CONSTANT FLOW REGULATOR (CFR)

Size: px
Start display at page:

Download "CONSTANT FLOW REGULATOR (CFR)"

Transcription

1 CONSTANT FLOW REGULATOR (CFR) CFR991 GENERAL NOTES The Crane CFR991: Can be used in variable volume heating and chilled water systems. Has a double regulating feature, allowing the valve opening to be set with a 3mm Allen key. Is operated by means of the handwheel with position indicator or with recordable set position. Has a linear control characteristic across setting operating range. Has built-in Differential Pressure Control. Has a maximum working = 4 bar Has built in pressure test points to verify operational differential pressures. Fig.1 DN25 / DN32 Style (left) and DN40 / DN50 Style (right) LIMITS OF USE These valves have been categorised in accordance with the Pressure Equipment Directive 2014/68/EU. The fluid to be transported is limited to group 2 liquids i.e. non-hazardous. On no account must these valves be used on any group 1 liquids, group 1 gases, group 2 gases or unstable fluids. Note: Valves are classified as SEP (sound engineering practice) and as such cannot be CE marked and do not require a declaration of conformity.

2 INSTALLATION These instructions are issued as guidelines only and do not cover all installed conditions. If unsure please contact our Technical Helpline on , before installation. It is advised that the valve should be installed in a run of pipe of the same nominal size. Crane Fluid Systems products are designed for installation and use within suitably designed systems reflecting CIBSE, BSRIA and HVAC guidelines. Particular care should be taken with regards to; o Accessibility to valve for setting/adjustment o Tube cutting after cutting and threading, the end must be deburred or reamed before fitting to the valve. o Jointing no thread jointing materials must be allowed to protrude inside the bore. o Bracketing/supports the piping system shall provide suitable support and must be carefully aligned and at the correct distance between centres for the size and type of valve. Orientation: The CFR991 can be positioned in any orientation. Normally installed on return pipework, i.e. after the equipment it is controlling, but can be installed in flow if required. Ensure direction of flow is correct - indicated by an arrow on the valve body. CFR991 operates between a minimum and maximum pressure drop across the valve - see commissioning section on page 4. CFR s are not designed as isolation valves. Dedicated isolation valves should be installed to isolate against system pressure, i.e. for maintenance etc., when disconnecting/draining pipework. Care should be taken to not exceed maximum operating differential pressure, to prevent damage to the internal components. Systems should be installed with strainers to protect the CFR and other installed items. Straight lengths of pipework are not required for CFR s but some straight lengths are recommended to create a more stable flow pattern. FLUSHING Control valves, like the CFR, are sized to give good control over the system water, therefore, have been designed with a small convoluted flow path. These water ways may not allow adequate water velocities for flushing of the coil, even when fully open. Therefore, in line with BSRIA recommendations, it is recommended that a flushing point be located between the coil and the CFR. This allows the coil to be flushed without the water passing through the CFR. Please refer to BSRIA Guide BG for guidance. 02

3 VALVE SETTING INDICATOR CFR991 valves operate from closed to fully open with 4 complete turns of the handwheel. The Microset handwheel indicates the valve setting by means of digits appearing in outer (black) and inner (red) windows. The digit in the outer window indicates tenths of a turn. The example to the right shows a valve setting of 4-0 turns (fully open). REGULATION regulation is achieved by adjusting the valve setting until the required flow rate is obtained. The Microset handwheel will indicate the final valve setting. See table 1 on page 4 for flow rate setting. SETTING FACILITY The valve setting at which the required flowrate is achieved may be retained as follows: 1. Remove cap in centre of handwheel 2. Using the Allen key provided tighten the centre screw until it stops. Do not over-wench. 3. Replace centre cap in handwheel. The valve is now set and be adjusted and re-set to the original set point. PRESSURE TEMPERATURE RATING TEMPERATURE C -10 to 120 PRESSURE (BAR) 16 03

4 COMMISSIONING The CFR991 controls the flow rate depending on its set position, therefore, removing the need to measure the flow rate. The CFR991 maintains a constant differential pressure across its internal seat, any excess pressure being removed by the internal differential pressure controller. To ensure that sufficient pressure is available for the differential pressure controller to control the flow rate correctly, a differential pressure reading should be taken using the test points provided. When taking differential pressure readings, it is important that the system is running at full load, i.e. with CFR s set to design flow rate. This ensures that differential pressure readings are carried out in the most unfavourable conditions, guaranteeing optimum performance in normal running conditions. To ensure that all CFRs are working at the required differential pressure, it is necessary to check the least favoured / index CFR. By verifying the least favoured CFR is set correctly then all other CFRs must have a higher differential pressure. However, we would also recommend that a selection of other CFRs are tested along the circuit to verify this. H/W Setting DIFFERENTIAL PRESSURE REQUIREMENTS At each % setting option all sizes require a specific constant (Differential Pressure) to ensure the CFR is within its working range: Table 1 - CFR Setting Table % Opening FLOW RATE DN25 DN32 DN40 DN

