Instruction Manual MicroChem 2 Chlorine Probes Series CL4000

Size: px
Start display at page:

Download "Instruction Manual MicroChem 2 Chlorine Probes Series CL4000"

Transcription

1 Instruction Manual MicroChem 2 Chlorine Probes Series CL

2 These instructions describe the installation, operation and maintenance of the subject equipment. Failure to strictly follow these instructions can lead to an equipment rupture that may cause significant property damage, severe personal injury and even death. If you do not understand these instructions, please call De Nora Water Technologies for clarification before commencing any work at and ask for a Field Service Manager. De Nora Water Technologies, Inc. reserves the rights to make engineering refinements that may not be described herein. It is the responsibility of the installer to contact De Nora Water Technologies, Inc. for information that cannot be answered specifically by these instructions. Any customer request to alter or reduce the design safeguards incorporated into De Nora Water Technologies equipment is conditioned on the customer absolving De Nora Water Technologies from any consequences of such a decision. De Nora Water Technologies has developed the recommended installation, operating and maintenance procedures with careful attention to safety. In addition to instruction/operating manuals, all instructions given on labels or attached tags should be followed. Regardless of these efforts, it is not possible to eliminate all hazards from the equipment or foresee every possible hazard that may occur. It is the responsibility of the installer to ensure that the recommended installation instructions are followed. It is the responsibility of the user to ensure that the recommended operating and maintenance instructions are followed. De Nora Water Technologies, Inc. cannot be responsible for deviations from the recommended instructions that may result in a hazardous or unsafe condition. De Nora Water Technologies, Inc. cannot be responsible for the overall system design of which our equipment may be an integral part of or any unauthorized modifications to the equipment made by any party other that De Nora Water Technologies, Inc. De Nora Water Technologies, Inc. takes all reasonable precautions in packaging the equipment to prevent shipping damage. Carefully inspect each item and report damages immediately to the shipping agent involved for equipment shipped F.O.B. Colmar or to De Nora Water Technologies for equipment shipped F.O.B Jobsite. Do not install damaged equipment. De Nora Water Technologies, COLMAR OPERATIONS COLMAR, PENNSYLVANIA, USA ISO 9001: 2008 CERTIFIED

3 TABLE OF CONTENTS 2 1 INTRODUCTION General Description Safety Chlorine Probes, Cables Accessories and Consumables Technical Data / Specifications Principle of Operation INSTALLATION General Mounting Dimensions Chlorine Probes Flow Cell Flow Regulation Components Electrical STARTUP MAINTENANCE Periodic functional Check Electrode Maintenance Electrode Membrane Cleaning the electrode surfaces TROUBLE SHOOTING PROCEDURE...16 FIGURES 1 Chlorine Probe Mounting Dimension Chlorine Probe Components Arrangement, Piping, CL4000 Sensor Probe Cable Connections

4 1 INTRODUCTION 1.1 General Description This manual describes the general description, installation, operation and maintenance of the CL4000 Chlorine probes and accessories. Chlorine is the most common chemical used in disinfection of municipal drinking water, cooling towers and many industrial applications. Once added to water the chlorine will react with chemicals already in the water forming combined chlorine or stay available as free chlorine. A chlorine measuring system incorporating the CL4000 chlorine probes, connected to the MicroChem 2 transmitter, provides automatic measurement/control of chlorine dosage in such systems. The CL4000 chlorine probe measures free chlorine. The transmitter is part of the MicroChem 2 series, which is capable of supporting up to three of the following measurements in all possible combinations: Dissolved Oxygen, Chlorine Dioxide, Residual Chlorine, Bromine, Ozone, ORP, Temperature, ph, Iodine and Conductivity. For a description and instructions regarding the transmitter see the MicroChem 2 transmitter instruction manual. The chlorine probes are 3 electrode amperometric cells covered with a permeable membrane. The probe exterior is manufactured from a durable PVC and stainless steel and has a diameter of 25mm (1 inch). The probes are engineered to fit a specially designed flow cell. De Nora Water Technologies chlorine probes can be used without the need for ph compensation. All the CL4000 probes are designed to run without the need for reagents. The probes have no moving parts and are designed to require minimal maintenance. Figure 1 - Chlorine Probe 1.2 Safety The recommended operating procedures have been designed with careful attention to safety. De Nora Water Technologies has made formal safety reviews of the initial design and any subsequent changes. This procedure is followed for all new products and covers areas in addition to those included in applicable safety standards. Observe the following safety precautions: a. Observe all safety warnings marked on the equipment. These warnings identify areas of immediate hazard, which could result in personal injury, or loss of life. b. Do not use this equipment for any purpose other than described in this manual. c. Disconnect power prior to making any terminal connections within the enclosure. d. Use the recommended connection procedures described in Section 2 of this manual. This equipment should only be installed by suitably qualified personnel

5 1.3 Chlorine Probes, Cables, Accessories and Consumables Chlorine Probe 0-2 ppm, ph tolerable (Note 1,2) Chlorine Probe 0-5 ppm, ph tolerable (Note 1,2) Chlorine Probe 0-10 ppm, ph tolerable (Note 1,2) Foot Cable (Note 3) Foot Cable (Note 3) Cable (Note 3) Sample/Drain Tubing, CLEAR, 3/16 ID X 5/16 OD R-376 Flow Through Cell with integral shut off valve (Note 4) Flow Through Cell and Flow Control Kit (Note 4, 6) Sample Flow Control Kit (Note 7) Flow Control Panel Kit (Note 6) Y Strainer 80 mesh, Max Inlet 75 PSIG Pressure Reducing Valve Kit, 0-25 PSIG, Max Inlet 300 PSIG w/15 PSIG Gauge & Bracket Flow Meter Assembly w/rate Valve, 0-10 GPH Flow Switch (Note 7) Carbon Dechlorinating Filter (Note 9) Annual Maintenance Kit for: and Probes Includes: PN and PN , 23184, 23185, and Probes Includes: PN and PN and Probes Includes: PN and PN M48 Membrane Cap to fit 23183, 23184, 23185, , , and Probes M20 Membrane Cap to fit and Probes G-Holder for 23183, 23184, 23185, and Probes Electrolyte Solution (100ml) for and Probes Electrolyte Solution (100ml) for 23183, 23184, 23185, and Probes Electrolyte Solution (100ml) for and Probes Notes: 1. The MicroChem2 Transmitter/Controller must be fitted with the expanded function board (P/N 1T686B129U12, U13 or U14) in order to provide power to the probe and the software must be Version 2.8 or above. Consult factory on upgrading earlier versions of microchem2 transmitter/controllers to the latest revision , 23184, and 23185, probes with 3-electrode sensor for the measurement of free available chlorine. Temperature compensated (0 to 40 C). ph tolerable within the operating range 4 to Cable , or must be used for probe to function properly. 4. Flow cell includes a low pressure fitting (installed) and is also provided with a back pressure fitting to prevent the formation of air bubbles in the probe chamber at sample pressures of 6-8 PSIG ( bar). 5. Flow Control Kit (P/N 23318) improves flow and pressure control of CL4000 probes. It includes a PRV Kit (P/N 23425), Flow Meter Assembly (P/N 23426), 10 ft of tubing and connectors. 6. The Flow Control Panel Kit (P/N 23451) (26" H X 28 W X 0.5" thick) is predrilled and tapped for mounting the Microchem2 and 2 acrylic flow cells for chlorine or for use with ph, conductivity, or ORP 12mm probes and is supplied with mounting hardware. 7. Flow Switch: dry contact opens on loss of sample flow. 8. Dechlorinating Filter provides a chlorine free sample stream, used for calibrating the MicroChem

6 1.4 Technical Data / Specifications Quality Management System: The design & manufacturing process of De Nora Water Technologies are certified to ISO9001. Range: Type of measurement: Temperature Compensation: Speed of Response: Ambient/sample Temp: Limit of Detection: Reproducibility: Accuracy: Sample Inlet Pressure: Sample Temperature: Sample Flow: Electrodes: 0-2 mg/l, 0-5 mg/l or 0-10 mg/l (probe dependant) Free chlorine Internal Ninety (90)% step change < 2 minutes. 32 F F (0 C - 40 C) Probe, chlorine, 0-2 ppm : 0.01 ppm Probe, chlorine, 0-5 ppm : 0.03 ppm Probe, chlorine, 0-10 ppm : 0.05 ppm 0.05 mg/l ± 5% of range 0 to 8 psi (0 to.5 bar) 32 F F (0 C - 40 C) 8 gph (30 liters per hour) Working Electrode - gold Counter Electrode - stainless steel Reference Electrode: Silver/Silver-Chloride ph: Chlorine: independent of ph (ph 4 to ph 9.5) Signal loss is 5% per ph unit (ph greater than 7) Dimensions: In flow cell: 14.6 (h) x 2.25 (dia) 370mm x 55 mm Probe alone 1 (dia) x 9 (l), 25mm (dia) x 230mm (l) Weight: probe and flow cell 1lb (450g) Connectors: Cable: Sample Limitations: Ammonia Interference: Permanganate Interference: 2 x compression fitting for flexible tubing ID 3/16, OD 5/16 Various lengths available Samples containing particles 100 microns (0.004 inches) in diameter and larger may require pre-filtration. There should be no surfactants in the water. CL4000 probes in the presence of ammonia will measure free and/or combined chlorine. 1 ppm permanganate = 0.5 ppm chlorine

7 1.5 Principle of Operation The chlorine probes are amperometric cells covered with a permeable membrane. The probes are engineered to fit a specially designed flow cell. A sample of liquid is delivered to the input (bottom) of the flow cell at an approximate rate of 500 ml/min. The sample passes the membrane on the tip of the membrane cap. Chlorine diffuses through the membrane and into the internal filling solution where a small DC current is generated between the stainless steel counter electrode and gold working electrode in direct linear proportion to the amount of residual present in the sample. A third reference electrode establishes a constant potential on the gold working electrode to provide an accurate and stable residual signal. The signal is amplified and transmitted to the MicroChem 2 transmitter/controller via the sensor cable. The probe needs to be loop powered. This power is generated within the MicroChem 2 and supplied to the probe in the same cable which transmits the residual signal. All the CL4000 chlorine probes are designed to run without the need for reagents. The probes have no moving parts and are designed to require minimal maintenance

8 2 INSTALLATION 2.1 General Remove the instrument from its box and carefully inspect each item and report damages immediately. The box will include the chlorine probe (electrode shaft, top cap and membrane cap), electrolyte bottle and a sheet of blue abrasive paper. The chlorine probes are designed for general duty indoor installation. Outdoor installation is possible if the instrument is shielded from dripping water and not mounted in direct sunlight. Ensure that the process and environmental conditions are within specified limits (see specification). Excessive heat and vibration will affect the sensors. 2.2 Mounting Dimensions Sample connectors are compression fitting, requiring flexible tubing 3/16 ID x 5/16 OD Figure 2 - Mounting Dimensions

9 2.3 Chlorine Probes WARNING Do not touch the electrode finger (see Figure 3) Do not touch the bottom of the membrane cap (see Figure 3) To assemble the probes for use: Vent hole Vent Seal When removing the membrane cap, move the vent seal away from the vent hole to allow air into the membrane cap. Not doing so may cause a vacuum to form and damage the membrane. Fill the membrane cap to the top with electrode filling solution (note each electrode has a specially formulated filling solution which is unique to that sensor see parts list for details). Tap the side of the membrane cap to remove any air bubbles that may have formed in the solution. Reposition the vent seal, making sure that the vent hole is completely covered. Fill up the G-holder with filling solution. Be careful that there are no bubbles. Hold the electrode shaft upright and push the electrode finger carefully into the filled G-holder. While holding the electrode shaft vertically with the G-holder in place, screw the filled membrane cap back on to the electrode shaft. Make sure not to press on the vent ring seal or cover the area of the vent hole with a finger when installing the membrane cap. Excess filling solution will escape from top or the vent in the membrane cap. Rinse off any filling solution that may have escaped during the installation with clean water

10 Note: The G-holder is supplied and required for use with the chlorine probes and with the annual maintenance kits containing the M48 membrane cap. See parts list for details. Note: When unscrewing the filled membrane cap from the electrode shaft, first remove the vent seal and ensure that the vent is not covered by a finger (air needs to be allowed through the vent hole to equalize the pressure). Note: Make sure the membrane cap is tightly fastened to the electrode shaft ensuring that no gap remains between the electrode shaft and the membrane cap. Note: It is best to wait 1-4 hours before the first calibration is performed. After one day repeat the calibration. See the MicroChem 2 electronics manual for calibration instructions. Note: Calibration must be made with a continuous flow of liquid at 500 ml/min across the cell membrane

11 Figure 3 - Chlorine Probe Components

12 2.4 Flow Cell The probe is inserted through a fitting which includes a slide ring and o-ring. Loosen or disassemble the fitting to allow the probe to slide through the o-ring. The fitting may include a cap through which the probe cable must be fed. Position the probe so it is about 1 inch (25 mm) from the bottom of the cell. Tighten the fitting into the housing to compress the o-ring around the probe, providing a seal. The inlet valve may be used to provide control the flow to the probe. It should be full open if the sample stream is controlled by other components. The adapter to be used on the outlet from the cell and is dependent on the sample supply. The sample flow as noted in the section 1.4 is required. Excessive air in the sample may adversely affect the readings. The small orifice adapter may be used to provide back pressure to keep the air from outgasing from the sample stream. 2.5 Flow Regulation Components (See Figure 4) To provide a sample to be measured for chlorine content with reduced potential for erratic readings and calibration problems, it is highly recommended that some or all of the components in Figure 4 are incorporated in the sample line. The Y-strainer is for particulate removal. The flow switch provides alarm when flow is not present. The remaining components through the back pressure assembly will ensure that you are providing the proper flow and pressure to allow optimum analysis. The back pressure assembly is used in applications where air bubbles effervesce from the sample

13 Figure 4 Arrangement, Piping, CL4000 Sensor Key Part Number Description Y-strainer - (optional) for particulate removal (See Note 1) Pressure Reducing Valve, 0-25 PSIG (See Note 1) Pressure Gauge, 0-15 PSIG, ¼ NPT SS (See Note 1) Flowmeter with Rate Valve, 0-10 GPH (See Note 2) Flow Switch CL4000 Flow Cell Fitting, ¼ MNPT x 5/16 Tube Fitting, 1/8 MNPT x 5/16 Tube 90 Deg Notes: 1. Included in Flow Control Kit P/N Used to indicate if sample flow is present. For connection to external device or alarm contact

14 2.6 Electrical The chlorine probes are connected to the transmitter analog board at pin 5 and 6 AND to the 24v power supply terminals (see Figure 5). For more details on the analog board see the transmitter manual. WARNING The transmitter power MUST be switched OFF before the probe is attached Terminals 9-12 are +24v Terminals are 0V (G) (6) (+) (5) (-) - + probe S4000 Cable Assembly 4 feet feet feet Figure 5 - Probe Cable Connections WARNING For proper operation of the chlorine probe, one of the above listed cable Assemblies must be used

15 3 STARTUP 1. Check that the entire installation is connected properly. Check the electrode is properly connected via the supplied cable. 2. Configure the transmitter channel that the probe is connected to for CL (Chlorine). Select CL probe (ma) as the probe type. Set the probe range (0-2, 0-5 or 0-10 ppm) as indicated on the chlorine probe label. Refer to the MicroChem 2 Transmitter instruction manual for additional start-up information. 3. A calibration must be performed. Please find the instructions related to the procedure in the MicroChem 2 instruction bulletin. 4. Output from CL4000 probes is never below 3.8 ma. At start-up, the probes may have an output as low as 2 to 2.5 ma, but will rise to about 4 ma after half an hour. If output is less, the electrolyte will need to be changed and the gold probe cleaned. Momentary power losses will also result in low output, but will increase in about 30 minutes. 4 MAINTENANCE 4.1 Periodic Functional Check The MicroChem 2 analyzer, like other analyzers, should be checked once per week to assure the best measurement accuracy. 4.2 Electrode Maintenance There is very little maintenance required on a chlorine electrode. Periodically the electrode should be removed, and rinsed with de-ionised water. CAUTION Do not touch the tip of the electrode Electrode Membrane The membrane cap needs to be replaced periodically (typically annually). The internal filling solution needs to be replaced at the same time (section 2.3) Note: pay particular attention to the notes on removing the membrane cap. If the membrane gets coated it is possible to clean it. Very carefully swirl the membrane in a 1% hydrochloric acid solution Cleaning the electrode surfaces If the electrode has been stored for a long period of time the (gold) working electrode surface may become tarnished and require polishing. Empty out the internal filling solution (section 2.3). Dry the electrode finger carefully using a clean dry cloth.holding the blue abrasive paper flat on a clean dry surface and holding the electrode body vertically move the tip of the electrode across the paper two or three times. Refill and reattach the membrane cap. (see section 2.3)

16 5 TROUBLE SHOOTING PROCEDURE PROBLEM PROBABLE CAUSE CORRECTIVE ACTION No indication No power supply to the transmitter Power the transmitter up or check the power supply fuse. Check power supply jumper setting. Reading on Display is not in agreement with Faulty transmitter Verify transmitter (especially analogue board) the chlorine level The sensor is not continuously in Modify sensor installation present in the sample contact with the sample The connection between the sensor Make correct connections and the transmitter is not correct. Membrane is split or coated; internal Replace membrane and filling solution filling solution contaminated or depleted The working electrode may be Clean the electrode surface tarnished The chlorine cell has been selected rather than the chlorine probe. (RT Fault will be displayed with this error) Reprogram the transmitter software The wrong chlorine range has been Reprogram the transmitter software Reading on Display is fluctuating or erratic set up Not properly calibrated Chlorine level is fluctuating Sample flow rate is too low or variable The sensor is not continuously in contact with the sample Air bubbles in the sample RTD Fault displayed Incorrect chlorine channel definition Wrong chlorine input selected Recalibrate P2 Check the process Resolve flow problems. Add Pressure Regulator and Flow meter for sample control. Modify sensor installation Eliminate the air bubbles or modify the installation Refer to transmitter instruction manual. Select chlorine probe channel definition. Design improvements may be made without notice. Represented By: De Nora Water Technologies 3000 Advance Lane Colmar, PA ph fax web: mail: Registered Trademark All Rights Reserved. De Nora Water Technologies Arley Drive Birch Coppice Business Park Dordon, Tamworth B78 1SA Tel +44 (0) Fax +44 (0) SEP

Instruction Manual Pressure Relief Valve and Rupture Disc Chlorine or Sulfur Dioxide, Series 869

Instruction Manual Pressure Relief Valve and Rupture Disc Chlorine or Sulfur Dioxide, Series 869 Instruction Manual Pressure Relief Valve and Rupture Disc Chlorine or Sulfur Dioxide, Series 869-1 - 115.6020.15 These instructions describe the installation, operation and maintenance of the subject equipment.

More information

Instruction Manual - Diaframless TM Ejector Chlorine, Sulfur Dioxide and Ammonia

Instruction Manual - Diaframless TM Ejector Chlorine, Sulfur Dioxide and Ammonia Instruction Manual - Diaframless TM Ejector Chlorine, Sulfur Dioxide and Ammonia - 1-122.6010.6 These instructions describe the installation, operation and maintenance of the subject equipment. Failure

More information

Instruction Manual O-Ring Ejector Chlorine & Sulfur Dioxide to 500 PPD (10 kg/h)

Instruction Manual O-Ring Ejector Chlorine & Sulfur Dioxide to 500 PPD (10 kg/h) Instruction Manual O-Ring Ejector Chlorine & Sulfur Dioxide to 500 PPD (10 kg/h) 100 PPD (2 kg/h) Maximum 250 PPD (5 kg/h) Maximum 500 PPD (10 kg/h) Maximum - 1-122.6006.9 These instructions describe the

More information

CAPITAL CONTROLS SERIES NXT3000

CAPITAL CONTROLS SERIES NXT3000 CAPITAL CONTROLS SERIES NXT3000 Modular design gas feed system with self contained automatic switchover capability. The Series NXT3000 Gas Feed System is a family of vacuumoperated, solution-feed gas dispensing

More information

CCS240 and CCS241. Technical Information. Sensors for chlorine dioxide Amperometric, membrane-covered sensors for installation in the CCA250 assembly

CCS240 and CCS241. Technical Information. Sensors for chlorine dioxide Amperometric, membrane-covered sensors for installation in the CCA250 assembly Technical Information CCS240 and CCS241 Sensors for chlorine dioxide Amperometric, membrane-covered sensors for installation in the CCA250 assembly Application Chlorine dioxide is used for disinfection

More information

Series 4000 Transmitter Analyzer Controller. Series CL4000 Chlorine Probes used with MicroChem 2

Series 4000 Transmitter Analyzer Controller. Series CL4000 Chlorine Probes used with MicroChem 2 www.severntrentservices.com MicroChem 2 Series 4000 Series 4000 Transmitter Analyzer Controller Series CL4000 Chlorine Probes used with MicroChem 2 Series 4000 Transmitter and CL4000 Bufferless Probe Series

More information

Capital Controls Series NXT3000 Modular design gas feed system with self-contained automatic switchover capability.

Capital Controls Series NXT3000 Modular design gas feed system with self-contained automatic switchover capability. Capital Controls Series NXT3000 Modular design gas feed system with self-contained automatic switchover capability. The Series NXT3000 Gas Feed System is a family of vacuum-operated, solution-feed gas

More information

Highest Quality. Gas Chlorination Systems

Highest Quality. Gas Chlorination Systems Highest Quality Gas Chlorination Systems Application: Gas chlorination systems are used for water disinfection and other purposes in a variety of applications. Compared to other disinfection methods, chlorine

More information

ACV-10 Automatic Control Valve

ACV-10 Automatic Control Valve ACV-10 Automatic Control Valve Installation, Operation & Maintenance General: The Archer Instruments ACV-10 is a precision automatic feed rate control valve for use in vacuum systems feeding Chlorine,

More information

Non-Membrane Disinfection Sensors Instruction Manual

Non-Membrane Disinfection Sensors Instruction Manual W A L C H E M IWAKI America Inc. Disinfection Sensors Non-Membrane Disinfection Sensors Instruction Manual Five Boynton Road Hopping Brook Park Holliston, MA 01746 USA TEL: 508-429-1110 WEB: www.walchem.com

More information

STERILIZABLE DISSOLVED OXYGEN SENSORS

STERILIZABLE DISSOLVED OXYGEN SENSORS STERILIZABLE DISSOLVED OXYGEN SENSORS USER MANUAL Table of Contents 1. Introduction 2. Operation 3. Calibration 4. Electrode Verification 5. Mounting 6. Maintenance 7. Storage 8. Instructions for Exchange

More information

T EK-SUB 4800C 19 mm Submersible Level Transmitter

T EK-SUB 4800C 19 mm Submersible Level Transmitter Technology Solutions T EK-SUB 4800C 19 mm Submersible Level Transmitter Instruction Manual Document Number: IM-4800C www.tek-trol.com Table of Contents 1 Safety Instructions... 2 1.1 Intended Use... 2

More information

Model PDT Dewpoint Transmitter

Model PDT Dewpoint Transmitter Model PDT Dewpoint Transmitter Instruction Manual Alpha Moisture Systems Alpha House 96 City Road Bradford BD8 8ES England Tel: +44 1274 733100 Fax: +44 1274 733200 email: mail@amsytems.co.uk web: www.amsystems.co.uk

More information

BI-680 Online Dissolved Oxygen Controller Instruction Manual

BI-680 Online Dissolved Oxygen Controller Instruction Manual BI-680 Online Dissolved Oxygen Controller Instruction Manual BANTE INSTRUMENTS CO., LTD BI-680 Online Dissolved Oxygen Controller 1 Introduction Thank you for selecting the BI-680 online dissolved oxygen

More information

Dissolved Oxygen Sensor

Dissolved Oxygen Sensor Instruction Manual 499ADO and 499ADO-VP LIQ_MAN_ABR_499ADO May 2014 Dissolved Oxygen Sensor CAUTION For additional information, please visit our website at www.rosemountanalytical.com SENSOR/PROCESS APPLICATION

More information

Free Chlorine Sensor For additional information, please visit our website at

Free Chlorine Sensor For additional information, please visit our website at Instruction Manual 499ACL01 LIQ_MAN_ABR_499ACL01 April 2014 Free Chlorine Sensor For additional information, please visit our website at www.rosemountanalytical.com. CAUTION Sensor/Process Application

More information

Quick Start Guide LIQ-QSG-499AOZ, Rev M July Rosemount 499AOZ. Dissolved Ozone Sensor

Quick Start Guide LIQ-QSG-499AOZ, Rev M July Rosemount 499AOZ. Dissolved Ozone Sensor Quick Start Guide LIQ-QSG-499AOZ, Rev M July 2017 Rosemount 499AOZ Dissolved Ozone Sensor Safety information CAUTION! SENSOR/PROCESS APPLICATION COMPATIBILITY The wetted sensor material may not be compatible

More information

Water Weir Flow Controller. Introduction. Safety Precautions. Mounting the Hardware

Water Weir Flow Controller. Introduction. Safety Precautions. Mounting the Hardware 57007-88 Introduction Safety Precautions This instruction sheet describes how to set up and use the Hach (Figure 1). A water weir is a device that raises or diverts water to regulate the flow. Hach s water

More information

Technical Information

Technical Information Technical Information Installation, Operation, Installation, Operation and Maintenance and Maintenance Manual Manual Balston Model 75700-K728 Nitrogen Generator Figure 1-75700-K728 Overall Dimensions These

More information

PART 1 GENERAL..2 Components of the gas chlorination system include, but are not limited to the following:

PART 1 GENERAL..2 Components of the gas chlorination system include, but are not limited to the following: PART 1 GENERAL 1.1 DESCRIPTION.1 This section includes the supply, delivery and installation, testing and placement into operation of a gas chlorination system, and appurtenances as specified herein and

More information

Welker Sampler. Model GSS-1. Installation, Operation, and Maintenance Manual

Welker Sampler. Model GSS-1. Installation, Operation, and Maintenance Manual Installation, Operation, and Maintenance Manual Welker Sampler Model GSS-1 The information in this manual has been carefully checked for accuracy and is intended to be used as a guide to operations. Correct

More information

INSTRUCTION MANUAL. 840 Transmitter. Loop Powered Dissolved Oxygen Transmitter

INSTRUCTION MANUAL. 840 Transmitter. Loop Powered Dissolved Oxygen Transmitter INSTRUCTION MANUAL Loop Powered Dissolved Oxygen Transmitter Contents Contents...2 Introduction...3 Range and Display Settings...4 Installation...5 Electrical Installation...6 Calibration...7 EasyCal...8

More information

Bante810 Benchtop Dissolved Oxygen Meter Instruction Manual

Bante810 Benchtop Dissolved Oxygen Meter Instruction Manual Bante810 Benchtop Dissolved Oxygen Meter Instruction Manual BANTE INSTRUMENTS CO., LTD Bante810 Benchtop Dissolved Oxygen Meter 1 Introduction Thank you for selecting the Bante810 benchtop dissolved oxygen

More information

Installation, Operation, and Maintenance Manual

Installation, Operation, and Maintenance Manual Installation, Operation, and Maintenance Manual Welker The information in this manual has been carefully checked for accuracy and is intended to be used as a guide for the installation, operation, and

More information

256 Pneumatic Pressure Indicator

256 Pneumatic Pressure Indicator 256 Pneumatic Pressure Indicator 51425699 Copyright 2002 Slope Indicator Company. All Rights Reserved. This equipment should be installed, maintained, and operated by technically qualified personnel. Any

More information

CSA Sample Draw Aspirator Adapter Operator s Manual

CSA Sample Draw Aspirator Adapter Operator s Manual 30-0951-CSA Sample Draw Aspirator Adapter Operator s Manual Part Number: 71-0367 Revision: 0 Released: 4/30/15 www.rkiinstruments.com WARNING Read and understand this instruction manual before operating

More information

Electropneumatic Transducer (I/P) Installation, Operation and

Electropneumatic Transducer (I/P) Installation, Operation and Nitra NCP1 Series Electropneumatic Transducer (I/P) Installation, Operation and Maintenance Instructions Ordering Information Contents Part Number I/P Transducers Output Range Input psig bar Section Description

More information

Instruction Bulletin Addendum For Pressure-Balanced In Situ Oxygen Probes

Instruction Bulletin Addendum For Pressure-Balanced In Situ Oxygen Probes Instruction Bulletin Addendum For Pressure-Balanced In Situ Oxygen Probes Instruction Bulletin Addendum IB PB1000 Part no. Serial no. Order no. Oxymitter 4000 Applicability: Used with pressure-balancing

More information

Model VR6 System. Installation, Operation & Maintenance

Model VR6 System. Installation, Operation & Maintenance Model VR6 System Installation, Operation & Maintenance General: All Archer Instruments chlorination systems are carefully designed and tested for years of safe, accurate field service. All Archer Instruments

More information

CS Controlled Dissolved Gas assembly with optional CS Air Aspirator assembly. Installation and Operation information

CS Controlled Dissolved Gas assembly with optional CS Air Aspirator assembly. Installation and Operation information CS-425-01 Controlled Dissolved Gas assembly with optional CS-603-01 Air Aspirator assembly Installation and Operation information Serial # CS-XXX Date of shipment:, 2005 Shipped to: Purchase order #: xxxxxxx

More information

UsER manual for Watersens ph -REDOX

UsER manual for Watersens ph -REDOX UsER manual for Watersens -REDOX Cl 8 1 2 6 3 3 7 7 4 4 4 4 Parts List 1 Redox Probe 1 x 2 PH Probe 1 x 5 Tube Weight 2 x 6 Connection Valve 1 x chlorine 3 Chlorine and Pumps 2 x 7 Dosing Valve 2 x 5 5

More information

Bante820 Portable Dissolved Oxygen Meter Instruction Manual

Bante820 Portable Dissolved Oxygen Meter Instruction Manual Bante820 Portable Dissolved Oxygen Meter Instruction Manual BANTE INSTRUMENTS CO., LTD Bante820 Portable Dissolved Oxygen Meter 1 Introduction Thank you for selecting the Bante820 portable dissolved oxygen

More information

Chlorine Supply Containers And Piping

Chlorine Supply Containers And Piping Chlorine Supply Containers And Piping Containers Chlorine is packaged in containers as a liquefied gas under pressure, resulting in the container having both a liquid phase and a gas phase. When removing

More information

GILMONT ACCUCAL FLOWMETERS

GILMONT ACCUCAL FLOWMETERS OPERATING MANUAL GILMONT ACCUCAL FLOWMETERS 28W092 Commercial Ave. Barrington, IL U.S.A. 60010-2392 (847) 381-4888 (847) 381-7053 (Fax) 800-962-7142 www.barnant.com e-mail: barnant@barnant.com A-1299-0766

More information

Oxygen Measurement Systems High Reliability and Wide Application Coverage

Oxygen Measurement Systems High Reliability and Wide Application Coverage Introduction High Process Efficiency Under Any Condition Oxygen Measurement Systems High Reliability and Wide Application Coverage METTLER TOLEDO provides sensors to measure dissolved oxygen (DO) in demanding

More information

Dextens Thermo Conductivity Sensors. Type 52101, 54101, 55101

Dextens Thermo Conductivity Sensors. Type 52101, 54101, 55101 Dextens Thermo Conductivity Sensors Type 52101, 54101, 55101 Operating Manual May 2012 Table of Content 1 GENERAL INFORMATION...4 1.1 DISCLAIMER...4 1.2 SYMBOLS AND CONVENTIONS...4 1.3 SERVICES AND REPAIRS...4

More information

STEAM STERILIZABLE POLAROGRAPHIC OXYGEN ELECTRODE

STEAM STERILIZABLE POLAROGRAPHIC OXYGEN ELECTRODE STEAM STERILIZABLE POLAROGRAPHIC OXYGEN ELECTRODE GENERAL INFORMATION This family of dissolved oxygen electrodes is of the steam sterilizable polarographic type, designed to be interchangeable with NBS

More information

QUICK START GUIDE TO DRINKING WATER MONITORING

QUICK START GUIDE TO DRINKING WATER MONITORING APPENDIX F QUICK START GUIDE TO DRINKING WATER MONITORING Introduction: This Quick Start guide is designed to allow users who are already familiar with the basic use of YSI 6-series sondes for surface

More information

Air Check Lite Toxic Gas Monitor

Air Check Lite Toxic Gas Monitor Air Check Lite Toxic Gas Monitor Instruction Manual PureAire Monitoring Systems, Inc. 557 Capital Drive Lake Zurich, Illinois 60047 Phone: 847-726-6000 Fax: 847-726-6051 Toll-Free: 888-788-8050 www.pureairemonitoring.com

More information

Sanitizers. Sanitizers. Sanitizers for Pools & Spas

Sanitizers. Sanitizers. Sanitizers for Pools & Spas for Pools & Spas 207 IntelliChlor Salt Chlorinator Featured Highlights IntelliChlor Salt Chlorinator IntelliChlor Salt Chlorinator uses common table salt to produce all the chlorine a pool needs, safely,

More information

DTG - LCD Digital Temperature Gauge USER MANUAL

DTG - LCD Digital Temperature Gauge USER MANUAL DTG - LCD USER MANUAL Page 1 of 7 USERS GUIDE page 1. Description 3 2. Function 3 3. Safety Instruction 3 3.1. Safety Conventions 3 3.2. Proper Use 3 4. Installation 4 4.1. Unpacking 4 4.2. Storage 4 4.3.

More information

SPECIFICATIONS ATTENTION

SPECIFICATIONS ATTENTION VPS 504 S06 Installation Manual - P/N 80122 - Ed. 01/09 VPS 504 S06 and S05 Valve Proving System Installation Instructions VPS 1 6 Gases Natural gas, air and other inert gases. NOT suitable for butane

More information

LogIT Dissolved Oxygen Probe

LogIT Dissolved Oxygen Probe LogIT Dissolved Oxygen Probe INTRODUCTION The LogIT Dissolved Oxygen Probe (DO2) has been designed especially for LogIT and is easy to set up and use. It features simple single control calibration and

More information

Installing a Probe. Typical Installation

Installing a Probe. Typical Installation for hazardous locations. Prior to any installation in a Classified Hazardous Location, verify installation methods by the Control Drawing referenced on the product s name tag 2. The Feed Through Assemblies

More information

Variable Area Flow Meters

Variable Area Flow Meters Variable Area Flow Meters Over sixty years of variable area meter expertise Brooks started designing and manufacturing variable area (VA) meters, also referred to as rotameters, in 1946. Now, with more

More information

TECHNICAL INFORMATION

TECHNICAL INFORMATION TECHNICAL INFORMATION Installation, Operation, and Maintenance Balston Model 75-77 Nitrogen Generator Figure 1-75-77 Overall Dimensions These instructions must be thoroughly read and understood before

More information

Installation, Operation, and Maintenance Manual

Installation, Operation, and Maintenance Manual Installation, Operation, and Maintenance Manual Welker Probe Instrument Regulator Model The information in this manual has been carefully checked for accuracy and is intended to be used as a guide for

More information

TEK-SUB 4800B. Submersible Level Transmitter. Flow Level Temperature Pressure Valves Analyzers Accessories TekValSys LEVEL

TEK-SUB 4800B. Submersible Level Transmitter.   Flow Level Temperature Pressure Valves Analyzers Accessories TekValSys LEVEL Technology Solutions TEK-SUB 4800B Submersible Level Transmitter LEVEL Flow Level Temperature Pressure Valves Analyzers Accessories TekValSys Introduction The Tek-Sub 4800B Submersible Level Transmitter

More information

Chemical Feed Equipment Floor-Mounted Gas Dispenser - Series CH4200

Chemical Feed Equipment Floor-Mounted Gas Dispenser - Series CH4200 Specification Bulletin (rev.01) Series CH4200 Chemical Feed Equipment Floor-Mounted Gas Dispenser - Series CH4200 Easy, fast& accurate digital with 11 points calibration Laser sensor offering actual feed

More information

EASTERN ENERGY SERVICES PTE LTD. 60 Kaki Bukit Place #02-19 Eunos Tech Park Singapore, SG Singapore Telephone: Fax:

EASTERN ENERGY SERVICES PTE LTD. 60 Kaki Bukit Place #02-19 Eunos Tech Park Singapore, SG Singapore Telephone: Fax: 2 Table Of Contents 1. Introduction 3 2. About this Manual 3 3. Contacting YZ Systems 3 4. Vessel Components 4 5. Specifications 5 6. Application 6 7. Theory of Operation 7 8. DuraSite Installation & Use

More information

Sanitizers. Sanitizers. Sanitizers for Pools & Spas

Sanitizers. Sanitizers. Sanitizers for Pools & Spas Sanitizers Sanitizers for Pools & Spas 213 213 IntelliChlor Salt Chlorinator Featured Highlights IntelliChlor Salt Chlorinator IntelliChlor Salt Chlorinator uses common table salt to produce all the chlorine

More information

Avenger Model 33M Installation & Operation Instructions

Avenger Model 33M Installation & Operation Instructions Avenger Model 33M Installation & Operation Instructions Manufacturing Contact Information A+ Corporation, LLC Call for expert product application assistance: 41041 Black Bayou Rd. Gonzales, LA 70737 Phone:

More information

DOscan10 Pocket Dissolved Oxygen Tester Instruction Manual

DOscan10 Pocket Dissolved Oxygen Tester Instruction Manual DOscan10 Pocket Dissolved Oxygen Tester Instruction Manual BANTE INSTRUMENTS CO., LTD DOscan10 Pocket Dissolved Oxygen Tester 1 Thank you for selecting the DOscan10 pocket dissolved oxygen tester. This

More information

36H SERIES Combination Gas Valve

36H SERIES Combination Gas Valve FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION The 36H series combination gas valve is

More information

Chemical Injection Technologies Installation/Service Bulletin

Chemical Injection Technologies Installation/Service Bulletin Bulletin 4002 Chemical Injection Technologies Installation/Service Bulletin SUPERIOR Series CL-16/26/56 Automatic Switchover Gas Chlorinator - Installation & Operation IMPORTANT!! READ THESE PRECAUTIONS

More information

Instruction Manual ADVANCE TM Wall Panel Gas Feeders Series WP70CV3

Instruction Manual ADVANCE TM Wall Panel Gas Feeders Series WP70CV3 LIQUID FIL DO NOT TAM Instruction Manual ADVANCE TM Wall Panel Gas Feeders Series WP70CV3 LIQUID FIL DO NOT TAM 500 PPD (10 kg/h Chlorine & Sulfur Dioxide 3000 PPD (60 kg/h Chlorine & Sulfur Dioxide Auto

More information

Calcimeter Instruction Manual

Calcimeter Instruction Manual Hohner (UK - Canada - Texas) Calcimeter Instruction Manual The Hohner Calcimeter is based on industry standard versions, and is used to measure the calcium carbonate and magnesium carbonate in samples.

More information

Model 130M Pneumatic Controller

Model 130M Pneumatic Controller Instruction MI 017-450 May 1978 Model 130M Pneumatic Controller Installation and Operation Manual Control Unit Controller Model 130M Controller is a pneumatic, shelf-mounted instrument with a separate

More information

Rosemount 140/141/142

Rosemount 140/141/142 Rosemount 140/141/142 Contacting Conductivity Sensors Instruction Manual LIQ-MAN-140 Rev. F May 2017 hasgkas Essential Instructions Read this page before proceeding! Emerson designs, manufactures and tests

More information

Installation, Operation, and Maintenance Manual Parker Balston Model N2-04 Nitrogen Generator

Installation, Operation, and Maintenance Manual Parker Balston Model N2-04 Nitrogen Generator Installation, Operation, and Maintenance Manual Parker Balston Figure 1 - N2-04 Nitrogen Generator These instructions must be thoroughly read and understood before installing and operating this product.

More information

Air Operated Hydraulic Pumping Systems to 50,000 psi

Air Operated Hydraulic Pumping Systems to 50,000 psi High Pressure Equipment Air Operated Hydraulic Pumping Systems to 50,000 psi PS-10: 10,000 psi PS-20: 20,000 psi PS-30: 30,000 psi PS-40: 40,000 psi PS-50: 50,000 psi PS-90: 90,000 psi High Pressure air

More information

RK-IR Sample Draw Aspirator Adapter Operator s Manual

RK-IR Sample Draw Aspirator Adapter Operator s Manual 30-0951RK-IR Sample Draw Aspirator Adapter Operator s Manual Part Number: 71-0018RK Revision: A Released: 6/2/10 www.rkiinstruments.com Product Warranty RKI Instruments, Inc. warrants gas alarm equipment

More information

Oxymax W COS41. Technical Information. Potentiostatic amperometric two-electrode sensor Long-term stable sensor for water and wastewater applications

Oxymax W COS41. Technical Information. Potentiostatic amperometric two-electrode sensor Long-term stable sensor for water and wastewater applications Technical Information Oxymax W COS41 Potentiostatic amperometric two-electrode sensor Long-term stable sensor for water and wastewater applications Application The continuous measurement of the dissolved

More information

Columbus Instruments

Columbus Instruments 0215-003M Portable O 2 /CO 2 /CH 4 Meter User s Manual Columbus Instruments 950 NORTH HAGUE AVENUE TEL:(614) 276-0861 COLUMBUS, OHIO 43204, USA FAX:(614) 276-0529 1 www.colinst.com TOLL FREE 1-800-669-5011

More information

OPERATION MANUAL NTF-15

OPERATION MANUAL NTF-15 OPERATION MANUAL NTF-15 Nitrogen Tire Filling Valve Stem Caps (Qty=200) Order P/N 436075 RTI Technologies, Inc 10 Innovation Drive York, PA 17402 800-468-2321 www.rtitech.com 035-81235-00 (Rev B) TABLE

More information

Model TX-FM/FN Sensor Head

Model TX-FM/FN Sensor Head Model TX-FM/FN Sensor Head Instruction Manual PureAire Monitoring Systems, Inc. 557 Capital Drive Lake Zurich, Illinois 60047 Phone: 847-726-6000 Fax: 847-726-6051 Toll-Free: 888-788-8050 Pureairemonitoring.com

More information

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model 50 Systems Outfitted with ABM-725 Monitor C O M P A N Y

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model 50 Systems Outfitted with ABM-725 Monitor C O M P A N Y INSTALLATION and INSTRUCTION MANUAL for QUALITY AIR BREATHING SYSTEMS Model 50 Systems Outfitted with ABM-725 Monitor M A R T E C H S E R V I C E S C O M P A N Y OFFICE: (507) 843-4700 P.O. BOX 7079 Toll

More information

Rejuvenation Instructions

Rejuvenation Instructions Rejuvenation Instructions #401 Air Systems UPR This NRI covers the following: Understanding the applications and operation of flow meters. Understand the application and operation of test pressure gauges.

More information

RAM 4021 Operation Manual

RAM 4021 Operation Manual RAM 4021 Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS RAM 4021 For your safety...3 Description...3 Set-up mode...4 Annunciator lights/alarms...4 Operation...5 Calibration...6

More information

OEM Manual MODEL 2305 ECONOMICAL DIGITAL SINGLE CYLINDER SCALE

OEM Manual MODEL 2305 ECONOMICAL DIGITAL SINGLE CYLINDER SCALE OEM Manual MODEL 2305 ECONOMICAL DIGITAL SINGLE CYLINDER SCALE 1 These instructions generally describe the installation, operation, and maintenance of subject equipment. The manufacturer reserves the right

More information

ABRASIVE SYSTEM ABRASIVE REGULATOR II 800# BULK ABRASIVE DELIVERY POT Abrasive Regulator II and 800# Pot Manual

ABRASIVE SYSTEM ABRASIVE REGULATOR II 800# BULK ABRASIVE DELIVERY POT Abrasive Regulator II and 800# Pot Manual ABRASIVE SYSTEM ABRASIVE REGULATOR II 800# BULK ABRASIVE DELIVERY POT TABLE OF CONTENTS Contact Information and Customer & Technical Service... 1 1 Introduction... 1 2 Abrasive Regulator... 1 Description:...

More information

TANK MANAGER FOR TWO TANKS OPERATING MANUAL. 10/31/11 C-More T6C L color touch panel

TANK MANAGER FOR TWO TANKS OPERATING MANUAL. 10/31/11 C-More T6C L color touch panel TANK MANAGER FOR TWO TANKS OPERATING MANUAL 10/31/11 C-More T6C L color touch panel 1 TABLE OF CONTENTS GENERAL...3 INSTALLATION...4 STONE TEST PROCEDURE...7 OPERATIONAL SUMMARY...7 AUTO CARBONATION...10

More information

PROPORTIONING VALVE. Model 150 INSTRUCTION MANUAL. March 2017 IMS Company Stafford Road

PROPORTIONING VALVE. Model 150 INSTRUCTION MANUAL. March 2017 IMS Company Stafford Road PROPORTIONING VALVE Model 150 INSTRUCTION MANUAL March 2017 IMS Company 10373 Stafford Road Telephone: (440) 543-1615 Fax: (440) 543-1069 Email: sales@imscompany.com 1 Introduction IMS Company reserves

More information

QBS Electronic Pressure Regulator

QBS Electronic Pressure Regulator INSTALLATION AND MAINTENANCE INSTRUCTIONS DESCRIPTION / IDENTIFICATION The QBS stainless steel series is an electronically controlled pressure regulator. The QBS controls the pressure on its output port

More information

RCD - Ultra-Rugged Differential Pressure Flowmeter

RCD - Ultra-Rugged Differential Pressure Flowmeter 0.15-1 to 85-600 GPM Liquids 2.5-25 to 300-1700 SCFM Gases 1/2 to 3 Line Sizes Bronze or 316-Ti Stainless Steel Mechanical Indicator, Digital Indicator, Transmitters and Switches Available Custom Calibrations

More information

1020 Industrial Drive, Orlinda, TN fax

1020 Industrial Drive, Orlinda, TN fax Operation Manual Ultrafiltration for High Purity Distribution K-A-HPTUF Series 615-654-4441 sales@specialtyh2o.com 615-654-4449 fax TABLE OF CONTENTS Section 1 GENERAL 1.1 Warnings and Cautions... 1 1.2

More information

Walchem Disinfection Sensors WCDB, WFCB, WOZB and WPAB Instruction Manual

Walchem Disinfection Sensors WCDB, WFCB, WOZB and WPAB Instruction Manual W A L C H E M An Iwaki America Company Disinfection Sensors Walchem Disinfection Sensors WCDB, WFCB, WOZB and WPAB Instruction Manual Five Boynton Road Hopping Brook Park Holliston, MA 01746 USA TEL: 508-429-1110

More information

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE INSTALLATION, OPERATION & MAINTENANCE MANUAL INTERFACE DEVICES, INC. 230 Depot Road, Milford, CT 06460 Ph: (203) 878-4648, Fx: (203) 882-0885, E-mail: info@interfacedevices.com

More information

TECHNICAL INFORMATION

TECHNICAL INFORMATION TECHNICAL INFORMATION Installation, Operation, and Maintenance Balston 75-96 and 75-98 Nitrogen Generation System Tower Pressure Gauge 5'-1" 3'-6" 7'-4" 6'-10 1/2" PLAN VIEW Figure 1 - Balston 75-96 and

More information

Gas Lines. Technical Manual. Sumitomo (SHI) Cryogenics of America, Inc Vultee Street Allentown, PA U.S.A.

Gas Lines. Technical Manual. Sumitomo (SHI) Cryogenics of America, Inc Vultee Street Allentown, PA U.S.A. Gas Lines Technical Manual Sumitomo (SHI) Cryogenics of America, Inc. 1833 Vultee Street Allentown, PA 18103-4783 U.S.A. Revision F: April 2008 261320A TABLE OF CONTENTS Page DESCRIPTION...1 SPECIFICATIONS...2

More information

OC Panel High Limit Aquastat Kit, Manual Reset p/n

OC Panel High Limit Aquastat Kit, Manual Reset p/n OC Panel High Limit Aquastat Kit, Manual Reset p/n 233202 Instruction Sheet APPLICATION The OC (Option Control) Panel High Limit Aquastat Kit provides electronic temperature sensing in a UL limit-rated

More information

P5513. Users Manual. Pneumatic Comparison Test Pump. Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot.

