FUNDAMENTAL PRINCIPLES OF SELF-OPERATED PRESSURE REDUCING REGULATORS. John R. Anderson Emerson Process Management Fluid Controls Institute

Similar documents
Principle of Operation. Features. Applications. CL34 Operating Schematic

FUNDAMENTALS OF PRESSURE REGULATORS ROBERT BENNETT MANAGER OF TRAINING ELSTER AMERICAN METER

CASH VALVE TYPE KP BACK PRESSURE VALVES

SB AXIAL FLOW VALVES

Spring Loaded Regulators Constant Loaded Regulators Twin Parallel Flow Regulators Field Service Regulators

Cash Valve TYPE KP PILOT OPERATED BACK PRESSURE VALVE. ISSUED - DECEMBER 2000 CAVMC-0518-US-0208 ISO 9001 Certified

BACK PRESSURE / SUSTAINING

BACK PRESSURE / SUSTAINING

Pressure and/or Temperature Pilot Operated Steam Regulators Series 2000

RHPS Series RD(H)F40 User Manual. Read the complete manual before installing and using the regulator.

COMPARING PLUG & SEAT REGULATORS & CONTROL VALVES. Lamar Jones. Equipment Controls Company 4555 South Berkeley Lake Road Norcross, GA 30071

CSB400 Series Commercial / Industrial Pressure Reducing Regulators

627 Series Pressure Reducing Regulators

Basic Hydraulics. Module 4: Flow Control Valves & Pressure Relief Valves. Academic Services PREPARED BY. January 2012

WW-730. Pressure Sustaining/Relief Control Valve

INTRODUCTION TO REGULATOR AND RELIEF VALVE SIZING. Introduction

Type 310A-32A Pressure Reducing Regulator and Type 310A-32A-32A Working Monitor Regulator

299H Series Pressure Reducing Regulators

1305 Series Pressure Reducing Regulators

CSB400 Series Commercial / Industrial Pressure Reducing Regulators

1200 Series Pressure Regulators

PRESSURE REDUCING VALVE RP45 (EN)

Type 92S Pilot-Operated Steam Regulator

WW-720. Pressure Reducing Control Valve

61 Series Pilots for Pilot-Operated Pressure Reducing Regulators

WW-720. Pressure Reducing Control Valve

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

General. Rugged, Reliable with Value-added Features. Pipe Sizes. Temperature Limits. Spring Ranges. Buried Service. Increased Outlet Pipe Sizes

Lesson 6: Flow Control Valves

MWEA MAINTENANCE SEMINAR SPECIALTY VALVES POWER GLOBES

Electropneumatic Transducer (I/P) Installation, Operation and

Rate of Flow Valve Series 120

Type R622 Pressure Reducing Regulator

EZH and EZHSO Series Pressure Reducing Regulators

Models 461-S, 461-8S and S Regulators. R-1330 Rev. 7

The Future of Hydraulic Control in Water-Systems

STANDARD FOR CONTROL VALVE SEAT LEAKAGE

CP200 Series Commercial / Industrial Pressure- Loaded Pressure Reducing Regulator

Types S100K and S102K Pressure Regulators

CL31 Series Commercial Regulator. Advanced Metering and Regulation Technology at Work.

Model PRS-07i. Stainless Steel Low Pressure, In-Line Pressure Regulator (Reducing Valve)

Pilot Operated Safety Relief Valves For Liquified Gas Carriers

What is pressure relief valve? Pressure relief valve

Type EZL Pressure Reducing Regulator for Low Differential Pressure Applications

Pressure Reducing Valves Pressure Reducing with. Broady Flow Control. D Series Range. Pressure Reducing Valves. Broady Flow Control

INDIAN INSTITUTE OF TECHNOLOGY KHARAGPUR NPTEL ONLINE CERTIFICATION COURSE. On Industrial Automation and Control

Type 299 Pressure Reducing Regulators

Cash Valve TYPE G-4 PILOT OPERATED PRESSURE REDUCING REGULATOR FOR STEAM, AIR AND GASES. ISSUED - MARCH 2001 CAVMC-0512-US-0208 ISO 9001 Certified

