Hill PHOENIX Second Nature Medium Temperature Secondary Refrigeration Start-Up Guide

Similar documents
KKT Training Series: ECO Series, Preventative Maintenance

Water Mist Systems Inspection, Testing, and Maintenance of Water Mist Systems

Installation and Operation 370ESP (Electric Single-Point Purger) & 370ESPR (Retrofit Purger)

INSTALLATION AND OPERATION INSTRUCTIONS

Bulletin TCR-104 & 109 Filling and adding to the Glycol pressure system

WPB 5 / 7 / 10 INSTALLATION, OPERATION, & MAINTENANCE

Copyright, 2005 GPM Hydraulic Consulting, Inc.

Accu-Tab PowerBase 3070AT by Axiall Corporation

Installation and commissioning instructions 255 series and 256 series

BS Series Basket Strainer

Operating Instructions

PumpAgents.com - Click here for Pricing/Ordering Nominal psi (bar) Cut-In Cut-Out

INSTALLATION AND OPERATION INSTRUCTIONS

Industrial Refrigeration Control Valves. Catalog C12-PVS Parker Valve Station (PVS) Sizing Guide

Accu-Tab PowerBase 3140AT by Axiall Corporation

Accu-Tab PowerBase 3012AT by Axiall Corporation

FloWash. Industrial Filter Cart

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

Acid- Rite ph Adjustment System 2500 by Axiall, a Westlake Company

TWC Services, Inc. Structured On-The-Job Training for JT- 1, 2, 3

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity

R E D I C O N T R O L S

SSFU SUPER SPRAYFAST UNIVERSAL ADHESIVE APPLICATOR

Accu-Tab Systems 1000 Series by Axiall Corporation

TROUBLESHOOTING GUIDELINES

Design DSA Steam-Atomized Desuperheater

HAYWARD FLOW CONTROL TFS SERIES FLOW METER INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

TECHNICAL DATA. Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve.

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Digital Range

Reverse Osmosis System Installation Guide and Operation Manual.

SEPARATION SYSTEMS. The Separation Systems consists of the Test Header (GAY-0302) and the Test Separator (MBD-4501).

TECHNICAL DATA. than the water inlet pressure to the concentrate

553 Series.

TOP VALVE. Pat. #5,857,486 & 5,944,050. Mid-Range Pressure PSIG Back Pressure and Pressure Relief Valves. Instruction Manual

Hi-Force Limited Prospect Way Daventry Northants NN11 8PL United Kingdom Tel: +44(0) : Fax: +44(0) : Website:

Accu-Tab Systems 2000 P Series by Axiall Corporation

SPECIFICATIONS APCEPH1

Installation Operation Maintenance

HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS

Heat Pump Connections and Interior Piping

INSTALLATION INSTRUCTIONS Non-Pressurized Tank. Non-Pressurized Tank Part Number: AFCG1PT

Marschalk Model # 94000

MODEL NUMBER: PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank

120 PSI FAST-FILL AIR SOURCE KIT 25% Duty Compressor on 1.5 Gallon Air Tank

System Pressure Manager Standard & System Pressure Manager Plus

TotalPac X Single interlock Preaction system Electric release

GAS COMPRESSION SYSTEM

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE

Jacuzzi. J-CQ420 Cartridge Filter Installation and Operating Instructions

NGP-250/500 Nitrogen Generator Quick Start Guide

Instruction Sheet. SUPERSEDES: New EFFECTIVE: August 1, 2013

DB 61 Dolphin TMV3 Integrated Thermostatic Mixing Valve

FRYSAFE COOKING OIL FILTRATION I&O MANUAL

ATL R/V Atlantis AUXILIARY PLANT OPERATION APPENDIX OPERATING PROCEDURES

1020 Industrial Drive, Orlinda, TN fax

Advanced Fluid Handling Cart Owner s Manual

GAS DEHYDRATION SYSTEM

South-Tek Systems - Nitrogen Generation Corrosion Inhibiting System. Designed for: Dry or Preaction Fire Protection Systems (FPS)

VTL VFL VCL. Low Profile Series V RIGGING & ASSEMBLY INSTRUCTIONS

AcornVac Vacuum Plumbing Systems - Trouble Shooting Guide

Gas-Lift Test Facility for High- Pressure and High-Temperature Gas Flow Testing

PC1131 Electric Air Compressor

MODEL NUMBER: M20005 AIR SOURCE KIT. 30% Duty Compressor on. 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE

Model B-1 Pipe Line Strainer 3, 4, 6 & 8 Inch (DN80, DN100, DN150 & DN200) 175 psi (12,1 bar) General Description. Technical Data

420C AIR COMPRESSOR KIT PART NO C AIR COMPRESSOR KIT PART NO

IMPORTANT SAFETY INSTRUCTIONS

WaterSource Heat Pump Hose Kit Performance Specification-Summary

GAS DEHYDRATION SYSTEM

Fisher DSA Steam-Atomized Desuperheater

Inert Air (N2) Systems Manual

Blue River Technologies Port-A-Poly Mixer w/2.5 GPH LMI Pump And Secondary Water Dilution Line INSTALLATION AND OPERATION

OPERATING INSTRUCTIONS Pressure Control System PCS-20 through PCS-100

42045 Heavy Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor Only) Heavy Duty ADA Base Model Kit: 110/145 PSI (ADA Compressor Only)

Vortex Dual. Refrigerant Recovery Machine

Operating Manual. Model BAC-30RT30/BAC-30DC

OPERATING INSTRUCTIONS

icon i150 / i350 Installation / Operation Manual

RadKits (Piping Packages)

Operating Manual. Model 25200B/25202B Refrigerant Recovery Unit. (Not for use in automotive R-134a applications)

STYLE 3414/3416 & 3421/3423 Apollo Monitor with Foldaway Legs OPERATING & MAINTENANCE INSTRUCTIONS

Proper Pump Installation Practices

200 PSI FAST-FILL AIR SOURCE KIT

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

200 PSI COMPRESSORS - MODEL NUMBERS

Spirax Compact FREME Flash Recovery Energy Management Equipment

200 PSI HIGH-FLOW AIR SOURCE KIT

100C Air Compressor Kit

LAKOS Waterworks. PWC Series Sand Separators. Installation & Operation Manual LS-829 (10/12)

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A

Remotely-installed Hydraulic Module

Sequence of Operations

Model GP PRESSURE REDUCING VALVE Installation & Operation Manual

Document How to Set Single Stage Press Pressures

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

Installation, Operation, & Maintenance Manual NX Seal Cooler

Wet pipe low flow foam/water system

Irrigation System Winterization and Pressurization Procedures

Troubleshooting Guide. Pg. 1

Model C Pipe Line Strainer 6, 8 & 10 Inch (DN150, DN200 & DN250) 250 psi (17,2) General Description. Technical Data. Page of 6 MAY, 2006 TFP1644

Technical Service Bulletin March 2015 TSB142.01

Transcription:

Hill PHOENIX Second Nature Medium Temperature Secondary Refrigeration Start-Up Guide Secondary Coolant System Start-Up Procedures June 2006 Produced by the Hill PHOENIX Learning Center

DISCLAIMER This guide is designed to provide only general information. If you need advice about a particular product application or installation, you should consult your Hill PHOENIX Representative. The applicable specification sheets, data sheets, handbooks, and instructions for Hill PHOENIX products should be consulted for information about that product, including, without limitation, information regarding the design, installation, maintenance, care, warnings relating to, and proper uses of each Hill PHOENIX product. INFORMATION CONTAINED WITHIN THIS MANUAL, IS PROVIDED AS IS, WITH ALL FAULTS, WITH NO REPRESENTATIONS OR WARRANTIES OF ANY KIND, EITHER EXPRESSED OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE, QUALITY OF INFORMATION, QUIET ENJOYMENT, AND TITLE/NONINFRINGEMENT. HILL PHOENIX SPECIFICALLY DISCLAIMS ALL LIABILITY FOR ERRORS OR OMISSIONS IN, OR THE MISUSE OR MISINTERPRETATION OF, ANY INFORMATION CONTAINED IN THIS MANUAL. HILL PHOENIX DOES NOT WARRANT THE ACCURACY, COMPLETENESS OR TIMELINESS OF THE INFORMATION CONTAINED IN THIS GUIDE. Copyright 2006

