1 Page 1 of 6 Companies Affected: NIPSCO CGV CMD CKY COH CMA CPA REFERENCE Code of Federal Regulations - Title 49 - Part , , , VA SCC NOPV GENERAL The purpose of this standard is to provide requirements and related guidance when inspecting and/or installing new residential and small commercial regulators. All service regulators showing external corrosion or damage shall be replaced. Refer to GS (VA), Meter Set Assembly Protection and GS (VA) Inspection Program for Risers and Meter Set Assemblies for Abnormal Operating Conditions for additional protection requirements. Service regulators are to be located where gas from the vent can escape freely into the atmosphere and away from any opening(s) into a building. Note: Mercury regulators and/or external mercury relief devices encountered in the field shall be removed as soon as practical. Upon discovery and prior to removal of a mercury regulator and/or external mercury relief device, a member of the Operations Center leadership team and a member of the Health Safety and Environmental (HSE) team shall be notified. Never attempt to remove a mercury regulator and/or external mercury relief device without assistance and guidance from a member of the Operations Center Leadership team and a member of the HSE team. For additional guidance on high pressure service regulator installation requirements, refer to GS High Pressure Service Regulator and Meter Setting Selection. 2. SERVICE REGULATOR REQUIREMENTS The regulator and/or relief device vent; vent line, if so equipped; screen; and cap, if present; shall be properly sized, installed, and free of blockage with no external leakage. Consideration should be given as to the location of the service regulator and/or relief device and the possibility of vent terminal freeze-up. Regulator vent skirts or a vent line extending the vent terminal away from the potential source of moisture should be considered if the potential for vent terminal blockage due to freeze-up is evident. This document is considered CONTROLLED only when viewed electronically on the Company's intranet. Printed or other electronic copies may not be current, and the intranet version should be used to verify.
2 Page 2 of Service Regulator Vent Requirements When a regulator and/or relief device is located inside a building, each regulator and/or relief device shall have a separate metallic relief line vented to the outdoors so in the event gas is discharged, it will not create a hazard- under no circumstances shall the relief lines of separate regulators and/or relief devices be manifolded. If tubing is used for the vent line, it shall be metallic and one size larger than the relief opening in no case shall corrugated tubing be used as a regulator vent line. Relief vent lines shall be as short as possible, and when in excess of 10 in length or contain more than 2 elbows, shall be increased one nominal pipe size for each additional 10 of length. Each elbow in the vent line will contribute approximately three (3) feet in effective length. Service regulators installed outdoors of a building requiring a vent line, may be equipped with a PVC vent line conforming to UL 651, schedule 40 or schedule 80 rigid PVC conduit. The same sizing guidance provided above applies Service regulator Vent Terminal Requirements NOTE: All measurements shall be taken from the service regulator vent terminal (relief opening) (see Exhibits A and B). Except as noted below, the vent terminal: a. Shall be installed outdoors above grade, at a height sufficient to prevent entry of water in areas where flooding may occur. b. Shall be installed to protect it from the entry of insects by a screen or an approved vent cap, and be installed so as to prevent the entry of rainwater. c. Shall be located not less than 3 feet radially and not directly below any rotating electrical equipment (e.g., an air conditioning unit). d. Except as noted below, the vent terminal should be installed with a minimum of 3 feet radial separation from an electric meter, electric panel, electric outlet, electric pedestal, electrical equipment disconnect, or pad mounted transformer, etc. When it is not possible to install the regulator vent terminal with a 3 foot radial separation, a minimum of 1 foot radial separation shall be maintained between the regulator vent terminal and any of the electric equipment listed above.
