MCS-Magnum Unsafe and Low Suction Control

Similar documents
Sequence of Operations

Magnum Version 8 Manual

Guida parametri EVD 200. Manuale d'uso User manual

COMPRESSOR PACK SUCTION CONTROLLER TYPE: LP41x

CHILLER CONTROL PANEL PROGRAMMING AND DATA ACCESS

WMC Magnetic Bearing Compressor Chillers

CONTROL PANEL OPERATING MANUAL. AIR COOLED SCREW CHILLER GLOBAL DESIGN Software version ASDU01C and later D-EOMCP EN

Troubleshooting Guide. Pg. 1

INSTRUCTION MANUAL STATION CONTROLLER SC100 MOTOR PROTECTION ELECTRONICS, INC.

Touch Screen Guide. OG-1500 and OG Part # T011

Hill PHOENIX Second Nature Medium Temperature Secondary Refrigeration Start-Up Guide

CONTROL PANEL OPERATING MANUAL

Practical Guide. By Steven T. Taylor, P.E., Member ASHRAE

1 STARTUP Overview Buttons Basics of Control Resetting Faults and Alarms OPERATION...

A TECHNICAL REFERENCE

MICRO BASED CONTROL SYSTEM YLCS-SA/HA/AA YAES-SA 2 System YAES-SA 3 System YAES-DSA 4 System

SCIENTIFIC DATA SYSTEMS, INC. Depth Tension Line Speed Panel. DTLS Manual

Copeland Discus with CoreSense Diagnostics January 2011

Standard Chiller 1/4 compressors Manual version: /10/96

Specifications and information are subject to change without notice. Up-to-date address information is available on our website.

Controlling the prefeeder

Quick Start Setup Instructions for Raven LRC & AgXcel Harness for NH3 Profile plus GX40 Synergist

MONSOON 6V Pump Control System

700 SERIES BMS II BUBBLER MONITORING SYSTEM

How to Select High Pressure and Gas Bypass

SSI Solaris 150 RTA Revision /27/2016 Page 1 of 9. SSI Solaris 150 RTA

ATL R/V Atlantis AUXILIARY PLANT OPERATION APPENDIX OPERATING PROCEDURES

Standard 1/4 compressor chiller/heat pump with heating recovery Manual version: /02/97

CONTROL LOGIC DESCRIPTION DOCUMENT IC-410ND

Built-in Purge Control Functions

BUBBLER CONTROL SYSTEM

Refrigeration and Air Conditioning Technical leaflet

C1960. Multi-recipe profile recorder/controller. Measurement made easy

BUBBLER CONTROL SYSTEM

FAULT CODE TROUBLESHOOTING INDEX

Revision 1 AIR & WATER COOLED LIQUID CHILLERS MICRO BASED CONTROL SYSTEM WITH IPUII

SHIMADZU LC-10/20 PUMP

Standard Operating Manual

UBEC 1AT. AUTO TANK Fill System Installation, Operation, & Setup Instructions

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE REFRIGERATION AND AIR CONDITIONING. Technical leaflet

SAUTER flexotron 800 heating. List of network variables for Modbus communication. Manual P A P

Capacity regulator (hot gas bypass)

Hydronic Systems Balance

GeQuip Joule Thomson Plant. Process Description (see Figure 1) Standard Control Instrumentation

Design Envelope Booster. Sequence of operation

ACV-10 Automatic Control Valve

LABORATORY EXERCISE 1 CONTROL VALVE CHARACTERISTICS

System Soft-optimization Tests of Refrigerant R-32 in a 6-ton Rooftop Packaged Air-Conditioner

A/C SYSTEM DIAGNOSIS

Basic Autoclave #1 Ideal Gas Law, Inert Gas

955730_1 4/17/18. FlowSense Operator s Guide For Gen2 20/20 SeedSense Displays

USER MANUAL. Intelligent Diagnostic Controller IDC24-A IDC24-AF IDC24-AFL IDC24-F IDP24-A * IDP24-AF * IDP24-AFL * IDP24-F * 1/73