1 Second Nature Start-Up Guide For Medium Temperature Propylene Glycol Hill PHOENIX warrants all of the refrigeration systems and equipment it manufactures. In order for that warranty to have value to the customer and to ensure profitability to the company, it is essential that following installation the systems be properly started up. The procedures listed below describe the startup practices for Hill PHOENIX Second Nature refrigeration systems and equipment. Careful execution of the start-up procedures for any refrigeration system is critical to the safe, effective, and efficient operation of the system. Every step must be followed in as much as possible the order and the way described in this guide, otherwise the equipment may not function properly. It is also critical that only the materials specified in the procedures be used. The procedures for Second Nature start-up fall into 4 main areas of activity: As you proced through the steps in this startup guide, use the column on the appropriate pages to record any settings, readings, or verifications that are described in the steps. A checklist at the end of the guide, following a Quick Start Set-Up chart, provides space for confriming the settings, readings, and verifications you record in the guide. The completed checklist should then be submitted to Hill PHOENIX for validation of warranty coverage. Start-Up Guide Initial start-up steps (10 steps including pressure testing the system, flushing the system, and starting the system) Add fluid to the system (7 steps) Set-up of the balance valve System control strategy (8 steps including Pump strategy) System operation (4 steps) This guide lays out the steps for each area. As you go through each of the steps, feel free to take advantage of the space in the outside column of each page to add any information that will help your understanding of the procedures. It is important to note that these procedures are intended only as guidelines to be followed as closely as the specifics of each installation allow.

2 Initial Start-up Procedures Initial Start-up Procedures 1. Set ¾ inch end of loop balance valves at 1.0. (Note: That the valve pictured shows a setting of 1.7. This is the only reference to the loop balance valves in these procedures which are hereafter excluded from any mention of valves for the remainder of the procedures.) 2. Verify that the control circuit is energized and fully open all: a. Balance valves b. Ball valves c. Solenoid valves 3. Close all: a. Vents b. Drains 4. Verify that the pre-charge pressure in the expansion tank is at 12 psig 5. Pressure test piping by isolating: a. the expansion tank b. the pumps c. any cases and/or components that are not rated for the test pressures that will be used

3 Use dry nitrogen, at the following durations and settings, once components a. through c. have been isolated. 1st 30 minutes 15 psig 2nd 30 minutes 30 psig 1 to 3 hours 60 psig Reduce to 15 psig if pressure charge is left on 6. Flush system by: a. Opening all system valves (including any closed in the preceding step) b. Closing a valve between the return and the supply on the pump skid in order to break the chiller loop which results in a one-way flow through the system. To create a one-way flow, connect the drain hose to the return side of the system and the supply hose to a point on the opposite side created by the closed valve. c. Fill the system with water to normal service pressure and allow water to flush through the drain until water runs clear Initial Start-up Procedures Note: All references to water assume acceptable quality regardless of source d. Stop draining water e. Open the valve referred to in step 6.b. f. Pressurize the system with water to approximately 30 psig h. Vent main loop lines to ensure loop is full of water (note: the number of loops may vary from system to system) is i. Vent air from the system starting at the lowest vent points and moving continually to higher vent points until all air purged from system including main vent lines again

4 Initial Start-up Procedures i. Lowest vent points are typically coils all coils must be purged of air ii. Remember to monitor and maintain approximately 30 psig water pressure through the system iii. Make sure to also purge air from pump skid since it is also part of the system j. Turn off the water supply 7. Starting pumps a. Verify that the correct pumps (model number, and motor hp, rpm, voltage) are installed the pump curve provided by Hill PHOENIX indicates model number, hp, and rpm b. Verify pumps are full of water by venting never run pumps dry as seal damage will occur c. Manually cycle pumps on and off one at a time to determine the direction of rotation is correct

5 Pump Amperage Pump #1 Nameplate Amp Pump #1 Actual Amp Pump #2 Nameplate Amp Pump #2 Actual Amp Pump #3 Nameplate Amp e. If amperage is too high, reduce by closing pump outlet balance valve until the proper amperage is reached f. Start and run all pumps g. From this point on, maintain return fluid pressure at 20 psig by adding water as needed h. Cycle system switches so that each of the circuits is the only one turned on for a period of 1 minute to fully flush each coil i. Cycle on and off warm fluid defrost solenoids j. Turn on all systems and allow water to circulate for 2 hours 8. Drain a. Once water is in the system it should never be drained until the system can immediately be filled with Secondary Fluid b. Shut off the pumps c. Drain all water from all drain points in the system and force out any water remaining with dry nitrogen d. Check drain water for cleanliness and repeat flush process if drain water is dirty Pump #3 Actual Amp Initial Start-up Procedures d. Start pumps one at a time and check amperage for each pump

