Instruction Manual O-Ring Ejector Chlorine & Sulfur Dioxide to 500 PPD (10 kg/h)

Size: px
Start display at page:

Download "Instruction Manual O-Ring Ejector Chlorine & Sulfur Dioxide to 500 PPD (10 kg/h)"

Transcription

1 Instruction Manual O-Ring Ejector Chlorine & Sulfur Dioxide to 500 PPD (10 kg/h) 100 PPD (2 kg/h) Maximum 250 PPD (5 kg/h) Maximum 500 PPD (10 kg/h) Maximum

2 These instructions describe the installation, operation and maintenance of the subject equipment. Failure to strictly follow these instructions can lead to an equipment rupture that may cause significant property damage, severe personal injury and even death. If you do not understand these instructions, please call Severn Trent Water Purification (STWP), Inc. for clarification before commencing any work at and ask for a Field Service Manager. Severn Trent Water Purification, Inc. reserves the rights to make engineering refinements that may not be described herein. It is the responsibility of the installer to contact STWP Inc. for information that cannot be answered specifically by these instructions. Any customer request to alter or reduce the design safeguards incorporated into STWP Inc. equipment is conditioned on the customer absolving STWP Inc. from any consequences of such a decision. STWP Inc. has developed the recommended installation, operating and maintenance procedures with careful attention to safety. In addition to instruction/operating manuals, all instructions given on labels or attached tags should be followed. Regardless of these efforts, it is not possible to eliminate all hazards from the equipment or foresee every possible hazard that may occur. It is the responsibility of the installer to ensure that the recommended installation instructions are followed. It is the responsibility of the user to ensure that the recommended operating and maintenance instructions are followed. Severn Trent Water Purification, Inc. cannot be responsible for deviations from the recommended instructions that may result in a hazardous or unsafe condition. STWP Inc. cannot be responsible for the overall system design of which our equipment may be an integral part of or any unauthorized modifications to the equipment made by any party other that STWP Inc. STWP Inc. takes all reasonable precautions in packaging the equipment to prevent shipping damage. Carefully inspect each item and report damages immediately to the shipping agent involved for equipment shipped F.O.B. Colmar or to STWP Inc. for equipment shipped F.O.B Jobsite. Do not install damaged equipment. SEVERN TRENT WATER PURIFICATION INC., COLMAR OPERATIONS COLMAR, PENNSYLVANIA, USA IS ISO 9001: 2000 CERTIFIED

3 TABLE OF CONTENTS 1 INTRODUCTION General Warranty Specifications OPERATION General Installation Ejector Vacuum Piping Vacuum Connections START-UP Vacuum Check SHUTDOWN SERVICE Nozzle Cleaning O-Ring Replacement Diaphragm Replacement Functional Test Recommended Torque Values TROUBLESHOOTING CHART FIGURES 1 Gas Feeder System Flow Diagram PPD (2 kg/h) Ejector PPD (5 kg/h) Ejector PPD (10 kg/h) Ejector

4 1 INTRODUCTION 1.1 General The ADVANCE ejectors are expertly engineered and carefully tested to assure yearsof satisfactory operation. They are constructed of the finest materials available for gas service. Correct installation and proper care will ensure best operation. Read instructions carefully and save for future reference. This instruction manual only covers our standard O-Ring ejector (Reference ). If another ejector is used, reference one of the following: Diaframless , Anti-siphon , Variable Orifice and NOTE: The Series 200 O-Ring ejectors are designed for use with Series 200 gas feeders. 1.2 Warranty See Bulletin for the ADVANCE equipment warranty. 1.3 Specifications Gas Flow Capacity Vacuum Tubing Size Inlet Nozzl e Outlet Diffuser 100 PPD (2 kg/h) 3/8" 1/2" 5/8" 1" hose/universal 3/4" thread Universal - 3/4" NPT male thread, spray or open-end, or 1" hose, 3/4" hose 250 PPD (5 kg/h) 1/2" 5/8" 1 1/4" thread 1 1/2" hose 1 1/4" thread 1 1/2" hose 500 PPD (10 kg/h) 5/8" 1 1/4" thread 1 1/2" hose 1 1/4" thread 1 1/2" hose Different inlet nozzle and diffuser combinations are available for the ejectors. Your particular combination was chosen for your application. a. A universal diffuser can be used four different ways; spray diffuser, open-end diffuser, 3/4" threaded connection, or 1" hose connection. Choose the type suited for the installation (spray is recommended for good mixing). If other than spray is desired, modify by cutting off the closed end. b. The ejector (nozzle and check valve assembly) may be located near the vacuum regulator. A wall mounting bracket is available for field assembly, and the universal diffuser can be modified for a pipe or hose connection. c. The entire diffuser-ejector assembly may be submersed in an open channel or tank. d. Diffuser tubes with corporation stops can be supplied for either close-coupled or remote ejectors. e. Corporation stops are recommended for high pressure pipeline applications and perforated pipe diffusers are recommended for good mixing in open tanks or channels Back Pressure Maximum back pressure at the point of application is 19 psig (1.3 bar). High pressure systems 20 to 140 psig (1.4 to 10 bar) can be accommodated with a high pressure ejector. Consult factory if higher than 140 psig (10 bar) back pressures are required

5 2 OPERATION 2.1 General The ejector is designed to complement Severn Trent Services Series 200 vacuum regulators. The ejector is the heart of the system providing the vacuum necessary to operate the vacuum regulator. The diaphragm ejector is to be used in continuous feed applications. 2.2 Installation - Figure 1 The ejector may be installed in any position, since the check valve is spring actuated. (However, downward water flow may cause cavitation and poor vacuum). The point of injection should be carefully chosen so the water pressure into which the gas is fed, is aslow as possible. If the ejector is installed in a pipe, the ejector-diffuser should not be installed in the top of the pipe where gas may discharge and collect in an empty area of the pipe. Diffuser penetration into the pipe should not exceed 1/3 of the diameter of the pipe. Proceed as follows to install pipe mounted close-coupled diffuser and ejector Unscrew the diffuser from the assembly. Do NOT install the ejector with the diffuser attached, or damage may occur Put Teflon tape on the diffuser pipe threads and screw the diffuser into the pipe by hand. Tighten carefully with pliers. (Make sure that the holes in the spray tube diffuser are in the main stream.) The end of an open- end type diffuser should not allow strong chemical solution to come in contact with pipe or fittings. (This will cause serious corrosion. Figure 1 - Gas Feed System Flow Diagram