5 For flow rates between settings, interpolation of position can be used. Please note that DN25 and DN32 test points measure the differential pressure across the seat, not overall pressure drop. Please note for the DN40 and DN50 the test points measure the overall differential pressure drop across the valve only. The pump speed should be set to ensure that the required differential pressure is always available. By setting the differential pressure across the least favoured CFR to the value stated in the above table, it ensures that minimum pump energy is used, therefore, reducing system running costs and CO2 emissions: DN25 & DN32 To set pump speed to achieve this: whilst measuring (across test points), increase pump speed until a constant is achieved, however please note that the typical value, as shown in the table above, can differ but in itself is not critical to operation. DN40 & DN50 To set pump speed to achieve this: whilst measuring (across test points), increase pump speed until a value greater than the minimum stated in the above table is achieved. As the measured is the total pressure drop across the PICV, the measured value will continue to rise as pump speed is increased. Any value above the minimum requirement will increase running costs, therefore, reducing system efficiency. The optimum setting is achieved when there is sufficient, but not excessive, pump pressure available. rate verification should be carried out using separate Measurement Devices (FMD) where fitted. In line with CIBSE & BSRIA recommendations, we recommend that as a minimum requirement, FMDs are installed in all branches. 05

6 CRANE HOUSE, EPSILON TERRACE, WEST ROAD, IPSWICH, SUFFOLK IP3 9FJ TELEPHONE: +44 (0) FAX: +44 (0) FM311 ISO 9001 Designed and manufactured under quality management systems in accordance with BS EN ISO 9001:2008 Every effort has been made to ensure that the information contained in this publication is accurate at the time of publishing. Crane Ltd assumes no responsibility or liability for typographical errors or omissions or for any misinterpretation of the information within the publication and reserves the right to change without notice. CFS_CFR_CFR991_1117 IOM_ R01_v1

PRESSURE INDEPENDENT CONTROL VALVE (PICV)

PRESSURE INDEPENDENT CONTROL VALVE (PICV) INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS PRESSURE INDEPENDENT CONTROL VALVE (PICV) D991 GENERAL NOTES OF SAFETY The Crane D991 PICV; can be used in variable volume heating and chilled water

More information

Pressure Independent Control Valve (PICV) Fig DN15-32

Pressure Independent Control Valve (PICV) Fig DN15-32 Installation and Operating Instructions Pressure Independent Control Valve (PICV) Fig. 1932 - DN15-32 GENERAL NOTES The Hattersley Fig.1932 PICV; can be used in variable volume heating and chilled water

More information

THERMOSTATIC MIXING VALVES

THERMOSTATIC MIXING VALVES THERMOSTATIC MIXING VALVES D1088 & D1089 INTRODUCTION Are self-acting Thermostatic Mixing Valves designed to blend hot and cold water, to ensure a constant, safe outlet temperature and prevent scalding.

More information

Issue 1. Air Valves OUR GENIUS IS FITTINGS.

Issue 1. Air Valves OUR GENIUS IS FITTINGS. Issue 1 Air Valves OUR GENIUS IS FITTINGS www.wadefittings.com PART NUMBERING SYSTEM An explanation of the Wade part numbering system: Series; 6000, 6100, 6200, 6300 & 6500 Safety Relief Valves Wade Safety

More information

Installation, Operating and Maintenance Instructions. V914 Cast Iron Flanged Swing Check Valve V914

Installation, Operating and Maintenance Instructions. V914 Cast Iron Flanged Swing Check Valve V914 Installation, Operating and Maintenance Instructions V914 Cast Iron Flanged Swing Check Valve V914 THE PRESSURE EQUIPMENT DIRECTIVE 97/23/EC and CE MARKING The Pressure Equipment Regulations 1999 (SI 1999/2001)

More information

Engineering Data Sheet

Engineering Data Sheet Page 1 of 6 CE MARKING AND THE PRESSURE EQUIPMENT DIRECTIVE 97/23/EC Valves must be installed into a well designed system and it is recommended that the system be inspected in accordance with the appropriate

More information

Cast iron swing check valve. BS EN 12334:2001 PN16

Cast iron swing check valve. BS EN 12334:2001 PN16 Cast iron swing check valve. BS EN 12334:2001 PN16 V914 Size Pattern No. Pack 1 Qty Pack 2 Qty Code Barcode Price ( ) ex VAT 65mm V914 1 0 15378 5022050079664 223.32 80mm V914 1 0 15379 5022050079824 247.60

More information

GN 2 CONSTANT FLOW REGULATORS. GUIDANCE NOTE GN 2 Constant Flow Regulators. Page 1 COMMISSIONING SPECIALISTS ASSOCIATION.

GN 2 CONSTANT FLOW REGULATORS. GUIDANCE NOTE GN 2 Constant Flow Regulators. Page 1 COMMISSIONING SPECIALISTS ASSOCIATION. GUIDANCE NOTE GN 2 Constant Flow Regulators Page 1 2017 Edition GUIDANCE NOTE GN2 CONSTANT FLOW REGULATORS Written By M. Lowe, Hattersley Newman Hender Ltd COMPILED BY THE TECHNICAL SUB-COMMITTEE OF THE

More information

Issue 1. Tubing OUR GENIUS IS FITTINGS.

Issue 1. Tubing OUR GENIUS IS FITTINGS. Issue 1 Tubing OUR GENIUS IS FITTINGS www.wadefittings.com Tubing NYLON TUBE NYLON TUBE -FEATURES & BENEFITS Wade Nylon Tube is manufactured and produced from raw material and by process and quality control

More information

Ductile iron gate valve PN16. BS EN 1171:2002 PN16

Ductile iron gate valve PN16. BS EN 1171:2002 PN16 gate valve PN16. BS EN 1171:2002 PN16 V950 Gate valve Size Pattern No. Pack 1 Qty Pack 2 Qty Code Barcode Price ( ) ex VAT DN50 V950 1 0 15510 5022050210906 233.60 DN65 V950 1 0 15511 5022050211262 233.60