6 Initial Start-up Procedures e. Open pump strainers and remove the fine-mesh startup screen from around of the outside of the permanent strainer and reassemble 9. Pump secondary fluid into system from tank or barrel (drum) a. Open all valves (but do not open vents and drains) b. Using Refractometer, check freeze-point of each drum (tank or barrel) before installing into system c. Pump 2 drums (or equivalent amount from tank or barrel) of 35% Secondary Fluid into system d. Pump 1 drum (or equivalent amount from tank or barrel) of 100% Secondary Fluid into system

7 Initial Start-up Procedures e. Finish filling system with secondary fluid in as much the same way as when filling system with water i. Do not discard any secondary fluid any secondary fluid that is purged from system should be returned to the fill tank to be reinstalled into system f. Purge all air from system in much the same way as when the system was filled with water i. Note that any secondary fluid purged with the air is kept and can be returned to the system via the fill tank 10. Restart Pumps a. Verify that the pumps are full of fluid and all air has been removed b. Verify that the pump balance valves are completely (100%) open c. Start pumps one at a time checking amperage for each pump Note: if any of the pumps are over amperage, repeat step 7.e. d. From this point on, maintain a return pressure of 20 psig by adding secondary fluid as needed e. Start and run all pumps f. Allow fluid to circulate, maintaining a return pressure of 20 psig g. Check the freeze-point of the system fluid using the Refractometer Pump Amperage Pump #1 Nameplate Amp Pump #1 Actual Amp Pump #2 Nameplate Amp Pump #2 Actual Amp Pump #3 Nameplate Amp Pump #3 Actual Amp

8 Adding Fluid to System Final fluid freeze-point for system h. Cycle system switches so that each system is the only one turned on at a time for a period of 1 minute each to fully fill each coil i. Repeat checking the the freeze-point of the system fluid j. Turn on all systems and allow to circulate for 1 hour k. Check the fluid freeze point for the system once more i. If the freeze-point is too high use 100% design fluid to adjust when adding to system ii. If the freeze-point is too low use water to adjust when adding to system Adding Fluid to System Using Fill Tank Never add water to the system with the chillers on. 1. Add fluid to the fill tank making sure not to fill the tank above the overflow 2. Locate and slowly open the ball valve between the fill tank and the pump inlet line 3. Never let a pump pull air into the system through the fill tank 4. When a pump no longer pulls fluid from the fill tank, slowly close the pump return ball valve 5. If a return pressure of 20 psig cannot be obtained, shut off the other pumps and try again with only the pump running to which the fill system is connected 6. Always shut the ball valve between the fill tank and the pump inlet valve (referred to in step 2. above) when finished 7. Compensate for contraction as the system cools to operating temperature by adding more fluid

9 Balance Valve Setup Balance valves can be set using either a flow meter or any approved method from the valve manufacture refer to the the Hill PHOENIX Refrigeration Schedule to find the correct flow rates 1. Complete setting of balance valves Controls Strategy 1. Set pressure relief valve on pump skid to 75 psig 2. Differential pressure control a. Set for 5 psi differential and check for operation by shutting off pumps 3. Freeze-stat a. Verify thermal grease in probe well b. Set freeze-stat to turn off liquid line solenoid at 10 F with a 5 F dead band c. Verify freeze-stat operation by confirming that the Freeze-stat alarm light lock-on works correctly 4. Verify that the rack low pressure switches are set to pressure equivalent to 8 F 5. In the controller, verify that the Fluid Loss Alarm is set for when the return fluid pressure reaches < 10 psig 6. In the controller, verify that the Critical Fluid Loss Alarm (this setting is also to lock out the primary pump the one with the fill tank attached) is set for when the return fluid pressure reaches < 2 psig 7. Verify that all setpoints in the controller for case temperatures, alarms, defrost times and termination temperatures match the manufacturer s specifications Check off each of the next steps as you complete them. Balance valves set Pressure relief valve set Differential pressure control set Thermal grease in well Freeze-stat operational Low pressure switches set Fluid Loss Alarm entered Critical Fluid Loss Alarm entered All controller set-points match manufacturer s specs Balance Valve Setup & Control Strategy

