Guidance on the maintenance and inspection of fixed CO 2 fire-extinguishing systems

Size: px
Start display at page:

Download "Guidance on the maintenance and inspection of fixed CO 2 fire-extinguishing systems"

Transcription

1 Translation. Only the Danish document has legal validity. Guidance no of 9 July 2014 issued by the Danish Maritime Authority Guidance on the maintenance and inspection of fixed CO 2 fire-extinguishing systems 1. Introduction 1.1 This guidance is a reproduction of the circular MSC.1/Circ.1318 issued by the International Maritime Organization (IMO), Guidelines for the maintenance and inspections of fixed carbon dioxide fire-extinguishing systems. 1.2 The purpose of this guidance is to provide a minimum level of maintenance and inspection of CO 2 fire-extinguishing systems in ships so that the systems are in good working order and ready for immediate use. The guidance supplements the manufacturer's maintenance manual for the systems. Maintenance and inspection may be carried by crewmembers holding the necessary competences; however, certain maintenance functions and inspections should be carried by especially trained personnel. This should be clearly stated in the ship's maintenance plans. 2. Safety plan 2.1 When maintenance and inspection of CO 2 fire-extinguishing systems are carried, the necessary safety precautions shall be followed. Prior to performing any work, a safety plan shall be developed to account for all personnel involved, including the ship's crew and service personnel. An effective communication system shall be established between the service/inspection personnel and the ship's other crewmembers. Measures shall be taken to avoid accidental release of the system, such as insertion of a blind flange after the main stop valve or any other means of preventing accidental release of the system. The entire crew and other personnel shall be informed that work is on-going. 3. Maintenance and inspection plan 3.1 CO 2 fire-extinguishing systems shall be kept in good working order and ready for immediate use. Maintenance and inspection should be carried in accordance with the ship's maintenance plan so as to secure the functions and reliability of the system. The plan should be part of the ship's ISM system and be based on the manufacturer's recommendations, including: 1) maintenance and inspection procedures and instructions; 2) required schedules for periodic maintenance and inspection; 3) listing of recommended spare parts; and 4) records of inspection and maintenance, including description of works carried to maintain the operability of the system. 4. Monthly inspections 4.1 At least once a month, a visual inspection should be made of the overall system condition for obvious signs of damage, and this shall contain a verification of the following: 1) all valves are in the proper position (open or closed); 2) all releasing controls are in the proper position and readily accessible for immediate use; 3) all piping and servo pipes/control pipes are intact and undamaged; 4) all pressure cylinders are in place and properly secured; and 5) all alarm devices are in place and undamaged. 4.2 In addition to the above, inspections of low-pressure CO 2 systems shall also verify that: 1

2 1) pressure gauges are reading the normal range; 2) the liquid CO 2 level indicator is reading within the proper level; 3) the manually operated storage tank main service valve is secured in the open position; and 4) the CO 2 vapour supply line valves are secured in the open position. 5. Annual inspections 5.1 The following minimum level of maintenance and inspection shall be carried in accordance with the manufacturer's instructions and safety recommendations: 1) the boundaries of the protected spaces are inspected visually in order to ensure that no modifications have been made that may have created uncloseable openings that would render the system ineffective; 2) all storage containers are inspected visually for any signs of damage, corrosion and loose mounting hardware. Cylinders that have leaked, have corroded, have indents or bulges are pressure tested or replaced; 3) all piping is inspected visually for damage, loose supports and corrosion. It is checked that there is free passage to and from all nozzles; 4) the manifold is inspected and it is verified that all flexible hoses and other fittings are correctly tightened; and 5) all entrance doors to the protected spaces close properly and are provided with a clear mark stating that the spaces are protected by CO 2 and shall be evacuated in case the alarm sounds. All remote releasing controls shall be checked for clear instructions and indications. 6. Minimum recommended maintenance 6.1 At least biennially in passenger ships or at each intermediate, periodical or renewal survey in cargo ships, the following maintenance should be carried (examples of checklists are enclosed as annexes 1 and 2): 1) All cylinders and pilot cylinders are weighed, or the content of the cylinders is verified in some other manner so as to check whether the content of each cylinder exceeds 90% of the nominal charge. Cylinders containing less than 90% of the nominal charge shall be recharged. The liquid level of CO 2 in low-pressure systems shall be checked so as to verify that the required quantity of CO 2 is available. 2) The date of the last pressure testing of all pressure cylinders, servo containers and pressure containers shall be checked. Pressure cylinders shall be periodically tested at least every ten years. At a 10-year inspection, a minimum of 10% of the total number of cylinders shall be checked. The control shall consist of an internal inspection and a hydrostatic test. If one or more cylinders fails, 50% of the total number of pressure cylinders shall be tested; if one more pressure cylinders fails, all the pressure cylinders shall be tested. Flexible hoses shall be replaced in accordance with the manufacturer's instructions; however, they should as a minimum be replaced every ten years. 3) It shall be checked that distributing pipes and nozzles for supplying CO 2 to the protected space are not blocked. This is checked by isolating each individual CO 2 pipe section and flowing dry air or nitrogen through them. 6.2 At least biennially in passenger ships or at each intermediate, periodical or renewal survey in cargo ships, the following maintenance should be carried by service technicians/specialists: 1) Where possible, all activators from the cylinders valves shall be dismounted and their functioning shall be tested at full working pressure through the pilot lines. Where this is not possible, the pilot lines shall be disconnected from the cylinders valves and blinded off or connected and tested with full 2

3 working pressure from the release station, whereafter a leak test is carried. In both cases, this shall be carried from the release station(s). In case manual pull cables/wires operate the remote release controls, it shall be checked that all cables and corner pulleys are in good condition, move freely and that an unreasonably great pull is not needed to activate the system; 2) all components of the cable carrying shall be cleaned and, if necessary, adjusted and all cable connections shall be adjusted. If the remote-release uses a pneumatic pressure, the connections shall be checked for leakages and the charge of the servo containers shall be checked. All controls and alarms shall function normally and the time-delay shall, if installed, prevent the release of CO 2 during the required period of time; and 3) when the above has been carried with a satisfactory result, the system shall be re-established in the normal operating condition. It shall be verified that all release controls are in the proper position and are connected to the correct control valves. All pressure gauges and interlocks, etc. shall be reset to zero and re-established in the normal operating condition. It shall be ensured that all valves are in the proper position (open or closed). Danish Maritime Authority, 9 July 2014 Per Sønderstrup / Palle Kristensen 3

4 Annex 1 Example of checklist for high-pressure CO 2 systems High-pressure CO 2 system Date Name of ship/system IMO no. Description of system No. Text To be filled in 1 Manufacture 2 Number of pressure cylinders 3 Pressure cylinder capacity (each) 4 Number of pilot cylinders/servo cylinders 5 Pilot cylinder capacity (each) 6 Number of distribution lines 7 Oldest cylinder pressure test date 8 Protected space(s) 9 Date flexible hoses fitted/renewed Description of inspection/test No. Description 1 The system is secured against accidental release by insertion of a blind flange after the main stop valves or in any other manner. 2 Contents in pressure cylinders checked by weighing. 3 Contents in pressure cylinders checked by liquid level indicator. 4 Contents of pilot cylinders checked. 5 All cylinder valves visually checked. 6 All cylinders, securing arrangements and connections checked. 7 Manifold visually inspected. 8 Manifold tested for leakage by applying dry working air. 9 Main stop valves and distribu- Not carried Not applicable Comments 4

5 No. Description tion valves visually inspected. 10 Main stop valves and distribution valves tested for operation. 11 Time-delay devices tested for correct setting (if installed). 12 Remote release systems visually inspected. 13 Remote release systems tested. 14 Servo tubing/pilot lines pressure tested at maximum working pressure and checked for leakage and blockage. 15 Pull cables/wires, pulleys, gang releases, etc. tested, serviced and tightened/adjusted as necessary. 16 Release stations visually inspected. 17 Alarms (audible/visual) tested. 18 Fan stop tested % of pressure cylinders and pilot cylinders pressure tested (every ten years). 20 Distribution lines and nozzles blown through by applying dry working air. 21 All doors, hinges and locks inspected. 22 All instruction and warning signs inspected. 23 All flexible hoses renewed and check valves in manifold inspected (every ten years). 24 Release control, control valves, distribution valves reconnected and system put back in service ready for immediate use. 25 Inspection date tags attached. Not carried Not applicable Comments 5

6 Example of checklist for low-pressure CO 2 system Annex 2 Low-pressure CO 2 system Date Name of ship/system IMO no. Description of system No. Text To be filled in 1 Manufacture 2 Number of tanks 3 Tank capacity (tonnes or m 3 ) 4 Number of pilot cylinders/servo cylinders 5 Pilot cylinder capacity (each) 6 Number of distribution lines 7 Protected space(s) Description of inspection/test No. Description 1 The system is secured against accidental discharge, e.g. by securing the tank main service valve in the closed position. 2 Distribution valves in the closed position. 3 Check correct function of liquid level indicator. 4 Contents of CO 2 tank checked by tank level indicator. 5 Contents of CO 2 tank checked by external level tube. 6 Contents of CO 2 tank checked by level control valve. 7 Supports of tank inspected. 8 Insulation on tank inspected. 9 Safety valves of tank inspected. 10 Safety valves of tank tested. 11 Contents of pilot cylinders checked. 12 Start/stop of cooling compressors tested. 13 All electrical alarms and indi- Not carried Not applicable Comments 6

7 No. Description cators tested. 14 Main manifold valves inspected. 15 Main manifold valves tested. 16 Distribution valves inspected. 17 Distribution valves tested. 18 Release stations inspected. 19 "Total flooding" release mechanism inspected. 20 "Total flooding" release mechanism tested. 21 Time delay devices checked for correct setting (if installed). 22 Alarms tested. 23 Fan stop tested. 24 Distribution lines and nozzles inspected. 25 Distribution lines and nozzles tested. 26 Distribution lines and nozzles blown through. 27 All doors, hinges and closing mechanisms checked. 28 All instruction plates checked. 29 Tank main service valve reopened and secured open. 30 System re-established in normal operation and ready for immediate use. 31 Inspection date tags attached. Not carried Not applicable Comments 7

Government of Bermuda Department of Maritime Administration BERMUDA SHIPPING NOTICE

Government of Bermuda Department of Maritime Administration BERMUDA SHIPPING NOTICE Government of Bermuda Department of Maritime Administration 2015 027 BERMUDA SHIPPING NOTICE Maintenance and Inspection of Fixed Carbon Dioxide Fire Extinguishing Systems Ref: SOLAS 74/88 as amended, Regulation

More information

Subject Maintenance, inspection and test of Fire-Protection Systems and Appliances on board the Panama-registered ships To whom it may concern Technic

Subject Maintenance, inspection and test of Fire-Protection Systems and Appliances on board the Panama-registered ships To whom it may concern Technic Subject Maintenance, inspection and test of Fire-Protection Systems and Appliances on board the Panama-registered ships To whom it may concern Technical Information No. TEC-0869 Date 14 October 2011 The

More information

2. Application This "Guidelines" applies to all ships. 3. General Requirements for the Maintenance and Inspection of Fire-protection Systems and Appli

2. Application This Guidelines applies to all ships. 3. General Requirements for the Maintenance and Inspection of Fire-protection Systems and Appli Subject Maintenance, inspection and test of Fire-Protection Systems and Appliances on board the Panama-registered ships To whom it may concern Technical Information No. TEC-0910 Date 25 June 2012 The Panama

More information

ADMINISTRATION REQUIREMENTS (Consolidated Version)

ADMINISTRATION REQUIREMENTS (Consolidated Version) ADMINISTRATION REQUIREMENTS (Consolidated Version) Merchant Shipping Directorate Transport Malta Ministry for Infrastructure, Transport and Communications Valletta, Malta 22 October, 2012 1 SOLAS 74 1.1

More information

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS Annex 3, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS The text of existing chapter 15 is replaced by the following: "1 Application This

More information

Water Mist Systems Inspection, Testing, and Maintenance of Water Mist Systems

Water Mist Systems Inspection, Testing, and Maintenance of Water Mist Systems Water Mist Systems Inspection, Testing, and Maintenance of Water Mist Systems Name of Property: Address: Phone Number: Inspector: Contract No.: Date: This Report Covers: Monthly Quarterly Annual Other

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S Preaction 346a 1. Description The 6 Model G-6000P Electric Release Preaction System Riser Assembly can be used as a Single Interlock Preaction System with Electric Release, or as a Double Interlock Preaction

More information

Periodical surveys of cargo installations on ships carrying liquefied gases in bulk

Periodical surveys of cargo installations on ships carrying liquefied gases in bulk (June 1999) (Rev.1 Mar 2006) (Rev.2 May 2007) (Rev.3 Mar 2010) (Corr.1 Feb 2011) (Rev.4 Oct 2013) Periodical surveys of cargo installations on ships carrying liquefied gases in bulk 1 General 1.1 Scope

More information

Periodic Survey of Fuel Installations on Ships other than Liquefied Gas Carriers utilizing gas or other low flash point fuels

Periodic Survey of Fuel Installations on Ships other than Liquefied Gas Carriers utilizing gas or other low flash point fuels (Jan 2017) Periodic Survey of Fuel Installations on Ships other than Liquefied Gas Carriers utilizing gas or other low flash point fuels CONTENTS 1. Application 2. Special Survey 2.1 Schedule 2.2 Scope

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 347a 1. Description Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems utilize the Viking G-6000P Valve. The small profile, lightweight, pilot operated

More information

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE 1 of 10 1. DESCRIPTION (Refer to Figures 1-3.) Viking supervised Single Interlocked Preaction Systems utilize a Viking Deluge Valve and a pneumatically pressurized automatic sprinkler system. The system

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 331a 1. Description Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems utilize the Viking G-3000P Valve. The small profile, lightweight, pilot-operated

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 348a 1. Description Viking supervised Surefire Preaction Systems utilize the Viking G-6000P Valve. The small profile, lightweight, pilot operated Viking G-6000P Valve comes complete

More information

LARGE DRY CHEMICAL, TWIN-AGENT, AFFF, HALON 1211, AND AQUASONIC (NITROGEN-OPERATED SYSTEMS) Pressure Regulator Test Manual

LARGE DRY CHEMICAL, TWIN-AGENT, AFFF, HALON 1211, AND AQUASONIC (NITROGEN-OPERATED SYSTEMS) Pressure Regulator Test Manual LARGE DRY CHEMICAL, TWIN-AGENT, AFFF, HALON 1211, AND AQUASONIC (NITROGEN-OPERATED SYSTEMS) Pressure Regulator Test Manual 002694 IntroductIon 8-1-11 Page 1 ForEWord This manual is intended for use with

More information

MSC Guidelines for Carbon Dioxide Fire Suppression Systems

MSC Guidelines for Carbon Dioxide Fire Suppression Systems C. J. Robuck, LCDR, Chief, Engineering Division References a. Title 46 CFR 34.15 (Subchapter D) b. Title 46 CFR 76.15 (Subchapter H) c. Title 46 CFR 95.15 (Subchapter I) d. Title 46 CFR 108.431 (Subchapter

More information

Common Discrepancies Uncovered on ADCI Diving Contractor & Training Program Audits

Common Discrepancies Uncovered on ADCI Diving Contractor & Training Program Audits Common Discrepancies Uncovered on ADCI Diving Contractor & Training Program Audits Ways to Set Your Company or School Up For Success on ADCI Audits and Reduce Costs In most instances, all discrepancies

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 333a 1. Description Viking supervised Surefire Preaction Systems Utilize the Viking G-3000P Valve. The small profile, lightweight, pilot-operated Viking G-3000P Valve comes complete

More information

Annual Inspection and Calibration Checklist VAF Oilcon MK-6(M) MEPC.108(49) Page 1 of 5

Annual Inspection and Calibration Checklist VAF Oilcon MK-6(M) MEPC.108(49) Page 1 of 5 Page 1 of 5 Vessel Name: Serial number MCU: Serial Number EPU: Serial Number Skid: Mains Supply: V AC @ Hz Software version MCU: Software version EPU: K-factor Cell: K-factor Skid Flowmeter: P/L Maximum

More information

PASSENGER SHIPS Guidelines for preparation of Hull Structural Surveys

PASSENGER SHIPS Guidelines for preparation of Hull Structural Surveys (Feb 2010) PASSENGER SHIPS Guidelines for preparation of Hull Structural Surveys Contents 1 Introduction 2 Preparations for Survey 2.1 General 2.2 Conditions for survey 2.3 Access to structures 2.4 Survey

More information

Installation and operating manual. Pneumatic control station LK product no: PCS 1-10

Installation and operating manual. Pneumatic control station LK product no: PCS 1-10 LK product no: PCS 1-10 Article no: 74503 Revision:8 Article no: 74503 Revision: 8 2 (23) Contents 1. General information... 5 2. Safety precautions... 5 2.1 Significance of symbols... 5 2.2 Explanatory

More information

Working Environment Safety Assessment

Working Environment Safety Assessment For your own safety and/or safety of your workforce, and to improve the efficiency of your business practices, you should be aware of, and be up to date with, the key safety issues and good practices relevant

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE April 9, 2009 Preaction 326a 1. DESCRIPTION Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems utilizing the Viking G-4000P Deluge Valve. The small profi le, lightweight,

More information

HYDROSTATIC LEAK TEST PROCEDURE

HYDROSTATIC LEAK TEST PROCEDURE This information is proprietary and shall not be disclosed outside your organization, nor shall it be duplicated, used or disclosed for purposes other than as permitted under the agreement with Kinetics