EXPERIMENT 1 AIR PRESSURE CONTROL SYSTEM

Hydro-Control V User Guide

How to use the PBM Flow Calculator Spreadsheet (V2.04)

ECL Comfort 110, application 131 (valid as of software version 2.00)

LENNOX SLP98UHV DIAGNOSTIC CODES

Exercise 8. Closed-Loop Pressure Control, Proportional-Plus-Integral Mode EXERCISE OBJECTIVE

EZ Boom 2010 System for the EZ Guide 500 Lightbar Triangle Ag Services Users Guide

Race Screen: Figure 2: Race Screen. Figure 3: Race Screen with Top Bulb Lock

Application Worksheet

Evaporator pressure regulator Type KVP

Superconducting Susceptometer (MPMS-5S) Quantum Design Room 296 (MPMS)

Technology issues regarding Blends of Refrigerants Buffalo Research Laboratory

Crankcase pressure regulator, type KVL REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Unisab III Control Version 1.10

SERIES 100 PACKAGED ROOFTOP UNIT WITH IPU CONTROL

Recovery from a Process Saturation Condition. Benefits of Using DeltaV PIDPlus

Monsoon3V+ Multiple Pump VFD Control System. Please pass these instructions on to the operator of this equipment.

Industrial Compressor Controls Standard Custom

Inprocess Operator Training Programme

TFC TM - Touch Force Control

660 Multipoint Electronic Level Switch

Expansion Tank Design (Chilled Water)

Figure SM1: Front panel of the multipatcher software graphic user interface (GUI) at the beginning of multipatcher operation.

ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION

JOLLY2. Installation user s manual. 6 different operating modes selectable. version 3.3. DATA TO BE FILLED OUT BY THE INSTALLER (Page 1)

Description of Device Parameters Proline Prowirl 200 HART. Vortex flowmeter. Products Solutions Services. Main menu Language.

Soft-optimization test of R-410A alternative refrigerant R-32 in a split condensing unit - Phase II

Functional Analysis and Control System for the Thermosiphon Chiller. Lukasz Zwalinski PH/DT/PO - Cooling

Electronic Commissioning Unit. Instructions

Injection Controller Program User Manual (for FloBoss 107 and ROC800-Series)

TANK MANAGER FOR TWO TANKS OPERATING MANUAL. 10/31/11 C-More T6C L color touch panel

XDF BURNERS DUAL FUEL EXCESS AIR BURNER FEATURES DESCRIPTION EXCESS AIR OPERATION

Two-Stage Linear Compressor with Economizer Cycle Where Piston(s) Stroke(s) are Varied to Optimize Energy Efficiency

FUEL GAS FIRING CONTROL RJ (Dick) Perry Safety Systems Consultant 6 June 2016

Evaporator pressure regulator Type KVP

Electro Controls. Pressure WattsIndustries.co.uk

KEM Scientific, Inc. Instruments for Science from Scientists

for Building facilities Industrial facilities etc.,multipurpose Pilot operated type(high capacity)

Multistack BACnet Solution: MS70/90 Standard Chiller Module

AE R1 February 2015

Refrigeration Scroll For Parallel Applications

SECTION P4 SEPARATION SYSTEMS

EZ-Boom 2010 Automated Application Control System Quick Reference Card INTRODUCTION

Dive Sheets & Running Events Meet Management Software Tutorial for EZMeet Version 3.1 revised 2/4/2006

SPLIT HOPKINSON PRESSURE BAR OPERATIONS MANUAL 5/9/2014

Angstrom Dielectric Sputterer Operation Manual

CHEMICAL ENGINEERING LABORATORY CHEG 239W. Control of a Steam-Heated Mixing Tank with a Pneumatic Process Controller

Micro Environmental Control Systems Woda Sci Sump Sprinkler and Home Water Control System Manual Contents

Transcription:

Micro Control Systems APPLICATION NOTE APP-090 MCS-Magnum Unsafe and Low Suction Control Revision History Date Author Description 02-06-14 John Walterick Created application note 02-07-14 Brian Walterick 1. Assigned App note #090 to this document 2. Changed title to include Unsafe Suction 3. Added to Magnum set point description section. 4. Added to Magnum config changes required for the new low suction control. 5. Added to the running adjustment section. 02-23-14 John Walterick Rewrote section 3.2 for easier implementation. 04-11-14 Will Powell Changes to Low Suction Pressure Control (3.2) 07-08-14 Brian Walterick 1. Add leading zero to all decimal values. 2. Remove highlights on values in the set point grid. 07-10-14 Michael Wozny 1. Changed MAX value on LOSUCTPSIDLY to 35. 2. Combined tables 3.2 and 3.3. 3. Changed Value on LOUSUCTPSIDLY to 5. 4. Changed Value on EXV rocfast to 1.5. 5. Changed MIN on EXV rocfast to 0.5. 6. Changed MAX on EXV rocfast to 2. 02-10-15 Don Walterick Modified Setpoint Values 02-11-15 Don Walterick 1.Changes per Brian s edit pgs 2,3,4 2. Change to chart pg 3 01-25-16 Don Walterick Changes per Brian, add changes to Setpoint 49 1

1. Description of the Problem 1.1. Chiller suction pressure has reached a low value that could cause operational problems if allowed to continue. 1.1.1. Low refrigerant could be a possible cause. 1.1.2. A temporary condition occurs where a mix of gas and liquid refrigerant flowing from the condenser to the expansion valve could be a possible cause. 2. Magnum Set Points Used Description 2.1. SP 77; LOW SUCTION : The Value field specifies the low pressure trip value and its Time field specifies the delay in seconds before causing a safety trip. Typically, this safety is setup for two trips within 2 hours of each other to cause a compressor lockout on low suction. The first occurrences place the compressor in a safety trip state for typically 10 minutes before an auto reset clears the safety and allows the compressor to run again when required. If a second occurrence within 2 hours of the first occurrence happens, the compressor is locked out and must be manually reset. 2.2. SP 78 LO SUCT UNLD : The Value field specifies the offset added to SP 77 s value to calculate the suction pressure that will force the compressor into low suction unloading. The system will start to unload the compressor to avoid a safety/lockout trip. 2.3. SP 79; LO SUCT RELD : The Value field specifies the offset added to SP 77 s value to calculate the suction pressure to allow the compressor to operator normal (exit low suction unloading or low suction holding states). This will allow the compressor to follow the chilled water out capacity control. 2.4. SP 79; LO SUCT RELD : The Value field is multiple by 2 and added to SP 77 s value to calculate the suction pressure to force the Electronic Expansion Valve (EXV) into low suction pressure opening. The EXV control logic will rapidly take corrective action to avoid an unsafe or low suction safety/lockout. 2.5. SP 65; EXV ZONE X1 : The Night Setback field specifies the offset to add to SP 9 s value to calculate the lowest suction superheat value to allow the low suction pressure open logic to override normal superheat control of the EXV. SP 65 Type of Set point must be selected as Target to use the Night Setback field. If not setup as Target type, the low suction pressure open EXV logic is allowed to operate until the suction superheat falls below fine adjustment (Closing 1X state) zone. 2.6. SP 13; EXV COURSE : The Value field specifies the course adjustment to the EXV. If it s Type of Set point is Time, then the Time field is used as a multiplier to the course adjust to calculate the adjustment to make to the EXV opening when in low suction pressure opening. The set point s Max Time Allowed field defines the upper limit the multiplier can be set at. 2