10 Pump Strategy Target temperature F 8. Note any variations from manufacturer s specifications 9. Rack Floating use common supply fluid probe set for desired target temperature F with a pressure float of + 6 psi 10. Warm Fluid Defrost system a. Set master warm fluid balance valve to ½ of the flow of the largest system that requires warm fluid to a maximum of 12 gpm b. Operate hot gas line solenoid valve controlled from the warm fluid outlet probe i. cut-in 65 F ii. cut-out 75 F c. Set defrost differential valve to meet temperature requirements of largest gpm warm fluid defrost system 11. Pump Strategy a. Record the listed flow rates. 2 Pump control

11 A. 100% flow 2 pumps on psi differential B. 100% flow 1 pump on psi differential C. 90% flow 1 pump on psi differential D. 70% flow 2 pumps on psi differential i. C = pump on ii. D = pump off 3 Pump control A. 100% flow 3 pumps on psi differential B. 100% flow 2 pumps on psi differential C. 100% flow 1 pump on psi differential D. 90% flow 2 pumps on psi differential E. 75% flow 3 pumps on psi differential F. 70% flow 1 pump on psi differential G. 50% flow 2 pumps on psi differential i. average of D and F = pump on ii. average of E and G = pump off System Operation System Operation 1. Check high vents after a couple of days operation to check for any air trapped in system 2. Set superheat settings on Chiller TXVs i. 100% valve: 6 F ii. 60% valve: 10 F 3. Fine tune balance valves inside individual circuits, adjust to give equal discharge air temperatures 4. Fine tune system by finding the warmest fluid required to satisfy all cases

Second Nature Medium Temp Start-Up Valves Open Isolate pumps Isolate Expansion Tank Motors And Pumps Pump Model Motor HP Motor RPM Motor Amperage Pressure Test Water Flush Valves Open Fill With Water Vent System Pressurize With Water Run Pumps Check Rotation Check Amperage Cycle System Switches Drain Water Add Secondary Fluid Valves Open Fill With Propylene Glycol Check freeze-point Vent System Pressurize With Fluid Run Pumps Check Amperage Cycle System Switches Check Freeze-point 35% Propylene Glycol = 2ºF Set Balance Valves Set Controls Differential Pressure 5 psig Freeze-stat 10ºF Fluid Loss Alarm <10 psig Critical Fluid Loss <2 psig Pump Strategy Chiller TEV Control Warm Fluid Hot Gas 70ºF Start Rack Low Pressure Controls 8ºF TEV Superheat 100% valve 6ºF 60% valve 10ºF Record Settings Second Nature Start-Up Guide Send List to Hill PHOENIX

Hill PHOENIX Warranty Validation Checklist 13 This checklist provides space for confirming the settings, readings, and verifications you recorded in the guide. Sign and submit a copy of the completed checklist to Hill PHOENIX for validation of warranty coverage. Mail: Systems Operations 709 Sigman Rd. Conyers, GA 30013 Fax: 770.285.3085 Email: service@hillphoenix.com Or: your local Fleld Service Engineer 1. Pump skid serial number Contact Information Technician perfroming checks: Name: Phone: Email: 17. List variations from manufacturer specs Warranty Checklist 2. Pump #1 Nameplate Amps Actual Amps 3. Pump #2 Nameplate Amps Actual Amps 4. Pump #3 Nameplate Amps Actual Amps 5. Final fluid freeze-point of the system F 6. Balance valves confirmed set 7. Pressure relief valve on pump skid set to psig 8. Expansion tank precharge pressure psig 9. Differential pressure control set for psid 10. Thermal grease verified in probe well 11. Enter these values: Freeze-stat settings Chiller #1 Chiller #2 Off F F On F F 13. Fluid Loss Alarm set-point at psig 14. Critical Fluid Loss Alarm set-point at psig 15. Confirm pump lock-out operation 16. Verify all controller set-points match manufacturer s specs 18. Enter these differential pressure values: 100% flow 90% flow 75% flow 70% flow 50% flow 1 pump on 2 pumps on 3 pumps on 19. Enter these values: Chiller #1 Chiller #2 60% valve cut-in F F 60% valve cut-out F F 60% valve superheat F F 100% valve cut-in F F 100% valve cut-out F F 100% valve superheat F F 20. Hot gas line solenoid cut-in set-point F Hot gas line solenoid cut-out set-point F 21. Final supply fluid with all cases calling for (requiring) refrigeration psig Final return fluid with all cases calling for (requiring) refrigeration psig Signature: Date: