ANALYTICAL SERVICES MAHANGA HOLDINGS LTD

Similar documents
6900 Maintenance Instruction System Flush

PO Box 370 Phone: Swansea NSW 2281 Fax: AUSTRALIA Mobile: Web:

Patients Guide for Self Administering Intravenous Antibiotics General points

M03 WUNDATRADE. Heat Pump Manifold. Before you start: Check the contents. Optional. ...a division of WUNDA GROUP PLC

CRP INSTALLATION, OPERATING AND MAINTENANCE INFORMATION FOR INLINE SAMPLING VALVES

Installing ST1300 Fairing Decals

Before you start sampling, be sure to read

Solvent System Walkthrough

easycomposites SETUP & DAILY USE INSTRUCTIONS NEVER SWITCH OFF YOUR PUMP WITHOUT FIRST CLOSING THE VALVE TO THE CHAMBER

Glasgow City Council EDUCATION SERVICES. Technician Support Service

6800 Maintenance Instruction System Flush Procedure

CRP Ltd INSTALLATION, OPERATING AND MAINTENANCE INFORMATION FOR INLINE SYRINGE SAMPLING SYSTEMS

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Knob Adjustment)

8. Carefully layout all the parts of the reservoir setup and clean any dirt, grime or dust from the parts. ( image 8 ) 8

36H SERIES Combination Gas Valve

BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications

Aseptic Techniques. Techniques for Sterile Compounding. Pharmacy Technician Training Systems Passassured, LLC

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model 50 Systems Outfitted with ABM-725 Monitor C O M P A N Y

Standard. Standard. Venepuncture Arm. Light. Part No: Brown. Part No: Black. Part No: 00332

IMPORTANT PLEASE READ BEFORE COMMENCING INSTALLATION

Operator: Save these instructions for future use!

Declaration of Conformity as per Directive 97/23/EC

Bar valve with fixed shower head Installation guide

BOYLE S / CHARLES LAW APPARATUS - 1m long

ACCUCRAFT UK LTD Unit 4, Long Meadow Industrial Estate, Pontrilas, Herefordshire. HR2 0UA Tel:

Operator: Save these instructions for future use!

USER'S GUIDE. Nanoflow Probe. Red Stripe. 3-4mm. ptfe Sleeve. To Injector. ZU1XC Fused Silica TTF115. Fused Silica. ptfe Sleeve

1. CONDITIONS FOR USE 2. SAFETY

General Precautions for handling compressed gases

GAS BBQ 4 burner. instructions for. model no: BBQ10

Glasgow City Council EDUCATION SERVICES. Technician Support Service

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

HYDRAULIC MOBILE LIFTING TABLE

For accurate measurements and to prevent damage to the micropipets, follow these important guidelines:

ML3M Monnier Miniature Compressed Air Lubricator

Standard. Bag & Stand Advanced Venepuncture Arm. Light. Part No: Brown. Part No: Black. Part No: 00442

PRS(TC)4,8 USER MANUAL. Read the complete manual before installing and using the regulator.

Guide for the Sampling of Oil from Trench COTA Bushings for DGA

EZI-DRY Pty Limited ABN:

Declaration of Conformity as per Directive 97/23/EC

Code AWC20HP Air Compressor

Declaration of Conformity as per Directive 97/23/EC

Operating Instructions

1. ABOUT THE PRODUCT:

UsER manual for Watersens ph -REDOX

36E DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

OXYTEMP Instructions 1

i) Filtration machine, measuring equipment and other related machinery

RECOMBINATE. [Antihemophilic Factor (Recombinant)] (For intravenous use only)

Chemical Spill Clean-up Protocol

Dri-Line Mk2 Spirax-Monnier Compressed Air Drain Trap

limbsandthings.com Advanced Venepuncture Arm User Guide For more skills training products visit Limbs & Things Ltd.