6 2.2.3 Reconnect nozzle and check valve assembly to diffuser. The nozzle may extend through the assembly from either side. A gasket should be on each side. Screw the nozzle into the diffuser HAND TIGHT. (The check valve assembly may be installed in any position.) Other types of diffuser and ejector installations may be desired for certain applications: a. The ejector (nozzle and check valve assembly) may be located near the vacuum regulator. A wall mounting bracket is available for field assembly, and the universal diffuser can be modified for a pipe or hose connection. b. The entire diffuser-ejector assembly may be submersed in an open channel or tank. c. Diffuser tubes with corporation stops can be supplied for either close-coupled or remote ejectors. 2.3 Ejector Vacuum The ejector creates a vacuum only when sufficient pressure differential exists between the ejector inlet water versus the water outlet pressure. For example, if the diffuser were discharging into an empty basin (zero back pressure), the supply pressure to the nozzle requires about 25 psig (2 bar) to create enough vacuum to operate a 50 PPD (1 kg/h) vacuum regulator. A lower supply pressure or a higher back pressure would reduce the gas flow rate. Then for each 1 psig (0.07 bar) of back pressure above zero, the supply pressure must be increased about 2 to 3 psig (0.1 to 0.2 bar) above 25 psig (2 bar). A back pressure of 10 psig (0.7 bar) would therefore require about 55 psig (4 bar) supply pressure in order to operate the 50 PPD (1 kg/h) vacuum regulator. Also, the water supply line to the nozzle must be large enough to allow sufficient water flow (3/4" or larger pipe is recommended) and minimize friction losses. 2.4 Piping For most installations, the ejector water supply line should be brought to within 4-6 ft. (1-2 m) of the nozzle with rigid copper or iron pipe. A shutoff valve followed by a Y-strainer, and a hose adapter or pipe union should be installed to allow removal for service. A pressure gauge between the Y-strainer and the ejector can be a useful service tool. If the hose is used, connect the hose between the hose adapter or pipe union and the ejector nozzle. Clamp the hose securely at both ends with single or double clamps. 2.5 Vacuum Connections - See Figure 1 and Introduction, Gas Flow section Table A. Black polyethylene tubing is normally used for the vacuum line between the vacuum regulator and ejector. Use enough length for each line to allow vacuum regulator movement from one cylinder to another Remove the connector nut from the vacuum regulator connection and slip onto the tubing. Push the tubing onto the connector and tighten connector nut HAND TIGHT

7 3 START-UP 3.1 Vacuum Check The ejector, its water supply and solution lines, must be properly installed and checked before operating the vacuum regulator. Unless the ejector is creating a vacuum, the vacuum regulator will not work Disconnect the vacuum tubing from the ejector Open the ejector water supply valve. The ejector should now be in operation and creating a vacuum Put your finger on the vacuum connector opening and feel the vacuum. There should be no doubt that a vacuum exists. If there is no vacuum, be certain the supply pressure is sufficient and the nozzle or piping is not plugged. Correct the condition and obtain proper vacuum before proceeding with vacuum regulator operation. (Reference vacuum regulator instruction manual) Reconnect the vacuum tubing to the ejector. Leave the ejector running

8 4 SHUTDOWN WARNING Before disconnecting or disassembling the ejector, shutdown the system as described below. Failure to do so may result in serious injury or death. 1. Close the gas supply valve at the pressure source(s) to shut off the gas flow. This is normally the gas cylinder and/or container valve(s) supplying the gas dispensing (regulator) system. The rate valve on the dispensing system meter panel(s) is/are not to be used to shut off the gas flow. The float in the gas flowmeter(s) should drop to the bottom of the flow meter indicating zero (no gas feed) 2. Continue the flow of water through the ejector for a few minutes to remove all gas remaining in the feeder, pressure piping and vacuum tubing. While the ejector continues to operate remove the vacuum tubing from the gas inlet of the ejector to allow air to enter the unit further diluting the residual gas. Stop the ejector water flow and relieve all residual water pressure. Close any water supply and chemical solution valves to isolate the ejector

9 5 SERVICE It is recommended that the Gas Dispensing System be inspected and serviced a minimum of once per year. More frequent service periods may be required due to: 1) the type, quality and quantity of the gas being handled, 2) the complexity of the gas supply system, 3) the quality and quantity of water or process liquid being used to operate the ejector(s), and 4) operation procedures. More frequent service periods are especially indicated when venting of the VR is occurring during the one year operational period. This is usually indicative of foreign debris holding the inlet valve open or destruction of the inlet valve parts caused by the gas quality not up to industry purity standards. Preventative maintenance kits for each of the assemblies are available from the factory. Each kit contains all the parts and detailed instructions that are required for complete maintenance. All o-rings and gaskets that have been disturbed during the disassembly must be replaced during reassembly in order to insure safe, trouble free operation. Failure to replace these parts could result in a shortened operation period and bodily injury. 5.1 Nozzle Cleaning Refer to Figures 1, 2 or 3 and remove the nozzle as follows: Ejector Disassembly NOTE: After it has been confirmed that all residual gas has been evacuated and water pressure has been relieved, proceed as follows: Remove the connecting hose to the ejector assembly For 100 PPD (2 kg/h) ejectors, rotate the complete ejector body counterclockwise. This loosens the threaded portion of the nozzle from the diffuser, eliminating the need for pliers on the hose connection which may damage the plastic. For 250 & 500 PPD (5 & 10 kg/h) ejectors, remove the two (2) screws and loosen the flange to remove the nozzle. NOTE: Nozzle plugging can be caused by foreign material (pipe scale, stone, dirt accumulation). This can usually be blown out or pushed out with a wire. Build-up of deposits caused by iron, manganese or other material can usually be remove by immersing the nozzle in muriatic acid and rinsing. Some waters may cause an inoperable ejector and require nozzle cleaning every two months To reinstall the nozzle, insert the nozzle through the ejector body and fasten to the diffuser using new gaskets, or o-rings on each side of the ejector body. NOTE: These parts are plastic and excessive tightening may cause breakage. For 100 PPD (2 kg/h) ejectors, tighten only hand tight with the ejector body 90 to the left of its final position, then turn the complete assembly Reinstall the ejector supply hose or pipe and vacuum tubing. 5.2 O-Ring Replacement Ejectors contain an o-ring that should be checked and the o-ring/diaphragm bolt assembly replaced as necessary. 5.3 Diaphragm Replacement - Refer to Figures 2, 3 or Remove the four bolts holding the ejector together to expose the internal parts The diaphragm bolt assembly is tightened at the factory, but can usually be separated by using large, jaw pliers or a vice. All assemblies contain a support diaphragm. In high pressure applications, the assembly includes two thin plastic support diaphragms Replace the diaphragm and reassemble the diaphragm nut and bolt. These must be assembled tightly using jaw pliers or a special tool to tighten. Install the diaphragm assembly in the recess of the top hole, and bolt the two sections together. (Note diaphragm orientation on Figure 2, 3 or 4) No adjustments are necessary, but ensure both ends of the spring are square

