69.6 90.9 14.4.1 7.02 10.06 12.91 19.60 1 psi = 0.07 bar / 9 (t 1 F -32) = t 2 C 1 TR = 3. kw 1 in. = 2.4 mm KVR 28 KVR 3 70 32.8 44.4 63.6 82.9 132.6.2 7.48 10.71 13.81 21.23 90 29.3 40.0 7. 74.7 119..8 7.93 11.32 16.62 22.66 110 2.7 3. 1. 66.8 106.6 6.18 8.34 11.91 1.43 24.0 130 22.0 30.8 4.0 8.3 93.1 6.37 8.61 12.3 16.06 2.14 1) The capacities are based on: Evaporating temperature t e = 40 F. For other evaporating temperatures see table below. Correction factors (evaporating temperature) t e [ F] -40-20 0 20 40 0 R404A/R07 1.32 1.22 1.14 1.06 1.0 0.9 R407C 1.20 1.1 1.09 1.04 1.0 0.96 System capacity x correction factor = table capacity. 4 DKRCC.PD.HC0.B3.22 / 20H8762

Sizing Valve selection For optimum performance, it is important to select a KVR valve according to system conditions and application. Example When selecting the appropriate valve it may be necessary to convert the actual evaporator capacity using a correction factors. This is required when your system conditions are different than the table conditions. The selection is also dependant on the acceptable pressure drop across the valve. The following example illustrates how this is done. The following data must be used when sizing a KVR valve: y Refrigerant: HCFC, HFC and HC:KVR 12-22, HCFC and non-flammable HFC: KVR 28-3 y Evaporator capacity Q e in [TR] y Evaporating temperature t e in [ F] y Condensing temperature t c in [ F] y Connection type: flare or solder y Connection size in [in.] KVR in a liquid capacity application y Refrigerant: R22 y Evaporator capacity: Q e = 28.7 TR y Evaporating temperature: t e = -40 F ~ 21 psig y Condensing temperature: t c = 90 F ~ 170 psig y Connection type: Solder y Connection size: / 8 in. Application example Liquid capacity application Hot gas capacity application DKRCC.PD.HC0.B3.22 / 20H8762

Valve selection (continued) Step 1 Determine the correction factor for evaporating temperature t e. Correction factors (evaporating temperature) From the correction factors table an evaporating temperature of -40 F, R22 corresponds to a factor of 1.12. t e [ F] -40-30 -20-10 0 10 R22 1.12 1.09 1.0 1.03 1.0 0.98 R134a 1.22 1.16 1.10 1.04 1.0 0.96 R404A/R07 1.32 1.22 1.14 1.06 1.0 0.9 R407C 1.20 1.1 1.09 1.04 1.0 0.96 Step 2 Corrected evaporator capacity is Q e = 28.7 x 1.12 = 32.14 TR Step 3 Now select the appropriate capacity table and choose the line for a condensing temperature t c = 90 F. Using the corrected evaporator capacity, select a valve that provides an equivalent or greater capacity at an acceptable pressure drop. KVR 12, KVR 1, KVR 22 delivers 38.2 TR at a 2 psi pressure drop across the valve. Based on the required connection size of / 8 in. ODF, the KVR 1 is the proper selection for this example. Step 4 KVR 1, / 8 in. solder connection: code no. 034L0097. 6 DKRCC.PD.HC0.B3.22 / 20H8762

Design / Function KVR NRD Danfoss 34L03.14.0 KVR 1. Seal cap 2. Gasket 3. Setting screw 4. Main spring. Valve body 6. Equalizing bellows 7. Valve plate 8. Valve seat 9. Damping device 10. Manometer connection 11. Cap 12. Gasket 13. Insert NRD 1. Piston 2. Valve plate 3. Piston guide 4. Valve body. Spring Danfoss 34L03.14.0 The condensing pressure regulator, type KVR opens upon a rise in pressure on the inlet side, i.e. when the pressure in the condenser reaches the set value. KVR regulates on the inlet pressure only. Pressure variations on the outlet side of the regulator do not affect the degree of opening, as the valve is equipped with equalization bellows (6). The bellows has an effective area corresponding to that of the valve seat neutralizing any changes to the setting. The valve is also equipped with a damping device (9) providing protection against pulsations which can normally arise in a refrigeration system. The damping device helps to ensure long life for the regulator without impairing regulation accuracy. Differential valve type NRD begins to open when the pressure drop in the valve is 20 psig, and is fully open when the pressure drop is 43 psig. DKRCC.PD.HC0.B3.22 / 20H8762 7

P-band and Offset Principle diagram Capacity Setting [psi] Offset 1 psi = 0.07 bar / 9 (t 1 F -32) = t 2 C P-band Proportional band The proportional band or P-band is defined as the amount of pressure required to move the valve plate from closed to full open position. Example: If the valve is set to open at 120 psig and the valve P-band is 90 psi, the valve will give maximum capacity when the inlet pressure reaches 210 psig. Offset The offset is defined as the permissible pressure variation in condenser pressure (temperature). It is calculated as the difference between the required working pressure and the minimum allowable pressure. The offset is always a part of the P-band. Example with R22: A working temperature of 110 F ~ 230 psig is required, and the temperature must not drop below 100 C ~ 200 psig (set point). The offset will then be 30 psi. 8 DKRCC.PD.HC0.B3.22 / 20H8762

Dimensions [mm] and weights [kg] KVR NRD KVR, NRD Type Connection Flare Solder ODF NV 1 NV 2 H 1 H 2 H 3 L L 1 B 1 B 2 C Solder ød Net weight KVR 12 1 / 2 1 / 2 0.748 0.748 7.04 3.898 2.98 2.20 1.614 0.394 1.181 0.88 KVR 1 / 8 / 8 0.94 0.94 7.04 3.898 2.98 2.20 1.614 0.472 1.181 0.88 KVR 22 7 / 8 7.04 3.898 2.98 2.20 1.614 0.669 1.181 0.88 KVR 28 1 1 / 8 10.197.94 4.0 4.134 1.890 0.787 1.693 2.20 1 in. = 2.4 mm 1 lb = 0.44 kg KVR 3 1 3 / 8 10.197.94 4.0 4.134 1.890 0.984 1.693 2.20 NRD 1 / 2.17 0.394 0.866 0.22 DKRCC.PD.HC0.B3.22 / 20H8762 9