P5513. Users Manual. Pneumatic Comparison Test Pump. Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot. Test Equipment Depot - 800.517.8431-99 Washington Street Melrose, MA 02176 TestEquipmentDepot.com P5513 Pneumatic Comparison Test Pump Users Manual PN 3963372 November 2010 2010 Fluke Corporation. All

More information

Genie Supreme TM Model 123HP Installation & Operation Instructions

Genie Supreme TM Model 123HP Installation & Operation Instructions Genie Supreme TM Model 123HP Installation & Operation Instructions Manufacturing Contact Information A+ Corporation, LLC Call for expert product application assistance: 41041 Black Bayou Rd. Gonzales,

More information

299H Series. Introduction. P.E.D. Categories. Specifications. Installation. Warning. Installation Guide English September 2012

299H Series. Introduction. P.E.D. Categories. Specifications. Installation. Warning. Installation Guide English September 2012 Installation Guide English September 2012 299H Series Introduction This Installation Guide provides instructions for installation, startup, and adjustment of 299H Series regulators. To receive a copy of

More information

SS32L Dissolved O 2 Probe

SS32L Dissolved O 2 Probe BIOPAC WWW.biopac.com Systems, Inc. Application Note PH-185 SS32L Dissolved O 2 Probe SS32L Dissolved O 2 Probe BIOPAC Software SS32L Specifications BSL PRO v. 3.6.6 BIOPAC Hardware SS32L Dissolved O 2

More information

SERVICE MANUAL MODEL BA050BMST BREATHING AIR PANEL

SERVICE MANUAL MODEL BA050BMST BREATHING AIR PANEL www.modsafe.com SERVICE MANUAL MODEL BA050BMST BREATHING AIR PANEL WARNING: Do not attempt to operate this equipment without first reading and understanding the service manual enclosed with this device.

More information

OPERATION MANUAL NTF-60 Plus

OPERATION MANUAL NTF-60 Plus OPERATION MANUAL NTF-60 Plus Nitrogen Tire Filling Valve Stem Caps (Qty=200) Order P/N 436075 RTI Technologies, Inc 10 Innovation Drive York, PA 17402 800-468-2321 www.rtitech.com 035-81264-00 (Rev A)

More information

WATER MADE EASY MARINE ENERGY MUNICIPAL INDUSTRIAL

WATER MADE EASY MARINE ENERGY MUNICIPAL INDUSTRIAL Capital Controls Series 71V3000 The Series 71V3000 electrically-heated vaporizer automatically vaporizes and superheats liquid chlorine, sulfur dioxide or ammonia at a rate controlled by the gas feed system.

More information

AW400 cell Chlorine/Chlorine dioxide/ozone

AW400 cell Chlorine/Chlorine dioxide/ozone ABB MEASUREMENT & ANALYTICS USER GUIDE IM/AW4SR REV. F AW400 cell Chlorine/Chlorine dioxide/ozone Measurement made easy AW400 cell For more information Further publications are available for free download

More information

Float Operated Level Controllers

Float Operated Level Controllers CONTENTS Float Operated Level Controllers IM0015 Nov. 2014 PAGE Introduction 1 Scope 1 Description 1 Specification 1 Control Installation 2 INTRODUCTION Side Mount Back Mount Prior to installing, the instructions

More information

LDO II AQ 2/2014, Edition 1.5

LDO II AQ 2/2014, Edition 1.5 9623800 LDO II AQ 2/2014, Edition 1.5 USER MANUAL Table of Contents Specifications on page 2 General information on page 3 Product overview on page 4 Installation on page 5 Operation on page 7 Maintenance

More information

Installation and Use Manual

Installation and Use Manual Installation and Use Manual EMASMB & LMASMB Surface Mount Bottle Filling Stations Model EMASMB IMPORTANT THIS IS AN INDOOR APPLICATION ONLY! ALL SERVICE TO BE PERFORMED BY AN AUTHORIZED SERVICE PERSONNEL.

More information

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves.

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves. Powers Controls RV 201 Pressure Reducing Valves Description Features Product Numbers Dual Pressure PRV Technical Instructions Document No. 155-049P25 RV 201-1 Single Pressure PRV The RV 201 Pressure Reducing

More information

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator. LRS(H)4 USER MANUAL Read the complete manual before installing and using the regulator. WARNING INCORRECT OR IMPROPER USE OF THIS PRODUCT CAN CAUSE SERIOUS PERSONAL INJURY AND PROPERTY DAMAGE. Due to the

More information

TECHNICAL DATA. TRIMPAC Model B-5 & B-5B

TECHNICAL DATA. TRIMPAC Model B-5 & B-5B September 16, 2013 Trimpac 250a 1. DESCRIPTION DEsCRIPTIoN is a factory assembled trim package for a ed an electric/pneumatic release module in a metal enclosure. The standard trim normally required on

More information

INSTALLATION & MAINTENANCE INSTRUCTIONS

INSTALLATION & MAINTENANCE INSTRUCTIONS DESCRIPTION / IDENTIFICATION The QBX series valve uses Proportion-Air closed loop technology for Pressure control. It gives an output pressure proportional to an electrical command signal input. The QB1X

More information

Operation Manual - PN A MENSOR MODEL 73 SHOP AIR BOOSTER

Operation Manual - PN A MENSOR MODEL 73 SHOP AIR BOOSTER Operation Manual - PN 0017946001 A MENSOR MODEL 73 SHOP AIR BOOSTER Mensor Model 73 Shop Air Booster System (750 psi Version) April 23, 2012 Trademarks / Copyright Mensor is a registered trademark of Mensor

More information

Quick Start Guide LIQ-QSG-499ACL-03, Rev I July Rosemount 499ACL-03. Monochloramine Sensor

Quick Start Guide LIQ-QSG-499ACL-03, Rev I July Rosemount 499ACL-03. Monochloramine Sensor Quick Start Guide LIQ-QSG-499ACL-03, Rev I July 2017 Rosemount 499ACL-03 Monochloramine Sensor Safety information CAUTION! SENSOR/PROCESS APPLICATION COMPATIBILITY The wetted sensor material may not be

More information

Un-Pressurized Orefice Fittings FIO EZ. Parts List and Operation Instructions TECHNICAL MANUAL. Dn 2-6 Class Lbs

Un-Pressurized Orefice Fittings FIO EZ. Parts List and Operation Instructions TECHNICAL MANUAL. Dn 2-6 Class Lbs Un-Pressurized Orefice Fittings FIO EZ Parts List and Operation Instructions TECHNICAL MANUAL Dn 2-6 Class 150-600 Lbs US US 2 FIO EZ - MT 108-US - 05-2016 FIO EZ Important Instructions US Pietro Fiorentini

More information

PERFORM Operating Document

PERFORM Operating Document PERFORM Operating Document Use and Maintenance of CO 2 Incubator PC-POD-CA-007-v03 Revision History Version Reason for Revision Date 01 New POD 30-Sep-13 02 Minor revisions for section 2.3, 3.1, 4.3. 14-April-16

More information