Instruction Manual - Diaframless TM Ejector Chlorine, Sulfur Dioxide and Ammonia

Save this PDF as:
 WORD  PNG  TXT  JPG

Size: px
Start display at page:

Download "Instruction Manual - Diaframless TM Ejector Chlorine, Sulfur Dioxide and Ammonia"

Transcription

1 Instruction Manual - Diaframless TM Ejector Chlorine, Sulfur Dioxide and Ammonia

2 These instructions describe the installation, operation and maintenance of the subject equipment. Failure to strictly follow these instructions can lead to an equipment rupture that may cause significant property damage, severe personal injury and even death. If you do not understand these instructions, please call De Nora Water Technologies for clarification before commencing any work at and ask for a Field Service Manager. De Nora Water Technologies, Inc. reserves the rights to make engineering refinements that may not be described herein. It is the responsibility of the installer to contact De Nora Water Technologies, Inc. for information that cannot be answered specifically by these instructions. Any customer request to alter or reduce the design safeguards incorporated into De Nora Water Technologies equipment is conditioned on the customer absolving De Nora Water Technologies from any consequences of such a decision. De Nora Water Technologies has developed the recommended installation, operating and maintenance procedures with careful attention to safety. In addition to instruction/operating manuals, all instructions given on labels or attached tags should be followed. Regardless of these efforts, it is not possible to eliminate all hazards from the equipment or fore see every possible hazard that may occur. It is the responsibility of the installer to ensure that the recommended installation instructions are followed. It is the responsibility of the user to ensure that the recommended operating and maintenance instructions are followed. De Nora Water Technologies, Inc. cannot be responsible deviations from the recommended instructions that may result in a hazardous or unsafe condition. De Nora Water Technologies, Inc. cannot be responsible for the overall system design of which our equipment may be an integral part of or any unauthorized modifications to the equipment made by any party other that De Nora Water Technologies, Inc. De Nora Water Technologies, Inc. takes all reasonable precautions in packaging the equipment to prevent shipping damage. Carefully inspect each item and report damages immediately to the shipping agent involved for equipment shipped F.O.B. Colmar or to De Nora Water Technologies for equipment shipped F.O.B Jobsite. Do not install damaged equipment. De Nora Water Technologies, COLMAR OPERATIONS COLMAR, PENNSYLVANIA, USA IS ISO 9001: 2008 CERTIFIED

3 TABLE OF CONTENTS 1 INTRODUCTION General Warranty Specifications 1.4 Back Pressure OPERATION General Installation Ejector Vacuum Piping Vacuum Connections START-UP Vacuum Check SHUTDOWN Service 5.1 Nozzle Cleaning O-Ring Replacement Functional Test Recommended Torque Values TROUBLESHOOTING CHART FIGURES 1 Gas Feed System Flow Diagram PPD (2 kg/h) Maximum Diaframless Ejector, Chlorine or Sulfur Dioxide PPD (2 kg/h) Maximum High Pressure Diaframless Ejector, Chlorine or Sulfur Dioxide & 500 PPD (4 & 10 kg/h) Maximum Diaframless Ejector, Chlorine or Sulfur Dioxide & 500 PPD (4 & 10 kg/h) Maximum High Pressure Diaframless Ejector, Chlorine or Sulfur Dioxide & 250 PPD (2 & 5 kg/h) Maximum Diaframless Ejector, Ammonia

4 1 INTRODUCTION 1.1 General The Diaframless ejectors are expertly engineered and carefully tested to assure years of satisfactory operation. They are constructed of the finest materials available for gas service. Correct installation and proper care will ensure best operation. Read instructions carefully and save for future reference. Diaframless ejectors are designed for use where back pressures are high (greater than 140 psig (10 bar) and/or are subject to frequent on/off operation. This is the standard ejector for ammonia feed to 250 PPD (5 kg/h). Pressure up to 250 psig (17.2 bar) are satisfactory when the ejector is a corporation stop and 200 psig (13.8 bar) when the ejector is used with a solution valve. 1.2 Warranty See Bulletin for the ADVANCE equipment warranty. 1.3 Specifications Gas Flow a. Chlorine and Sulfur Dioxide On/Off Operation Capacity 100 PPD (2 kg/h) 3/8" 200 PPD (4 kg/h) 1/2" 500 PPD (10 kg/h) 5/8" Vacuum Tubing Size Inlet Nozzle 1" hose 3/4" NPT 1-1/4" NPT 1-1/2" NPT 1-1/4" NPT 1-1/2" hose Outlet Diffuser Universal - 3/4" NPT male thread, spray or open-end, or 1" hose 1-1/4" NPT 1-1/2" NPT 1-1/4" NPT 1-1/2" hose b. Chlorine and Sulfur Dioxide High Pressure Operation Capacity 100 PPD (2 kg/h) 3/8" Vacuum Tubing Size Inlet Nozzle 1" NPT (inlet fitting) 1-1/4" NPT Outlet Diffuser 1" NPT outlet fitting 200 PPD (4 kg/h) 1/2" 1-1/4" NPT 1-1/4" NPT 500 PPD (10 kg/h) 5/8" 1-1/4" NPT 1-1/4" NPT c. Ammonia Capacity Vacuum Tubing Size 50 PPD (1 kg/h) 3/8" 1" hose 3/4" NPT 100 PPD (2 kg/h) 1/2" 250 PPD (5 kg/h) 5/8" Inlet Nozzle Outlet Diffuser Universal - 3/4" NPT male thread, spray or open-end, or 1" hose NOTE: For ammonia ejectors, you must watch precipitation problems. If the ejector waters contain greater than 40 ppm hardness as CaCO3, there is a chance of precipitation and the ejector will clog. Therefore, vacuum systems should not be used if the hardness is greater than 40 ppm as CaCO3. Different inlet nozzle and diffuser combinations are available for the ejectors. The combination supplied was chosen for your particular application

5 1.3.2 A universal diffuser can be used in four different ways; spray diffuser, open-end diffuser, 3/4" threaded connection, or 1" hose connection. Choose the type suited for the installation (spray is recommended for good mixing). If other than spray is desired, modify by cutting off the closed end The ejector (nozzle and check valve assembly) may be located near the vacuum regulator. A wall mounting bracket is available for field assembly, and the universal diffuser can be modified for a pipe or hose connection The entire diffuser-ejector assembly may be submersed in an open channel or tank Diffuser tubes with corporation stops can be supplied for either close-coupled or remote ejectors Corporation stops are recommended for high pressure pipeline applications and perforated pipe diffusers are recommended for good mixing in open tanks or channels. 1.4 Back Pressure Used in applications when back pressure exceeds 140 psig (10 bar). It may be used against back pressures as low as 20 psig (1.4 bar). Minimum back pressure - 20 psig (1.4 bar) Maximum back pressure psig (17.5 bar) using corporation stop, 200 psig (14 bar) using a solution Valve (See bulletin )