3 Page 3 of Testing Requirements e. Shall be located 3 feet radially from, and not below, any first floor opening into a building, such as a door, window(s) (that can be opened) or other gravity air opening(s) into a building (including clothes dryer exhaust terminals, and appliance air intakes). f. Shall be located not less than 10 feet radially from, and not below any forced air inlet into a building (excluding appliance air intakes). Self Operated - Single Ported Service Regulators under 2 inch, serving domestic or large volume meters, shall be tested/inspected at the time of regulator installation, regulator repair, meter change or meter installation Set Pressure and Lock-Up Pressure Tests Service regulators to be set at 7" W.C. shall have a set pressure and lock up test performed with the meter removed, unless other means have been provided. The set pressure shall be adjusted to a minimum of 7 W.C. and the lock up pressure shall not exceed 12" W.C. If the set pressure is between 7 W.C. and 9 W.C. and the lock up pressure is 12 W.C. or less, no further action is necessary. If the set pressure is between 7 W.C. and 9 W.C. and the lock up pressure exceeds 12" W.C., the regulator must be adjusted, repaired or replaced. If a higher set pressure is necessary to adequately serve the customer, this condition shall be reported to the New Business Team, who may decide to install Fixed Pressure Factor Metering (FPFM). See GS Fixed Pressure Factor Metering for additional guidance. If the lock up pressure of a regulator set at 0.5 psig (14" W.C.) is in excess of 20" W.C., the regulator shall be repaired or replaced. If the lock up pressure of a regulator set at 2.0 psig is in excess of 2.25 psig, the regulator shall be repaired or replaced. If the lock-up pressure of a service regulator delivering an outlet pressure in excess of 2 psig exceeds the set point more than 0.25 psig, the regulator shall be repaired or replaced. A lock up test need not be performed for an in-service regulator serving more than one meter or when a bypass around the meter has been provided; however, the set pressure must be determined and corrected, if necessary. A service regulator without full internal or without associated external relief
4 Page 4 of 6 devices shall be changed at the time of the meter change unless changing the orifice will provide full relief. 3. ESTABLISH/REESTABLISH SERVICE See GS (VA), Lighting Appliances When Establishing or Reestablishing Service. 4. RECORDS Record the necessary information on the MDT Order, including pertinent information regarding the service regulator(s) (e.g., Meter Pressure Compensation Codes, Service Regulator Codes).
5 Page 5 of 6 EXHIBIT A Regulator vent terminal must be installed to maintain a minimum clearance of 3 feet radial separation from any door, window, gravity air opening into a building, or rotating electrical equipment. However, in no circumstance shall the vent terminal be installed beneath any 1 st floor air opening into a building nor under any rotating electrical equipment.
6 Page 6 of 6 EXHIBIT B
Residential and Small Commercial
Page 1 of 7 Companies Affected: NIPSCO CGV CMD CKY COH CMA CPA REFERENCE 49 CFR Part 192.353, 192.355, 192.357 1. GENERAL The purpose of this standard is to provide requirements for the inspection or installation
More informationTypes 749B and R130 Changeover Manifolds
Instruction Manual MCK-1179 Types 749B and R130 June 2012 Types 749B and R130 Changeover Manifolds TYPE HSRL-749B TYPE 64SR/122 TYPE R130/21 TYPE 749B/21 Figure 1. Changeover Manifolds and Regulator Assemblies
More informationR600 and HSRL Series Instruction Manual
Instruction Manual MCK 2141 November 2009 R600 and HSRL Series Instruction Manual! Warning Failure to follow these instructions or to properly install and maintain this equipment could result in an explosion
More informationR122H, R222, R232A, and R232E Series Instruction Manual
Instruction Manual MCK 2156 R122H, R222, R232A, and R232E Series October 2012 R122H, R222, R232A, and R232E Series Instruction Manual Failure to follow these instructions or to properly install and maintain
More information1213B2 Service Regulators Maximum Inlet Pressure 125 PSIG
SB-8506. B Service Regulators Maximum Inlet Pressure 5 PSIG Measurement Engineers Since 86 www.americanmeter.com B Service Regulators General Information The American Meter Series B pressure regulator
More informationR600 and HSRL Series Instruction Manual
Instruction Manual MCK 2141 R600 and HSRL Series LP-Gas Regulators October 2015 R600 and HSRL Series Instruction Manual Failure to follow these instructions or to properly install and maintain this equipment
More informationType S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual
Fisher Controls Instruction Manual Type S301 & S302 Gas Regulators October 1981 Form 5180 WARNING Fisher regulators must be installed, operated, and maintained in accordance with federal, state, and local
More informationInspecting LP-Gas Regulators
February 2011 Inspecting LP-Gas Regulators Introduction LP-Gas regulators are very durable pieces of equipment that are able to automatically supply gas, year in and year out, and thus it's easy to take
More informationSAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER
SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER SUPPLIMENT TO eom IMPORTANT READ THIS MANUAL BEFORE PRODUCT INSTALLATION, OPERATION, INSPECTION & MAINTENANCE Tougher and more rigid guidelines are being established
More informationInert Air (N2) Systems Manual
INSTRUCTION MANUAL Inert Air (N2) Systems Manual N2-MANUAL 2.10 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. GENERAL INFORMATION Positive pressure nitrogen gas pressurizing
More information1800C and 1800C-HC Service Regulators
SB 855.9 800C and 800C-HC Service Regulators Maximum Pressure 5 Table of Contents 800C Regulator Information...................... 800C-HC Regulator Information.................. 800C and 8C Service Regulators...............