More information

RULES PUBLICATION NO. 119/P

RULES PUBLICATION NO. 119/P RULES PUBLICATION NO. 119/P PERIODIC SURVEYS OF FUEL INSTALLATIONS ON SHIPS OTHER THAN LIQUEFIED GAS CARRIERS UTILIZING GAS OR OTHER LOW FLASH POINT FUELS 2019 January Publications P (Additional Rule Requirements)

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S Page 1 of 13 1. DESCRIPTION The Viking 6 Model G-6000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler

More information

RESOLUTION A.855(20) adopted on 27 November 1997 STANDARDS FOR ON-BOARD HELICOPTER FACILITIES

RESOLUTION A.855(20) adopted on 27 November 1997 STANDARDS FOR ON-BOARD HELICOPTER FACILITIES A 20/Res.855 17 December 1997 Original: ENGLISH ASSEMBLY 20th session Agenda item 9 RESOLUTION A.855(20) adopted on 27 November 1997 THE ASSEMBLY, STANDARDS FOR ON-BOARD HELICOPTER FACILITIES RECALLING

More information

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection February 9, 1998 Foam 201a 1. DESCRIPTION A Deluge Bladder Tank Foam/Water System is a standard deluge system capable of discharging a foam/water solution automatically through open sprinklers, spray nozzles,

More information

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY Page 1 of 13 1. DESCRIPTION The Viking 3 Model G-3000 Dry Valve Riser Assembly is equipped with a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry

More information

FOGEX HIGH-PRESSURE WATER MIST CYLINDER SYSTEMS

FOGEX HIGH-PRESSURE WATER MIST CYLINDER SYSTEMS Manual FOGEX HIGH-PRESSURE WATER MIST CYLINDER SYSTEMS User Guide Issue 1 October 2004 Assessed to ISO 9001: 2000 Certificate number 018 Chapter 2 Safety and Environmental Considerations Safety is of paramount

More information

TABLE OF CONTENTS PART 2 - CONFINED SPACES

TABLE OF CONTENTS PART 2 - CONFINED SPACES May 11, 2006 TABLE OF CONTENTS PART 2 - CONFINED SPACES Page DEFINITIONS... 2-1 GENERAL... 2-2 RESPONSIBILITIES... 2-2 HAZARD ASSESSMENT AND WORK PROCEDURES... 2-3 IDENTIFICATION AND ENTRY PERMITS... 2-3

More information

TECHNICAL DATA. Q= Cv S

TECHNICAL DATA. Q= Cv S Page 1 of 13 1. DESCRIPTION The Viking 4 inch Model G-4000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry

More information

Focus Area Campaign for November 2014 SCBA

Focus Area Campaign for November 2014 SCBA Focus Area Campaign for 2014-2015 November 2014 SCBA SMS Reference SBP 13.04 FTM 04.06 FM 13 FM ANX 1,2 &3 and APP 1 H&S 05.04 H&S 06.02 ECM 05.08 ECM 09.03 ECM 14.02 MTM 05.08 Guidance for the FOCUS area

More information

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13 Page 1 of 13 1. Description The Viking 2 Model G-2000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler

More information

AcornVac Vacuum Plumbing Systems - Trouble Shooting Guide

AcornVac Vacuum Plumbing Systems - Trouble Shooting Guide AcornVac Vacuum Plumbing Systems - Trouble Shooting Guide 1. Accumulators Problem Accumulator is overflowing If Accumulator continues to overflow Correction 1. Push and hold the manual activation button

More information

ACCU-PULSE Installation and Operation Instructions

ACCU-PULSE Installation and Operation Instructions ACCU-PULSE Installation and Operation Instructions Pump Discharge Installation: Chargeable Models Step 1: Mounting Position Mount ACCU-PULSE as close to the pump discharge as possible to absorb the pulse

More information

RESOLUTION MSC.397(95) (adopted on 11 June 2015) AMENDMENTS TO PART A OF THE SEAFARERS' TRAINING, CERTIFICATION AND WATCHKEEPING (STCW) CODE

RESOLUTION MSC.397(95) (adopted on 11 June 2015) AMENDMENTS TO PART A OF THE SEAFARERS' TRAINING, CERTIFICATION AND WATCHKEEPING (STCW) CODE RESOLUTION MSC.397(95) (adopted on 11 June 2015) THE MARITIME SAFETY COMMITTEE, RECALLING Article 28(b) of the Convention on the International Maritime Organization concerning the functions of the Committee,

More information

Effective protection thanks to the latest technology

Effective protection thanks to the latest technology Effective protection thanks to the latest technology Fire protection is a top priority for any company, institution or public space. An accident of this type can irreparably affect the building, property

More information

Using propane cylinders safely

Using propane cylinders safely Using propane cylinders safely This leaflet is for the safe use of Calor Gas propane cylinders. If you have any queries please contact your local retailer. Calor supplies Liquefied Petroleum Gas (LPG)

More information

ST. VINCENT AND THE GRENADINES

ST. VINCENT AND THE GRENADINES ST. VINCENT AND THE GRENADINES MARITIME ADMINISTRATION CIRCULAR N SOL 036 Amendment to SOLAS 1974 as amended, Resolution MSC.256 (84) TO: SHIPOWNERS & SHIPS OPERATORS & MANAGERS, MASTERS SURVEYORS TO FLAG

More information

TEST BENCH SAFETY VALVES ¼ - 5 DN10 DN125

TEST BENCH SAFETY VALVES ¼ - 5 DN10 DN125 TEST BENCH SAFETY VALVES ¼ - 5 DN10 DN125 Model: VC-40-VYC Table of contents 1. - Installing the test bench 1.1.1- Connecting the compressed air / nitrogen source 1.1.2- Maximum test pressure according

More information

AREA VALVE SERVICE UNITS

AREA VALVE SERVICE UNITS AREA VALVE SERVICE UNITS. Unit 8, McKenzie Industrial Park, Tel No.: 44 (0) 161 428 7200 Bird Hall Lane, Fax No.: 44 (0) 161 428 7010 Stockport, Email: info@p3-phoenix.com U.K., SK3 0SB www.p3-phoenix.com

More information

Guidelines for Clean Agent Fire Suppression Systems

Guidelines for Clean Agent Fire Suppression Systems References: S. T. Brady, Chief, Engineering Division a. National Fire Protection Association (NFPA) 2001, 2012 Edition (Clean Agent Fire Extinguishing ) b. International Code for Fire Safety (FSS), Chapter

More information

TOOL BOX 031- SERVICE OF CARTRIDGE EXTINGUISHERS

TOOL BOX 031- SERVICE OF CARTRIDGE EXTINGUISHERS A. SANS1475.1:2012 3.8 gas cartridge Cylinder that is attached externally to the extinguisher cylinder and that contains either compressed or liquefied gas. 3.14.1 External cartridge operated type Extinguisher

More information

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1 Dry 131h 1. DESCRIPTION The Viking Model G-1 Maintenance Air Compressor is an electric motor-driven, aircooled, single-stage, oil-less compressor. The unit is equipped with a check valve and provides a

More information

GUIDELINES FOR SURVEY OF OIL FLOATING STORAGE VESSELS FIXED AT ANCHORAGE

GUIDELINES FOR SURVEY OF OIL FLOATING STORAGE VESSELS FIXED AT ANCHORAGE GUIDANCE NOTES GD03-2017 CHINA CLASSIFICATION SOCIETY GUIDELINES FOR SURVEY OF OIL FLOATING STORAGE VESSELS FIXED AT ANCHORAGE 2017 Effective from 1 March 2017 BEIJING Chapter 1 GENERAL 1.1 Application

More information

MUD 1. Vent check valves. Instruction and maintenance manual.

MUD 1. Vent check valves. Instruction and maintenance manual. MUD 1 Vent check valves Instruction and maintenance manual. Version: 04-02-2011. 2 List of Contents 1. INTRODUCTION 3 1.1 The Problem... 3 1.2 The Solution... 3 2. RULES AND REGULATIONS 3 2.1 General requirements....

More information

User Information Sheet 013

User Information Sheet 013 User Information Sheet 013 Formerly LPGA Technical Memorandum NO.81 Issue 2 September 2007 ACME threaded couplings 1 INTRODUCTION ACME threaded couplings/end fittings are widely used for LPG transfer operations

More information

Piped Air SCBA Refilling System Standard

Piped Air SCBA Refilling System Standard WALT WHITE Fire Chief 5770 Freeport Blvd., Suite 200 Sacramento, CA 95822-3516 Ph: (916) 808-1300 Fax: (916) 808-1629 www.sacfire.org Piped Air SCBA Refilling System Standard SCOPE: This specification

More information

Testing Procedures of Watertight Compartments

Testing Procedures of Watertight Compartments (1996) (Rev.1 Feb 2001) (Rev.2 May 2001) (Rev.3 May 2010) (Rev.4 Aug 2012) Testing Procedures of Watertight Compartments.1 Application Revision 4 of this UR is to be complied with in respect of the testing

More information

Instruction Manual - Diaframless TM Ejector Chlorine, Sulfur Dioxide and Ammonia

Instruction Manual - Diaframless TM Ejector Chlorine, Sulfur Dioxide and Ammonia Instruction Manual - Diaframless TM Ejector Chlorine, Sulfur Dioxide and Ammonia - 1-122.6010.6 These instructions describe the installation, operation and maintenance of the subject equipment. Failure

More information

TECHNICAL DATA. System water supply pressure enters the priming chamber of the deluge valve (A.1) through the 1/4 (8 mm) priming line, which

TECHNICAL DATA. System water supply pressure enters the priming chamber of the deluge valve (A.1) through the 1/4 (8 mm) priming line, which January 27, 2012 307a 1. (Refer to Figures 1-3.) A Viking Non-Interlocked Preaction system utilizes a Viking Deluge Valve to control water flow into system piping equipped with closed sprinklers. Under

More information

INTERPLANT STANDARD - STEEL INDUSTRY

INTERPLANT STANDARD - STEEL INDUSTRY INTERPLANT STANDARD - STEEL INDUSTRY IPSS STANDARD MAINTENANCE PRACTICE FOR PNEUMATIC OPERATED SHUT OFF VALVES No Corresponding IS Exists IPSS: 2-07-105-15 Formerly-: (New Standard) 0. Foreword 0.1. Interplant

More information

CLASS DH - PNEUMATIC TESTING - GREATER THAN 1 BAR (15 PSIG)

CLASS DH - PNEUMATIC TESTING - GREATER THAN 1 BAR (15 PSIG) Page 1 of 10 CLASS DH - PNEUMATIC TESTING - GREATER THAN 1 BAR (15 PSIG) 1. SCOPE 1.1 To provide definitive requirements for HIGH PRESSURE PNEUMATIC testing of piping systems according to ASME B31.3. This

More information

SAFETY POLICY AND PROCEDURE MANUAL All Euramax Subsidiaries. Number K-3.0 Welding Safety Procedures

SAFETY POLICY AND PROCEDURE MANUAL All Euramax Subsidiaries. Number K-3.0 Welding Safety Procedures Number K-3.0 Issued: 1/2009 Revised: 3/2016 Page 1 of 3 1.0 PURPOSE: To standardize procedures associated with production and maintenance welding and to minimize the potential risk of accident or injury

More information

ST. VINCENT AND THE GRENADINES

ST. VINCENT AND THE GRENADINES ST. VINCENT AND THE GRENADINES MARITIME ADMINISTRATION CIRCULAR N SOL 001 Rev. 2 SOLAS 74 as Amended Ch. III Revised Reg. 32.3 IMO Resolution MSC.152 (78), MSC/Circ. 1046, MSC/Circ. 1047 MSC/Circ. 1114

More information

MANUAL GAS MANIFOLDS

MANUAL GAS MANIFOLDS MANUAL GAS MANIFOLDS Phoenix Pipeline Products Limited. Unit 8, McKenzie Industrial Park, Tel No.: 44 (0) 161 428 7200 Bird Hall Lane, Fax No.: 44 (0) 161 428 7010 Stockport, Email: info@p3-phoenix.com

More information

Isolation of power supplies

Isolation of power supplies Isolation of power supplies Guidance Note 14 Jan 14 1 Isolation of power supplies Legal Obligations The Health and Safety at Work Act 1974 sets out the general health and safety duties of employers, employees

More information

TOOL BOX 033- HOSEREEL SERVICE / FAULT FINDING

TOOL BOX 033- HOSEREEL SERVICE / FAULT FINDING In SANS 10105 you will find the Minimum water pressure for both the hydrant and the hose reel. Which is 300KPA Manufacturing Standard SANS 543 1 Front & Back plates 2 Curved Plate 3 Waterway assembly 4

More information

Installation Instructions and valve Maintenance Rev. 0 of 29/09/15

Installation Instructions and valve Maintenance Rev. 0 of 29/09/15 Pag1 ASSEMBLING PROCEDURE AND VALVE MAINTENANCE 1.0.... Safety Information 2.0.. INTRODUCTION 3.0 VARIATIONS 4.0..ASSEMBLING PROCEDURE FOR THE STEM 5.0 ASSEMBLING PROCEDURE FOR OUTLET CONNECTIONS 6.0 PROCEDURE

More information

Cable Pressurization Buffering

Cable Pressurization Buffering Cable Pressurization Buffering What This Practice Is About Introduction This practice describes the various buffering practices that are used to protect the integrity of the pressurized cable network during

More information

Residential and Small Commercial

Residential and Small Commercial Page 1 of 7 Companies Affected: NIPSCO CGV CMD CKY COH CMA CPA REFERENCE 49 CFR Part 192.353, 192.355, 192.357 1. GENERAL The purpose of this standard is to provide requirements for the inspection or installation

More information

Sinorix MANOB480, MANOCAB, MANOEOL Installation Maintenance

Sinorix MANOB480, MANOCAB, MANOEOL Installation Maintenance Sinorix MANOB480, MANOCAB, MANOEOL Installation Maintenance Building Technologies 2017-10-24 Control Products and Systems Legal notice Legal notice The specifications and availability are subject to change

More information

CIRCULAR LETTER. Subject: Paris and Tokyo MoUs - Concentrated Inspection Campaign (CIC) on Crew Familiarization for Enclosed Space Entry

CIRCULAR LETTER. Subject: Paris and Tokyo MoUs - Concentrated Inspection Campaign (CIC) on Crew Familiarization for Enclosed Space Entry CIRCULAR LETTER Piraeus, 28 August 2015 Subject: Paris and Tokyo MoUs - Concentrated Inspection Campaign (CIC) on Crew Familiarization for Enclosed Space Entry The Paris and Tokyo MoUs on Port State Control

More information

RCV-125 REMOTE CONTROL SYSTEM IMPORTANT WARNING FOR SAFER BLAST CLEANING

RCV-125 REMOTE CONTROL SYSTEM IMPORTANT WARNING FOR SAFER BLAST CLEANING OWNER S MANUAL RCV-125 REMOTE CONTROL SYSTEM IMPORTANT WARNING FOR SAFER BLAST CLEANING 1. Use protective equipment: Abrasive-resistant clothing, safety shoes, leather gloves, ear protection, CE-approved

More information

Instruction Manual O-Ring Ejector Chlorine & Sulfur Dioxide to 500 PPD (10 kg/h)

Instruction Manual O-Ring Ejector Chlorine & Sulfur Dioxide to 500 PPD (10 kg/h) Instruction Manual O-Ring Ejector Chlorine & Sulfur Dioxide to 500 PPD (10 kg/h) 100 PPD (2 kg/h) Maximum 250 PPD (5 kg/h) Maximum 500 PPD (10 kg/h) Maximum - 1-122.6006.9 These instructions describe the

More information

Fleet in Service, Technical Support (Section MCTDE665) Checklist for Maintenance of Safety Equipment. Hamburg, January 2014

Fleet in Service, Technical Support (Section MCTDE665) Checklist for Maintenance of Safety Equipment. Hamburg, January 2014 Fleet in Service, Technical Support (Section MCTDE665) Checklist for Maintenance of Safety Equipment Hamburg, January 2014 0 Rev. 01/2014 Introduction This overview by Germanischer Lloyd provides requirements

More information

Installation of Your SprayMaster System

Installation of Your SprayMaster System Installation of Your SprayMaster System 1. At the installation site, remove all equipment from the corrugated box and the polyethylene drum and replace the drum lid. Check the picture to identify each

More information

Operating Instructions for BAIR22-6 AIR-POWERED CRIMPING TOOL

Operating Instructions for BAIR22-6 AIR-POWERED CRIMPING TOOL Operating Instructions for BAIR22-6 AIR-POWERED CRIMPING TOOL Read and understand all of the instructions and safety information in this manual before operating or servicing this tool. Table of Contents

More information

LNG Marine Loading Arms and Manifold Draining, Purging and Disconnection Procedure

LNG Marine Loading Arms and Manifold Draining, Purging and Disconnection Procedure LNG Marine Loading Arms and Manifold Draining, Purging and Disconnection Procedure i The Society of International Gas Tanker and Terminal Operators (SIGTTO) The Society of International Gas Tanker and

More information

Medical Gas Control Panel

Medical Gas Control Panel Medical Gas Control Panel INSTALLATION & MAINTENANCE MANUAL 255105 (Rev. 6) 2018-04 2 255105 (Rev. 6) 2018-04 1.0 User Responsibilities The information contained in this installation and operation maintenance

More information

Installation of Ballast Water Management Systems

Installation of Ballast Water Management Systems (Sept 2015) (Rev.1 May 2016) Installation of Ballast Water Management Systems 1. Application In addition to the requirements contained in BWM Convention (2004), the following requirements are applied to

More information

Manual Actuated Boiler Blowdown Valves

Manual Actuated Boiler Blowdown Valves Manual Actuated Boiler Blowdown Valves Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Operation 5. Maintenance 6. Spare parts p.1 1. Safety

More information

ANNEX 4 ALTERNATIVE TEXT FOR OPERATIONAL GUIDELINES FOR VERIFICATION OF DAMAGE STABILITY REQUIREMENTS FOR TANKERS

ANNEX 4 ALTERNATIVE TEXT FOR OPERATIONAL GUIDELINES FOR VERIFICATION OF DAMAGE STABILITY REQUIREMENTS FOR TANKERS Annex 4, page 1 ANNEX 4 ALTERNATIVE TEXT FOR OPERATIONAL GUIDELINES FOR VERIFICATION OF DAMAGE STABILITY REQUIREMENTS FOR TANKERS GUIDELINES FOR VERIFICATION OF DAMAGE STABILITY FOR TANKERS PART 2 OPERATIONAL

More information

III. Identify the initial installation requirements for standpipe systems

III. Identify the initial installation requirements for standpipe systems Design Basic Design Requirements 1. Must provide 500 GPM at 65 PSI to the highest most remote standpipe riser outlet. 2. 250 GPM for each additional standpipe total not to exceed 2500 GPM III. Identify

More information

Model: 43T. Bermad Pressure Relief Valve

Model: 43T. Bermad Pressure Relief Valve Model: 43T Bermad Pressure Relief Valve Installation Operation Maintenance Manual () Rev.C1_01.08.17 Page 1 of 10 Safety First BERMAD believes that the safety of personnel working with and around our equipment

More information

Design DSA Steam-Atomized Desuperheater

Design DSA Steam-Atomized Desuperheater Instruction Manual DSA Desuperheater Design DSA Steam-Atomized Desuperheater Contents Introduction............................... 1 Scope of Manual......................... 1 Description..............................

More information

Bermad Pressure Reducing. Model: 42T

Bermad Pressure Reducing. Model: 42T Bermad Pressure Reducing Pilot Operated Pressure Control Valve Model: 42T Installation Operation Maintenance Manual (IOM) REV. 27.7.17 Page 1 of 12 Safety First BERMAD believes that the safety of personnel

More information

CLASS D - SENSITIVE LEAK TEST GAS AND BUBBLE METHOD. 1.1 To provide definitive requirements for PNEUMATIC pressure testing of piping systems.

CLASS D - SENSITIVE LEAK TEST GAS AND BUBBLE METHOD. 1.1 To provide definitive requirements for PNEUMATIC pressure testing of piping systems. Page 1 of 7 CLASS D - SENSITIVE LEAK TEST GAS AND BUBBLE METHOD 1. SCOPE 1.1 To provide definitive requirements for PNEUMATIC pressure testing of piping systems. 1.2 The piping system as used herein is

More information

MoveRoll Conveyor Operating and Maintenance Manual

MoveRoll Conveyor Operating and Maintenance Manual MoveRoll Conveyor Operating and Maintenance Manual 1. Read this first! This manual contains information for protection of personnel in the roll handling area from possible injury and/or equipment damage.

More information

Method Statement: Testing Dry Riser System

Method Statement: Testing Dry Riser System Method Statement: Testing Dry Riser System Page 1 of 6 Scope of work Test dry riser system in accordance with BS 5306. Definitions For the purposes of this document, the following definitions apply Rising

More information

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST OIL-LESS TYPE IMPORTANT: PLEASE READ CAREFULLY BEFORE STARTING OPERATIONS. THE CONTENTS ARE FOR GENERAL INFORMATION OF ALL THE SIMILAR MODELS. Record

More information

CIRCULAR LETTER. Subject: Riyadh MoU - Concentrated Inspection Campaign (CIC) on Crew Familiarization for Enclosed Space Entry

CIRCULAR LETTER. Subject: Riyadh MoU - Concentrated Inspection Campaign (CIC) on Crew Familiarization for Enclosed Space Entry CIRCULAR LETTER Piraeus, 28 August 2017 Subject: Riyadh MoU - Concentrated Inspection Campaign (CIC) on Crew Familiarization for Enclosed Space Entry The Riyadh MoU on Port State Control (PSC) have announced

More information

Date of Issue: July 2016 Affected Publication: API Specification 16C, Choke and Kill Equipment, Second Edition, March 2015 ADDENDUM 1

Date of Issue: July 2016 Affected Publication: API Specification 16C, Choke and Kill Equipment, Second Edition, March 2015 ADDENDUM 1 Date of Issue: July 2016 Affected Publication: API Specification 16C, Choke and Kill Equipment, Second Edition, March 2015 ADDENDUM 1 Page 16, Section 4.6, delete the entire section and renumber all subsequent

More information

Part IV: Troubleshooting

Part IV: Troubleshooting Part IV: Troubleshooting Excessive Oil Carryover Pump-Up Time Test Excessive oil carryover can have adverse effects on the performance of pneumatic climate control systems. Although some oil entrainment

More information

with FE -13 TM Most DuPont FE-13 systems are designed with a concentration of 15.9% whereas the NOAEL level of this extinguishing agent is 30%.

with FE -13 TM Most DuPont FE-13 systems are designed with a concentration of 15.9% whereas the NOAEL level of this extinguishing agent is 30%. LPG Systems with FE -13 TM Most DuPont FE-13 systems are designed with a concentration of 15.9% whereas the NOAEL level of this extinguishing agent is 30%. The agent is stored in seamless drawn steel high

More information

SLOP RECEPTION AND PROCESSING FACILITIES

SLOP RECEPTION AND PROCESSING FACILITIES RULES FOR CLASSIFICATION OF SHIPS NEWBUILDINGS SPECIAL SERVICE AND TYPE ADDITIONAL CLASS PART 5 CHAPTER 8 SLOP RECEPTION AND PROCESSING FACILITIES JANUARY 2011 CONTENTS PAGE Sec. 1 General Requirements...

More information

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE February 9, 1998 Foam 101a A BLADDER TANK WITH 1. DESCRIPTION A Wet Pipe Bladder Tank Foam/Water System is a standard wet pipe automatic sprinkler system capable of discharging a foam/water solution automatically

More information

TOPLINE ELECTRONICS LTD CO2 CONTROL UNIT MANUAL

TOPLINE ELECTRONICS LTD CO2 CONTROL UNIT MANUAL TOPLINE ELECTRONICS LTD CO2 CONTROL UNIT MANUAL CO2 MANUAL Page 1 of 10 General This control equipment has been designed to add CO2 (carbon dioxide) to a swimming pool to control the ph level downwards.

More information

Compiled by: B Beard. Approved by: SH Carstens. Description of requirements and procedures for compact provers to be used as verification standards.

Compiled by: B Beard. Approved by: SH Carstens. Description of requirements and procedures for compact provers to be used as verification standards. 1. Scope Description of requirements and procedures for compact provers to be used as verification standards. 2. Reference documents Trade Metrology Act SANS1698 3. Policy A. BASIC REQUIREMENTS Compact

More information

ANNEX 2. RESOLUTION MSC.256(84) (adopted on 16 May 2008)

ANNEX 2. RESOLUTION MSC.256(84) (adopted on 16 May 2008) RESOLUTION MSC.256(84) (adopted on 16 May 2008) ADOPTION OF AMENDMENTS TO THE INTERNATIONAL CONVENTION FOR THE SAFETY OF LIFE AT SEA, 1974, AS AMENDED THE MARITIME SAFETY COMMITTEE, RECALLING Article 28(b)

More information

Guideline No.M-05(201510) M-05 AIR COMPRESSOR. Issued date: 20 October China Classification Society

Guideline No.M-05(201510) M-05 AIR COMPRESSOR. Issued date: 20 October China Classification Society Guideline No.M-05(201510) M-05 AIR COMPRESSOR Issued date: 20 October 2015 China Classification Society Foreword This Guideline constitutes the CCS rules, and establishes the applicable technical requirements

More information

STCW Code Table A-V/1-1-1 Specification of minimum standard of competence in basic training for oil and chemical tanker cargo operations

STCW Code Table A-V/1-1-1 Specification of minimum standard of competence in basic training for oil and chemical tanker cargo operations STCW Code Table A-V/1-1-1 Specification of minimum standard of in basic for oil and chemical tanker cargo operations Ref: https://www.edumaritime.net/stcw-code Source: IMO Contribute to Basic knowledge

More information

GUIDELINES. Systems. Pressure

GUIDELINES. Systems. Pressure GUIDELINES Pressure Systems Guidelines Pressure Systems Safety Regulations SI 2000 No 128 In-service Examination Requirements in Written Schemes of Examination Document Reference: PSG 07 Issue 01 Dated

More information

NORMAL OPERATING PROCEDURES Operating Parameter Information

NORMAL OPERATING PROCEDURES Operating Parameter Information Operating Parameter Information Each operator performing the normal operating procedures (routine checks) of the facility should be familiar with the current normal operating parameters of all systems

More information

Rules for Classification and Construction Additional Rules and Guidelines

Rules for Classification and Construction Additional Rules and Guidelines VI Rules for Classification and Construction Additional Rules and Guidelines 3 Machinery Installations 4 Guidelines for Equipment on Fire Fighting Ships Edition 2008 The following Guidelines come into

More information

Operator s Manual. with Maintenance Schedule. Fourth Edition Second Printing Part No

Operator s Manual. with Maintenance Schedule. Fourth Edition Second Printing Part No Operator s Manual with Maintenance Schedule Fourth Edition Second Printing Part No. 82297 Operator s Manual Fourth Edition Second Printing Important Read, understand and obey these safety rules and operating

More information

RESOLUTION A.567(14) adopted on 20 November 1985 REGULATION FOR INERT GAS SYSTEMS ON CHEMICAL TANKERS

RESOLUTION A.567(14) adopted on 20 November 1985 REGULATION FOR INERT GAS SYSTEMS ON CHEMICAL TANKERS INTERNATIONAL MARITIME ORGANIZATION A 14/Res.567 16 January 1986 Original: ENGLISH ASSEMBLY - 14th session Agenda item lo(b) IMO RESOLUTION A.567(14) adopted on 20 November 1985 THE ASSEMBLY, RECALLING

More information

FireLock NXT Preaction Valve with Series 798 Pneumatic/Pneumatic Actuator

FireLock NXT Preaction Valve with Series 798 Pneumatic/Pneumatic Actuator (DOUBLE-INTERLOCKED, PNEUMATIC/PNEUMATIC RELEASE) HANG THESE INSTRUCTIONS ON THE INSTALLED VALVE FOR EASY FUTURE REFERENCE WARNING WARNING Failure to follow instructions and warnings can cause product

More information

2 Sentry MCL Installation, Operation & Maintenance

2 Sentry MCL Installation, Operation & Maintenance Gas Liquid & Slurry Solid & Powder Steam & Water Installation, Operation & Maintenance Manual Original Instructions Liquid Sampling Manual Low-Emission Samplers S-GA-IOM-00249-7 11-17 Sentry MCL 966 Blue

More information

1.0 PURPOSE 2.0 SCOPE 3.0 DEFINITIONS. ANSI: American National Standards Institute. CCC: Chemical Control Centre

1.0 PURPOSE 2.0 SCOPE 3.0 DEFINITIONS. ANSI: American National Standards Institute. CCC: Chemical Control Centre Revision Date: 5/17/2016 Page: 1 of 13 Health & Safety has developed the emergency eyewash & safety shower equipment procedure which will be implemented in 3 phases over the next four years. Phase 1 will

More information