10 5.4 Functional Test When the ejector is reassembled, a functional test of the check valve assembly is recommended to check for proper ejector assembly and prevent future flooding of the vacuum regulator Do not connect vacuum tubing to vacuum regulator Turn on water supply Verify vacuum at ejector Turn water supply off for approximately 5 minutes. If ejector is assembled properly, no water will leak from vacuum tubing. 5.5 Recommended Torque Values Torque values of 14 inch pounds for ejector body screws on units up to 500 PPD/10 kg/h are used at the factory, and are recommended guidelines for Reassembly of a repaired unit

11 Figure PPD (2 kg/h) Ejector

12 Figure PPD (5 kg/h) Ejector

13 Figure PPD (10 kg/h) Ejector

14 6 TROUBLE SHOOTING CHART Trouble Probable Cause Corrective Action 1. Insufficient ejector vacuum. a. Y-strainer in water supply dirty. b. Supply pressure too low. c. Back pressure too high. 1. Solution valve, if supplied, not fully open. 2. Solution line, if present, partially blocked. d. Velocity too low (cavitation.) e. Nozzle 1. Flow restricted 2. worn or damaged. f. Incorrect nozzle size. g. Improper installation. 2. Flooded flowmeter a. Dirt on the ejector o-ring. b. Worn or damaged diaphragm c. Improper application a. Clean Y-strainer b and c. Open solution valve; clean solution line; correct back pressure condition. d. Increase pressure to ejector. e-g. Clean nozzle and/or throat. See Service section and bulletin a. Clean or replace ejector o-ring. See Service section. b. Replace worn diaphragm. See Service section. c. See bulletin on hydraulic considerations. d. Use a slow acting solenoid valve. Extend vacuum line, at ejector, a few feet above the ejector to allow the water to empty the next time the ejector is placed in service. 3. O-Ring sealing surface of ejector top body is extruding into diaphram bolt. a. Rare chemical anomaly. a. Replace ejector P/N U top body with Design improvements may be made without notice. Represented by: Severn Trent Services 3000 Advance Lane Colmar, PA United States Tel Fax Web: marketing@severntrentservices.com MAY/ Copyright 2010 Severn Trent Services

Instruction Manual - Diaframless TM Ejector Chlorine, Sulfur Dioxide and Ammonia

Instruction Manual - Diaframless TM Ejector Chlorine, Sulfur Dioxide and Ammonia Instruction Manual - Diaframless TM Ejector Chlorine, Sulfur Dioxide and Ammonia - 1-122.6010.6 These instructions describe the installation, operation and maintenance of the subject equipment. Failure

More information

Instruction Manual Pressure Relief Valve and Rupture Disc Chlorine or Sulfur Dioxide, Series 869

Instruction Manual Pressure Relief Valve and Rupture Disc Chlorine or Sulfur Dioxide, Series 869 Instruction Manual Pressure Relief Valve and Rupture Disc Chlorine or Sulfur Dioxide, Series 869-1 - 115.6020.15 These instructions describe the installation, operation and maintenance of the subject equipment.

More information

Instruction Manual ADVANCE Series 480 Vacuum Regulator

Instruction Manual ADVANCE Series 480 Vacuum Regulator Instruction Manual ADVANCE Series 480 Vacuum Regulator 80 60 40 20 R - 1-100.6001.15 These instructions describe the installation, operation and maintenance of the subject equipment. Failure to strictly

More information

Chemical Injection Technologies Installation/Service Bulletin

Chemical Injection Technologies Installation/Service Bulletin Bulletin 4002 Chemical Injection Technologies Installation/Service Bulletin SUPERIOR Series CL-16/26/56 Automatic Switchover Gas Chlorinator - Installation & Operation IMPORTANT!! READ THESE PRECAUTIONS

More information

Instruction Manual Series 200 ADVANCE Cylinder or Ton Container Mounted Vacuum Regulators

Instruction Manual Series 200 ADVANCE Cylinder or Ton Container Mounted Vacuum Regulators Instruction Manual Series 200 ADVANCE Cylinder or Ton Container Mounted Vacuum Regulators 100 & 250 PPD (2 & 5 kg/h) Cylinder Mounted 500 PPD (10 kg/h) Cylinder Mounted 500 PPD (10 kg/h) Ton Container

More information

CAPITAL CONTROLS SERIES NXT3000

CAPITAL CONTROLS SERIES NXT3000 CAPITAL CONTROLS SERIES NXT3000 Modular design gas feed system with self contained automatic switchover capability. The Series NXT3000 Gas Feed System is a family of vacuumoperated, solution-feed gas dispensing

More information

Capital Controls Series NXT3000 Modular design gas feed system with self-contained automatic switchover capability.

Capital Controls Series NXT3000 Modular design gas feed system with self-contained automatic switchover capability. Capital Controls Series NXT3000 Modular design gas feed system with self-contained automatic switchover capability. The Series NXT3000 Gas Feed System is a family of vacuum-operated, solution-feed gas

More information

Model VR6 System. Installation, Operation & Maintenance

Model VR6 System. Installation, Operation & Maintenance Model VR6 System Installation, Operation & Maintenance General: All Archer Instruments chlorination systems are carefully designed and tested for years of safe, accurate field service. All Archer Instruments

More information

Gas Chlorination Systems Series E5000 Up to 100ppd Instruction Manual

Gas Chlorination Systems Series E5000 Up to 100ppd Instruction Manual Gas Chlorination Systems Series E5000 Up to 100ppd Instruction Manual All ENCHLOR Chlorination systems are carefully designed and tested for years of safe, accurate field service. All ENCHLOR Chlorination