3. Magnum changes required for new Low Suction Pressure control 3.1. Please use the latest V16 firmware version, 16.10-N or later. 3.1.1. The CFG file must be version 14. If the CFG file is V11 CFG Type (for HVAC V8 & HVAC V9 Magnum firmware) it can be automatically converted to V14 CFG Type. Open the V11 CFG file with MCS-Config (14.01-D or later). Then click on File in the upper left corner. Then select V8/V9 (V11 CFG) to V14-CFG option. 3.2. Using the latest version of MCS-Config make the following recommended changes, (Chiller Refrigerant 134A units in ºF & PSI): ST/ PT Name Value MIN MAX Adjust Value Time MAX Time Allowed Active or Non-Active Type of Set point High Zone High Zone Night Setback 9999 9 SUPERHT TRGT 12 10 16 0.5 3 10 Active Alarm 10 SPRHT ZONE+- 2 1.5 2 0.1 0 0 Active Set point 11 EXV LOAD ADJ 0.2 0.1 5 0.1 0 0 Active Set point 12 EXV FINE ADJ 0.1 0.1.5 0.1 0 0 Active Set point 13 EXV COURSE 0.5.2 1.5 0.1 4 6 Active Time 18 LOSUCTPSIDLY 3 2 5 1 0 0 Active Set point 19 EXV DELAY 60 60 120 5 0 0 Active Set point 65 EXV ZONE X1 2 1.5 2 0.5 0 0 Active Target 0 0-4 66 EXV ZONE X2 1.5 1 2 0.5 0 0 Active Set point 67 EXV roczone1 0.2 0.5 0.1 5 15 Active Alarm 69 EXV roczone2 0.3 0.1.7 0.1 5 10 Active Alarm 70 EXV roczone3.4.1 1 0.1 5 10 Active Alarm 71 EXV roc FAST 5.0 2 8 0.1 10 15 Active Alarm 72 EXV roc CHG 3.5 1 6 0.1 10 15 Active Alarm 77 LOW SUCTION 25 20 30 1 60 120 Active Lockout 78 LO SUCT UNLD 0.5 0.5 2 0.5 40 40 Active Set point 3

79 LO SUCT RELD 1 1 3 1 0 0 Active Set point 80 UNSAFE SUCT 5 0 5 1 5 10 Active Lockout 101 SAFETY HOLD 120 60 300 1 2 2 Active Set point 230 PSID EXV Adj. 5 1 10 1 3 6 Inactive Lockout 120 1 16 3.3. SP #9: Change SUPERHT TRGT Time (sec) field to 3 seconds. 3.4. Set Point s 10, 11 and 12: Set based on system response. 3.5. SP #13: Change EXV COURSE type of set point field to Time ; set Time field to 4; set Max Time Allowed field to 6. 3.6. SP #18: Change LOSUCTPSIDLY : Value field to 3, the Min field to 2 and Max field to 5. It is important to set this value as low as possible to allow quick reaction of the EXV when a low suction pressure occurs. 3.7. SP #19: The EXV DELAY Value field must be between 48 and 60 seconds, with 60 being preferred. Verbatim Expansion Valve Changes for New Low Suction Pressure Control SP 65; EXV ZONE X1 : Active, Value 2.0F, Min 1F, Max 3F, Type = Target, High & Low Zone to 0 & Night Setback = -4. 3.8. SP# 66; EXV ZONE X2 : Active, Value 1.5F, Min 1F, Max 3F, Type = Set point. 3.9. SP #67; EXV roczone1 : Active, Value 0.2F, Min 0.0F, Max 0.5F, Type = Alarm, Time (sec) 5, Max Time 15 3.10. SP #69; EXV roczone2 : Active, Value 0.3F, Min 0.1F, Max 0.7F, Type = Alarm, Time (sec) 5, Max Time 10 3.11. SP #70; EXV roczone3 : Active, Value 0.4F, Min 0.1F, Max 1.0F, Type = Alarm, Time (sec) 5, Max Time 10 3.12. SP#71; EXV rocfast : Active, Value 5.0F, Min 2.0F, Max 8.0F, Type = Alarm, Time (sec) 10, Max Time 15 3.13. SP #72; EXV rocchg : Active, Value 3.5F, Min 1.0F, Max 6.0F, Type = Alarm, Time (sec) 10, Max Time 15 3.14. SP #77; LOW SUCTION : value to a suction pressure at where ice will start to form in the evaporator (this is low suction freeze safety). Typically value for R134a refrigerant is 25psi. 3.15. Change Set Point #78 Low Suct Unld Time (sec) field to 40 seconds. 3.16. If the compressor has steps of capacity (recip with unload or step screw), make sure set point 153 SttyUnld Dly is active. This is the time delay between each stage of unliading when a compressor safety condition is near the trip point. 4

3.17. In the ROs screen, check the following items when using a compressor type with step loading/unloading: 3.17.1. Check the EXV Start value for each compressor relay. Make sure this value is not too large causing the compressor to be fooled with liquid refrigeration. A value between 25% and 45% is typical. Check the size of the EXV compared to the size of the compressor when it starts (unload). Best to set the EXV Start value a little low and then fine tune the value during testing/startup. 3.17.2. Check the EXV Load Adjust % value for each compressor and each step of unloading relays. This set point value is a percentage used to calculate a jump in the EXV position. The adjustment made to the position EXV is calculated by take percentage of the current EXV position. 3.17.3. Check the EXV Unld Adjust % value for each comp and step of unloading relay. This set point value is a percentage used to calculate a jump in the EXV position. The adjustment made to the position EXV is calculated by take percentage of the current EXV position. 3.17.4. Setup User Logic virtual points for each of the compressor s calculated values so they can be tracked in the MCS- Magnum history: 3.17.4.1. Saturated Suction temperature 3.17.4.2. Suction Superheat for each comp 3.17.4.3 Comp State 3.17.4.4 EXV State 4. Running Adjustments 4.12. Using either Magnum Keypad/Display or MCS-Connect, set History sample time to 1 second. 4.13. When a compressor starts, the suction superheat (SSH) will react as follows: 4.13.1. The EXV opening start % is set to the opening value as specified in the Relay Output in the cfg. 4.13.2. SSH stays at 0 for about 10 to 15 seconds as the compressor builds up momentum. 4.13.3. The SSH should then settle to the SSH target or slightly below. During the start period it is best to have the SSH slightly below the target. This allows the system to maintain adequate suction pressure. If the circuit s SSH is above the target you need to adjust the starting opening% lower. Do not adjust the EXV START value too large that it causes low superheat or low discharge superheat safety trips. 4.14. Watch the system loading and unloading. And if required adjust the Fine & Course EXV Set Points. In a system with steady load on the chiller, the suction superheat should remain in the superheat control zone. 5

4.15. At 1 second sample rate for history you have 16.7 minutes of data. Approximately 15 minutes into startup, pull back the History. You can then verify the results by reviewing the runtime history of all the inputs and outputs. 4.16. Let the system continue to run until an unsafe or low suction occurs. After the system has corrected the problem again pull back the history and verify the results as follows: 4.16.1. As the compressor speed increases or decreases check the following: 4.16.2. With step loading adjust the EXV % change to match the Capacity change. 4.16.3. With infinite capacity, the unit will increase or decrease the Capacity based on Set Point 56 PULSE or CMP LOAD DELAY until the total change is made. Here the system uses Set Point 11, Load Adjust. 4.17. Adjust the low suction pressure open set point. Cause a Low Suction pressure condition and watch how the EXV recovers and how the SSH reacts. If opening the EXV causes too low of SSH, lower the multiplier in set point 13 EXV COURSE time field. If suction pressure does not recover quickly and SSH is ok or high, increase the multiple in set point 13 Time field. Set point #18 value field can also be adjust to help fine tune the EXV reaction to low suction pressure condition. 4.18. Use the graph to see where the EXV adjustments stop being made during a Low Suction pressure condition. If you think an additional adjustment needed to be made increase the Time value in Set Point 9, SUPER HEAT TARG. If you think one less adjustment needed to be made decrease the Time value in Set Point 9, SUPER HEAT TARG. 4.19 Make setpoint #49 CND MIN RUN non-active with a value of 0, min of 0 and max of 0, in all config files. 4.20 For R134a suggest the following setting is a good starting point for air cooled condenser: ST/ PT Name Value MIN MAX Adjust Value Time MAX Time Allowed 9999 45 CND STG1 ON 150 140 170 1 0 0 Active 46 CND STG1 OFF 120 100 130 1 0 0 Active 47 CND DIFF ON 30 20 40 1 0 0 Active 48 CND DIFF OFF 10 5 20 1 0 0 Active Active or Non-Active 49 CND MIN RUN 0 0 0 1 0 0 Non-Active 6