More information

Forged stainless steel ASTM A182 F316

Forged stainless steel ASTM A182 F316 MADE OF STAINLESS... Certificate 3.1 Size : Ends : Min Temperature : Max Temperature : DN 8 to 25 (NPS 1/4" to 1") Female - Female NPT - 29 C + 538 C Max Pressure : 138 Bars (Class 800) Specifications

More information

Size : Ends : Min Temperature : Max Temperature : Materials : Cast iron body

Size : Ends : Min Temperature : Max Temperature : Materials : Cast iron body Size : Ends : Min Temperature : Max Temperature : DN 15 to DN 400 Flanges GN10/16-10 C + 120 C Max Pressure : 16 Bars up to DN 200 ( 10 bars over ) Specifications : Removable stainless steel filter Bolted

More information

Materials : Forged carbon steel A105N

Materials : Forged carbon steel A105N Certificate 3.1 Size : Ends : Min Temperature : Max Temperature : DN 1/4" to 2 Female - Female BSP or NPT, Socket Welding - 29 C + 425 C Max Pressure : 136 Bars (Class 800) Specifications : With draining

More information

Materials : Forged carbon steel A105N

Materials : Forged carbon steel A105N Size : Ends : Min Temperature : Max Temperature : DN 15 to 50 (NPS 1/2" to 2") Socket Welding -29 C + 425 C Max Pressure : 250 Bars (Class 1500) Specifications : Rising stem (OS&Y) Welded bonnet Full bore

More information

Installation Guide - C01202 & C01203 Thermostatic Mixing Valve TMV2

Installation Guide - C01202 & C01203 Thermostatic Mixing Valve TMV2 The following information is required for use when the Saracen range of thermostatic mixing valves is used in a TMV2 Applications under the requirements of BS EN 1111: 1999 Sanitary tap ware Thermostatic

More information

DN 1/2" to 2" Female BSP + 0 C C Max Pressure : 16 Bars Specifications : Stainless steel removable filter Female / Female With draining valve

DN 1/2 to 2 Female BSP + 0 C C Max Pressure : 16 Bars Specifications : Stainless steel removable filter Female / Female With draining valve Size : Ends : Min Temperature : Max Temperature : DN 1/2" to 2" Female BSP + 0 C + 120 C Max Pressure : 16 Bars Specifications : Stainless steel removable filter Female / Female With draining valve Materials

More information

CLASS TLP Pressure Reducing Valve

CLASS TLP Pressure Reducing Valve CLASS TLP Pressure Reducing Valve CLASS TLP Direct Acting Pressure Reducing Valve The Class TLP balanced direct acting pressure regulator is designed for use on installations that have varying inlet pressures

More information

Thermostatic Mixing Valves 61022CPB & 61028CPB Intamix Pro V

Thermostatic Mixing Valves 61022CPB & 61028CPB Intamix Pro V Thermostatic Mixing Valves 61022CPB & 61028CPB Intamix Pro V Installation and Maintenance Instructions 2 1 MIN MAX 7 In this procedure document we have endeavoured to make the information as accurate as

More information

Installation Operation Maintenance

Installation Operation Maintenance 682 Seal Cooler New generation seal cooler to meet and exceed the seal cooler requirements stated in the 4th Edition of API Standard 682 Installation Operation Maintenance Experience In Motion Description

More information

DN 3/8" to 4" Female BSP - 10 C C Max Pressure : 16 Bars up to DN 2 Specifications : Removable stainless steel filter Female / Female

DN 3/8 to 4 Female BSP - 10 C C Max Pressure : 16 Bars up to DN 2 Specifications : Removable stainless steel filter Female / Female Size : Ends : Min Temperature : Max Temperature : DN 3/8" to 4" Female BSP - 10 C + 120 C Max Pressure : 16 Bars up to DN 2 Specifications : Removable stainless steel filter Female / Female Materials :

More information

differential pressure regulating valve - threaded

differential pressure regulating valve - threaded 140-142 differential pressure regulating valve - threaded Introduction Differential pressure regulating valves (DPRV) maintain the differential pressure across a circuit or sub-branch at a set differential

More information

DN 1/2" to 2 Female - Female BSP - 20 C C Max Pressure : 16 Bars Specifications : Rotating non rising stem Inside screw stem Full bore

DN 1/2 to 2 Female - Female BSP - 20 C C Max Pressure : 16 Bars Specifications : Rotating non rising stem Inside screw stem Full bore Size : Ends : Min Temperature : Max Temperature : DN 1/2" to 2 Female - Female BSP - 20 C + 180 C Max Pressure : 16 Bars Specifications : Rotating non rising stem Inside screw stem Full bore Materials

More information

Materials : Stainless steel ASTM A351 CF8M

Materials : Stainless steel ASTM A351 CF8M Certificat 3.1 Size: Ends : Min Temperature : Max Temperature : DN 15 to DN 200 PN16 Flanges R.F. - 20 C + 200 C Max Pressure : 16 Bars Specifiations : Removable stainless steel filter Bolted bonnet with

More information

MZX. Three-Port Seat Valves SPECIFICIATIONS AND GUIDE TO SELECTION

MZX. Three-Port Seat Valves SPECIFICIATIONS AND GUIDE TO SELECTION 01 These seat valves are of globe construction with a linear moving spindle and a modified parabolic characterised plug operating against the upper seat which controls flow quantity to suit the load. The

More information

Two-port valves, male threaded, PN25

Two-port valves, male threaded, PN25 4 379 Two-port valves, male threaded, PN25 VVG55... Two-port valves, externally threaded, PN25 Bronze Rg5 DN15... 25 mm (½"... 1") k vs 0.25... 6.3 m 3 /h Stroke 5.5 mm Suitable for type SQS35... or SQS65...

More information

Differential Pressure Control Valve (DPCV)

Differential Pressure Control Valve (DPCV) Differential Pressure Control Valve (DPCV) PATENTED Technical Data and Installation Instructions Page 1 V2 The modulating valves ART 241 balance and control the differential pressure (DPCV) automatically

More information

Product Sheet Pre-Fabricated Flushing Bypass Assembly for Terminal Applications Mini-Flush 40

Product Sheet Pre-Fabricated Flushing Bypass Assembly for Terminal Applications Mini-Flush 40 Product Sheet Pre-Fabricated Flushing Bypass Assembly for Terminal Applications Mini-Flush 40 Description Miniflush 40 is a pre-fabricated, flushing bypass arrangement for balance, control, isolation,

More information

SCA Series Inverted Bucket Steam Traps

SCA Series Inverted Bucket Steam Traps 0770050/5 IM-P077-06 ST Issue 5 SCA Series Inverted Bucket Steam Traps Installation and Maintenance Instructions 1. General safety information 2. General product information 3. Installation 4. Commissioning

More information

STAG. Balancing valves Balancing valve with grooved ends DN

STAG. Balancing valves Balancing valve with grooved ends DN STAG Balancing valves Balancing valve with grooved ends DN 65-300 IMI TA / Balancing valves / STAG STAG A grooved end, ductile iron balancing valve that delivers accurate hydronic performance in an impressive

More information

Intamix Thermostatic Mixing Valve

Intamix Thermostatic Mixing Valve Intamix Thermostatic Mixing Valve TMV2 & TMV3 Installation Guide Intatec Ltd Airfield Industrial Estate Hixon Staffordshire ST18 0PF In this procedure document we have endeavoured to make the information

More information

Versions. Benefits. Balancing DN15-32 DN40 DN50 DN15, DN20, DN25, DN32, DN40, DN50. Dimensions

Versions. Benefits. Balancing DN15-32 DN40 DN50 DN15, DN20, DN25, DN32, DN40, DN50. Dimensions Ballorex Delta Description The Ballorex Delta is a differential pressure control valve used in hydronic heating or cooling systems. By ensuring a constant differential pressure across motorized or static

More information

FloCon Commissioning Modules DESIGN GUIDE - JUNE Variable Flow Systems & Solutions brought to you by Hurlstones

FloCon Commissioning Modules DESIGN GUIDE - JUNE Variable Flow Systems &   Solutions brought to you by Hurlstones DESIGN GUIDE - JUNE 2008 Variable Flow Systems & FloCon Commissioning Modules Patent No. GB2 376 066B www.savmodules.com Solutions brought to you by Hurlstones CONTENTS Page 1. INTRODUCTION 3 2. BENEFITS

More information

k valve 2 (50)HF 2½ (65)SF installation guide aylesbury For valve sizes (DN): tel fax

k valve 2 (50)HF 2½ (65)SF installation guide aylesbury For valve sizes (DN): tel fax aylesbury k valve installation guide For valve sizes (DN): 2 (50)HF 2½ (65)SF 3 (80)RB IMPORTANT Please keep for future reference. PLEASE READ THESE INSTRUCTIONS CAREFULLY AND REFER TO ANY DIAGRAMS BEFORE

More information

Materials : Forged carbon steel A350 LF2

Materials : Forged carbon steel A350 LF2 Size : Ends : Min Temperature : Max Temperature : DN 15 to 50 (NPS 1/2" to 2") Female - Female NPT, Socket Welding - 46 C + 425 C Max Pressure : 250 Bars (Class 1500) Specifications : Rising rotating stem

More information

2-port and 3-port valves PN 16

2-port and 3-port valves PN 16 OEM 2-port valves VVP459.10-0.63 to VVP459.25-6.3 3-port valves VXP459.10-0.63 to VXP459.25-6.3 3-port valves with bypass VMP459.10-0.63 to VMP459.20-4 2-port valves VVP459.25-6.3 to VVP459.40-25 3-port

More information

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions

KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions 4059051/3 IM-P405-48 EMM Issue 3 KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4.

More information

Union joints 23. Fulfilling Solutions Through Knowledge

Union joints 23. Fulfilling Solutions Through Knowledge 06 08 08 08 10 12 13 14 14 16 18 19 19 19 22 23 Union joints 23 23 23 24 24 24 Fulfilling Solutions Through Knowledge 25 25 26 26 26 27 28 29 29 29 30 30 30 32 32 32 32 32 37 37 38 Further reading 39 Diagram

More information

C 10 Pressure Reducing Valve

C 10 Pressure Reducing Valve C 10 Pressure Reducing Valve C 10 Direct Acting Pressure Reducing Valve The C10 balanced pressure reducing valve range is designed for use on water/air (gas) applications and for installations which have

More information

Pilot Operated Pressure Reducing Valve

Pilot Operated Pressure Reducing Valve OPTIONS: USE: Pilot Operated Pressure Reducing Valve Steam & Compressed Air PRV 37 (DN15-DN50) DESCRIPTION The ADCA PRV37 pilot operated pressure reducing valves are designed for use on steam, compressed

More information

Materials : Carbon steel ASTM A216 WCB

Materials : Carbon steel ASTM A216 WCB Certificate 3.1 Size : Ends : Min Temperature : Max Temperature : DN 50 to DN 400 ( NPS 2" to 16" ) Flanges R.F. Class 150 (PN20) - 29 C + 425 C Max Pressure : 20 Bars Specifications : Removable stainless

More information

Size : Ends : Min Temperature : Max Temperature : Materials : Cast iron body

Size : Ends : Min Temperature : Max Temperature : Materials : Cast iron body Size : Ends : Min Temperature : Max Temperature : DN 40 to DN 300 Flanges R.F. PN10/16-10 C + 80 C Max Pressure : 16 Bars up to DN200 Specifications : Removable stainless steel filter Bolted bonnet with

More information

Electronic Commissioning Unit. Instructions

Electronic Commissioning Unit. Instructions Electronic Commissioning Unit Instructions 1. The Comdronic AC6 Electronic Commissioning Unit 2. Health and Safety 3. Description of Unit 4. Connection and Set-up Procedure 5. Menu System a. Main Menu

More information

BSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions

BSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions 1843950/3 IM-P184-03 ST Issue 3 BSA6T and BSA64T Stainless Steel Bellows Sealed Stop Valves Installation and Maintenance Instructions 1. General safety information 2. General product information 3. Installation

More information

3-port seat valves with externally threaded connection, PN 16

3-port seat valves with externally threaded connection, PN 16 4 463 Acvatix 3-port seat valves with externally threaded connection, PN 16 VXG41.. ronze CuSn5Zn5Pb2 valve body DN 15 50 k vs 1.6 40 m 3 /h Flat sealing connections with external thread G to ISO 228-1

More information

Automatic balancing valves

Automatic balancing valves Automatic balancing valves ASV DN 15-50 (4th gen.) ASV-PV ASV-BD ASV-M DN 15-50 DN 15-50 DN 15-50 Description ASV whiteboard animation ASV valves are automatic balancing valves. Together with Danfoss presetting

More information

Combination Air Valve

Combination Air Valve Combination Air Valve For Sewage and Wastewater Model C50 Installation, Operation and Maintenance Manual (IOM) Table of Contents General... Page 2 Safety... Page 2 Operational Data... Page 3 Materials

More information

2-port seat valves PN25 with externally threaded connections

2-port seat valves PN25 with externally threaded connections 4 379 2-port seat valves PN25 with externally threaded connections VVG55.. Valve body bronze CC491K (Rg5) DN 15...25 (½...1 ") kvs 0.25...6.3 m3/h Stroke 5.5 mm Sets of ALG.. with threaded and ALS.. with

More information

Installation Instructions and User Guide 15mm & 22mm Thermostatic Mixing Valve

Installation Instructions and User Guide 15mm & 22mm Thermostatic Mixing Valve Installation Instructions and User Guide 15mm & 22mm Thermostatic Mixing Valve TMV3 / TMV2 Combined Valve C85079 C85081 C85080 C85082 It is important that these guidance notes are read and fully understood

More information

Combination Air Valve Model

Combination Air Valve Model Combination Air Valve Model Model C10 /C11 Installation, Operation and Maintenance Manual (IOM) Table of Contents General...Page 2 Safety...Page 2 Operational Data...Page 3 Materials and Connections...Page

More information

KBV21i and KBV40i Air Actuated Boiler Blowdown Valves

KBV21i and KBV40i Air Actuated Boiler Blowdown Valves 4059051/1 IM-P405-48 AB Issue 1 KBV21i and KBV40i Air Actuated Boiler Blowdown Valves Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning

More information

STAD. Balancing valves DN (MD60, MD61, MD62)

STAD. Balancing valves DN (MD60, MD61, MD62) STAD Balancing valves DN 15-50 (MD60, MD61, MD62) IMI TA / Balancing valves / STAD STAD The STAD balancing valve delivers accurate hydronic performance in an impressive range of applications. Ideally suited

More information

3-PIECE BALL VALVE, 3600 PSI/ PN 248, WITH ISO DIRECT MOUNTING PAD 306M SERIES/ PED Category II

3-PIECE BALL VALVE, 3600 PSI/ PN 248, WITH ISO DIRECT MOUNTING PAD 306M SERIES/ PED Category II 3-PIECE BALL VALVE, 3600 PSI/ PN 248, WITH ISO DIRECT MOUNTING PAD 306M SERIES/ PED Category II 306M User Manual English Version Use for company in Europe who will place the product on the market, please

More information

k valve ½ (15) ¾ (20) 1 (25) 1¼ (32) 1½ (40)HF 2 (50)SF installation guide aylesbury For valve sizes (DN):

k valve ½ (15) ¾ (20) 1 (25) 1¼ (32) 1½ (40)HF 2 (50)SF installation guide aylesbury For valve sizes (DN): aylesbury k valve installation guide For valve sizes (DN): ½ (15) ¾ (20) 1 (25) 1¼ (32) 1½ (40)HF 2 (50)SF IMPORTANT Please keep for future reference. PLEASE READ THESE INSTRUCTIONS CAREFULLY AND REFER

More information

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25 Self-operated Pressure Regulators Differential Pressure Regulators (opening) Type 42-20 Type 42-25 Type 42-20 Differential Pressure Regulator Type 42-25 Differential Pressure Regulator Mounting and Operating

More information

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions 6250250/1 IM-P625-03 ST Issue 1 USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions 1. General safety information 2. General product information

More information

KAX VALVE ¾ (20) 1 (25) 1¼ (32) 1½ (40)HF 2 (50)SF INSTALLATION GUIDE AYLESBURY FOR VALVE SIZES (DN):

KAX VALVE ¾ (20) 1 (25) 1¼ (32) 1½ (40)HF 2 (50)SF INSTALLATION GUIDE AYLESBURY FOR VALVE SIZES (DN): AYLESBURY KAX VALVE INSTALLATION GUIDE FOR VALVE SIZES (DN): ¾ (20) 1 (25) 1¼ (32) 1½ (40)HF 2 (50)SF IMPORTANT PLEASE KEEP FOR FUTURE REFERENCE. PLEASE READ THESE INSTRUCTIONS CAREFULLY AND REFER TO ANY

More information

Automatic Balancing Valve Pressure difference controller with integrated flow limiter AB-PM DN

Automatic Balancing Valve Pressure difference controller with integrated flow limiter AB-PM DN Data sheet Automatic Balancing Valve Pressure difference controller with integrated flow limiter AB-PM DN 40-100 Description AB-PM is ideal for staged installation and commissioning AB-PM is a combined

More information

Materials : Forged carbon steel A105N

Materials : Forged carbon steel A105N Certificate 3.1 Size : Ends : Min Temperature : Max Temperature : DN 15 to 50 (NPS 1/2" to 2") Flanges RF CLASS 150 (PN20) - 29 C + 425 C Max Pressure : 20 Bars Specifications : Rising non rotating stem

More information

CRP INSTALLATION, OPERATING AND MAINTENANCE INFORMATION FOR INLINE SAMPLING VALVES

CRP INSTALLATION, OPERATING AND MAINTENANCE INFORMATION FOR INLINE SAMPLING VALVES CRP INSTALLATION, OPERATING AND MAINTENANCE INFORMATION FOR INLINE SAMPLING VALVES Sampling Valves Installation Commissioning and Operating Instructions SD IL 300 & SD IL 400 Inline Sampling Valve This

More information

Installation, Operation and Maintenance Instructions Buffer Vessel OM006

Installation, Operation and Maintenance Instructions Buffer Vessel OM006 Installation, Operation and Maintenance Instructions Buffer Vessel OM006 Calorifiers Heat Exchangers Pressurisation Units Sales Tel: 01457 835700 Sales Fax: 01457 832700 E-mail: sales@gmsthermal.co.uk

More information

SHHP50 FLOOR STANDING HYDRAULIC PRESS

SHHP50 FLOOR STANDING HYDRAULIC PRESS SHHP50 FLOOR STANDING HYDRAULIC PRESS OWNER S MANUAL FOR YOUR SAFETY PLEASE READ THESE INSTRUCTIONS CAREFULLY AND RETAIN THEM FOR FUTURE USE. SPECIFICATION MAX CAPACITY STROKE WORK RANGE WEIGHT 50 TON

More information

Deluge Optimo Shower valve and kit 10032CP

Deluge Optimo Shower valve and kit 10032CP Deluge Optimo Shower valve and kit 10032CP Installation, Operation and Maintenance Please leave these instructions with the user Intatec Limited Airfield Industrial Estate, Hixon, Staffordshire, ST18 0PF

More information

Brass full bore gate valve with lockshield. Compression ends to EN 1254/2, PN16

Brass full bore gate valve with lockshield. Compression ends to EN 1254/2, PN16 Brass full bore gate valve with lockshield. Compression ends to EN 1254/2, PN16 63LS Gate valve Size Pattern No. Pack 1 Qty Pack 2 Qty Code Barcode Price ( ) ex VAT 15mm 63LS 10 0 506037 5013866016103

More information

DS MZ, MZF, MJF THREE-PORT SEAT VALVES

DS MZ, MZF, MJF THREE-PORT SEAT VALVES DS 4.610 11/99, F, THREE-PORT SEAT VALVES Specification No. 626-3-XXX These seat valves are of 'globe' construction with a linear moving spindle and a modified parabolic characterised plug operating against

More information

HORNE 20 THERMOSTATIC MIXING VALVE TYPE H-2003

HORNE 20 THERMOSTATIC MIXING VALVE TYPE H-2003 PO Box 7, Rankine Street Johnstone, Renfrewshire Scotland. PA5 8BD Tel: 01505 321 455 Fax: 01505 336 287 Email: technical@horne.co.uk Web: www.horne.co.uk HORNE 20 THERMOSTATIC MIXING VALVE TYPE H-2003

More information

SEQUENTIAL SHOWER VALVE INSTRUCTION MANUAL PLEASE LEAVE THIS MANUAL WITH THE END USER

SEQUENTIAL SHOWER VALVE INSTRUCTION MANUAL PLEASE LEAVE THIS MANUAL WITH THE END USER SEQUENTIAL SHOWER VALVE INSTRUCTION MANUAL PLEASE LEAVE THIS MANUAL WITH THE END USER CONTENTS 1. INTRODUCTION & SAFETY 1 2. DIMENSIONS 2 3. TECHNICAL DATA 3 4. OPERATION 4 5. COMPONENTS 5 6. SITE INSTALLATION

More information

Pressure Independent Control Series

Pressure Independent Control Series Document No. 155-522 Pressure Independent Control Series Two-Way Cast Iron Flanged Bodies, ANSI 125 and 250 Description Siemens Pressure Independent Control Valves integrate three functions into a single

More information

Mainsboost Installation, Operation & Maintenance Instructions

Mainsboost Installation, Operation & Maintenance Instructions mainsboost Mainsboost Installation, Operation & Maintenance Instructions Please leave this instruction booklet with the home owner as it contains important guarantee, maintenance and safety information

More information

STAD Series. Balancing and control valves. Technical Data Sheet. WattsIndustries.com