More information

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual Fisher Controls Instruction Manual Type S301 & S302 Gas Regulators October 1981 Form 5180 WARNING Fisher regulators must be installed, operated, and maintained in accordance with federal, state, and local

More information

Vacuum Operated Liquid Chemical Feed Systems

Vacuum Operated Liquid Chemical Feed Systems Vacuum Operated Liquid Chemical Feed Systems Instruction Manual All HYDRO Chemical Feed systems are carefully designed and tested for years of safe, accurate field service. All HYDRO systems are tested

More information

Instruction Manual ADVANCE TM Wall Panel Gas Feeders Series WP70CV3

Instruction Manual ADVANCE TM Wall Panel Gas Feeders Series WP70CV3 LIQUID FIL DO NOT TAM Instruction Manual ADVANCE TM Wall Panel Gas Feeders Series WP70CV3 LIQUID FIL DO NOT TAM 500 PPD (10 kg/h Chlorine & Sulfur Dioxide 3000 PPD (60 kg/h Chlorine & Sulfur Dioxide Auto

More information

HGC-200 Hydro Gas Chlorinator

HGC-200 Hydro Gas Chlorinator HGC-200 Hydro Gas Chlorinator ProMinent Fluid Controls Pty Ltd Head Office: Unit 4, 4 Narabang Way BELROSE NSW 2085 AUSTRALIA (PO Box 85, BELROSE WEST NSW 2085) Phone: (02) 9450 0995 Fax: (02) 9450 0996

More information

1805 Series Relief Valves

1805 Series Relief Valves Instruction Manual Form 1211 1805 Series October 2011 1805 Series Relief Valves! WARNING Failure to follow these instructions or to properly install and maintain this equipment could result in an explosion

More information

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator. LRS(H)4 USER MANUAL Read the complete manual before installing and using the regulator. WARNING INCORRECT OR IMPROPER USE OF THIS PRODUCT CAN CAUSE SERIOUS PERSONAL INJURY AND PROPERTY DAMAGE. Due to the

More information

INSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION

INSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION INSTALLATION INSTRUCTIONS CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION The CVS Controls 67CFR Filter regulator is a pressure reducing supply regulator typically used for pneumatic

More information

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator. RS(H)10,15 USER MANUAL Read the complete manual before installing and using the regulator. WARNING INCORRECT OR IMPROPER USE OF THIS PRODUCT CAN CAUSE SERIOUS PERSONAL INJURY AND PROPERTY DAMAGE. Due to

More information

PRS(TC)4,8 USER MANUAL. Read the complete manual before installing and using the regulator.

PRS(TC)4,8 USER MANUAL. Read the complete manual before installing and using the regulator. PRS(TC)4,8 USER MANUAL Read the complete manual before installing and using the regulator. WARNING INCORRECT OR IMPROPER USE OF THIS PRODUCT CAN CAUSE SERIOUS PERSONAL INJURY AND PROPERTY DAMAGE. Due to

More information

Types 749B and R130 Changeover Manifolds

Types 749B and R130 Changeover Manifolds Instruction Manual MCK-1179 Types 749B and R130 June 2012 Types 749B and R130 Changeover Manifolds TYPE HSRL-749B TYPE 64SR/122 TYPE R130/21 TYPE 749B/21 Figure 1. Changeover Manifolds and Regulator Assemblies

More information

Installation, Operation, and Maintenance Manual

Installation, Operation, and Maintenance Manual Installation, Operation, and Maintenance Manual Welker Instrument Supply Pressure System Model WIC The information in this manual has been carefully checked for accuracy and is intended to be used as a

More information

Installation, Operation and Maintenance Manual for Back Pressure Regulator

Installation, Operation and Maintenance Manual for Back Pressure Regulator Installation, Operation and Maintenance Manual for Back Pressure Regulator Model 8860 2009 Groth Corporation IOM-8860 Rev. B 12541 Ref. ID: 95565 Page 2 of 13 Table of Contents I. INTRODUCTION 3 II. DESIGN

More information

APCO ARV CLEAN WATER AIR RELEASE VALVES. Model 50A

APCO ARV CLEAN WATER AIR RELEASE VALVES. Model 50A APCO ARV CLEAN WATER AIR RELEASE VALVES Model 50A Instruction D12013 February 2017 Instructions These instructions provide installation, operation and maintenance information for APCO ARV Clean Water Air

More information

Pressure Dump Valve Service Kit for Series 2300 Units

Pressure Dump Valve Service Kit for Series 2300 Units Instruction Sheet Pressure Dump Valve Service Kit for Series 00 Units. Overview The Nordson pressure dump valve is used to relieve hydraulic pressure instantly in Series 00 applicator tanks when the unit

More information

Float Operated Level Controllers

Float Operated Level Controllers CONTENTS Float Operated Level Controllers IM0015 Nov. 2014 PAGE Introduction 1 Scope 1 Description 1 Specification 1 Control Installation 2 INTRODUCTION Side Mount Back Mount Prior to installing, the instructions

More information

TOP VALVE. Pat. #5,857,486 & 5,944,050. Mid-Range Pressure PSIG Back Pressure and Pressure Relief Valves. Instruction Manual

TOP VALVE. Pat. #5,857,486 & 5,944,050. Mid-Range Pressure PSIG Back Pressure and Pressure Relief Valves. Instruction Manual TOP VALVE Pat. #5,857,486 & 5,944,050 Mid-Range Pressure 50 232 PSIG Back Pressure and Pressure Relief Valves Instruction Manual Please Note: This instruction manual provides detailed information and instructions

More information

Combination Air Valve

Combination Air Valve Combination Air Valve For Sewage and Wastewater Model C50 Installation, Operation and Maintenance Manual (IOM) Table of Contents General... Page 2 Safety... Page 2 Operational Data... Page 3 Materials

More information

Installation of Your SprayMaster System

Installation of Your SprayMaster System Installation of Your SprayMaster System 1. At the installation site, remove all equipment from the corrugated box and the polyethylene drum and replace the drum lid. Check the picture to identify each

More information

TOP VALVE. Pat. #5,857,486 & 5,944,050. High Temperature: max. 300 F (149 C) Back Pressure And Pressure Relief Valves. Instruction Manual

TOP VALVE. Pat. #5,857,486 & 5,944,050. High Temperature: max. 300 F (149 C) Back Pressure And Pressure Relief Valves. Instruction Manual TOP VALVE Pat. #5,857,486 & 5,944,050 High Temperature: max. 300 F (149 C) Back Pressure And Pressure Relief Valves Instruction Manual PLEASE NOTE: This instruction manual provides information and instructions