ALE-32. Miniature General Purpose Regulators R07, R46 (non-repairable) Air line equipment. Technical data

1805 Series Relief Valves

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

Pressure independent control valve (PICV) FLOWMATIC

Pressure and Temperature Controls

COMMITTEE DRAFT. API 520 Part I 10 th Edition Ballot Item 2.1. This ballot covers the following item:

Regulator Product Line

V DGX Series. Direct-Operated Regulators Manual D103834X012

TESCOM 50-4X Series Safety, Installation & Start-Up Procedures

PRO-50 Instrument Supply Regulator

GE Oil & Gas. Mooney * Flowgrid * Slam Shut Regulator. Delivering accuracy, performance and protection

(Refer Slide Time: 0:26)

Pressure Reducing Valve for steam RP 45

SUBMITTAL NOTES PROJECT: Ross Model 50RWR-A Pilot Operated Surge Relief Valve with Hydraulic Anticipation. Size: inch / mm

Actuator HON 670 / 671

Model 1800 PFM Series Regulator. Technical Bulletin

Cash Valve. Type G-4. Pilot Operated Pressure Reducing Regulator for Steam, Air and Gases. Flow Control

Pressure Reducing Regulator Manual

T e l N o : F a x N o : E m a i l : a i s h c m c - m e. c o m w w w. c m c - m e.

Types S108K and S109K Pressure Reducing Regulators with Integral Slam-Shut Device

299H Series. Introduction. P.E.D. Categories. Specifications. Installation. Warning. Installation Guide English September 2012

Training Fees 4,000 US$ per participant for Public Training includes Materials/Handouts, tea/coffee breaks, refreshments & Buffet Lunch.

Becker Precision Equipment

Hydraulics. Hydraulic Pressure Control

Power Valve: Precision Regulator. High precision, large capacity relief regulator

Tank Blanketing. Application Jordan Valve Product Offering Competition

Petro-Chemical & Analyzer Sampling Systems

Petro-Chemical & Analyzer Sampling Systems

SINGLE VALVE WITH LOW-FLOW BYPASS

PRESSURE REDUCING VALVE RP45 (ANSI)

Type ACE97. Introduction. Installation. P.E.D. Categories. Specifications. Overpressure Protection. Installation Guide English May 2002

Operation Manual. Diaphragm Sensed Gas Pressure Regulators

Type HSR Pressure Reducing Regulator for Residential, Commercial, or Industrial Applications

Precision Pressure Regulators

ANDERSON GREENWOOD TANK BLANKETING REGULATORS

FILTER BYPASS CONTROL

RESIDENTIAL REGULATORS

Mounting and operating instructions EB 2530 EN. Self-operated Pressure Regulator. Pressure Reducing Valve Type M 44-2

Type EZH Relief or Backpressure Regulator

Type 1098-EGR. Pilot-Operated Valve Link Regulators. Features. Fisher Controls

64 Series Pressure Reducing Regulators

Type 99 Pressure Reducing Regulators

V DFX Series. Direct-Operated Tank Blanketing Regulator Manual D103808X012

Operation & Maintenance Manual Place this manual with valve or person responsible for maintenance of the valve

Types 1098-EGR and 1098H-EGR Pressure Reducing Regulators

The Shand & Jurs Model Vapor Guard Tank Blanketing Valve

Temperature Controllers

C 10 Pressure Reducing Valve

FLUID POWER FLUID POWER EQUIPMENT TUTORIAL OTHER FLUID POWER VALVES. This work covers part of outcome 2 of the Edexcel standard module:

1800CPB2 Pilot-Loaded Service Regulators

POP Safety Valve. POP Safety Valve INTRODUCTION DEFINITIONS

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

Transcription:

FUNDAMENTAL PRINCIPLES OF SELF-OPERATED PRESSURE REDUCING REGULATORS John R. Anderson Emerson Process Management Fluid Controls Institute For pressure control in process or utility applications, control valves or regulators are commonly used. In many applications, a pressure regulator is more economical and simpler than a control valve. If electronic feedback to a distributed control system is not required, a pressure regulator could be considered a viable option over a pneumatically actuated control valve. A pressure regulator is defined as a self-contained valve and actuator combination that uses the internal pressure of the pipeline for actuation. Therefore, there are no external power requirements such as a pneumatic supply, electricity, or hydraulics required for actuation. Pressure regulators may be used in applications for gases, steam, water, and most other fluids. The fluid must be relatively clean for most regulator types. Most regulators are not suitable for slurries or high viscosity fluids which are usually better applications for control valves. Most regulators have limitations with high temperature applications. A control valve should be considered in these cases. However, there are many regulator models suitable for cryogenic applications. Most industrial pressure reducing regulators can be placed in either of two categories: 1. Self-Operated or Direct Operated 2. Pilot-Operated The most commonly used regulator type is the self-operated because of its simplicity and most of all cost. A self-operated regulator is usually considered much faster reacting than a pneumatic control valve in many applications. For applications that require a fast response to load changes, consider selecting a selfoperated regulator if it will meet the pressure, and flow, temperature, and accuracy requirements. There are dome or pressure loaded styles of regulators that are considered self-operated also. FUNCTION OF REGULATORS The primary function of any pressure regulator is to match a downstream flow demand, while maintaining the controlled pressure within certain acceptable limits. The pressure in which the regulator is trying to control is called the setpoint or controlled variable. The outlet or setpoint pressure is commonly referred to as P 2. A typical pressure reducing control application might be similar to that shown in Figure 1 where the regulator is placed upstream of the valve or other load that will vary demand for fluid from the regulator. 5/8/08 Page 1 of 5 This sheet is reviewed periodically and may be updated. Visit www.fluidcontrolsinstitute.org for the latest version.

FIGURE 1 Typical Regulator System If the demand decreases causing an upward change in the pressure being controlled, then the regulator must throttle to a closed position while maintaining a steady outlet pressure. Otherwise the regulator would put too much fluid into the downstream system and the outlet pressure, P 2, would tend to increase. On the other hand, if the demand increases, the regulator must throttle open in order to keep P 2 from decreasing due to a shortage of fluid in the downstream system. THREE ESSENTIAL ELEMENTS There are three essential elements of any regulator used in a pressure control system. One of the essential elements of any regulator is a restricting element that will restrict the flow of fluid within the flow stream. Figure 2 shows a schematic of a typical regulator restricting element. The restricting element is usually some type of valve plug and orifice combination in a straight or angled body. Other technologies include the sliding gate design. When selecting the orifice and valve plug combination, always select the smallest orifice available which will still handle the maximum flow required by the application. This decreases the potential of instability in the system at lower flows. If required, it also allows for the selection of a smaller relief valve to protect the downstream components in the system from overpressure in the event of a system failure. Restricting Element FIGURE 2 Typical Restricting Element Restricting elements can be made of a variety of materials including elastomer, teflon, nylon, or metal. Selection is based on temperature, material compatibility with the process fluid, and maximum pressure drop. The lock up pressure of the regulator varies also by material selection. Lock up pressure is defined 5/8/08 Page 2 of 5 This sheet is reviewed periodically and may be updated. Visit www.fluidcontrolsinstitute.org for the latest version.

as the pressure rise above the regulator s setpoint to achieve the acceptable shut off class. Harder materials may have higher lock up characteristics and shut off classes. For further information on leakage class for pressure regulators, refer to ANSI/FCI 70-3. So far we have a restricting element that modulates the flow through the regulator. But how do we know when the regulator flow is matching the downstream demand? We need some type of measuring element which will sense the correct downstream pressure and reposition the restricting element to match the flow demand. With a pressure reducing regulator, we can use a diaphragm (Figure 3), bellows, or piston to measure the downstream pressure. Diaphragms are the most commonly used measuring element but are usually limited in pressure and temperature. Diaphragms can be made from a flat sheet or molded piece of rubber or stamped metal. Pistons and bellows offer high pressure and temperature capability for measuring pressure. The area under the measuring element creates a force which results in travel to both the measuring and the restricting elements. Diaphragm FIGURE 3 Typical Measuring Element The third essential element of a pressure regulator is a loading element. The loading element can be a weight, spring, or pressure load above the measuring element. A spring, as shown in Figure 4, forms the most common type of loading element. When the outlet pressure rises and the force created underneath the diaphragm exceeds the force of the spring, the restricting element will throttle closed. As outlet pressure goes lower, the spring force will push on the diaphragm opening the restricting element. The spring force adjustment is usually accomplished by an adjusting screw. P 1 P 2 FIGURE 4 5/8/08 Page 3 of 5 This sheet is reviewed periodically and may be updated. Visit www.fluidcontrolsinstitute.org for the latest version.

Self-Operated Regulator Basic Design Regulator models have many variations. They can be balanced or unbalanced, single-ported or doubleported. But common to all regulator valves is a control inaccuracy caused mainly by the spring effect. Spring effect occurs as the force of fluid acting on the diaphragm compresses the spring in the regulator. As spring compression increases, there is a greater increase in the amount of diaphragm force required to move the restricting element to the closed position. For example, the spring effect may cause the regulator valve plug to remain open even though downstream pressure equals or is greater than the setpoint. When the flow demand goes to zero, the restricting element in the pressure regulator is required to close. In order for the valve plug to travel to a closed position, there must be an increase in downstream pressure over setpoint. The increase in outlet pressure over the set pressure is called the lock-up or shut-off pressure. This is normal with any pressure regulator to see some pressure rise downstream over setpoint when the regulator is in the closed position. All springs have a spring rate. This is the amount of force required to compress a spring one inch. When selecting springs for regulator applications, the higher the spring rate, the more force that is required to move the restricting element to a closed position. Also, with higher spring rates there will be more inaccuracy in maintaining a set point over a given flow range. Best accuracy in a self-operated regulator is defined by which regulator can pass the most amount of flow with the least deviation from the setpoint expressed as a percentage of a fixed unit of measure. Setpoint of a regulator is determined by the end user. Manufacturers will present accuracy in a tabular or graphical format in their technical literature. See Figure 5, taken from ANSI/FCI 99-2 Regulator Pressure Capacity Standard, as an example of a flow curve that could be found in a manufacturer s bulletin. The downward deviation from setpoint as flow increases is called offset. Offset is also referred to as droop. Offset is determined by multiple variables including spring rate, diaphragm area, pressure drop, unbalanced forces, etc The desired result of any pressure regulator is to maintain pressure accurately throughout the flow range. FIGURE 5 5/8/08 Page 4 of 5 This sheet is reviewed periodically and may be updated. Visit www.fluidcontrolsinstitute.org for the latest version.

During the testing process, manufacturers will make setpoint, usually with a small amount of flow anywhere from 1-10% of flowing capacity. From this initial flow, the flow curve is developed that determines the regulator capacity. Normally for self-operated regulators, a 5-20% deviation in setpoint is allowed and that will determine the rated capacity. Accuracy will vary based upon the type of regulator technology used. Some self operated regulator will maintain accuracy better than 1% while others are less than 50%. This will change based on application and regulator model. In most cases, the maximum capacity is much higher than the rated capacity. To compare regulator models, always look at the rated capacity at a comparable offset and not the wide open capacity. The wide open capacity is typically used for relief valve sizing and is not reliable for determining regulating capacity. Regulators are designed to minimize the droop or offset that occurs. When sizing and selecting a regulator, a rule of thumb is to use the lowest spring rate possible to achieve the highest accuracy. Most manufacturers will publish spring ranges that can be used from their upper to lower ranges. If a pressure regulator is unstable, many times changing to a higher rate spring can alleviate the instability because it decreases the sensitivity. CONCLUSION Every type of regulator represents an evaluation involving such factors as price, capacity, accuracy, stability, simplicity, safety, and speed of response. A careful analysis of control applications usually reveals that more of these factors should be considered when selecting a pressure regulator. Regulators offer a lower installation cost compared to a control valve in simple pressure control applications. 5/8/08 Page 5 of 5 This sheet is reviewed periodically and may be updated. Visit www.fluidcontrolsinstitute.org for the latest version.