STAD Series. Balancing and control valves. Technical Data Sheet. WattsIndustries.com STAD Series Balancing and control valves Technical Data Sheet WattsIndustries.com Description STAD Series variable-orifice threaded valves are designed for flow control and monitoring in climate control

More information

130400A 1/2 NPT Female A 3/4 NPT Female A 1 NPT Female A 1 1/4 NPT Female A 1 1/2 NPT Female A 2 NPT Female

130400A 1/2 NPT Female A 3/4 NPT Female A 1 NPT Female A 1 1/4 NPT Female A 1 1/2 NPT Female A 2 NPT Female 88.0A www.caleffi.com Venturi Style Balancing Valve Copyright 0 Caleffi 0 Series Function Product Range Balancing valves are hydraulic devices that can precisely control the flow rate of the fluid that

More information

Bermad Pressure Reducing. Model: 42T

Bermad Pressure Reducing. Model: 42T Bermad Pressure Reducing Pilot Operated Pressure Control Valve Model: 42T Installation Operation Maintenance Manual (IOM) REV. 27.7.17 Page 1 of 12 Safety First BERMAD believes that the safety of personnel

More information

2-Port Seat Valves with Flange, PN 16

2-Port Seat Valves with Flange, PN 16 4 45 2-Port Seat Valves with Flange, PN 6 VVF45... dular cast iron EN-GJS-400-5 valve body DN 50...50 k vs 9...00 m /h Can be equipped with SKB...- or SKC...- electrohydraulic actuators Use For use in

More information

HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions

HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions 0670350/4 IM-S03-11 ST Issue 4 HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions 1. Safety information 2. General product information HM Series 3. Installation 4. Commissioning

More information

STAD-D. Balancing valves Balancing valve for domestic water systems, DN Balancing valves

STAD-D. Balancing valves Balancing valve for domestic water systems, DN Balancing valves STAD-D Balancing valves Balancing valve for domestic water systems, DN 15-50 Balancing valves IMI TA / Balancing valves / STAD-D STAD-D The STAD-D balancing valve delivers accurate hydronic performance

More information

KTM 50 (DN ) Installation, maintenance and operating instructions

KTM 50 (DN ) Installation, maintenance and operating instructions 52 762-306 09.2014 KTM 50 (DN 100-200) Installation, maintenance and operating instructions General High-performing and compact, these pressure-independent control valves for variable flow heating and

More information

bathrooms.com Concentric Thermostatic Shower Mixers Cleaning and Care Installation Manual Contents

bathrooms.com Concentric Thermostatic Shower Mixers Cleaning and Care Installation Manual Contents bathrooms.com Concentric Thermostatic Shower Mixers Contents Page 3 - General Information & Safety Page 4 - Installation Page 5 - Concentric Valve Set-up Page 6 - Exposed fitting of Concentric Mixer Valves

More information

Size : Connection Ends : Min Temperature : Max Temperature : Materials : Cast iron body

Size : Connection Ends : Min Temperature : Max Temperature : Materials : Cast iron body Size : Connection Ends : Min Temperature : Max Temperature : DN 50 to 200 Flanged ISO PN 10/16 ( ISO PN16 for DN200 ) 0 C + 50 C Max Pressure : 16 Bars Specifications : Tangential type Dry dial Magnetic

More information

Serie 06-M6. Swing wafer check valve. made in. Application fields. Check valves E U R O P E WATER CONDITIONING INDUSTRY

Serie 06-M6. Swing wafer check valve. made in. Application fields. Check valves E U R O P E WATER CONDITIONING INDUSTRY Swing wafer check valve BRANDONI made in E U R O P E Application fields WATER CONDITIONING INDUSTRY HEATING 38 www.brandoni.it The valves in series 06 are swing wafer check valves, manufactured in accordance

More information

PV4 and PV6 Piston Valves

PV4 and PV6 Piston Valves 1181250/1 IM-P118-05 ST Issue 1 PV4 and PV6 Piston Valves Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning 5. Operation 6.

More information

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

INSTALLATION, OPERATION AND MAINTENANCE GUIDE INSTALLATION, OPERATION AND Placement in Pipeline System When installing Process Development & Control s ElastoTITE Elastomer-Hinged Check Valves in a pipeline, a minimum of five pipe diameters should

More information

HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS

HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS Page 1 of 20 Page 2 of 20 TABLE OF CONTENTS Safety Warnings

More information

INSTRUCTION MANUAL. process. Ultrasonic Flowmeter Range

INSTRUCTION MANUAL. process. Ultrasonic Flowmeter Range INSTRUCTION MANUAL process TM Ultrasonic Flowmeter Range process TM CONTENTS Page No 1 General 4 2 Order Codes 4 3 Installation 5 & 6 4 Specifications 7 & 8 1 General 3 Installation The Process Atrato

More information

A3S Bellows Sealed Stop Valve Installation and Maintenance Instructions

A3S Bellows Sealed Stop Valve Installation and Maintenance Instructions 1326050/3 IM-P132-11 ST Issue 3 A3S Bellows Sealed Stop Valve Installation and Maintenance Instructions 1 General safety information 2 General product information 3 Installation 4 Commissioning 5 Operation

More information

M111 Spiraflo Transducer

M111 Spiraflo Transducer 3309551/ 7 IM-P330-38 MI Issue 7 M111 Spiraflo Transducer Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Technical data 4. Mechanical installation: M111

More information

Installation, Operation and Maintenance Instructions for Mild Steel Buffer Vessel

Installation, Operation and Maintenance Instructions for Mild Steel Buffer Vessel OM006 Installation, Operation and Maintenance Instructions for Mild Steel Buffer Vessel The operating and maintenance instructions contained within this package are for standard mild steel buffer vessels