More information

Bray/ VAAS O-Ported Series Knife Gate Valve 770/780 Series Operation and Maintenance Manual

Bray/ VAAS O-Ported Series Knife Gate Valve 770/780 Series Operation and Maintenance Manual Bray/ VAAS Knife Gate Valve 770/780 Series Operations and Maintenance Manual Table of Contents Definition of Terms 1 Safety Instructions 1 Introduction 2 Unpacking 2 Storage 2 Installation 2 Commissioning

More information

Easy Nest Kits. Installation Suggestions

Easy Nest Kits. Installation Suggestions Easy Nest Kits Installation Suggestions 2 General Recommendations Hydraulics Vacuum breakers should be installed to prevent siphoning. Flexible connectors should follow FRP tank manufacturers recommendations.

More information

PENBERTHY SUBMERSIBLE AUTOMATIC SUMP DRAINER INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

PENBERTHY SUBMERSIBLE AUTOMATIC SUMP DRAINER INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS Before installation, these instructions must be read carefully and understood. PRODUCT WARRANTY Emerson warrants its Penberthy products as designed and manufactured to be free of defects in the material

More information

TECHNICAL DATA. than the water inlet pressure to the concentrate

TECHNICAL DATA. than the water inlet pressure to the concentrate Foam102a 1. DESCRIPTION The Viking Low Flow Foam/Water proportioning system, is a UL Listed and FM Approved system, for use with 3M foam concentrates. This system consists of a standard wet pipe sprinkler

More information

64 Series Pressure Reducing Regulators

64 Series Pressure Reducing Regulators Instruction Manual Form 1245 64 Series March 2006 64 Series Pressure Reducing Regulators W1943 Figure 1. 64 Series Regulator Introduction Scope of Manual This manual provides instructions for the installation,

More information

Anti-flood device Model B-1

Anti-flood device Model B-1 December 4, 2009 Dry Systems 123a 1. DESCRIPTION The Anti-flood Device is required when Viking accelerators are installed on dry systems according to Viking Model E-1 Accelerator Trim Charts. In the SET

More information

LRS(H)4 Pressure-Reducing Regulator User Manual

LRS(H)4 Pressure-Reducing Regulator User Manual LRS(H)4 Pressure-Reducing Regulator User Manual Read the complete manual before installing and using the regulator. 2 Safe Product Selection When selecting a product, the total system design must be considered

More information

RD(H)20/25 Pressure-Reducing Regulator User Manual

RD(H)20/25 Pressure-Reducing Regulator User Manual RD(H)20/25 Pressure-Reducing Regulator User Manual Read the complete manual before installing and using the regulator. 2 Safe Product Selection When selecting a product, the total system design must be

More information

Halsey Taylor Owners Manual 4410 Freeze Resistant Tubular Fountain STOP!

Halsey Taylor Owners Manual 4410 Freeze Resistant Tubular Fountain STOP! Halsey Taylor Owners Manual 4410 Freeze Resistant Tubular Fountain STOP! PLEASE READ THE FOLLOWING INFORMATION. ITALLATION ITRUCTIO FOR THE 4410FR FTN. WITH 97243C SINGLE VALVE CONTROL ASSEMBLY ARE LOCATED

More information

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE February 9, 1998 Foam 101a A BLADDER TANK WITH 1. DESCRIPTION A Wet Pipe Bladder Tank Foam/Water System is a standard wet pipe automatic sprinkler system capable of discharging a foam/water solution automatically

More information

GILMONT ACCUCAL FLOWMETERS

GILMONT ACCUCAL FLOWMETERS OPERATING MANUAL GILMONT ACCUCAL FLOWMETERS 28W092 Commercial Ave. Barrington, IL U.S.A. 60010-2392 (847) 381-4888 (847) 381-7053 (Fax) 800-962-7142 www.barnant.com e-mail: barnant@barnant.com A-1299-0766

More information

RHPS Series RD(H)F40 User Manual. Read the complete manual before installing and using the regulator.

RHPS Series RD(H)F40 User Manual. Read the complete manual before installing and using the regulator. RHPS Series RD(H)F40 User Manual Read the complete manual before installing and using the regulator. 2 WARNING Before removing a regulator from the system for service, you must depressurize system purge

More information

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO 97C COMPRESSOR KIT 12V PART NO. 00097 97C COMPRESSOR KIT 24V PART NO. 02497 98C COMPRESSOR KIT PART NO. 00098 97C 98C IMPORTANT: It is essential that you and any other operator of this product read and

More information

TECHNICAL DATA. Page 1 of 12

TECHNICAL DATA. Page 1 of 12 Page 1 of 12 1. DESCRIPTION The Viking Regulating Valve is a direct-acting, single-seated, spring-loaded diaphragm valve. When installed as a pilot regulating valve on a Viking Model H or J Flow Control

More information

INSTALLATION & MAINTENANCE INSTRUCTION

INSTALLATION & MAINTENANCE INSTRUCTION ARCHON Industries, Inc Liquid Level Gauges Models: BT-LLG ND-LLG INSTALLATION & MAINTENANCE INSTRUCTION Instruction No.: 1014.2 Revision Issued: 3/01/03 Approved: Engineering Manager Warning ONLY QUALIFIED

More information

Installation, Operation, and Maintenance Manual

Installation, Operation, and Maintenance Manual Installation, Operation, and Maintenance Manual Welker The information in this manual has been carefully checked for accuracy and is intended to be used as a guide for the installation, operation, and

More information

OPERATING AND MAINTENANCE MANUAL

OPERATING AND MAINTENANCE MANUAL Series 4300 Engineered Performance TABLE OF CONTENTS 0 INTRODUCTION 1 1 Scope 1 2 Description 1 3 Specifications 1 0 INSTALLATION 1 1 Mounting 1 2 Piping 1 1 Connecting Process Pressure 2 2 Vent Connections

More information

TECHNICAL DATA ANTI-FLOOD DEVICE MODEL B-1 1. DESCRIPTION

TECHNICAL DATA ANTI-FLOOD DEVICE MODEL B-1 1. DESCRIPTION Page 1 of 6 1. DESCRIPTION The Model B-1 Anti-flood Device is required when Viking accelerators are installed on dry systems according to Viking Model E-1 Accelerator Trim Charts. In the SET condition,

More information

Halsey Taylor Owners Manual STOP!

Halsey Taylor Owners Manual STOP! Halsey Taylor Owners Manual 4710 Freeze Resistant Floor Mounted Steel Fountain STOP! PLEASE READ THE FOLLOWING INFORMATION. ITALLATION ITRUCTIO FOR THE 4710FR FTN. WITH 97243C SINGLE VALVE CONTROL ASSEMBLY

More information

Natural Gas Conversion Kit

Natural Gas Conversion Kit SERIAL #: Attention: Centro recommends that a qualified gas technician perform the gas supply conversion and orifice replacement for this BBQ model. Natural Gas Conversion Kit F O R U S E W I T H M O D

More information

MEGR-1627 Instruction Manual

MEGR-1627 Instruction Manual MEGR-1627 HIGH FLOW GAS REGULATOR Instruction Manual- Look Inside For: Description Installation Remote Vent Line Installations Startup and Adjustment Shutdown Maintenance Body Maintenance Procedures Diaphragm

More information

1301 Series High-Pressure Regulators

1301 Series High-Pressure Regulators Instruction Manual Form 1111 Types 1301F and 1301G March 2013 1301 Series High-Pressure Regulators! WARNING Failure to follow these instructions or to properly install and maintain this equipment could

More information

User's Manual. MixRite TF 10. Edition 05.08

User's Manual. MixRite TF 10. Edition 05.08 User's Manual MixRite TF 10 Edition 05.08 1 Tefen MixRite TF 10 fertilizer and chemicals Injector Congratulations on your purchase of one of Tefen s high quality products. To get the best results from

More information

LARGE DRY CHEMICAL, TWIN-AGENT, AFFF, HALON 1211, AND AQUASONIC (NITROGEN-OPERATED SYSTEMS) Pressure Regulator Test Manual

LARGE DRY CHEMICAL, TWIN-AGENT, AFFF, HALON 1211, AND AQUASONIC (NITROGEN-OPERATED SYSTEMS) Pressure Regulator Test Manual LARGE DRY CHEMICAL, TWIN-AGENT, AFFF, HALON 1211, AND AQUASONIC (NITROGEN-OPERATED SYSTEMS) Pressure Regulator Test Manual 002694 IntroductIon 8-1-11 Page 1 ForEWord This manual is intended for use with

More information

Gas Lines. Technical Manual. Sumitomo (SHI) Cryogenics of America, Inc Vultee Street Allentown, PA U.S.A.

Gas Lines. Technical Manual. Sumitomo (SHI) Cryogenics of America, Inc Vultee Street Allentown, PA U.S.A. Gas Lines Technical Manual Sumitomo (SHI) Cryogenics of America, Inc. 1833 Vultee Street Allentown, PA 18103-4783 U.S.A. Revision F: April 2008 261320A TABLE OF CONTENTS Page DESCRIPTION...1 SPECIFICATIONS...2

More information

SWIRLFLO Refrigerated fountains with FLEXI-GUARD

SWIRLFLO Refrigerated fountains with FLEXI-GUARD TM INSTALLATION, CARE & USE MANUAL SWIRLFLO Refrigerated fountains with FLEXI-GUARD TM INSTALLER! CAUTION: Review these instructions before beginning installation. Be sure that installation conforms to

More information

TECHNICAL DATA. Pressure Regulation 531a. April 24, 2009

TECHNICAL DATA. Pressure Regulation 531a. April 24, 2009 April 24, 29 Pressure Regulation 531a 1. DESCRIPTION The Viking Regulating Valve is a direct-acting, single-seated, spring-loaded diaphragm valve. When installed as a pilot regulating valve on a Viking

More information

Installation, Operation, and Maintenance Manual

Installation, Operation, and Maintenance Manual Installation, Operation, and Maintenance Manual Welker Probe Instrument Regulator Model The information in this manual has been carefully checked for accuracy and is intended to be used as a guide for

More information

I T T Pressure Reducing Valve WARNING INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

I T T Pressure Reducing Valve WARNING INSTALLATION, OPERATION, AND MAINTENANCE MANUAL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL I-867-4T 867-4T Pressure Reducing Valve HANG THESE INSTRUCTIONS ON THE INSTALLED VALVE FOR FUTURE REFERENCE WARNING Read and understand all instructions

More information

Automatic Switchover Gas Chlorination Systems Series 900

Automatic Switchover Gas Chlorination Systems Series 900 Automatic Switchover Gas Chlorination Systems Series 900 Instruction Manual All Hydro Instruments Chlorination systems are carefully designed and tested for years of safe, accurate field service. All Hydro

More information

Installation Troubleshooting Maintenance Instructions Installation / Start-up

Installation Troubleshooting Maintenance Instructions Installation / Start-up Model ZW207 Installation Troubleshooting Maintenance Instructions Installation / Start-up NOTE: Flushing of all pipe lines is to be performed to remove all debris prior to installing valve. 1. For making

More information

Installation Instructions

Installation Instructions Installation Instructions S65-135 (Circular) S65-136 (Semi-Circular) Air Valve Retrofit For Non-Sectional Classic Washfountain Table of Contents.......................2-6 Metering Air Valve Parts List....................6

More information

Eaton Filtration, LLC

Eaton Filtration, LLC Eaton Filtration, LLC 900 Fairmount Avenue, Elizabeth, NJ 07207 Phone: 908-787-1000 Fax: 908-351-7893 E-Mail: filtration@eaton.com Web: www.filtration.eaton.com Installation, Operation & Service Manual

More information

Eaton Filtration, LLC

Eaton Filtration, LLC Eaton Filtration, LLC 900 Fairmount Avenue, Elizabeth, NJ 07207 Phone: 908-787-1000 Fax: 908-351-7893 E-Mail: filtration@eaton.com Web: www.filtration.eaton.com Installation, Operation & Service Manual

More information

Product Manual. Description. Specifications. CVS Type 1301F and CVS Type 1301G Regulator. Introduction

Product Manual. Description. Specifications. CVS Type 1301F and CVS Type 1301G Regulator. Introduction Product Manual CVS Type 1301F and CVS Type 1301G Regulator Introduction This CVS Controls product manual includes instructions for the installation, adjustment, maintenance and parts ordering of the CVS

More information

2.0 INSTALLATION & SERVICE

2.0 INSTALLATION & SERVICE Installation, Operation, and Maintenance Instructions MODEL 5600 / 5600R January 2005 CONTENTS 1.0 GENERAL 1.1 5600 Model Number Information -----------------------------------------------------------------------

More information

Bermad Pressure Reducing. Model: 42T

Bermad Pressure Reducing. Model: 42T Bermad Pressure Reducing Pilot Operated Pressure Control Valve Model: 42T Installation Operation Maintenance Manual (IOM) REV. 27.7.17 Page 1 of 12 Safety First BERMAD believes that the safety of personnel

More information

2008 by Controlmatik ABW

2008 by Controlmatik ABW I N S T R U C T I O N M A N U A L F OR Installation and use of high capacity Vacuum regulator 2008 by Controlmatik ABW CONTENTS 1 GENERAL... 2 2 THE CHLORINE GAS DOSING SYSTEM... 2 2.1 Parts of the chlorine

More information

BUTTERFLY VALVES Series 800

BUTTERFLY VALVES Series 800 BUTTERFLY VALVES Series 800 WARNING Before proceeding read ALL instructions and become familiar with the equipment and associated drawings. Follow ALL applicable safety regulations and codes for pressurized

More information

299H Series. Introduction. P.E.D. Categories. Specifications. Installation. Warning. Installation Guide English September 2012

299H Series. Introduction. P.E.D. Categories. Specifications. Installation. Warning. Installation Guide English September 2012 Installation Guide English September 2012 299H Series Introduction This Installation Guide provides instructions for installation, startup, and adjustment of 299H Series regulators. To receive a copy of

More information

FOR INSTALLING CO 2 BLENDER KIT (P/N IN BEER SYSTEM

FOR INSTALLING CO 2 BLENDER KIT (P/N IN BEER SYSTEM IMI CORNELIUS INC One Cornelius Place Anoka, MN 55303-623 Telephone (800) 238-3600 Facsimile (612) 22-326 INSTALLATION INSTRUCTIONS FOR INSTALLING CO 2 BLENDER KIT (P/N 111612000 IN BEER SYSTEM SECONDARY

More information

TEST SPECIFICATION NYT-909-C

TEST SPECIFICATION NYT-909-C 748 Starbuck Ave, Watertown, NY 13601 Phone: +1-315-786-5200 Engineering Fax: +1-315-786-5673 TEST SPECIFICATION NYT-909-C CODE OF TESTS FOR TESTING "AB" TEST RACK P/N 702546 & 702612 ISSUE NO. 5 1.0 THE

More information

Welker Sampler. Model GSS-1. Installation, Operation, and Maintenance Manual

Welker Sampler. Model GSS-1. Installation, Operation, and Maintenance Manual Installation, Operation, and Maintenance Manual Welker Sampler Model GSS-1 The information in this manual has been carefully checked for accuracy and is intended to be used as a guide to operations. Correct

More information

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity WATER HEATER THERMAL EXPANSION TANKS Owner s Manual Safety Instructions Installation Maintenance Warranty Models: 2-5 Gallon Capacity Thank You for purchasing this Thermal Expansion Tank. Properly installed

More information

V43 Pressure Actuated Water Regulating Valve

V43 Pressure Actuated Water Regulating Valve FANs 125, 121 Product/Technical Bulletin V43 Issue Date 0996 V43 Pressure Actuated Water Regulating Valve The V43 Pressure Actuated Water Regulating Valves are designed to regulate water flow for water-cooled

More information

Fisher DVI Desuperheater Venturi Inline

Fisher DVI Desuperheater Venturi Inline Instruction Manual DVI Desuperheater Fisher DVI Desuperheater Venturi Inline Contents Introduction... 1 Scope of Manual... 1 Description... 1 Principle of Operation... 2 Installation... 3 Operating Instructions...

More information

Assembly Drawing: W-311B-A01, or as applicable Parts List: W-311B-A01-1, or as applicable Special Tools: , , &

Assembly Drawing: W-311B-A01, or as applicable Parts List: W-311B-A01-1, or as applicable Special Tools: , , & REDQ Regulators Model 411B Barstock Design Powreactor Dome Regulator OPERATION AND MAINTENANCE Contents Scope..............................1 Installation..........................1 General Description....................1

More information

627 Series Pressure Reducing Regulators

627 Series Pressure Reducing Regulators 627 Series Pressure Reducing Regulators Introduction The 627 Series direct-operated pressure reducing regulators (Figure 1) are for low and high-pressure systems. These regulators can be used with natural

More information

Binks SG-2 Plus TM Rotary 2 QT. PRESSURE CUP

Binks SG-2 Plus TM Rotary 2 QT. PRESSURE CUP Binks SG-2 Plus TM Rotary 2 QT. PRESSURE CUP Model No. 80-651 Rotary Agitator INTRODUCTION Binks SG-2 TM Plus Rotary 2 Qt. Pressure Cup is ideal for component spraying and industrial applications where

More information

ACV-10 Automatic Control Valve

ACV-10 Automatic Control Valve ACV-10 Automatic Control Valve Installation, Operation & Maintenance General: The Archer Instruments ACV-10 is a precision automatic feed rate control valve for use in vacuum systems feeding Chlorine,

More information

Operation & Maintenance Manual Place this manual with valve or person responsible for maintenance of the valve

Operation & Maintenance Manual Place this manual with valve or person responsible for maintenance of the valve Operation & Maintenance Manual Place this manual with valve or person responsible for maintenance of the valve Model CYCLE GARD II, CI & CNA YOUR PRODUCT INFORMATION: Model Number: Date: Serial Number:

More information

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER SUPPLIMENT TO eom IMPORTANT READ THIS MANUAL BEFORE PRODUCT INSTALLATION, OPERATION, INSPECTION & MAINTENANCE Tougher and more rigid guidelines are being established

More information

TECHNICAL DATA CAUTION

TECHNICAL DATA CAUTION Page 1 of 6 1. DESCRIPTION The Viking Model D-2 Accelerator is a quick-opening device, with an integral anti-flood assembly, used to increase the operating speed of a differential type dry pipe valve.

More information

ABRASIVE REGULATOR II

ABRASIVE REGULATOR II ABRASIVE REGULATOR II 13096 Abrasive Regulator II TABLE OF CONTENTS Contact Information and Customer & Technical Service... 1 1 Introduction... 1 2 Abrasive Regulator... 1 Description:... 1 2.1 Regulator

More information

Design DSA Steam-Atomized Desuperheater

Design DSA Steam-Atomized Desuperheater Instruction Manual DSA Desuperheater Design DSA Steam-Atomized Desuperheater Contents Introduction............................... 1 Scope of Manual......................... 1 Description..............................

More information

Operation Manual - PN A MENSOR MODEL 73 SHOP AIR BOOSTER

Operation Manual - PN A MENSOR MODEL 73 SHOP AIR BOOSTER Operation Manual - PN 0017946001 A MENSOR MODEL 73 SHOP AIR BOOSTER Mensor Model 73 Shop Air Booster System (750 psi Version) April 23, 2012 Trademarks / Copyright Mensor is a registered trademark of Mensor

More information

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection February 9, 1998 Foam 201a 1. DESCRIPTION A Deluge Bladder Tank Foam/Water System is a standard deluge system capable of discharging a foam/water solution automatically through open sprinklers, spray nozzles,

More information

Temperature Controllers

Temperature Controllers IM0004 April 2013 CONTENTS T-12 Thermostat PAGE Introduction 1 Scope 1 Description 1 Specification 1 Temperature Controllers 2 INTRODUCTION CAUTION Prior to installing, the instructions provided herein

More information

Type 1367 High-Pressure Instrument Supply System with Overpressure Protection

Type 1367 High-Pressure Instrument Supply System with Overpressure Protection Instruction Manual D100343X012 Type 1367 November 2017 Type 1367 High-Pressure Instrument Supply System with Overpressure Protection TYPE 252 FILTER 2ND-STAGE TYPE 67CF FILTER-STYLE REGULATOR INLET TYPE

More information

SPECIFICATIONS CAPACITY

SPECIFICATIONS CAPACITY DMV-ZRD(LE)/6 SERIES Installation Instructions SPECIFICATIONS DMV-ZRD/6 DMV-ZRDLE/6 Two normally closed safety shutoff valves in one housing. V1 and V2 are fast opening, fast closing. Two stage and adjustable

More information

Un-Pressurized Orefice Fittings FIO EZ. Parts List and Operation Instructions TECHNICAL MANUAL. Dn 2-6 Class Lbs

Un-Pressurized Orefice Fittings FIO EZ. Parts List and Operation Instructions TECHNICAL MANUAL. Dn 2-6 Class Lbs Un-Pressurized Orefice Fittings FIO EZ Parts List and Operation Instructions TECHNICAL MANUAL Dn 2-6 Class 150-600 Lbs US US 2 FIO EZ - MT 108-US - 05-2016 FIO EZ Important Instructions US Pietro Fiorentini

More information

Pressure Dump Valve Service Kit for Series 3000 Units

Pressure Dump Valve Service Kit for Series 3000 Units Instruction Sheet Pressure Dump Valve Service Kit for Series 000 Units. Overview The Nordson pressure dump valve is used to relieve hydraulic pressure instantly in Series 00, 400, 500, and 700 applicator

More information

AQUAMATIC EASY NEST KITS INSTALLATION SUGGESTIONS

AQUAMATIC EASY NEST KITS INSTALLATION SUGGESTIONS AQUAMATIC EASY NEST KITS INSTALLATION SUGGESTIONS TABLE OF CONTENTS TABLE OF CONTENTS...2 GENERAL RECOMMENDATIONS...2 TROUBLESHOOTING GUIDE...3 EXISTING EASY NEST SYSTEM TROUBLESHOOTING GUIDE...4 COMPONENT

More information

INTRODUCTION IMPORTANT NOTES AND WARNINGS

INTRODUCTION IMPORTANT NOTES AND WARNINGS INSTRUCTION BULLETIN 26 044 SE Dixie Cutoff Road, Stuart, Florida 34994 USA Phone: (772) 288-4854 Fax: (772) 287-3238 www.regalchlorinators.com Email: regal@regalchlorinators.com REGAL Gas Chlorinator,

More information

Compact Triple Cabinet Outlet Station Model Installation and Operating Instructions

Compact Triple Cabinet Outlet Station Model Installation and Operating Instructions Compact Triple Cabinet Outlet Station Model 6258-1 Installation and Operating Instructions The Porter Compact Triple Outlet Station (6258-1) provides a quick, safe, and reliable method of connection to

More information

TECHNICAL DATA CAUTION

TECHNICAL DATA CAUTION Page 1 of 12 1. DESCRIPTION The Viking Model C-2 Pilot Pressure Regulating Valve is a direct-acting, single-seated, spring-loaded diaphragm valve. When installed as a pilot regulating valve on a Viking

More information

420C AIR COMPRESSOR KIT PART NO C AIR COMPRESSOR KIT PART NO

420C AIR COMPRESSOR KIT PART NO C AIR COMPRESSOR KIT PART NO 420C AIR COMPRESSOR KIT PART NO. 42042 460C AIR COMPRESSOR KIT PART NO. 46043 420C 460C IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this

More information

ABRASIVE REGULATOR II

ABRASIVE REGULATOR II ABRASIVE REGULATOR II 13096 Abrasive Regulator II TABLE OF CONTENTS 1 Introduction... 1 2 Abrasive Regulator... 2 2.1 Regulator Installation... 2 Location... 2 Attaching the Regulator to the Machine...

More information

IMPORTANT SAFETY INSTRUCTIONS

IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS CAUTION - To reduce risk of electrical shock: - Do not disassemble. Do not attempt repairs or modifications. Refer to qualified service agencies for all service and repairs.

More information

Medical Gas Control Panel

Medical Gas Control Panel Medical Gas Control Panel INSTALLATION & MAINTENANCE MANUAL 255105 (Rev. 6) 2018-04 2 255105 (Rev. 6) 2018-04 1.0 User Responsibilities The information contained in this installation and operation maintenance

More information

1200B2 Series Service Regulators. Instruction Manual

1200B2 Series Service Regulators. Instruction Manual 00B Series Service Regulators Instruction Manual 00B Series Service Regulators 0 Elster American Meter 00B Series Service Regulators General Information The 00B Series Service Regulators are available

More information

TITAN FLOW CONTROL, INC.

TITAN FLOW CONTROL, INC. PREFACE: This manual contains information concerning the installation, operation, and maintenance of Titan Flow Control (Titan FCI) Simplex Basket Strainers. To ensure efficient and safe operation of Titan

More information