6 2 OPERATION 2.1 General Vacuum created by the nozzle opens the Diaframless check valve assembly allowing gas to flow into the vacuum connection across the open Diaframless valve disc assembly into the water flowing through the nozzle. Loss of vacuum permits water pressure to close the valve disc pressing the o-ring to seal against the underside of the ejector s top body. The Diaframless ejector should be used for ON/OFF applications which can cause premature wear and tear of the diaphragm or o-ring. It may also be used when back pressure exceeds 140 psig (10 bar). On all Series 200 ammonia gas feeders, the Diaframless ejector is the standard ejector. 2.2 Installation The ejector may be installed in any position, since the check valve is spring actuated (however, downward water flow may cause cavitation and poor vacuum when there is limited pressure). The point of injection should be carefully chosen so the back pressure into which the gas is fed is as low as possible. If the ejector is installed in a pipe, the ejector/diffuser should not be installed in the top of the pipe where gas may discharge and collect in an empty area of the pipe. Diffuser penetration into the pipe should not exceed 1/3 the diameter of the pipe Unscrew the diffuser from the assembly. Do NOT install ejector with the diffuser attached, or damage may occur Put Teflon tape on the diffuser pipe threads and screw the diffuser into the pipe by hand. Tighten carefully with pliers. (Make sure that the holes in the spray tube diffuser are in the main stream). The end of an open-end type diffuser should not allow strong chemical solution to come in Contact with pipe or fittings. (This will cause serious corrosion) Reconnect nozzle and check valve assembly to diffuser. The nozzle may extend through the assembly from either side. A gasket should be on each side. Screw the nozzle into the diffuser HAND TIGHT. (The check valve assembly may be installed in any position) Other types of diffuser and ejector installations may be desired for certain applications: a. The ejector (nozzle and check valve assembly) may be located near the vacuum regulator. A wall mounting bracket is available for field assembly, and the universal diffuser can be modified for a pipe or hose connection. b. The entire diffuser-ejector assembly may be submerged in an open channel or tank. c. Diffuser tubes with corporation stops can be supplied for either close coupled or remote ejectors. 2.3 Ejector Vacuum The ejector creates a vacuum only when sufficient pressure differential exists between the ejector inlet water versus the water outlet pressure. Proceed as follows to install a pipe mounted close coupled diffuser and ejector. For example, if the diffuser were discharging into an empty basin (zero back pressure), the supply pressure to the nozzle requires about 25 psig (2 bar) to create enough vacuum to operate a 50 PPD (1 kg/h) vacuum regulator. A lower supply pressure or a higher back pressure would reduce the gas flow rate. Then for each 1 psig (0.07 bar) of back pressure above zero, the supply pressure must be increased about 2 to 3 psig (0.1 to 0.2 bar) above 25 psig (2 bar). A back pressure of 10 psig (0.7 bar) would therefore require about 55 psig (4 bar) supply pressure in order to operate the 50 PPD (1 kg/h) vacuum regulator. Also, the water supply line to the nozzle must be large enough to allow sufficient water flow (3/4" or larger Pipe is recommended) and minimize friction losses

7 2.4 Piping For most installations, the ejector water supply line should be brought to within 4-6 ft. (1-2 m) of the nozzle with rigid copper or iron pipe. A shutoff valve followed by a Y-strainer, and a hose adapter should be installed. A pressure gauge between the Y-strainer and the ejector can be a useful service tool Connect the hose between the hose adapter and the ejector nozzle. Clamp the hose securely at both ends with single or double clamps. 2.5 Vacuum Connections - See Figure 1 and Introduction, Gas Flow section Table A Black polyethylene tubing is normally used for the vacuum line between the vacuum regulator and ejector. Use enough length for each line to allow vacuum regulator movement from one cylinder to another Remove the connector nut from the vacuum regulator connection and slip onto the tubing. Push the tubing onto the connector and tighten connector nut HAND TIGHT The upper connection on the vacuum regulator is for vacuum tubing to ejector. Figure 1 - Gas Feed System Flow Diagram

8 3 start-up 3.1 Vacuum Check The ejector, its water supply and solution lines, must be properly installed and checked before operating the vacuum regulator. Unless the ejector is creating a vacuum, the vacuum regulator will not work Disconnect the vacuum tubing from the ejector Open the ejector water supply valve. The ejector should now be in operation and creating a vacuum Put your finger on the vacuum connector opening and feel the vacuum. There should be no doubt that a vacuum exists. If there is no vacuum, be certain the supply pressure is sufficient and the nozzle or piping is not plugged. Correct the condition and obtain proper vacuum before proceeding with vacuum regulator operation. (Reference vacuum regulator instruction manual) Reconnect the vacuum tubing to the ejector. Leave the ejector running. 4 SHUTDOWN WARNING Before disconnecting or disassembling the ejector, shutdown the system as described below 4.1. Failure to do so may result in serious injury or death. 1. Close the gas supply valve at the pressure source(s) to shut off the gas flow. This is normally the gas cylinder and/or container valve(s) supplying the gas dispensing (regulator) system. The rate valve on the dispensing system meter panel(s) is/are not to be used to shut off the gas flow. The float in the gas flow meter(s) should drop to the bottom of the flow meter indicating zero (no gas feed) 2. Continue the flow of water through the ejector for a few minutes to remove all gas remaining in the feeder, pressure piping and vacuum tubing. While the ejector continues to operate remove the vacuum tubing from the gas inlet of the ejector to allow air to enter the unit further diluting the residual gas. Stop the ejector water flow and relieve all residual water pressure. Close any water supply and chemical solution valves to isolate the ejector

9 5 SERVICE It is recommended that the Gas Dispensing System be inspected and serviced a minimum of once per year. More frequent service periods may be required due to: 1) the type, quality and quantity of the gas being handled, 2) the complexity of the gas supply system, 3) the quality and quantity of water or process liquid being used to operate the ejector(s), and 4) operation procedures. More frequent service periods are especially indicated when venting of the VR is occurring during the one year operational period. This is usually indicative of foreign debris holding the inlet valve open or destruction of the inlet valve parts caused by the gas quality not up to industry purity standards. Preventative maintenance kits for each of the assemblies are available from the factory. Each kit contains all the parts and detailed instructions that are required for complete maintenance. All o-rings and gaskets that have been disturbed during the disassembly must be replaced during reassembly in order to insure safe, trouble free operation. Failure to replace these parts could result in a shortened operation period and bodily injury. Refer to Figures Nozzle Cleaning Shut off the water supply valve or bypass the ejector. Remove the ejector. Refer to Figures 2-6 and remove the nozzle as follows: Remove the connecting hose to the ejector assembly For 100 PPD (2 kg/h) chlorine or sulfur dioxide ejectors, rotate the complete ejector body counter clockwise. This loosens the threaded portion of the nozzle from the diffuser, eliminating the need for pliers on the hose connection which may damage the plastic For 250 & 500 PPD (5 & 10 kg/h), and all ammonia ejectors, remove the two (2) screws and loosen the flange to remove the nozzle. NOTE: Nozzle plugging can be caused by foreign material (pipe scale, stone, dirt accumulation). This can usually be blown out or pushed out with a wire. Build-up of deposits may caused by iron, manganese or other material can usually be remove by immersing the nozzle in muriatic acid and rinsing. Some waters may cause an inoperable ejector and require nozzle cleaning every two months To reinstall the nozzle, insert the nozzle through the ejector body and fasten to the diffuser using new gaskets, or o-rings on each side of the ejector body. NOTE: These parts are plastic and excessive tightening may cause breakage. For 100 PPD (2 kg/h) chlorine or sulfur dioxide ejectors, tighten only hand tight with the ejector body 90 to the left of its final position, then turn the complete assembly Reinstall the ejector supply hose or pipe and vacuum tubing. 5.2 O-Ring Replacement Diaframless ejectors are designed for on/off application, but will require occasional maintenance of the diaphragm bolt/o-ring assembly. On a regular basis, this o-ring should be checked and the o-ring/diaphragm bolt assembly replaced as necessary. 5.3 Functional Test When the ejector is reassembled, a functional test of the check valve assembly is recommended to check for proper ejector assembly and prevent future flooding of the vacuum regulator Do not connect vacuum tubing to vacuum regulator Turn on water supply Verify vacuum at ejector Turn water supply off for approximately 5 minutes. If ejector is assembled properly, no water will leak from vacuum tubing. 5.4 Recommended Torque Values Torque values of 14 inch pounds for ejector body screws on units up to 500 PPD/10 kg/h are used at the factory, and are recommended guidelines for Reassembly of a repaired unit

10 Figure PPD (2 kg/h) Maximum Diaframless Ejector, Chlorine or Sulfur Dioxide

11 Figure PPD (2 kg/h) Maximum High Pressure Diaframless Ejector, Chlorine or Sulfur Dioxide

12 Figure and 500 PPD (4 and 10 kg/h) Maximum Diaframless Ejector, Chlorine or Sulfur Dioxide

13 Figure and 500 PPD (4 and 10 kg/h) Maximum High Pressure Diaframless Ejector, Chlorine or Sulfur Dioxide

14 Figure and 250 PPD (2 and 5 kg/h) Maximum Diaframless Ejector, Ammonia

15 5 TROUBLESHOOTING CHART Trouble Probable Cause Corrective Action 1. Insufficient ejector vacuum. a. Y-strainer in water supply dirty. b. Supply pressure too low. c. Back pressure too high 1. Solution valve, if supplied, not fully open. 2. Solution line if present, partially blocked. d. Velocity too low (cavitation) e. Nozzle 1. Flow restricted 2. Worn or damaged f. Incorrect nozzle size g. Improper installation a. Clean Y-strainer b and c. Open solution valve, clean line correct back pressure condition d. Increase pressure to ejector e.g. Clean nozzle and/or throat. See Service section and Flooded flowmeter. a. Dirt on o-ring. b. Improperly sealed or defective o-ring. c. Improper application. a. Clean or replace o-ring. See Service section. b. Replace o-ring. See Service section. c. See Bulletin on hydraulic conditions

16 Design improvements may be made without notice. Represented by: De Nora Water Technologies 3000 Advance Lane Colmar, PA ph fax web: mail: Registered Trademark All Rights Reserved. SEP

Instruction Manual O-Ring Ejector Chlorine & Sulfur Dioxide to 500 PPD (10 kg/h)

Instruction Manual O-Ring Ejector Chlorine & Sulfur Dioxide to 500 PPD (10 kg/h) Instruction Manual O-Ring Ejector Chlorine & Sulfur Dioxide to 500 PPD (10 kg/h) 100 PPD (2 kg/h) Maximum 250 PPD (5 kg/h) Maximum 500 PPD (10 kg/h) Maximum - 1-122.6006.9 These instructions describe the

More information

CAPITAL CONTROLS SERIES NXT3000

CAPITAL CONTROLS SERIES NXT3000 CAPITAL CONTROLS SERIES NXT3000 Modular design gas feed system with self contained automatic switchover capability. The Series NXT3000 Gas Feed System is a family of vacuumoperated, solution-feed gas dispensing

More information

HGC-200 Hydro Gas Chlorinator

HGC-200 Hydro Gas Chlorinator HGC-200 Hydro Gas Chlorinator ProMinent Fluid Controls Pty Ltd Head Office: Unit 4, 4 Narabang Way BELROSE NSW 2085 AUSTRALIA (PO Box 85, BELROSE WEST NSW 2085) Phone: (02) 9450 0995 Fax: (02) 9450 0996

More information

Model VR6 System. Installation, Operation & Maintenance

Model VR6 System. Installation, Operation & Maintenance Model VR6 System Installation, Operation & Maintenance General: All Archer Instruments chlorination systems are carefully designed and tested for years of safe, accurate field service. All Archer Instruments

More information

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual Fisher Controls Instruction Manual Type S301 & S302 Gas Regulators October 1981 Form 5180 WARNING Fisher regulators must be installed, operated, and maintained in accordance with federal, state, and local

More information

Float Operated Level Controllers

Float Operated Level Controllers CONTENTS Float Operated Level Controllers IM0015 Nov. 2014 PAGE Introduction 1 Scope 1 Description 1 Specification 1 Control Installation 2 INTRODUCTION Side Mount Back Mount Prior to installing, the instructions

More information

WATER MADE EASY MARINE ENERGY MUNICIPAL INDUSTRIAL

WATER MADE EASY MARINE ENERGY MUNICIPAL INDUSTRIAL Capital Controls Series 71V3000 The Series 71V3000 electrically-heated vaporizer automatically vaporizes and superheats liquid chlorine, sulfur dioxide or ammonia at a rate controlled by the gas feed system.

More information

INSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION

INSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION INSTALLATION INSTRUCTIONS CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION The CVS Controls 67CFR Filter regulator is a pressure reducing supply regulator typically used for pneumatic

More information

APCO ARV CLEAN WATER AIR RELEASE VALVES. Model 50A

APCO ARV CLEAN WATER AIR RELEASE VALVES. Model 50A APCO ARV CLEAN WATER AIR RELEASE VALVES Model 50A Instruction D12013 February 2017 Instructions These instructions provide installation, operation and maintenance information for APCO ARV Clean Water Air

More information

Halsey Taylor Owners Manual 4410 Freeze Resistant Tubular Fountain STOP!

Halsey Taylor Owners Manual 4410 Freeze Resistant Tubular Fountain STOP! Halsey Taylor Owners Manual 4410 Freeze Resistant Tubular Fountain STOP! PLEASE READ THE FOLLOWING INFORMATION. ITALLATION ITRUCTIO FOR THE 4410FR FTN. WITH 97243C SINGLE VALVE CONTROL ASSEMBLY ARE LOCATED

More information

User's Manual. MixRite TF 10. Edition 05.08

User's Manual. MixRite TF 10. Edition 05.08 User's Manual MixRite TF 10 Edition 05.08 1 Tefen MixRite TF 10 fertilizer and chemicals Injector Congratulations on your purchase of one of Tefen s high quality products. To get the best results from

More information

GILMONT ACCUCAL FLOWMETERS

GILMONT ACCUCAL FLOWMETERS OPERATING MANUAL GILMONT ACCUCAL FLOWMETERS 28W092 Commercial Ave. Barrington, IL U.S.A. 60010-2392 (847) 381-4888 (847) 381-7053 (Fax) 800-962-7142 www.barnant.com e-mail: barnant@barnant.com A-1299-0766

More information

2008 by Controlmatik ABW

2008 by Controlmatik ABW I N S T R U C T I O N M A N U A L F OR Installation and use of high capacity Vacuum regulator 2008 by Controlmatik ABW CONTENTS 1 GENERAL... 2 2 THE CHLORINE GAS DOSING SYSTEM... 2 2.1 Parts of the chlorine

More information

INTRODUCTION IMPORTANT NOTES AND WARNINGS

INTRODUCTION IMPORTANT NOTES AND WARNINGS INSTRUCTION BULLETIN 26 044 SE Dixie Cutoff Road, Stuart, Florida 34994 USA Phone: (772) 288-4854 Fax: (772) 287-3238 www.regalchlorinators.com Email: regal@regalchlorinators.com REGAL Gas Chlorinator,

More information

INTRODUCTION IMPORTANT NOTES AND WARNINGS

INTRODUCTION IMPORTANT NOTES AND WARNINGS INSTRUCTION BULLETIN 2 044 SE Dixie Cutoff Road, Stuart, Florida 34994 USA Phone: (772) 288-4854 Fax: (772) 287-3238 www.regalchlorinators.com Email: regal@regalchlorinators.com REGAL Gas Chlorinator,

More information

Pressure Dump Valve Service Kit for Series 2300 Units

Pressure Dump Valve Service Kit for Series 2300 Units Instruction Sheet Pressure Dump Valve Service Kit for Series 00 Units. Overview The Nordson pressure dump valve is used to relieve hydraulic pressure instantly in Series 00 applicator tanks when the unit

More information

Installation, Operation and Maintenance Manual for Back Pressure Regulator

Installation, Operation and Maintenance Manual for Back Pressure Regulator Installation, Operation and Maintenance Manual for Back Pressure Regulator Model 8860 2009 Groth Corporation IOM-8860 Rev. B 12541 Ref. ID: 95565 Page 2 of 13 Table of Contents I. INTRODUCTION 3 II. DESIGN

More information

Product Manual. Description. Specifications. CVS Type 1301F and CVS Type 1301G Regulator. Introduction

Product Manual. Description. Specifications. CVS Type 1301F and CVS Type 1301G Regulator. Introduction Product Manual CVS Type 1301F and CVS Type 1301G Regulator Introduction This CVS Controls product manual includes instructions for the installation, adjustment, maintenance and parts ordering of the CVS

More information

Fisher DVI Desuperheater Venturi Inline

Fisher DVI Desuperheater Venturi Inline Instruction Manual DVI Desuperheater Fisher DVI Desuperheater Venturi Inline Contents Introduction... 1 Scope of Manual... 1 Description... 1 Principle of Operation... 2 Installation... 3 Operating Instructions...

More information

Types S100K and S102K Pressure Regulators

Types S100K and S102K Pressure Regulators Instruction Manual Form 5624 Types S0K and S2K 01/01 Types S0K and S2K Pressure Regulators W7478-1 Figure 1. Types S0K and S2K Pressure Regulator Introduction Scope of Manual This manual provides instructions

More information

PRS(TC)4,8 USER MANUAL. Read the complete manual before installing and using the regulator.

PRS(TC)4,8 USER MANUAL. Read the complete manual before installing and using the regulator. PRS(TC)4,8 USER MANUAL Read the complete manual before installing and using the regulator. WARNING INCORRECT OR IMPROPER USE OF THIS PRODUCT CAN CAUSE SERIOUS PERSONAL INJURY AND PROPERTY DAMAGE. Due to

More information

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE INSTALLATION, OPERATION & MAINTENANCE MANUAL INTERFACE DEVICES, INC. 230 Depot Road, Milford, CT 06460 Ph: (203) 878-4648, Fx: (203) 882-0885, E-mail: info@interfacedevices.com

More information

S-COS-16 / S-COSR-16

S-COS-16 / S-COSR-16 172-65260m-05 (S-COS/S-COSR Pressure Reducing Valve) 27 October 2008 ISO 9001/ ISO 14001 Manufacturer Kakogawa, Japan is approved by LRQA LTD. to ISO 9001/14001 Pressure Reducing Valve for Steam S-COS-16

More information

Type 1367 High-Pressure Instrument Supply System with Overpressure Protection

Type 1367 High-Pressure Instrument Supply System with Overpressure Protection Instruction Manual D100343X012 Type 1367 November 2017 Type 1367 High-Pressure Instrument Supply System with Overpressure Protection TYPE 252 FILTER 2ND-STAGE TYPE 67CF FILTER-STYLE REGULATOR INLET TYPE

More information

2.0 INSTALLATION & SERVICE

2.0 INSTALLATION & SERVICE Installation, Operation, and Maintenance Instructions MODEL 5600 / 5600R January 2005 CONTENTS 1.0 GENERAL 1.1 5600 Model Number Information -----------------------------------------------------------------------

More information

Anderson Greenwood Series 93 Positive Pressure POSRV Installation and Maintenance Instructions

Anderson Greenwood Series 93 Positive Pressure POSRV Installation and Maintenance Instructions Before installation these instructions must be fully read and understood Installation and maintenance instructions for Series 93 Positive Pressure Pilot Operated Safety Relief Valves (POSRV). The intent

More information

TITAN FLOW CONTROL, INC.

TITAN FLOW CONTROL, INC. PREFACE: This manual contains information concerning the installation, operation, and maintenance of Titan Flow Control (Titan FCI) Simplex Basket Strainers. To ensure efficient and safe operation of Titan

More information

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1 Dry 131h 1. DESCRIPTION The Viking Model G-1 Maintenance Air Compressor is an electric motor-driven, aircooled, single-stage, oil-less compressor. The unit is equipped with a check valve and provides a

More information

Type HSR Pressure Reducing Regulator for Residential, Commercial, or Industrial Applications

Type HSR Pressure Reducing Regulator for Residential, Commercial, or Industrial Applications Instruction Manual Form 5753 Type HSR October 2003 Type HSR Pressure Reducing Regulator for Residential, Commercial, or Industrial Applications W8648 Figure 1. Type HSR Pressure Regulator Introduction

More information

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity WATER HEATER THERMAL EXPANSION TANKS Owner s Manual Safety Instructions Installation Maintenance Warranty Models: 2-5 Gallon Capacity Thank You for purchasing this Thermal Expansion Tank. Properly installed

More information

Fisher DSA Steam-Atomized Desuperheater

Fisher DSA Steam-Atomized Desuperheater Instruction Manual DSA Desuperheater Fisher DSA Steam-Atomized Desuperheater Contents Introduction... 1 Scope of Manual... 1 Description... 1 Principle of Operation... 2 Installation... 2 Operating Instructions...

More information

Installation Instructions

Installation Instructions Installation Instructions S65-135 (Circular) S65-136 (Semi-Circular) Air Valve Retrofit For Non-Sectional Classic Washfountain Table of Contents.......................2-6 Metering Air Valve Parts List....................6

More information

AQUAMATIC EASY NEST KITS INSTALLATION SUGGESTIONS

AQUAMATIC EASY NEST KITS INSTALLATION SUGGESTIONS AQUAMATIC EASY NEST KITS INSTALLATION SUGGESTIONS TABLE OF CONTENTS TABLE OF CONTENTS...2 GENERAL RECOMMENDATIONS...2 TROUBLESHOOTING GUIDE...3 EXISTING EASY NEST SYSTEM TROUBLESHOOTING GUIDE...4 COMPONENT

More information

Chlorine Supply Containers And Piping

Chlorine Supply Containers And Piping Chlorine Supply Containers And Piping Containers Chlorine is packaged in containers as a liquefied gas under pressure, resulting in the container having both a liquid phase and a gas phase. When removing

More information

SWIRLFLO Refrigerated fountains with FLEXI-GUARD

SWIRLFLO Refrigerated fountains with FLEXI-GUARD TM INSTALLATION, CARE & USE MANUAL SWIRLFLO Refrigerated fountains with FLEXI-GUARD TM INSTALLER! CAUTION: Review these instructions before beginning installation. Be sure that installation conforms to

More information

INSTALLATION and OPERATION INSTRUCTIONS

INSTALLATION and OPERATION INSTRUCTIONS INSTALLATION and OPERATION INSTRUCTIONS FLOJET Beer Pump Panels MODEL NO. 66134-1 66134-2 66134-3 66134-4 IMPORTANT INFORMATION This manual has been prepared to assist you in the operation of Perlick Beer

More information

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO 250C-IG COMPRESSOR KIT 12V PART NO. 25050 250C-IG COMPRESSOR KIT 24V PART NO. 25058 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual

More information

Installation, Operation, and Maintenance Manual

Installation, Operation, and Maintenance Manual Installation, Operation, and Maintenance Manual Welker Probe Instrument Regulator Model The information in this manual has been carefully checked for accuracy and is intended to be used as a guide for

More information

2 GALLON TWIN STACK AIR COMPRESSOR W/ HOSE REEL

2 GALLON TWIN STACK AIR COMPRESSOR W/ HOSE REEL 2 GALLON TWIN STACK AIR COMPRESSOR W/ HOSE REEL Model: 52024 CALIFORNIA PROPOSITION 65 WARNING: You can create dust when you cut, sand, drill or grind materials such as wood, paint, metal, concrete, cement,

More information

INSTALLATION & MAINTENANCE INSTRUCTION

INSTALLATION & MAINTENANCE INSTRUCTION ARCHON Industries, Inc Liquid Level Gauges Models: BT-LLG ND-LLG INSTALLATION & MAINTENANCE INSTRUCTION Instruction No.: 1014.2 Revision Issued: 3/01/03 Approved: Engineering Manager Warning ONLY QUALIFIED

More information

Chlorinator. MODEL C-731 (Floor Mounted)

Chlorinator. MODEL C-731 (Floor Mounted) Chlorinator MODEL C-731 (Floor Mounted) CHLOROTECH Model C-731 is the advance technology Chlorinator designed to feed chlorine gas at a controlled rate. The flow rate of gas is maintained by constant positive

More information

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO 250C-IG COMPRESSOR KIT 12V PART NO. 25050 250C-IG COMPRESSOR KIT 24V PART NO. 25058 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual

More information

Installation, Operation, and Maintenance Manual. Welker Constant Pressure Cylinder With Welker Magnetic Indicator (With Gravity Mixer) Model CP2GM-HP

Installation, Operation, and Maintenance Manual. Welker Constant Pressure Cylinder With Welker Magnetic Indicator (With Gravity Mixer) Model CP2GM-HP Installation, Operation, and Maintenance Manual Welker Constant Pressure Cylinder With Welker Magnetic Indicator (With Gravity Mixer) Model The information in this manual has been carefully checked for

More information

Series 203 Granville-Phillips Variable Leak Valve

Series 203 Granville-Phillips Variable Leak Valve Series 203 Granville-Phillips Variable Leak Valve Instruction Manual Instruction manual part number 203026 Revision B - November 2016 Series 203 Granville-Phillips Variable Leak Valve Customer Service

More information

Gas Lines. Technical Manual. Sumitomo (SHI) Cryogenics of America, Inc Vultee Street Allentown, PA U.S.A.

Gas Lines. Technical Manual. Sumitomo (SHI) Cryogenics of America, Inc Vultee Street Allentown, PA U.S.A. Gas Lines Technical Manual Sumitomo (SHI) Cryogenics of America, Inc. 1833 Vultee Street Allentown, PA 18103-4783 U.S.A. Revision F: April 2008 261320A TABLE OF CONTENTS Page DESCRIPTION...1 SPECIFICATIONS...2

More information

COMBINATION AIR RELEASE DEGASSING (CARD) VALVES INSTALLATION AND MAINTENANCE MANUAL

COMBINATION AIR RELEASE DEGASSING (CARD) VALVES INSTALLATION AND MAINTENANCE MANUAL COMBINATION AIR RELEASE DEGASSING (CARD) VALVES INSTALLATION AND MAINTENANCE MANUAL SPECIFICATIONS: The CARD series air valves are available in 3 pipe sizes, 1, 2 and 4 NPT or socket. Maximum inlet pressure

More information

SPECIFICATIONS Type: Twin stack, single phase Tank: 4 gallon Air Output: PSI; PSI Max PSI: 125 PSI HP: 1.

SPECIFICATIONS Type: Twin stack, single phase Tank: 4 gallon Air Output: PSI; PSI Max PSI: 125 PSI HP: 1. 2 GALLON TWIN STACK AIR COMPRESSOR Model: 9526 DO NOT RETURN TO STORE. Please CALL 800-348-5004 for parts and service. CALIFORNIA PROPOSITION 65 WARNING: You can create dust when you cut, sand, drill or

More information

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST OIL-LESS TYPE IMPORTANT: PLEASE READ CAREFULLY BEFORE STARTING OPERATIONS. THE CONTENTS ARE FOR GENERAL INFORMATION OF ALL THE SIMILAR MODELS. Record

More information

LNG Regulator Test Kit

LNG Regulator Test Kit OVERVIEW Chart provides a LNG Economizer/Regulator Test Kit to help save money and time by allowing a technician to more accurately and easily diagnose the operability of the pressure control regulator/economizer

More information

Needle valve. Contents. User s Manual. (1) Be sure to read the following warranty clauses of our product 1. (2) General operating instructions 2

Needle valve. Contents. User s Manual. (1) Be sure to read the following warranty clauses of our product 1. (2) General operating instructions 2 Serial No. H-V024-E-7 Needle valve User s Manual Contents (1) Be sure to read the following warranty clauses of our product 1 (2) General operating instructions 2 (3) General instructions for transportation,

More information

Model GP PRESSURE REDUCING VALVE Installation & Operation Manual

Model GP PRESSURE REDUCING VALVE Installation & Operation Manual Model GP-2000 PRESSURE REDUCING VALVE Installation & Operation Manual Please read this bulletin thoroughly before using the pressure reducing valve, so that you may do so correctly and safely. Please carefully

More information

ABRASIVE REGULATOR II

ABRASIVE REGULATOR II ABRASIVE REGULATOR II 13096 Abrasive Regulator II TABLE OF CONTENTS 1 Introduction... 1 2 Abrasive Regulator... 2 2.1 Regulator Installation... 2 Location... 2 Attaching the Regulator to the Machine...

More information

TEST SPECIFICATION NYT-909-C

TEST SPECIFICATION NYT-909-C 748 Starbuck Ave, Watertown, NY 13601 Phone: +1-315-786-5200 Engineering Fax: +1-315-786-5673 TEST SPECIFICATION NYT-909-C CODE OF TESTS FOR TESTING "AB" TEST RACK P/N 702546 & 702612 ISSUE NO. 5 1.0 THE

More information

Installation and operating manual. Pneumatic control station LK product no: PCS 1-10

Installation and operating manual. Pneumatic control station LK product no: PCS 1-10 LK product no: PCS 1-10 Article no: 74503 Revision:8 Article no: 74503 Revision: 8 2 (23) Contents 1. General information... 5 2. Safety precautions... 5 2.1 Significance of symbols... 5 2.2 Explanatory

More information

1800C and 1800C-HC Series Service Regulators

1800C and 1800C-HC Series Service Regulators 1800C and 1800C-HC Series Service Regulators Installation Instructions www.elster-americanmeter.com General Information: The 1800C and 1800C-HC Regulators are available as Full Capacity Internal Relief

More information

Certified ISO 9000 INSTALLATION AND OPERATION INSTRUCTIONS. Before Installing or Operating, Read and Comply with These Instructions

Certified ISO 9000 INSTALLATION AND OPERATION INSTRUCTIONS. Before Installing or Operating, Read and Comply with These Instructions ADI 1219-M Certified ISO 9000 1600 Series Dual-Range Flowmeters INSTALLATION AND OPERATION INSTRUCTIONS Before Installing or Operating, Read and Comply with These Instructions Controls Corporation of America

More information

Compact Triple Cabinet Outlet Station Model Installation and Operating Instructions

Compact Triple Cabinet Outlet Station Model Installation and Operating Instructions Compact Triple Cabinet Outlet Station Model 6258-1 Installation and Operating Instructions The Porter Compact Triple Outlet Station (6258-1) provides a quick, safe, and reliable method of connection to

More information

5 Gallon Pressure Pot with HVLP Spray Gun and Hose

5 Gallon Pressure Pot with HVLP Spray Gun and Hose California Air Tools 5 Gallon Pressure Pot with HVLP Spray Gun and Hose Model No. 365 Technical Data Type of feed.pressure Maximum pressure in the tank... 0,413Mpa (60PSI) Working pressure in the tank.0,

More information

Un-Pressurized Orefice Fittings FIO EZ. Parts List and Operation Instructions TECHNICAL MANUAL. Dn 2-6 Class Lbs

Un-Pressurized Orefice Fittings FIO EZ. Parts List and Operation Instructions TECHNICAL MANUAL. Dn 2-6 Class Lbs Un-Pressurized Orefice Fittings FIO EZ Parts List and Operation Instructions TECHNICAL MANUAL Dn 2-6 Class 150-600 Lbs US US 2 FIO EZ - MT 108-US - 05-2016 FIO EZ Important Instructions US Pietro Fiorentini

More information

TECHNICAL DATA. Page 1 of 8. model f /2 (dn40) & 2 (dn50)

TECHNICAL DATA. Page 1 of 8. model f /2 (dn40) & 2 (dn50) Page 1 of 8 1. DESCRIPTION The Viking Model F-1 Deluge Valve is a quick opening, differential diaphragm, flood valve with one moving mechanism. The Deluge Valve is used to control water flow in Deluge

More information

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289 3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS Item #31289 The EASTWOOD 3 GALLON, OILLESS PANCAKE COMPRESSOR, with an Integral Air Regulator, efficiently supplies all compressed air requirements for

More information

MODEL 840 AIR HYDRAULIC PUMP INSTRUCTION

MODEL 840 AIR HYDRAULIC PUMP INSTRUCTION MODEL 840 AIR HYDRAULIC PUMP INSTRUCTION Jackco Transnational Inc. 202 South El Monte, CA 888-452-2526 www.jackco.com FOR YOUR SAFETY Read all instructions, warnings and cautions carefully. Follow all

More information

Preparation and Installation of the Sanitary BDI-FLX Sensor and Connection to the BDI-FLX Interface Cable

Preparation and Installation of the Sanitary BDI-FLX Sensor and Connection to the BDI-FLX Interface Cable GEP-6075 Rev. B 101574 Ref. I.D.: 16973 Preparation and Installation of the Sanitary BDI-FLX Sensor and Connection to the BDI-FLX Interface Cable WARNING USER SHOULD READ AND THOROUGHLY UNDERSTAND THESE

More information

Your safety and the safety of others are very important.

Your safety and the safety of others are very important. NATURAL GAS TO PROPANE CONVERSION KIT ALPKT57- INSTALLATION INSTRUCTIONS PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements... Table of Contents INSTALLATION

More information

Types 95L and 95H Pressure Regulators

Types 95L and 95H Pressure Regulators Instruction Manual Form 1151 Types 95L and 95H July 1990 Types 95L and 95H Pressure Regulators W1888 W1888 W5652 Figure 1. NPT Body (Left), NPT Body (Middle), and Flanged Body (Right) Pressure Regulators

More information

Installation Instructions For Flat Seated Bolted Type RAH Series Disk Holders

Installation Instructions For Flat Seated Bolted Type RAH Series Disk Holders Installation Instructions For Flat Seated Bolted Type RAH Series Disk Holders RA Series Rupture Disks 1. WARNING a) Read the complete instructions before attempting to install the rupture disk and holder

More information

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13 Page 1 of 13 1. Description The Viking 2 Model G-2000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler

More information

Anti-flood device Model B-1

Anti-flood device Model B-1 December 4, 2009 Dry Systems 123a 1. DESCRIPTION The Anti-flood Device is required when Viking accelerators are installed on dry systems according to Viking Model E-1 Accelerator Trim Charts. In the SET

More information

Compact Triple Cabinet Outlet Station Model B Installation and Operating Instructions

Compact Triple Cabinet Outlet Station Model B Installation and Operating Instructions PORTER Parker Hannifin Corporation Porter Instrument Division 245 Township Line Rd. P.O. Box 907 Hatfield, PA 19440-0907 USA (215) 723-4000 / fax (215) 723-5106 Compact Triple Cabinet Outlet Station Model

More information

Wet pipe low flow foam/water system

Wet pipe low flow foam/water system December 6, 2010 Foam 14a 1. The Viking Low Flow Foam/Water proportioning system, is a UL Listed and FM Approved system, for use with Viking supplied foam concentrates. This system consists of a standard

More information

ULTRA-LIGHT DUTY ONBOARD AIR SYSTEM

ULTRA-LIGHT DUTY ONBOARD AIR SYSTEM ULTRA-LIGHT DUTY ONBOARD AIR SYSTEM PART NO. 10000 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual before installing and using

More information

Installation Instructions

Installation Instructions LP and High Altitude LP Gas Conversion Kit For United States Installations Installation Instructions For Model Series *G6/PGF1 Furnaces, *L1/PGC1 Furnaces, and *R4/PPG1 Gas/Electric Appliances using Honeywell

More information

RE: PROPANE SYSTEM & REGULATOR TESTING/INSPECTION PROCEDURE

RE: PROPANE SYSTEM & REGULATOR TESTING/INSPECTION PROCEDURE March 22, 2013 RE: PROPANE SYSTEM & REGULATOR TESTING/INSPECTION PROCEDURE Regulators: Symptom: Pressure Drop Cause: External leaks detected at pigtail hose MPT fitting connection(s) to regulator body

More information

For use with select HPC Fire Pits ONLY- refer to product catalog or website. 100K BTU Maximum WARNING: FOR OUTDOOR USE ONLY

For use with select HPC Fire Pits ONLY- refer to product catalog or website. 100K BTU Maximum WARNING: FOR OUTDOOR USE ONLY For use with select HPC Fire Pits ONLY- refer to product catalog or website. 100K BTU Maximum : FOR OUTDOOR USE ONLY Small Tank LP Kit (STLPK) Installation & Operation Instructions Installation We suggest

More information

GM Series Dual-Block Multi-Function Gas Control Valves

GM Series Dual-Block Multi-Function Gas Control Valves Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin GM Issue Date 0297 GM Series Dual-Block Multi-Function Gas Control Valves Figure 1: GM Series

More information

Model 420-HY Pressure Regulating Hydrant Valve

Model 420-HY Pressure Regulating Hydrant Valve Model 420-HY Pressure Regulating Hydrant Valve INSTALLATION OPERATION MAINTENANCE 1. Safety First BERMAD believes that the safety of personnel working with and around our equipment is the most important

More information

HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS

HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS Page 1 of 20 Page 2 of 20 TABLE OF CONTENTS Safety Warnings

More information

Operation Manual Piston Sensed Gas Pressure Regulators

Operation Manual Piston Sensed Gas Pressure Regulators 687 Technology Way Napa, CA 94558 Phone: (707) 259-0102 FAX: (707) 259-0117 www.aptech-online.com Operation Manual Piston Sensed Gas Pressure Regulators (Models KT9, KT10, Welded KT10, KT12) Table of Contents:

More information

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model 50 Systems Outfitted with ABM-725 Monitor C O M P A N Y

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model 50 Systems Outfitted with ABM-725 Monitor C O M P A N Y INSTALLATION and INSTRUCTION MANUAL for QUALITY AIR BREATHING SYSTEMS Model 50 Systems Outfitted with ABM-725 Monitor M A R T E C H S E R V I C E S C O M P A N Y OFFICE: (507) 843-4700 P.O. BOX 7079 Toll

More information

Accu-Tab PowerBase 3012AT by Axiall Corporation

Accu-Tab PowerBase 3012AT by Axiall Corporation Accu-Tab PowerBase 3012AT by Axiall Corporation Installation and Operating Instructions DANGER: DO NOT MIX CHEMICALS! The PowerBase 3012AT chlorinator system is designed for use with Axiall Corp. approved

More information

WW-720. Pressure Reducing Control Valve

WW-720. Pressure Reducing Control Valve WW-720 Pressure Reducing Control Valve (Size Ranges: 2-4 and 6-14 ) Installation Operation & Maintenance Page 1 of 6 1. DESCRIPTION The Model 720 Pressure Reducing is an automatic control valve (powered

More information

Hot Tapping Machine. OPERATIONS MANUAL and OPERATING INSTRUCTIONS

Hot Tapping Machine. OPERATIONS MANUAL and OPERATING INSTRUCTIONS 262-2040 Hot Tapping Machine For performing 1/4 6 Hot taps 285 psi or less. Municipal Water, Sewage, & Building Services Use OPERATIONS MANUAL and OPERATING INSTRUCTIONS WARNING: These instructions are

More information

Type ACE97 Pad-Depad Valve

Type ACE97 Pad-Depad Valve Instruction Manual Form 5665 Type ACE97 November 2011 Type ACE97 Pad-Depad Valve DEPAD PILOT VALVE DEPAD MAIN VALVE W8161 ACTUATOR VENT GAS INLET PAD VALVE TO TANK Figure 1. Type ACE97 Pad-Depad Valve

More information

PumpAgents.com - Click here for Pricing/Ordering Nominal psi (bar) Cut-In Cut-Out

PumpAgents.com - Click here for Pricing/Ordering Nominal psi (bar) Cut-In Cut-Out PumpAgents.com - Click here for Pricing/Ordering Model 31670-Series Dual Max 7.5 GPM (28 LPM) AUTOMATIC TWO STAGE WATER SYSTEM WITH ACCUMULATOR TANK AND PUMPGARD STRAINER IDEAL FOR PLEASURE AND COMMERCIAL

More information

Model B-1 Pipe Line Strainer 3, 4, 6 & 8 Inch (DN80, DN100, DN150 & DN200) 175 psi (12,1 bar) General Description. Technical Data

Model B-1 Pipe Line Strainer 3, 4, 6 & 8 Inch (DN80, DN100, DN150 & DN200) 175 psi (12,1 bar) General Description. Technical Data Technical Services: Tel: (800) 381-312 / Fax: (800) 71-5500 Customer Service/Sales: Tel: (215) 362-0700 / (800) 523-6512 Fax: (215) 362-5385 Model B-1 Pipe Line Strainer 3,, 6 & 8 Inch (DN80, DN100, DN150

More information

10 DRIP NOZZLE WATERING DRIP KIT Model / Model 46095

10 DRIP NOZZLE WATERING DRIP KIT Model / Model 46095 10 DRIP NOZZLE WATERING DRIP KIT Model 93261 / Model ASSEMBLY AND OPERATING INSTRUCTIONS Due to continuing improvements, actual product may differ slightly from the product described herein. 3491 Mission

More information

RDK-408D2 Cold Head. Technical Manual. SHI-APD Cryogenics Inc Vultee Street Allentown, PA U.S.A. Revision A: September 2005

RDK-408D2 Cold Head. Technical Manual. SHI-APD Cryogenics Inc Vultee Street Allentown, PA U.S.A. Revision A: September 2005 RDK-408D2 Cold Head Technical Manual SHI-APD Cryogenics Inc. 1833 Vultee Street Allentown, PA 18103-4783 U.S.A. Revision A: September 2005 (Reference SHI Manual: December 18, 2003 266404A CD32ZZ-160A)

More information

Pressure Relief Valve Instruction Manual

Pressure Relief Valve Instruction Manual CVR3-M0_062017 Pressure Relief Valve Instruction Manual MODEL: CVR3 SFA Companies 10939 N. Pomona Ave. Kansas City, MO 64153 Tel: 888-332-6419 * Fax: 816-448-2142 E-mail: sales@bvahydraulics.com Website:

More information

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25 Self-operated Pressure Regulators Differential Pressure Regulators (opening) Type 42-20 Type 42-25 Type 42-20 Differential Pressure Regulator Type 42-25 Differential Pressure Regulator Mounting and Operating

More information

HP-104 & HP-106 Tapping Machine OPERATIONS MANUAL

HP-104 & HP-106 Tapping Machine OPERATIONS MANUAL 30230 Los Alamos Rd. Murrieta, CA 92563 800-279-5659 FAX 951-926-2334 TappingMachines.com HP-104 & HP-106 Tapping Machine OPERATIONS MANUAL & OPERATING INSTRUCTIONS WARNING READ: Before using this product,

More information

Yoke Block Instruction Manual

Yoke Block Instruction Manual Yoke Block Instruction Manual ! WARNING IMPORTANT: READ MANUAL COMPLETELY BEFORE OPERATING THIS DEVICE This manual contains instructions on periodically required checks to be performed by the user. These

More information

DS05C,D,G Dial Set Pressure Regulating Valves

DS05C,D,G Dial Set Pressure Regulating Valves DS05C,D,G Dial Set Pressure Regulating Valves APPLICATION The Honeywell DS05C,D,G Dial Set Pressure Regulating Valve is a high quality pressure regulating valve that maintains a constant outlet pressure

More information

ABRASIVE SYSTEM ABRASIVE REGULATOR II 800# BULK ABRASIVE DELIVERY POT Abrasive Regulator II and 800# Pot Manual

ABRASIVE SYSTEM ABRASIVE REGULATOR II 800# BULK ABRASIVE DELIVERY POT Abrasive Regulator II and 800# Pot Manual ABRASIVE SYSTEM ABRASIVE REGULATOR II 800# BULK ABRASIVE DELIVERY POT TABLE OF CONTENTS Contact Information and Customer & Technical Service... 1 1 Introduction... 1 2 Abrasive Regulator... 1 Description:...

More information

OWNERS SERVICE MANUAL NO INSTALLATION, OPERATING & SERVICING INSTRUCTIONS

OWNERS SERVICE MANUAL NO INSTALLATION, OPERATING & SERVICING INSTRUCTIONS MODEL 630 WHEELED / MODEL 63 STATIONARY 33 GALLON (FFFP) ALCOHOL RESISTANT FOAM FIRE EXTINGUISHER 23 CU FT NITROGEN CYLINDER OPERATED OWNERS SERVICE MANUAL NO. 0565 INSTALLATION, OPERATING & SERVICING

More information

TECHNICAL DATA. Inlet Type Outlet Type OBSOLETE. 4. TECHNICAL DATA Approvals:

TECHNICAL DATA. Inlet Type Outlet Type OBSOLETE. 4. TECHNICAL DATA Approvals: February 11, 2005 Deluge Valves 218 a 1. PRODUCT NAME Viking Model F-1 Deluge Valve 8" - Manufactured since 2002 4" & 6" - Manufactured since 2003 2-1/2" & 3" - Manufactured since 2004 2. MANUFACTURER

More information

Model ASSEMBLY and OPERATING INSTRUCTIONS

Model ASSEMBLY and OPERATING INSTRUCTIONS QUICK CHANGE AIR BRUSH KIT Model 93506 ASSEMBLY and OPERATING INSTRUCTIONS Due to continuing improvements, actual product may differ slightly from the product described herein. 3491 Mission Oaks Blvd.,

More information

accidents which arise due to non-observance of these instructions and the safety information herein. SPECIFICATIONS

accidents which arise due to non-observance of these instructions and the safety information herein. SPECIFICATIONS 18 GAUGE 1-1/4 INCH BRAD NAILER Model: 7611 CALIFORNIA PROPOSITION 65 WARNING: You can create dust when you cut, sand, drill or grind materials such as wood, paint, metal, concrete, cement, or other masonry.

More information

SPECIFICATIONS. Normally closed automatic shutoff valve with proof of closure. Fast opening, fast closing. ATTENTION

SPECIFICATIONS. Normally closed automatic shutoff valve with proof of closure. Fast opening, fast closing. ATTENTION SV/614 Installation Manual -P/N 80128 - Ed. 01/08 SV-(DLE) 10../614 Safety Shutoff Valve with Proof of Closure Installation Instructions 1 6 SV/614 SV-DLE/614 SPECIFICATIONS Normally closed automatic shutoff

More information

Operating instruction

Operating instruction Operating instruction MV, XV, HG, HP, RKO, D2G, TV, BV, WB & SLV 1 Introduction 2 2 Stafsjö s knife gate valves 2 3 Technical information 2 3.1 Pressure test 2 3.2 Labelling 2 4 Storage 3 5 Transportation

More information

CARTRIDGE FILTERS. Models: CF50, CF75, CF100, CF150,

CARTRIDGE FILTERS. Models: CF50, CF75, CF100, CF150, CARTRIDGE FILTERS Models: CF50, CF75, CF00, CF50, The installation of this product should be carried out by a qualified pool technician, following the installation instructions provided in this manual.

More information