FOGEX HIGH-PRESSURE WATER MIST CYLINDER SYSTEMS

Size: px
Start display at page:

Download "FOGEX HIGH-PRESSURE WATER MIST CYLINDER SYSTEMS"

Transcription

1 Manual FOGEX HIGH-PRESSURE WATER MIST CYLINDER SYSTEMS User Guide Issue 1 October 2004 Assessed to ISO 9001: 2000 Certificate number 018

2 Chapter 2 Safety and Environmental Considerations Safety is of paramount importance. No-one should interfere or operate water mist systems without the proper training and instruction. All personnel who are assigned to maintain and operate the equipment should be properly trained. Water Mist (Fire) Technologies Ltd recommends that all personnel involved in such activities are accredited by Water Mist (Fire) Technologies Ltd and are in possession of the relevant IOSH Safety Passport or CSCS Skills Card. All personnel working in an enclosure protected by a water mist system should be warned of any and all dangers associated with such. Personnel in the protected area should be trained in the modes of actuation in case of fire and system activation. All personnel operating on the system should wear the appropriate PPE (Personal Protective Equipment), which should include as a minimum safety boots and goggles. As a safety measure, the protection cap supplied with the cylinders must always be fitted when the cylinder is being transported. During maintenance or building works that could activate the water mist system, e.g. dust in a detector, the system should be isolated or disconnected. Human safety relating to the deployment of water mist in manned areas has been addressed by the US Environmental Protection Agency (E.P.A). The overall conclusion was that water mist using potable water is safe for use in occupied areas. Areas protected by a water mist system should be evacuated in the event of a fire alarm, not because of the application of mist itself but in order to prevent harm to personnel due to exposure to the fire and its combustion products. Water mist can significantly reduce visibility in the protected areas during discharge. It will dissipate fairly rapidly afterwards, depending on factors such as air temperature and humidity. The design of escape routes should take into account this fact. Water mist using potable water does not present an environmental hazard unless the water absorbs dangerous substances from the fuel or fire. In such cases careful consideration should be given to preventing water entering the drainage system or the ground. Page 4 Watermist Fire Technologies

3 Chapter 3 Design of the System The design of the system will determine the system performance and user expectations. It is important to review the design with the system supplier. At present, there are no European prescriptive water mist standards. However, the product supplied will be in accordance with the relevant product and technical standards available at the time of design. These documents are referenced in Appendix 2. Specific details such as system run time, nozzle type and from this, water quantity, will have been determined by specific type testing for the application; fuel type; size and layout of the protected area and contents therein; insurer requirement; fire brigade attendance time; consultant brief; particular manufacturer recommendations; or a combination of the above. Water mist systems are designed to perform one of the following functions: To extinguish a fire completely so that no re-ignition will occur To suppress a fire, so that extinguishment has taken place and intervention can occur to prevent further re-ignition To control a fire scenario, to allow time for evacuation or fire brigade attendance Particular system components, water quantity and run time should be detailed in the Commissioning Certificate and Appendix 1. Water Mist Fire Technologies Page 5

4 Chapter 4 System Components FOGEX high-pressure water mist cylinder systems are based on similar technology. The actual components used will depend on the particular design of the application. The FOGEX water mist system comprises of the following main components: One or more 67.5 litre nitrogen cylinders charged with nitrogen to 230 bars at 15 o C Nitrogen valve, dependent on the type of system and number of cylinders can be one of the following:» Indirect High-Pressure Valve (for automatic closed head systems)» Electric valve for open deluge systems» Pneumatic valve (where there is more than one nitrogen cylinder)» Manual release valve (mounted on master nitrogen cylinder valve) Pressure regulator Pressure monitoring gauge (mounted on all nitrogen cylinder valve(s)) Discharge monitoring pressure switch Low pressure monitoring switch 67.5 litre water cylinder (plastic lined) Water valve (actuator head), fitted into each water cylinder Interconnecting hoses Water manifold (where more than 1 water cylinder is installed) Check valve (where more than 1 water cylinder is installed) Test point Directional valve Stainless steel pipe work Stainless steel compression fittings FOGEX water mist nozzle(s) The quantity of the water and nitrogen cylinders depends on design factors including the number and type of nozzle and the system discharge (or run) time. The ratio of water to nitrogen cylinders is 2:1. Cylinder configurations are normally as indicated in Table 4.1. Page 6 Watermist Fire Technologies

5 System Designation Qty of water cylinders Qty of nitrogen cylinders Total System Water Qty litres litres litres litres litres litres Table 4.1 Quantity of Water and Nitrogen Cylinders Nitrogen Cylinder The nitrogen cylinder has a water capacity of 67.5 litres and is charged with 230 bars of dry nitrogen at 15 o C. The cylinder is seamless with a working pressure of 230 bars and a test pressure of 345 bars. The cylinder is π-marked and complies fully with the European Transportable Pressure Directive. A system may have more than one nitrogen cylinder. In this case, it is always the first (or master) cylinder that is fitted with the discharge-initiating valve. Figure 4.1 Nitrogen Cylinder fi tted with protective head cap Indirect High-Pressure Valve The Indirect High-Pressure Valve (IHP) is fitted to the first nitrogen cylinder of closed-head systems that contain FOGEX FA automatic bulb-type nozzles. Figure 4.2 Indirect High-Pressure Valve as used on the fi rst (master) nitrogen cylinder The valve comes complete with the following attachments and outlets: Pressure Gauge Discharge Outlet Low pressure actuator c/w manual ball valve Manual release c/w gauge for low-pressure side and manual ball valve Water Mist Fire Technologies Page 7

6 The IHP valve is a differential pressure valve that is normally closed. The valve is held closed by a balance from the high pressure side of the stored nitrogen with that of the low pressure side at the top of the valve. The low pressure outlet is fitted with a ball valve and then is connected via a non-return valve to the system pipe work. The high pressure discharge outlet also connects to the system pipe work via a T piece. Upon commissioning, the system pipe work is pressurised to 19 bars, and the manual ball valve to the low pressure actuator is opened. When one or more nozzles actuate the pressure drops in the pipe work. The drop in pressure causes a pressure difference across the valve. The valve opens releasing the cylinder contents at 230 bars through the discharge outlet. The nitrogen flows via a pressure regulator, where the pressure is reduced to 110 bars. It then flows to pressurise the water cylinder(s). Other nitrogen cylinders that maybe connected to the system are actuated via the pressure opening a pneumatic valve. Electric Nitrogen Valve The electric nitrogen valve is used on open deluge systems only, that use the FOGEX F type nozzle. A signal from the fire alarm control panel opens the valve to discharge the nitrogen. The valve comes complete with the following attachments and outlets: Pressure Gauge Discharge Outlet Low pressure switch Manual release Figure 4.3 Electric Valve as used on the fi rst (master) nitrogen cylinder of open deluge systems Pneumatic Nitrogen Valve A pneumatic valve is used where more than one nitrogen cylinder is required. The valve is opened by external pressure generated through the opening of an IHP valve, electric valve or manual release of the first nitrogen cylinder. Page 8 Watermist Fire Technologies

7 Figure 4.4 Pneumatic Valve as used on all secondary nitrogen cylinders Manual Release The manual release requires the user operate to open the first nitrogen cylinder to initiate a system discharge. Figure 4.5 Manual Release as fi tted on the IHP valve on the fi rst nitrogen cylinder Figure 4.6 Manual Release as fi tted on the electric valve on the fi rst nitrogen cylinder The manual release should only be used in the following cases: On manual only systems; When a fire has been identified and intervention is required before the detection system has operated; If the detection system has failed Water Mist Fire Technologies Page 9

8 Pressure Regulator The pressure regulator is a device that reduces the pressure discharged from the nitrogen cylinder from 230 bars to 110 bars. This ensures that the optimum design pressure of 100 bar at the nozzle is achieved allowing for potential pressure loss in the pipe work and fittings. Figure 4.7 Pressure Regulator Low Pressure Switch The low pressure switch is fitted to all nitrogen cylinders to monitor loss of pressure. The switch is a volt-free contact set at 160 bars that should be connected and monitored by the control panel. Should the nitrogen pressure fall below this a fault is generated. The nitrogen should be recharged as soon as possible thereafter. Discharge Pressure Switch The discharge pressure switch is a monitored volt-free contact that is normally open. In the case of a single water cylinder arrangement it can be fitted to the water cylinder valve, nitrogen valve, or via a T -piece in the downstream pipe work. For more than one water cylinder the pressure switch is fitted to the manifold. As the water discharges the switch closes and a signal is sent to the control panel, indicating system discharge. An alternative arrangement is on the nitrogen cylinder valve. In this case, switch closure is achieved through the flow of nitrogen at pressure when the valve opens. The discharge pressure switch is stainless steel in construction. Figure 4.8 Discharge Pressure Switch Water Cylinder The water cylinder has a water capacity of 67.5 litres. The cylinder is seamless with a working pressure of 200 bars and a test pressure of 300 bars. The cylinder is π-marked and complies fully with the European Transportable Pressure Directive. The cylinder is lined with a plastic coating to prevent corrosion of the steel. The water used is de-mineralised. Page 10 Watermist Fire Technologies

9 Figure 4.9 Water Cylinder c/w Valve Water Cylinder Valve The water cylinder valve consists of two nitrogen ports (one in, one out); and an outlet port. The outlet section of the valve is a service removable. The ½" outlet is connected directly to the pipe work for a single cylinder system or to a manifold for a multi-cylinder system. The quiescent storage pressure of the water cylinder is zero. To ensure that the system operating pressure of 100 bars is attained quickly the internal valve mechanism has been tested to operate at no more than 80 bars. At this point, the valve opens and water discharges through the system to the nozzles. Should one of the nitrogen ports not be used, a blanking plug is inserted. Water Manifold A water manifold is a device that collects all the water outlets from the water cylinders. Water manifolds may be one of two sizes: 3-port, allows connection of between 1 and up to 3 water cylinders 6-port, allows connection of between 1 and up to 6 water cylinders Figure 4.10 Manifold Assemblies The inlet and outlet ports of the manifold are as follows: 3-port water inlet manifold» 3 off ½" inlet ports from water cylinders» 4 off ¾" outlet ports 6-port water inlet manifold» 6 off ½" inlet ports from water cylinders» 5 off ¾" outlet ports Water Mist Fire Technologies Page 11

10 At least one outlet port connects to pipe work that extends to the nozzles. Orientation of the outlet ports mean that one or more choice of direction is available for the pipe work extending to the nozzles. The other outlet ports may be used as connections to: A test point used for system pressure test or charging A discharge pressure switch Check Valve A check valve is a non-return valve that prevents the flow of water or nitrogen back through the manifold to the storage cylinder. It also prevents system failure or potential injury should one of the connected cylinders be removed from the system. Figure 4.11 Check Valve Directional Valve A directional valve is a manual or more normally an electric ball valve, installed in line with the pipe work. Its purpose is to direct the flow of water upon discharge to a particular area of the system. An example would be a common cylinder bank protecting 3 risks. The water quantity could be designed so that only sufficient water was available for a single risk. Upon detection of a fire, the system would be activated and only the directional valve associated with the risk with a fire would be opened. Figure 4.12 Manual Ball Valve that can operate as a directional valve Figure 4.13 Electric Ball Valve that can operate as a directional valve Page 12 Watermist Fire Technologies

11 Directional valves are only generally used when a risk assessment or insurer has determined that no more than one fire incident will occur. Water quantity will always be for the largest risk. In the above case, if one risk were larger than the remaining two, the water quantity would be determined on the largest risk. Compression Fittings A compression fitting consists of a body constructed out of 316L grade stainless steel, a locking nut and a compression ferrule. Compression fittings can have either one ferrule or two ferrules. Tightening of the locking nut compresses the ferrule(s) onto the pipe and forms a leak-tight seal. Different fitting types include stud couplings (a combination of a compression coupling to a BSP thread); bushes (male-female adaptors); sockets; male-male adaptors; bonded seals; adaptors with parallel and/or tapered BSP threads; tees, elbows, crosses, caps and plugs. Figure 4.14 Examples of Stainless Steel Compression Fittings Nozzles The type of nozzle used will depend on the type of system (see below). There are two basic types of nozzle: Open Deluge (or F nozzle) Closed-Head (or FA nozzle) Both types of nozzles are constructed of an aluminium-bronze or stainless steel body dependent on the application. All nozzles are fitted with a stainless-steel strainer within to prevent blockage. Figure 4.15 Open deluge F type nozzles The closed-head nozzle contains an alcohol filled bulb that is temperature dependent. Once the temperature has been achieved the alcohol will expand, and the bulb will shatter, opening up the nozzle. Water Mist Fire Technologies Page 13

12 Figure 4.16 Closed-head FA type nozzles For particularly harsh or dirty environments, or applications where the nozzle could be tampered with, tamper-proof blow-off caps are available. Figure 4.17 Tamperproof blow-off cap for an open deluge F type nozzle Figure 4.18 Tamperproof blow-off cap for a closed-head FA type nozzle Page 14 Watermist Fire Technologies

13 Chapter 5 System Operation This chapter details how the system will operate in an event of a fire. There are two types of system: one type uses the FOGEX F-type - open deluge nozzle (i.e. F20, F27 or F11); the other type uses the FOGEX FA-type automatic bulb nozzle (i.e. FA20, FA27 or FA11). These types of systems are referred to as open deluge and closed head respectively. Open Deluge Open deluge systems use the F range of FOGEX nozzles. Once the system is activated water mist is generated at each and every nozzle Table 5.1 below details the application of the types of nozzle: Type of Nozzle Flow Rate per Nozzle Application F litres/min General room protection below 5m in height F litre/min Door opening or water curtain protection below 5m in height; escalator protection; oven or fat-fryer protection F11 10 litres/min Local application or general room protection above 5m height Table 5.1 Types and applications of the F series open deluge nozzles Open deluge systems are most commonly activated by a detection system. The detection system type will depend on the application. Heat probes are generally used in ovens; flame detectors on printing presses and optical or ionisation smoke for general room applications. Activation of the system will be by the co-incidence connection principle, whereby at least two detectors, wired on separate circuits, will register an alarm or fire condition. The control panel will then signal to the water mist to discharge, after a pre-programmed delay time. Open deluge systems can also be activated manually, either by way of a manual release fitted to the first nitrogen cylinder (without the requirement for a detection system); or via the manual release or break glass of the detection circuit. Open deluge systems will use an electric valve fitted with manual release override on the first nitrogen cylinder. The nitrogen flows out of the discharge port, through the pressure regulator and into water cylinder(s). The water cylinder(s) discharge water at 110 bars into the system pipe work and to the nozzles. The nitrogen will also open the remaining nitrogen cylinders installed via their pneumatic valve. NOTE In an open deluge system water mist will discharge from all open nozzles. As the water flows through the pipe work a pressure switch will close, indicating that discharge is taking place. Water discharge will continue until all of the water has been depleted, unless an isolation valve (if fitted) is closed. Water Mist Fire Technologies Page 15

14 Closed Head Closed head systems use the FA range of FOGEX nozzles. Each nozzle is fitted with an alcohol-filled, temperature-sensitive bulb. The system will only discharge water if one or more of the bulbs are activated. The system is designed for the worst-case scenario where a designed maximum number of nozzles could be actuated. The water quantity required, and hence the number of cylinders, requires this maximum area of coverage, design runtime and nozzle flow-rate at design stage. The type of nozzle and the temperature of the bulb installed will have been determined at design stage. Table 5.2 below details the application of the types of nozzle: Type of Nozzle Flow Rate per Nozzle Application FA litres/min General room protection below 5m in height FA litre/min Door opening or water curtain protection below 5m in height FA11 10 litres/min Local application or general room protection above 5m height Table 5.2 Types and applications of the FA series closed-head nozzles Table 5.3 indicates the temperature release ratings of the alcohol filled bulbs. Bulb Temperature Rating Bulb Colour 57 o C Orange 68 o C Red 79 o C Yellow 93 o C Green 141 o C Blue 182 o C Mauve 240 o C Black Table 5.3 Colour designation of alcohol fi lled temperature-sensitive bulbs The 57 o C bulbs are fitted as standard. A closed-head system has to be charged with either dry nitrogen or water during the commissioningphase. This pressure is the normal quiescent pressure of operation. At 15 o C the pressure contained in the system pipe work and held back at the nozzle is 19 bars. A closed-head system always uses one nitrogen cylinder with an Indirect High Pressure (IHP) valve. If more than one nitrogen cylinder is installed the remaining nitrogen cylinders are fitted with a pneumatic valve. In the event of a fire that activates a bulb, the pressure will drop in the system, which will open the IHP valve on the first nitrogen cylinder. The nitrogen flows out of the discharge port, through the pressure regulator and into water cylinder(s). The water cylinder(s) discharge water at 110 bars into the system pipe work and to the nozzle that activated. The nitrogen will also open the remaining nitrogen cylinders installed via their pneumatic valve. Page 16 Watermist Fire Technologies

15 NOTE In a closed head system water mist will only discharge from nozzles that have activated. All other nozzles will remain closed unless activated through temperature of the fire spread. As the water flows through the pipe work a pressure switch will close, indicating that discharge is taking place. Water discharge will continue until all of the water has been depleted, unless an isolation valve (if fitted) is closed. Water Mist Fire Technologies Page 17

16 Chapter 6 Post-Discharge & Recharge Procedure In the event of a system discharge, precautions should be made and a procedure adopted for recharging and re-commissioning the system. In the event of a fire the protected area should not be re-entered unless deemed safe to do so by the local fire brigade or other suitably qualified personnel. Should there be any standing water near electrical equipment where possible live-voltages may be present, power should be shut-down, and suitable health and safety precautions should be followed. The authorised supplier or maintainer of the system should be contacted as soon as possible to recharge and re-commission the system. Nitrogen and water cylinders will need to be recharged. The water cylinder valve will need to be refurbished in accordance with the manufacturer s procedures. The nozzle(s) through which water has discharged should be removed and replaced. This is to ensure that system performance remains unaffected for subsequent activations. In the case of automatic closed-head bulbs, the alcohol filled bulb will need to be replaced, if activated or damaged. Should any tamperproof nozzle caps have been damaged or discharge has occurred, these should be replaced. Page 18 Watermist Fire Technologies

17 Chapter 7 Maintenance Procedures For the water mist system to protect and operate at optimum performance for the life-time of the application certain maintenance procedures should be followed. The system has been designed to meet the design criteria and application at the time of installation. Change of use, fire hazard, size or construction may affect the performance of the system and the system supplier should be contacted as soon as possible after any such changes. Inspection intervals and procedures are as indicated below. Weekly Visual check of the hazard for changes or alterations that could affect the system performance. Visual check of the control panel to check for faults. Inspect pressure gauges on the nitrogen cylinders for correct reading. If installed, check trace heating and localized heating systems. Carry out a visual check that there is no obvious damage to pipe work. Carry out a check that all operating controls and components are properly set and undamaged. Monthly Check that all personnel who may have to operate the equipment or system are properly trained and authorised to do so and, in particular, that new employees have been instructed in its use. Six Monthly To be carried out by qualified and authorised service providers. Check connecting hoses for tightness and integrity Check water cylinder contents Inspect support brackets and frame of cylinders/manifold Inspect and test the fire alarm system, if fitted. Yearly Check water quality for signs of deterioration or bacterial contamination. Ten yearly Ensure all cylinders undergo a hydrostatic test in accordance with current standards. Water Mist Fire Technologies Page 19

18 Appendix 1 Particular System Specification Client Name Client Address Telephone Fax Responsible Person Protected Hazard Fuel Class (please circle) Class A Class B Particular Fuel Type of System (please circle) Open Deluge Closed Head Type of Actuation (please circle) IHP Electric Manual Self-contained Type of Detectors Type of Control Panel Type of Nozzle Number of Nozzles (include any in voids) Tamperproof blow-off caps (please circle) Yes No System Design Run Time Total Water Quantity Number of Water Cylinders minutes litres Number of Nitrogen Cylinders Number of Directional Valves Type of Directional Valve Date of Installation Date of Commissioning and Handover As Fitted Drawings present (please circle) Yes No Hydraulic Calculations present (please circle) Yes No Page 20 Watermist Fire Technologies

19 Other Information Authorised Signature Name Position Date Water Mist Fire Technologies Page 21

20 Appendix 2 Relevant Documentation FOGEX Design and Installation Manual NFPA750 Standard on Water Mist Fire Protection Systems (2003) Draft ISO Standard ISO Fire protection Automatic sprinkler system Part 9: Requirements and test methods for water mist nozzles CEN/TC 91 Draft on Fixed fire fighting systems Water mist systems Design and installation TBN 14 Loss Prevention Council Technical Briefing Note Legionella and Fire Fighting Systems, May 1999 BS (2002) Part 1: Code of Practice for System Design, Installation, Commissioning and Maintenance BS6266 (2002) Code of practice for fire protection for electronic equipment installations BS EN 1968 (2002) Transportable Gas Cylinders Periodic inspection and testing of seamless steel gas cylinders Page 22 Watermist Fire Technologies

AUTOMATIC GAS MANIFOLDS

AUTOMATIC GAS MANIFOLDS AUTOMATIC GAS MANIFOLDS Phoenix Pipeline Products Limited. Unit 8, McKenzie Industrial Park, Tel No.: 44 (0) 161 428 7200 Bird Hall Lane, Fax No.: 44 (0) 161 428 7010 Stockport, Email: info@p3-phoenix.com

More information

INSTALLATION OPERATION MAINTENANCE

INSTALLATION OPERATION MAINTENANCE Bermad Electrically Controlled On-Off Deluge Valve Model: 400E-3D INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 1. Safety First BERMAD believes that the safety of personnel working

More information

MANUAL GAS MANIFOLDS

MANUAL GAS MANIFOLDS MANUAL GAS MANIFOLDS Phoenix Pipeline Products Limited. Unit 8, McKenzie Industrial Park, Tel No.: 44 (0) 161 428 7200 Bird Hall Lane, Fax No.: 44 (0) 161 428 7010 Stockport, Email: info@p3-phoenix.com

More information

System Pressure Manager Standard & System Pressure Manager Plus

System Pressure Manager Standard & System Pressure Manager Plus System Pressure Manager Standard & System Pressure Manager Plus Installation, Commissioning & Servicing Instructions Note: THESE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE INSTALLING, COMMISSIONING,

More information

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series Introduction Powerex manifolds are cleaned, tested and prepared for the indicated gas service and are built in accordance with the Compressed Gas Association guidelines. The manifold consists of a regulator

More information

Working Environment Safety Assessment

Working Environment Safety Assessment For your own safety and/or safety of your workforce, and to improve the efficiency of your business practices, you should be aware of, and be up to date with, the key safety issues and good practices relevant

More information

TECHNICAL DATA. Trimpac 256a. October 31, 2013

TECHNICAL DATA. Trimpac 256a. October 31, 2013 October 31, 2013 Trimpac 256a 1. DESCRIPTION The Viking SUREFIRE SIngle Interlock Preaction TRIMPAC Model D-1 and D- 1B used with either a Model E or F Deluge Valve (A.1), a Viking Easy Riser check valve

More information

CPX EMERGENCY STANDBY MANIFOLD INSTALLATION, OPERATIONS & MAINTENANCE MANUAL

CPX EMERGENCY STANDBY MANIFOLD INSTALLATION, OPERATIONS & MAINTENANCE MANUAL CPX EMERGENCY STANDBY MANIFOLD INSTALLATION, OPERATIONS & MAINTENANCE MANUAL Company Registered Office: Crown House, Stockport, Cheshire, SK13RB No. 850 0700 67 Registered in England and Wales No. 05058855

More information

TECHNICAL DATA. Trimpac 257a. September 16, 2013

TECHNICAL DATA. Trimpac 257a. September 16, 2013 September 16, 2013 Trimpac 257a 1. DESCrIpTION DESCRIPTION The Viking Double SUREFIRE SIngle Interlock Preaction TRIMPAC Model D-2 and D-2B used with either a Model E or F Deluge Valve (A.1), a Viking

More information

Installation and operating manual. Pneumatic control station LK product no: PCS 1-10

Installation and operating manual. Pneumatic control station LK product no: PCS 1-10 LK product no: PCS 1-10 Article no: 74503 Revision:8 Article no: 74503 Revision: 8 2 (23) Contents 1. General information... 5 2. Safety precautions... 5 2.1 Significance of symbols... 5 2.2 Explanatory

More information

Installation, Operating, Maintenance and Safety Instructions for. Pressurised water systems for boats

Installation, Operating, Maintenance and Safety Instructions for. Pressurised water systems for boats FLOMAX-SYSTEM DOC532/11 Installation, Operating, Maintenance and Safety Instructions for FLOMAX-SYSTEM Pressurised water systems for boats CW343A FloMax System 12 volt d.c. CW344A FloMax System 24 volt

More information

Water Mist Systems Inspection, Testing, and Maintenance of Water Mist Systems

Water Mist Systems Inspection, Testing, and Maintenance of Water Mist Systems Water Mist Systems Inspection, Testing, and Maintenance of Water Mist Systems Name of Property: Address: Phone Number: Inspector: Contract No.: Date: This Report Covers: Monthly Quarterly Annual Other

More information

Propane Conversion Kit Instructions

Propane Conversion Kit Instructions 604 8 0/ US/CA For heating engineers Propane Conversion Kit Instructions Logano G4 X gas-fired boiler This conversion kit and the accompanying instructions are for conversion of G4 X gas-fired boilers

More information

Worldwide Contacts. General Description

Worldwide Contacts.  General Description Worldwide Contacts www.tyco-fire.com AQUAMIST Red-E Mist Supply Skid Table of Contents Sections General Description....1 Training...3 Technical Data...3 Skid Operation...3 System Components...6 Planning...6

More information

Method Statement: Testing Dry Riser System

Method Statement: Testing Dry Riser System Method Statement: Testing Dry Riser System Page 1 of 6 Scope of work Test dry riser system in accordance with BS 5306. Definitions For the purposes of this document, the following definitions apply Rising

More information

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1 Dry 131h 1. DESCRIPTION The Viking Model G-1 Maintenance Air Compressor is an electric motor-driven, aircooled, single-stage, oil-less compressor. The unit is equipped with a check valve and provides a

More information

TECHNICAL DATA. TRIMPAC Model B-5 & B-5B

TECHNICAL DATA. TRIMPAC Model B-5 & B-5B September 16, 2013 Trimpac 250a 1. DESCRIPTION DEsCRIPTIoN is a factory assembled trim package for a ed an electric/pneumatic release module in a metal enclosure. The standard trim normally required on

More information

Government of Bermuda Department of Maritime Administration BERMUDA SHIPPING NOTICE

Government of Bermuda Department of Maritime Administration BERMUDA SHIPPING NOTICE Government of Bermuda Department of Maritime Administration 2015 027 BERMUDA SHIPPING NOTICE Maintenance and Inspection of Fixed Carbon Dioxide Fire Extinguishing Systems Ref: SOLAS 74/88 as amended, Regulation

More information

Piped Air SCBA Refilling System Standard

Piped Air SCBA Refilling System Standard WALT WHITE Fire Chief 5770 Freeport Blvd., Suite 200 Sacramento, CA 95822-3516 Ph: (916) 808-1300 Fax: (916) 808-1629 www.sacfire.org Piped Air SCBA Refilling System Standard SCOPE: This specification

More information

PGM PREPIPED GAS MANIFOLD

PGM PREPIPED GAS MANIFOLD INSTRUCTIONS PGM PREPIPED GAS MANIFOLD WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components by unqualified

More information

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13 Page 1 of 13 1. Description The Viking 2 Model G-2000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler

More information

Premium Series. Economical Price & Reliable Performance. High Quality. Rust-Resistant. Long Life. Tamper-Resistant locking Screw.

Premium Series. Economical Price & Reliable Performance. High Quality. Rust-Resistant. Long Life. Tamper-Resistant locking Screw. Premium Series High Quality Forged Brass Body Rust-Resistant Nickel Plated Finish Long Life Corrosion Resistant Valve Seat Economical Price & Reliable Performance Tamper-Resistant locking Screw Reduces

More information

Code AWC20HP Air Compressor

Code AWC20HP Air Compressor Code 951816 AWC20HP Air Compressor Index of Contents Index of Contents 02 Declaration of Conformity 02 What s Included 03 Safety Precautions 03 Specifications (AWC20HP Air Compressor) 04 Assembly Instructions

More information

Installation Operating Instructions for Duplex Manual Manifolds PX-TMD Series

Installation Operating Instructions for Duplex Manual Manifolds PX-TMD Series Introduction Powerex manifolds are cleaned, tested and prepared for the indicated gas service and are built in accordance with the Compressed Gas Association guidelines. The manifold consists of a regulator

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S Page 1 of 13 1. DESCRIPTION The Viking 6 Model G-6000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler

More information

HANDBOOK. Squeeze Off Unit SOU 400. Please refer any queries to:

HANDBOOK. Squeeze Off Unit SOU 400. Please refer any queries to: HANDBOOK Squeeze Off Unit SOU 400 Please refer any queries to: Hy Ram Engineering Co Ltd Pelham Street Mansfield Nottinghamshire NG18 2EY Telephone No: (01623) 422982 Please note all queries should state

More information

Glasgow City Council EDUCATION SERVICES. Technician Support Service

Glasgow City Council EDUCATION SERVICES. Technician Support Service Glasgow City Council EDUCATION SERVICES Technician Support Service Technician Guidance Sheets TGS/10a Use & Inspection of Gas Cylinders & Associated s Issued by Technician Support Service Date September

More information

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection February 9, 1998 Foam 201a 1. DESCRIPTION A Deluge Bladder Tank Foam/Water System is a standard deluge system capable of discharging a foam/water solution automatically through open sprinklers, spray nozzles,

More information

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE February 9, 1998 Foam 101a A BLADDER TANK WITH 1. DESCRIPTION A Wet Pipe Bladder Tank Foam/Water System is a standard wet pipe automatic sprinkler system capable of discharging a foam/water solution automatically

More information

Wilkins Safety Group

Wilkins Safety Group Gas Welding INTRODUCTION Welding is the union of pieces of metal by fusing the opposing surfaces that have been made molten by heat. Processes similar to welding include brazing and soldering. Allied processes

More information

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY Page 1 of 13 1. DESCRIPTION The Viking 3 Model G-3000 Dry Valve Riser Assembly is equipped with a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry

More information

Guidance on the maintenance and inspection of fixed CO 2 fire-extinguishing systems

Guidance on the maintenance and inspection of fixed CO 2 fire-extinguishing systems Translation. Only the Danish document has legal validity. Guidance no. 9514 of 9 July 2014 issued by the Danish Maritime Authority Guidance on the maintenance and inspection of fixed CO 2 fire-extinguishing

More information

TECHNICAL DATA. Q= Cv S

TECHNICAL DATA. Q= Cv S Page 1 of 13 1. DESCRIPTION The Viking 4 inch Model G-4000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry

More information

TECHNICAL DATA PILOT PRESSURE REGULATED DELUGE SYSTEM CONTROLLED BY PNEUMATIC RELEASE. 1. DESCRIPTION (Refer to Figures 1, 2 or 3.

TECHNICAL DATA PILOT PRESSURE REGULATED DELUGE SYSTEM CONTROLLED BY PNEUMATIC RELEASE. 1. DESCRIPTION (Refer to Figures 1, 2 or 3. Page 1 of 8 1. DESCRIPTION A Viking Pilot Pressure Regulated Deluge System utilizes a Viking Flow Control Valve to control water flow into the deluge system. The flow control valve must be installed with

More information

TECHNICAL DATA. Trimpac 244a. September 16, 2013

TECHNICAL DATA. Trimpac 244a. September 16, 2013 September 16, 2013 Trimpac 244a 1. DEsCrIpTION DESCRIPTION TRIMPAC Model B-1 and B-1B is a factory-assembled trim package with an electric release module in a metal enclosure. The standard trim normally

More information

PRESSURE REDUCING STATION INSTALLATION, OPERATIONS & MAINTENANCE MANUAL

PRESSURE REDUCING STATION INSTALLATION, OPERATIONS & MAINTENANCE MANUAL PRESSURE REDUCING STATION INSTALLATION, OPERATIONS & MAINTENANCE MANUAL Company Registered Office: Crown House, Stockport, Cheshire, SK13RB No. 850 0700 67 Registered in England and Wales No. 05058855

More information

ECS Protector Nitrogen Inerting Vent (PAV-WN)

ECS Protector Nitrogen Inerting Vent (PAV-WN) ECS Protector (PAV-WN) U.S. Pat. No. 8,636,023, 9,526,933 and 9,717,935 B2 Specifications Stock Number: Service Pressure: Regulator Setting: System Connection: Temperature Range: Dimensions: Weight: Clear

More information

Installation & Maintenance Manual. Economy Manifold

Installation & Maintenance Manual. Economy Manifold Installation & Maintenance Manual Economy Manifold Contents User Responsibility 3 Introduction 4 Features 4 Description of the Manifold 5 Shipment Details 5 Description of Parts 5-6 Pressure Regulators

More information

TECHNICAL DATA. Trimpac 251a. Spetember 16, 2013

TECHNICAL DATA. Trimpac 251a. Spetember 16, 2013 Spetember 16, 2013 Trimpac 251a 1. DEsCrIpTION DESCRIPTION TRIMPAC Model B-6 and B-6B is a factory assembled trim package for a double interlocked preaction system with an electric/pneu-lectric release

More information

Tri-Tech Medical Inc.

Tri-Tech Medical Inc. Introduction Tri-Tech Medical manifolds are cleaned, tested and prepared for the indicated gas service and are built in accordance with the Compressed Gas Association guidelines. The manifold consists

More information

PROPORTIONING VALVE. Model 150 INSTRUCTION MANUAL. March 2017 IMS Company Stafford Road

PROPORTIONING VALVE. Model 150 INSTRUCTION MANUAL. March 2017 IMS Company Stafford Road PROPORTIONING VALVE Model 150 INSTRUCTION MANUAL March 2017 IMS Company 10373 Stafford Road Telephone: (440) 543-1615 Fax: (440) 543-1069 Email: sales@imscompany.com 1 Introduction IMS Company reserves

More information

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE INSTALLATION, OPERATION & MAINTENANCE MANUAL INTERFACE DEVICES, INC. 230 Depot Road, Milford, CT 06460 Ph: (203) 878-4648, Fx: (203) 882-0885, E-mail: info@interfacedevices.com

More information

PRODUCT OPERATING MANUAL

PRODUCT OPERATING MANUAL PRODUCT OPERATING MANUAL PANBLAST TM VISIFLO RESPIRATOR AIRLINE FILTERS Manual Number: ZVP PC 0084 01 Pressure Equipment Directive 97/23/EC SECTION 1. GENERAL INFORMATION 2. INTRODUCTION 3. PREPARATION

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE April 9, 2009 Preaction 326a 1. DESCRIPTION Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems utilizing the Viking G-4000P Deluge Valve. The small profi le, lightweight,

More information

AREA VALVE SERVICE UNITS

AREA VALVE SERVICE UNITS AREA VALVE SERVICE UNITS. Unit 8, McKenzie Industrial Park, Tel No.: 44 (0) 161 428 7200 Bird Hall Lane, Fax No.: 44 (0) 161 428 7010 Stockport, Email: info@p3-phoenix.com U.K., SK3 0SB www.p3-phoenix.com

More information

Level 3 Certificate in Fire Science, Operations, Fire Safety and Management (All Examinations)

Level 3 Certificate in Fire Science, Operations, Fire Safety and Management (All Examinations) Level 3 Certificate in Fire Science, Operations, Fire Safety and Management (All Examinations) Examiner Report on October 2018 Examinations Introduction Candidates generally performed well with good pass

More information

HANDBOOK. Squeeze Off Unit SOU 250. Please refer any queries to:

HANDBOOK. Squeeze Off Unit SOU 250. Please refer any queries to: HANDBOOK Squeeze Off Unit SOU 250 Please refer any queries to: Hy Ram Engineering Co Ltd Pelham Street Mansfield Nottinghamshire NG18 2EY Telephone No: (01623) 422982 Please note all queries should state

More information

Operating Manual. Model MP-4R and MP-4RSS MULTI-PAK TM RESCUE AIR CARTS Manual No. PAK013 (Rev 1 January 2001)

Operating Manual. Model MP-4R and MP-4RSS MULTI-PAK TM RESCUE AIR CARTS Manual No. PAK013 (Rev 1 January 2001) Model MP-4R and MP-4RSS MULTI-PAK TM RESCUE AIR CARTS Manual No. PAK013 (Rev 1 January 2001) Operating Manual AIR SYSTEMS INTERNATIONAL, INC. 829 Juniper Crescent, Chesapeake, Va., 23320 Telephone (757)

More information

FRAGMENTATION INSTRUCTION & OPERATION HANDBOOK

FRAGMENTATION INSTRUCTION & OPERATION HANDBOOK FRAGMENTATION INSTRUCTION & OPERATION HANDBOOK Doc. Jordair FRAGMENTATION-MANUAL WARNING! HIGH PRESSURE UNITS Under no circumstances should the fill stations be operated with the safety relief valves removed

More information

TECHNICAL DATA. Trimpac 247a_Euro. September 16, 2013

TECHNICAL DATA. Trimpac 247a_Euro. September 16, 2013 September 16, 2013 Trimpac 247a_Euro 1. DESCRIPTION DEsCrIpTIoN TRIMPAC Model B-11 LPCB Type 1 is a factory assembled trim package for a single interlocked electric release module in a metal enclosure.

More information

2. Application This "Guidelines" applies to all ships. 3. General Requirements for the Maintenance and Inspection of Fire-protection Systems and Appli

2. Application This Guidelines applies to all ships. 3. General Requirements for the Maintenance and Inspection of Fire-protection Systems and Appli Subject Maintenance, inspection and test of Fire-Protection Systems and Appliances on board the Panama-registered ships To whom it may concern Technical Information No. TEC-0910 Date 25 June 2012 The Panama

More information

Dri-Line Mk3 Monnier Compressed Air Drain Trap

Dri-Line Mk3 Monnier Compressed Air Drain Trap 5044050/2 IM-P504-24 CH Issue 2 Dri-Line Mk3 Monnier Compressed Air Drain Trap Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation and Operation

More information

Speed control assembly model A-1

Speed control assembly model A-1 Pressure Regulation 533a 1. DESCRIPTION The Viking Speed Control Assembly provides adjustment of the opening speed of Viking Deluge Valves, and adjustment of both the opening and closing speed of Viking

More information

LARGE DRY CHEMICAL, TWIN-AGENT, AFFF, HALON 1211, AND AQUASONIC (NITROGEN-OPERATED SYSTEMS) Pressure Regulator Test Manual

LARGE DRY CHEMICAL, TWIN-AGENT, AFFF, HALON 1211, AND AQUASONIC (NITROGEN-OPERATED SYSTEMS) Pressure Regulator Test Manual LARGE DRY CHEMICAL, TWIN-AGENT, AFFF, HALON 1211, AND AQUASONIC (NITROGEN-OPERATED SYSTEMS) Pressure Regulator Test Manual 002694 IntroductIon 8-1-11 Page 1 ForEWord This manual is intended for use with

More information

Conversion instructions from natural gas to propane

Conversion instructions from natural gas to propane 6 720 804 895 202/0 EN-US For heating engineers Conversion instructions from natural gas to propane Room air-independent special gas-fired boiler Logano GA24 This conversion kit and the instructions are

More information

User Manual 1 P a g e Rev. V1.6-EN 11/08/2014

User Manual 1 P a g e Rev. V1.6-EN 11/08/2014 User Manual 1 P a g e Rev. V1.6-EN 11/08/2014 Copyright Disclaimer Trademarks and patents Intended use Contact info 2011 Inflotrolix, Inc. This document may not be copied in whole or in part or otherwise

More information

EDUCATION DEPARTMENT ACCU-TEST

EDUCATION DEPARTMENT ACCU-TEST ABN 17 100 208 964 EDUCATION DEPARTMENT ACCU-TEST GAS SAFETY SHUT OFF SYSTEM Operating & Installation Manual Head Office (Melbourne) Sydney Brisbane (Distributor) 1/5 Samantha Court 2/14 Welder Road 17

More information

Pressure Dump Valve Service Kit for Series 2300 Units

Pressure Dump Valve Service Kit for Series 2300 Units Instruction Sheet Pressure Dump Valve Service Kit for Series 00 Units. Overview The Nordson pressure dump valve is used to relieve hydraulic pressure instantly in Series 00 applicator tanks when the unit

More information

Instructions for High Altitude Conversion

Instructions for High Altitude Conversion 6304 38 0/ US/CA For heating engineers Instructions for High Altitude Conversion Logano G334 X gas-fired boiler This conversion kit and the accompanying instructions are for conversion of G334 X gas-fired

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 348a 1. Description Viking supervised Surefire Preaction Systems utilize the Viking G-6000P Valve. The small profile, lightweight, pilot operated Viking G-6000P Valve comes complete

More information

A guide to Part 10 of the

A guide to Part 10 of the OCCUPATIONAL HEALTH AND SAFETY DIVISION Welding, Cutting, Burning and Soldering A guide to Part 10 of the Occupational Safety General Regulations October 2007 A GUIDE TO PART 10 WELDING, CUTTING, BURNING

More information

Instruction Manual. Alfa Laval SB Membrane Sample Valve ESE02963-EN Original manual

Instruction Manual. Alfa Laval SB Membrane Sample Valve ESE02963-EN Original manual Instruction Manual Alfa Laval SB Membrane Sample Valve ESE02963-EN2 2016-02 Original manual Table of contents The information herein is correct at the time of issue but may be subject to change without

More information

Incorrect installation, adjustment, or misuse of this burner could result severe personal injury, or substantial property damage.

Incorrect installation, adjustment, or misuse of this burner could result severe personal injury, or substantial property damage. Operating instructions GB VD Burners Incorrect installation, adjustment, or misuse of this burner could result severe personal injury, or substantial property damage. To the Equipment Owner: Please read

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 333a 1. Description Viking supervised Surefire Preaction Systems Utilize the Viking G-3000P Valve. The small profile, lightweight, pilot-operated Viking G-3000P Valve comes complete

More information

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions

USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions 6250250/1 IM-P625-03 ST Issue 1 USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions 1. General safety information 2. General product information

More information

Installation Instructions

Installation Instructions Page 5750-S-1 Installation Instructions General These mounting instructions for Circular INCINO- PAK Burners are in addition to the specific instructions offered for other Maxon component items: Shut-Off

More information

TEST BENCH SAFETY VALVES ¼ - 5 DN10 DN125

TEST BENCH SAFETY VALVES ¼ - 5 DN10 DN125 TEST BENCH SAFETY VALVES ¼ - 5 DN10 DN125 Model: VC-40-VYC Table of contents 1. - Installing the test bench 1.1.1- Connecting the compressed air / nitrogen source 1.1.2- Maximum test pressure according

More information

DUPLEX PRESSURE REDUCING SET

DUPLEX PRESSURE REDUCING SET DUPLEX PRESSURE REDUCING SET Phoenix Pipeline Products Limited. Unit 8, McKenzie Industrial Park, Tel No.: 44 (0) 161 428 7200 Bird Hall Lane, Fax No.: 44 (0) 161 428 7010 Stockport, Email: info@p3-phoenix.com

More information

Pressure Dump Valve Service Kit for Series 3000 Units

Pressure Dump Valve Service Kit for Series 3000 Units Instruction Sheet Pressure Dump Valve Service Kit for Series 000 Units. Overview The Nordson pressure dump valve is used to relieve hydraulic pressure instantly in Series 00, 400, 500, and 700 applicator

More information

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST OIL-LESS TYPE IMPORTANT: PLEASE READ CAREFULLY BEFORE STARTING OPERATIONS. THE CONTENTS ARE FOR GENERAL INFORMATION OF ALL THE SIMILAR MODELS. Record

More information

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS Annex 3, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS The text of existing chapter 15 is replaced by the following: "1 Application This

More information

Class 2 Gases Learning Tool

Class 2 Gases Learning Tool Class 2 Gases Learning Tool This work has been produced by DGL (Aust) Pty Ltd This Learner s Guide is about the skills and knowledge required to store and warehouse Class 2 Gases at DGL (Aust) facilities.

More information

Budget Range Operators Handbook

Budget Range Operators Handbook Budget Range Operators Handbook BAMBI AIR COMPRESSORS LTD 152 Thimble Mill Lane Heartlands Birmingham B7 5HT United Kingdom Tel: 0121 322 2299 Fax: 0121 322 2297 Email: sales@bambi-air.co.uk www.bambi-air.co.uk

More information

Hi-Force Limited Prospect Way Daventry Northants NN11 8PL United Kingdom Tel: +44(0) : Fax: +44(0) : Website:

Hi-Force Limited Prospect Way Daventry Northants NN11 8PL United Kingdom Tel: +44(0) : Fax: +44(0) : Website: 1.0 Inspection of the product upon receipt: On receipt of the product, visually inspect the item for any evidence of shipping damage. Please note shipping damage is not covered by warranty. If shipping

More information

Installation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM.

Installation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow Model: FP 450-80 Installation Operation Maintenance PAGE 1 OF 5 1. Safety First BERMAD believes that the safety of personnel

More information

Pressure Automated Calibration Equipment

Pressure Automated Calibration Equipment GE Measurement & control Pressure Automated Calibration Equipment Safety Instructions and User Guide - K0447 PACE5000 PACE6000 K0447 Issue No. 9 1 10 1 PACE5000 1 2 3 4 5 PACE6000 2 6 7 8 3 4 5 6 7 8 9

More information

TECHNICAL DATA. System water supply pressure enters the priming chamber of the deluge valve (A.1) through the 1/4 (8 mm) priming line, which

TECHNICAL DATA. System water supply pressure enters the priming chamber of the deluge valve (A.1) through the 1/4 (8 mm) priming line, which January 27, 2012 307a 1. (Refer to Figures 1-3.) A Viking Non-Interlocked Preaction system utilizes a Viking Deluge Valve to control water flow into system piping equipped with closed sprinklers. Under

More information

Vision Painting Inc Safety Management System

Vision Painting Inc Safety Management System Abrasive Blasting 1. PURPOSE The purpose of this program is to provide training and qualification guidelines for the safe operation of Abrasive Blasting. The Safety Officer is responsible for facilitating

More information

BGA158 Series CE Approved Class A Shutoff Gas Valve

BGA158 Series CE Approved Class A Shutoff Gas Valve Installation Instructions BGA158 Issue Date August 24, 2011 BGA158 Series CE Approved Class A Shutoff Gas Valve Applications The BGA158 Series shutoff gas valve is an electrically operated gas valve that

More information

TECHNICAL DATA. Page 1 of 12

TECHNICAL DATA. Page 1 of 12 Page 1 of 12 1. DESCRIPTION The Viking Regulating Valve is a direct-acting, single-seated, spring-loaded diaphragm valve. When installed as a pilot regulating valve on a Viking Model H or J Flow Control

More information

Instruction manual. for. high purity gas pigtails 200 bar / 300 bar

Instruction manual. for. high purity gas pigtails 200 bar / 300 bar Instruction manual for high purity gas pigtails 200 bar / 300 bar Contents Contents... 2 1. Preface... 3 1.1 Overview... 3 1.2 General... 3 1.3 Intended use... 4 1.4 Personnel requirements... 4 2. For

More information

Gas Network Craftsperson

Gas Network Craftsperson Gas Network Craftsperson Unit EIAU06 Maintaining Instrumentation and Control Equipment Circuits This assessment specification has been developed as part of the network maintenance craftsperson standard

More information

Installation, Operating, Maintenance and Safety Instructions for MAXI-SYSTEM Pressurised water systems for boats

Installation, Operating, Maintenance and Safety Instructions for MAXI-SYSTEM Pressurised water systems for boats MAXI-SYSTEM DOC50/ Installation, Operating, Maintenance and Safety Instructions for MAXI-SYSTEM Pressurised water systems for boats CW CW Maxi-System.9+ volt d.c. Maxi-System.9+ volt d.c. CW99A Maxi-System

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S Preaction 346a 1. Description The 6 Model G-6000P Electric Release Preaction System Riser Assembly can be used as a Single Interlock Preaction System with Electric Release, or as a Double Interlock Preaction

More information

Installation, Operation and Maintenance Instructions for Mild Steel Buffer Vessel

Installation, Operation and Maintenance Instructions for Mild Steel Buffer Vessel OM006 Installation, Operation and Maintenance Instructions for Mild Steel Buffer Vessel The operating and maintenance instructions contained within this package are for standard mild steel buffer vessels

More information

Oxygen Usage Best Practice Guide

Oxygen Usage Best Practice Guide Oxygen Usage Best Practice Guide 1. Introduction Oxygen enriched systems possess a risk of fire and explosion since ignition and combustion hazards are present in all oxygen systems, and oxygen related

More information

TECHNICAL DATA. Pressure Regulation 531a. April 24, 2009

TECHNICAL DATA. Pressure Regulation 531a. April 24, 2009 April 24, 29 Pressure Regulation 531a 1. DESCRIPTION The Viking Regulating Valve is a direct-acting, single-seated, spring-loaded diaphragm valve. When installed as a pilot regulating valve on a Viking

More information

IPG IGNITION GAS PILOTS BACK-LOADED GAS

IPG IGNITION GAS PILOTS BACK-LOADED GAS INSTRUCTIONS IPG IGNITION GAS PILOTS BACK-LOADED GAS WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components

More information

INSTRUCTIONS FOR MODELS SG3897 AND SG3898 CROSS PURGE ASSEMBLIES

INSTRUCTIONS FOR MODELS SG3897 AND SG3898 CROSS PURGE ASSEMBLIES INSTRUCTIONS FOR MODELS SG3897 AND SG3898 CROSS PURGE ASSEMBLIES THIS BOOKLET CONTAINS PROPRIETARY INFORMATION OF ADVANCED SPECIALTY GAS EQUIPMENT CORP. AND IS PROVIDED TO THE PURCHASER SOLELY FOR USE

More information

General Precautions for handling compressed gases

General Precautions for handling compressed gases General Precautions for handling compressed gases Introduction Compressed gas cylinders can be extremely hazardous when misused or abused. Compressed gas cylinders can present a variety of hazards due

More information

GM Series Dual-Block Multi-Function Gas Control Valves

GM Series Dual-Block Multi-Function Gas Control Valves Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin GM Issue Date 0297 GM Series Dual-Block Multi-Function Gas Control Valves Figure 1: GM Series

More information

ACS.CoNGLP1 SAFETY ASSESSMENT CRITERIA INITIAL & RE-ASSESSMENT DOMESTIC NATURAL GAS TO LPG GENERIC

ACS.CoNGLP1 SAFETY ASSESSMENT CRITERIA INITIAL & RE-ASSESSMENT DOMESTIC NATURAL GAS TO LPG GENERIC ACS.CoNGLP1 SAFETY ASSESSMENT CRITERIA INITIAL & RE-ASSESSMENT DOMESTIC NATURAL GAS TO LPG GENERIC Issue 4.2 ACS. SMB 1 CoNGLP1 INITIAL & RE-ASSESSMENT Range All LPG fittings. Comprises: 2. Gas emergency

More information

Technical Data. UL Listing is based on the following criteria:

Technical Data. UL Listing is based on the following criteria: Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve with Trim Inch and 6 Inch (DN and DN5) General Description The TYCO DV-5 Deluge Valve with Trim is a diaphragm-style valve that depends upon water

More information

Pipe threads for tubes and fittings where pressure-tight joints are not made on the threads. (requires PTFE sealing tape or liquid sealant).

Pipe threads for tubes and fittings where pressure-tight joints are not made on the threads. (requires PTFE sealing tape or liquid sealant). Fittings for CO 2 Pipe Threads Pipe thread references quoted in this catalogue conform with the requirements specified in the latest issue and amendments of the following ISO Standards: ISO 7-1 (BS21)

More information

Product Manual B-Safety ClassicLine & PremiumLine Emergency Eyewash and Eye/Face Wash Equipment

Product Manual B-Safety ClassicLine & PremiumLine Emergency Eyewash and Eye/Face Wash Equipment Product Manual B-Safety ClassicLine & PremiumLine Emergency Eyewash and Eye/Face Wash Equipment 1. Application Emergency eyewash and eye/face wash equipment are prescribed first aid installations for workplaces

More information

ACCUMULATOR OPERATING & MAINTENANCE INSTRUCTIONS

ACCUMULATOR OPERATING & MAINTENANCE INSTRUCTIONS ACCUMULATOR OPERATING & MAINTENANCE INSTRUCTIONS READ ALL INSTRUCTIONS PRIOR TO INSTALLATION AND OPERATION TO AVOID POSSIBLE INJURY Warning: Always consider any accumulator to contain pressure until proven

More information

MEDICAL EQUIPMENT CATALOG

MEDICAL EQUIPMENT CATALOG THE MOST TRUSTED MEDICAL EQUIPMENT IN NORTH AMERICA MEDICAL EQUIPMENT CATALOG Total Components Including Bulk Oxygen Supply, Back up and Delivery Equipment Designs for High Pressure, Liquid or Bulk Applications

More information

SIMPLAIR PIPING TOOL. JXT Company

SIMPLAIR PIPING TOOL. JXT Company SIMPLAIR PIPING INGERSOLL-RAND SIMPLAIR PIPING With push-in fittings and lightweight anodized aluminum pipe, a SimplAir system provides ideal connection throughout your entire air distribution system.

More information

Safety Powder Spray Systems

Safety Powder Spray Systems Instruction Sheet P/N 107 952C Safety Powder Spray Systems 1. Introduction This section contains general safety instructions for using your Nordson equipment. Task- and equipment-specific warnings are

More information

THE BP-301 SERIES. Operating and Service Manual. Series includes all variants of BP-301 (LF 0.1Cv / MF 0.5Cv)

THE BP-301 SERIES. Operating and Service Manual. Series includes all variants of BP-301 (LF 0.1Cv / MF 0.5Cv) THE BP-301 SERIES Operating and Service Manual Series includes all variants of BP-301 (LF 0.1Cv / MF 0.5Cv) Issue B October 2015 1 TABLE OF CONTENTS 1. Description... 3 2. Installation... 3 3. Operation...

More information