More information

Installation Instructions and User Guide

Installation Instructions and User Guide Installation Instructions and User Guide 15mm & 22mm In-Line Thermostatic Mixing Valve-TMV2 Model P404 It is important that these guidance notes are read and fully understood prior to product installation

More information

TA-FUSION-P. Combined control & balancing valves Pressure independent combined balancing and control valves with independent EQM characteristics

TA-FUSION-P. Combined control & balancing valves Pressure independent combined balancing and control valves with independent EQM characteristics TA-FUSION-P Combined control & balancing valves Pressure independent combined balancing and control valves with independent EQM characteristics IMI TA / Control valves / TA-FUSION-P TA-FUSION-P These innovative

More information

776 Cryogenic Safety Valve

776 Cryogenic Safety Valve 776 Cryogenic Safety Valve INTRODUCTION 776 Cryogenic Safety Valve The effects of exceeding safe pressure levels in an unprotected pressure vessel or system, can have catastrophic effects on both plant

More information

STAINLESS STEEL LOW PRESSURE REDUCING VALVE LPRV ELITE

STAINLESS STEEL LOW PRESSURE REDUCING VALVE LPRV ELITE MAIN CHARACTERISTICS The stainless steel LPRV elite low pressure reducer is intended for the pressure reduction of the fluids such as water, air, clear liquids not in charge of and the compatible gases

More information

2-Port Seat Valves with Flange, PN 16

2-Port Seat Valves with Flange, PN 16 4 40 2-Port Seat Valves with Flange, PN 6 VVF4... Grey cast iron EN-GJL-250 valve body DN 50...50 k vs 9...00 m /h Can be equipped with SQX- electromotoric or SKD...-, SKB...- or SKC...- electrohydraulic

More information

Tempering valve for solar and instantaneous applications Installation, commissioning and servicing instructions 2522HP series

Tempering valve for solar and instantaneous applications Installation, commissioning and servicing instructions 2522HP series www.reece.com.au 28255.01 Tempering valve for solar and instantaneous applications 2522HP series Installation, commissioning and servicing instructions The tempering valve is used to regulate the set temperature

More information

USER MANUAL Version: 1/2017

USER MANUAL Version: 1/2017 ZETKAMA Sp. z o.o. ul. 3 Maja 12 PL 57-410 Ścinawka Średnia DIFREN PRESSURE REGULATING VALVE USER MANUAL Version: 1/2017 Fig. 223 Data: 01.01.2017 TABLE OF CONTENS 1. Product description 2. Requirements

More information

Model: 43T. Bermad Pressure Relief Valve

Model: 43T. Bermad Pressure Relief Valve Model: 43T Bermad Pressure Relief Valve Installation Operation Maintenance Manual () Rev.C1_01.08.17 Page 1 of 10 Safety First BERMAD believes that the safety of personnel working with and around our equipment

More information

Automatic balancing valves ASV

Automatic balancing valves ASV Automatic balancing valves ASV ASV-P ASV-PV ASV-PV ASV-PV ASV-I ASV-M 15-40 15-40 50 65-100 15-50 15-50 Description / Application ASV balancing valves are used for dynamic hydronic balance in heating and

More information

Installation, Operation and Maintenance Instructions for Direct Hot Water Storage Vessels

Installation, Operation and Maintenance Instructions for Direct Hot Water Storage Vessels OM003 Installation, Operation and Maintenance Instructions for Direct Hot Water Storage Vessels The operating and maintenance instructions contained within this package are for standard storage vessels

More information

GUIDANCE IN-SERVICE INSPECTION PROCEDURES

GUIDANCE IN-SERVICE INSPECTION PROCEDURES GUIDANCE IN-SERVICE INSPECTION PROCEDURES Number: PEC 13 Prepared by: Pressure Equipment Committee (TC1) Status: Issue: 07 Date: 16 th January 2018 Reference: Guidance for safety valve examination. SITUATION:

More information

Materials : Electro galvanized steel flanges

Materials : Electro galvanized steel flanges Size : Ends : Min Temperature : Max Temperature : DN 32 to 600 Flanges PN10/16-10 C + 100 C for EPDM and + 80 C for NBR Max Pressure : 16 Bars up to DN 300 Specifications : Absorb vibrations and noises

More information

M03 WUNDATRADE. Heat Pump Manifold. Before you start: Check the contents. Optional. ...a division of WUNDA GROUP PLC

M03 WUNDATRADE. Heat Pump Manifold. Before you start:  Check the contents. Optional. ...a division of WUNDA GROUP PLC Before you start: Check the manifold box contents against the list below. Check the contents Flow gauges 1. Bar assembly with manual return valves 2. 2 x Auto air vent & drain hose attachments Optional

More information

Type Operating Instructions. 2/2-way solenoid valve 2/2-Wege Magnetventil Electrovanne 2/2 voies.

Type Operating Instructions. 2/2-way solenoid valve 2/2-Wege Magnetventil Electrovanne 2/2 voies. 2/2-way solenoid valve 2/2-Wege Magnetventil Electrovanne 2/2 voies We reserve the right to make technical changes without notice. Technische Änderungen vorbehalten. Sous réserve de modifications techniques.

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS Part No. IS275 Rev A- 09584-09584 TM HeatGuard INSTALLATION INSTRUCTIONS Certified Product Australian Standard AS4032.2 Lic. No. 1593 SAI-Global CONTENTS Choosing the correct model......... 3 How to install

More information