Endura AZ40 Sensor assembly High temperature filter assembly kit

INSTALLATION AND OPERATION MANUAL CHEMICAL BYPASS FEEDER General Instructions Regarding All Models

KTM 50 (DN ) Installation, maintenance and operating instructions

Regulator for 2 MPa ARX 20. How to Order. Bracket. Pressure gauge. Port size 1/8 1/4. Panel nut

After filling the pool with clean water in the summer, two basic factors can take place due to the exposure of water to the sun and the air.

For accurate measurements and to prevent damage to the micropipets, follow these important guidelines:

Chapter 2. Pipetting techniques. Guide to Pipetting

Handle the film very carefully. As with aluminum foil, once creased, the film will remain creased.

Mounting and Operating Instructions EB 2558 EN. Self-operated Pressure Regulators. Type Pressure Build-up Regulator

PREPARING GAS SAMPLES IN LARGE PLASTIC SYRINGES

SA121, SA122, SA123, SA128 and SA1219 Self-acting Temperature Control Systems (Dial Adjustment)

Compact Ball Valves ASAHI AV VALVES. Contents. User s Manual. (Page) (1) Be sure to read the following warranty clauses of our product 1

Instruction Manual. PE-25/32/37 Tapping Machines. POLYTAPP Valves

CVS10 Sanitary Check Valves

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS TYPE BV2-LD

OPERATING INSTRUCTIONS

MODEL 1329 Tank Gauge

HEAT EXCHANGE AND TRANSFER, INC. 500 Superior Street Carnegie, PA (412) Fax: (412)

Dual Solenoid Gas Valve Installation

System Pressure Manager Standard & System Pressure Manager Plus

SEMIC05 Installing mechanical equipment

INSTALLATION AND MAINTENANCE INSTRUCTIONS IB - INVERTED BUCKET STEAM TRAPS (IB12 - IBB - IB30 IB35)

Preliminary filter Precision measurement chamber Flow meter Instruction manual

INSTALLATION, CARE & USE MANUAL. EMASMB & LMASMB Surface Mount Bottle Filling Stations

Gaseous oxygen technical grade Specification

Method Statement: Testing Dry Riser System

Procedure 85 Attaching The Humidifier To The Oxygen Flow Meter Or Regulator. Procedure 86 Administering Oxygen Through A Nasal Cannula

Instruction Manual - War Department Baldwin Live Steam Instruction Manual

P5513. Users Manual. Pneumatic Comparison Test Pump. Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot.

Setup Guide for your HVO Naked Drone

Caution: Safety Precautions: Installation, Operation & Maintenance Manual. For Modentic Needle Valves with Threaded Ends

Wet Lamination of Dry Film Photoresist for the Hobbyist

KTM OM-2 SPLIT BODY FLOATING BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

Instructions for Use

TECH SHEET ORANGE PIVOT TOOL INSTRUCTIONS

SEries 29 Hydrant valves installation, operation & maintenance manual

AR251/AR251-B. Venepuncture and Infusion Arm. Instruction Manual

B. Assemble the Method-25 sample train with a heated probe/filter.

Adjust the Volume Display

Technical Service Bulletin June 2015 TSB122.06

Rubber Dock Hose care, Use & Maintenance

EASTERN ENERGY SERVICES PTE LTD. 60 Kaki Bukit Place #02-19 Eunos Tech Park Singapore, SG Singapore Telephone: Fax:

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

THE HF-300 SERIES. Operating and Service Manual. Series includes all variants of HF-300/301

Speed control assembly model A-1

Title/Description: Fuel Cell Fill Procedure

LPG SAFETY INFORMATION. Kwik-Gas. Safety Manual. Less talk more energy

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

Transcription:

Body ANALYTICAL SERVICES 1.PURPOSE AND SCOPE The correct use of syringe results in oil samples is of a much higher quality than other containers particularly for Dissolved Gas Analysis and Moisture measurements. This procedure describes the correct sampling method. 2.REFERENCES - P21-6-24 Oil Sampling From Live Transformers - P21-3-2 Site Safety Risk assessment - P21-1-2 Company Safety Rules - P21-9-43 Polychlorinated biphenyls (PCB s) - P21-9-44 Handling PCB s - IEC 60567 Guide for the Sampling of Gases and of Oil-Filled Electrical Equipment and for the Analysis of Free and Dissolved Gases. 3.DEFINITIONS The Plunger The plunger must be kept free from dir t and dust, as this will seize the syringe if the dirt or dust gets between the b ody and the plunger. If thi s area is contaminated and operation b ecomes gritty, stop sampling with that syringe, and exchange for another syringe. The Body The body is the most fragile item of the comple te syringe, and will break if dropped. The seal between the body and the plunger is a polished surf ace, which relies on capillary action to ensure sealing. Plunger The Valve The valve is designed with 3 positions. The positioning is indicated by an arrow on the handle, and 3 notches at the pivot point of the han dle. Ensure that the valve is firmly attached to the body before starting to take a sample. A 360-degree turn anticlockwise or the opposite to tighten can remove the valve. Care needs to be taken with the valve and it s operation. If care is not taken it is possible to place the valve in the wrong position once the sample has been taken. This Notches showing direction of valve operation may completely fall out of the body, breaking the causes air to be sucked into the syringe, or the plunger plunger and spilling the sample. Familiarise yourself with the valve positioning before taking any oil samples. Valve

4.PROCEDURE Tools Needed Syringes and sample bottles Sampling Tubes Latex or rubber gloves Fittings to connect to the equipment Large adjustable spanner Medium size pipe wrench Thread tape rags and rubbish bags Bucket Spare 1 litre bottle clearly marked WASTE OIL Step 1 Undertake a risk assessment and ensure all necessary safety precautions and regulations are observed. Ensure that proper precautions are observed if the oil contains PCB s or if the PCB level is unknown. Step 2 Ensure that there is a positive pressure of oil from the proposed sampling position. If there is a possibility that this is NOT the case, ensure that appropriate precautions are observed. If the unit is hermetically sealed do not proceed any further, a different procedure is required. Please contact Mahanga Holdings Ltd office 09 4440663. Step 3 Establish that there is enough oil in the equipment to sample and then clean the immediate sampling area using a lint-free cloth. Step 4 Before removing the sealing bung on the valve, ensure that the valve is closed and place the bucket under the valve to catch any oil, which may be sitting in the valve body. Remove the bung. Step 5 Flush the valve to remove debris, water etc in the valve assembly. The flushing quantity of oil should be proportionate to the volume in the device being sampled. Basically, the larger the unit, the more oil that you can afford to flush. Step 6 Attach the sampling fittings and tube to the equipment. Make sure they are sealed well to prevent air or moisture ingress. Use thread tape to make a good seal. Fill the spare bottle halfway to flush the fittings and tube and remove any trapped air. Use the oil in the spare bottle to take the sample temperature and record it on the data sheet Step 7 In the majority of cases a bottle sample will be required. Wipe down the outside of the sampling tube with a c lean lint free cloth and place tube in th e sample bottle. Allow approximately 25mm of oil into the sample bottle.

Step 8 Push the syringe plunger fully closed, place the valve in the purge position and attach to the sampling tube. Allow oil to flow from the equipment through the valve into the sample bottle until satisfied that all air is purged from the sampling tube. It is important to follow the next steps without deviation. If a mistake is made, go back to step 8 and repeat. Step 9 Hold the syringe horizontal and turn the valve to allow the oil to enter the syringe and the resultant pressure to force the plunger out Allow about 10mm of oil into the syringe then return the valve to the purge position. Place the tube back into the sample bottle to continue filling. Step 10 Hold the syringe vertical and support the plunger with the little finger of the same hand. Turn the valve to the fill position and draw the plunger and oil down to about 15mm past the 50mm mark, en suring that all the inside of the syring e has be en coated with oi l. Expel t hat oil into the waste container. This step is necessary to assimilate the syringe and prevent leakage between the plunger and the body. Step 11 When the sample bottle is half full repeat Step 9 and allow the oil to fill the syringe approximately 5mm past the 50mm mark. Let the head pressure push the oil into the syringe. DO NOT FILL THE SYRINGE BY PULLING ON THE PLUNGER. You will note that there is an air bubble in the oil - Do not remove that bubble at this stage. Return the valve to the purge position and carefully remove the syringe from the tube and return it to the sample bottle to continue filling. Clean any surplus oil from the outside of the syringe. Put the syringe in its box and lean it upright at an angle against solid support out of direct sunlight. Step 12 Allow the bottle to fill to the top shoulder, close the equipment valve and seal the bottle with its cap. Seal the bottle as soon as the sample has been taken. Exposure to air can adversely affect the sample. Place the bottle out of direct sunlight. Drain any remaining oil from the equipment valve and sampling fittings, remove fittings from equipment, clean equipment drain valve and replace bung. Step 13 Remove the syringe from the box and hold vert ical, once again support the p lunger with the little fi nger and turn the valve to the fill position. Eject the air bubble from the syringe and close the valve. (see Note 1). Try not to move the syringe away from the vertical position and closely survey the oil sample for further trapped air bubbles. Eject any larger bubbles in the same manner as above. Close the plunger to the 50mm mark, close the valve and clean any oil from the outside of the syringe and pack in its box.

Note 1: There will be times that you will see lots of what look like tiny air bubbles rising in the oil after you eject the main air bubble. Provided the above procedures have been carried out correctly, 5 to 10 minutes have passed between taking the sample and ejecting the air bubble. Do not t ry to eject th ese bubbles as they are more likely to be gas migrating from the oil as it cools. If you later check your samples and see a bubble in the syringe, do NOT assume that this is air which you missed expelling. Nine chances out of ten it will be gasses that have migrated from the oil forming this bubble. This bubble holds important information. Do not expel this bubble under any circumstances. Step 14 Label the bottle as per the photo below with your company s name, the location and designation of the equipment, TASA for tapchanger, TCA for transformer or BOA for circuit breaker and the syringe number. Please label the bottle both on the lid and on top of the shoulder with indelible ink. Complete the Data Information sheet including nameplate and other critical information. It is important that all information is recorded accurately. Incorrect information can result in a mis-diagnosis. Package the syringe, bottle and paperwork and send to MHL Ltd with all the paperwork completed.

Some Important Notes If there are any questions or doubt about any sampling procedure please contact Tony Lewis of Mahanga Holdings Ltd on 021 464103 or 09 4440663. Use a new sampling tube for each sample. Cross contamination is always an issue. Keep the flow of oil into the bottles and syringes slow. An average sample time is about 20 minutes. If it is taking less time, you are probably not doing it correctly. Complete the paperwork as you take the sample. This will minimise the risk of mixing up samples if you wait until all the samples are taken before you do the paperwork or if you do all the paperwork first. Keep a close track on the syringes and bottles. Take careful note of the syringe number and record it onto the plastic bottle as well as the associated paperwork. Keep a copy of the paperwork in case there is a spillage during shipping and the originals are destroyed. Never remove bubbles from the syringes except at the initial sampling time. Record the top oil temperature of the equipment and if possible the oil sample temperature when taken. For transformers the following information is critical: - Nameplate information - Free breathing or sealed - If a silica gel breather is fitted - If a conservator oil preservation system is fitted (such as an oil bladder/bag) - If an On Load Tap Changer (OLTC) is fitted If the oil in the transformer is common with the oil in the OLTC If there is a common head space between the transformer oil and OLTC oil If the OLTC selector and diverter compartments are common or separate 5.SUPPORTING DOCUMENTATION Work Site Safety & Risk Assessment Form 230-1630P Transformer Condition Assessment Sampling Forms Tapchanger Activity Signature Analysis Sampling Forms Breaker Oil Analysis Sampling Forms (Above mentioned forms available from www.tjh2b.com.au) Contact Details Adam Slater Mob 021 464103 Phone 09 4440663 Email: Adam.Slater@mhl.co.nz Revisi on Feb 2006