More informationG196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve
Installation Instructions Issue Date August 19, 2008 G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Application The G196 valves are suitable for use with natural gas, Liquefied
More information61R2 STANDARD REGULATOR COMPACT REGULATOR. Phone Fax
6R STANDARD REGULATOR COMPACT REGULATOR 496 Phone 7.63.888 Fax 7.63.690 6R AND 496 REGULATORS General Information The Model 6R and 496 Compact Regulator (CR) are designed to deliver reliable and safe regulation
More informationG196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve
Installation Instructions Issue Date March 13, 2013 G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Application The G196 valves are suitable for use with natural gas, Liquefied
More informationTECHNICAL DATA. the Viking Pilot Pressure Regulating Valve 1 Model A-1 Speed Control Assembly: OBSOLETE. the Viking Speed Control Assembly 1
November 30, 1994 534 a 1. PRODUCT NAME VIKING 2" (50mm), 3" (75mm), 4" (100mm), 6" (150mm) 2. MANUFACTURER THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone:
More informationTECHNICAL DATA Q= C. Table 1 - Specifications
September 25, 2013 Pressure Regulation 537a 1. Description The Model B-3 Pilot Operated Pressure Control Valve is a factory assembled unit. The unit consists of a Model J-2 Halar coated Flow Control Valve,
More informationTypes S100K and S102K Pressure Regulators
Instruction Manual Form 5624 Types S0K and S2K 01/01 Types S0K and S2K Pressure Regulators W7478-1 Figure 1. Types S0K and S2K Pressure Regulator Introduction Scope of Manual This manual provides instructions
More informationFirst Stage Regulators
DOMESTIC First stage regulators are typically used to reduce tank pressure to an intermediate pressure, usually 5 to 10 PSI for further pressure reduction by a second stage regulator located closer to
More informationINSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION
INSTALLATION INSTRUCTIONS CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION The CVS Controls 67CFR Filter regulator is a pressure reducing supply regulator typically used for pneumatic
More informationTECHNICAL DATA. Table 1 - Specifications
Page 1 of 6 1. DESCRIPTION Model A-3 Pilot Operated Pressure Control Valves are factory assembled units. Each unit consists of a Model H-2 Halar coated Flow Control Valve, a Speed Control Valve, a Model
More information1800C and 1800C-HC Series Service Regulators
1800C and 1800C-HC Series Service Regulators Installation Instructions www.elster-americanmeter.com General Information: The 1800C and 1800C-HC Regulators are available as Full Capacity Internal Relief
More information1800CPB2 Service Regulators Maximum Inlet Pressure 125 PSIG
A C E D SB-8520.2 1800CPB2 Service Regulators Maximum Inlet 125 PSIG AMC Quality System QMI is Accredited by: C R E D I T ISO 9001 Certified Certificate #006697 R E ANSI RAB G I S T R A R Dutch Council
More information1200B2 Series Service Regulators. Instruction Manual
00B Series Service Regulators Instruction Manual 00B Series Service Regulators 0 Elster American Meter 00B Series Service Regulators General Information The 00B Series Service Regulators are available
More informationTypes S108K and S109K Pressure Reducing Regulators with Integral Slam-Shut Device
Instruction Manual Form 5492 Types S108K and S109K May 1999 Types S108K and S109K Pressure Reducing Regulators with Integral Slam-Shut Device Introduction Fisher regulators must be installed, operated
More informationType HSR Pressure Reducing Regulator for Residential, Commercial, or Industrial Applications
Instruction Manual Form 5753 Type HSR October 2003 Type HSR Pressure Reducing Regulator for Residential, Commercial, or Industrial Applications W8648 Figure 1. Type HSR Pressure Regulator Introduction
More informationGAS SUPPLY APPLICATION GUIDE
GAS SUPPLY APPLICATION GUIDE Natural Gas or Propane Modulating & Condensing Boilers and Water Heaters This document applies to the following models: Boilers AM 399B AM 500B AM 750B AM 1000B Gas-Fired Boilers
More informationSR100 Series Service Regulators. Technical Bulletin
SR00 Series Service Regulators Technical Bulletin Model SR00 Series Regulator 0 Elster American Meter The compact, high capacity SR service regulator is designed for residential or light commercial/industrial
More informationType 1367 High-Pressure Instrument Supply System with Overpressure Protection
Instruction Manual D100343X012 Type 1367 November 2017 Type 1367 High-Pressure Instrument Supply System with Overpressure Protection TYPE 252 FILTER 2ND-STAGE TYPE 67CF FILTER-STYLE REGULATOR INLET TYPE
More informationINSTALLATION GUIDE Gas Rangetops
INSTALLATION GUIDE Gas Rangetops Contents Wolf Gas Rangetops........................... 3 Safety Instructions............................ 4 Gas Rangetop Specifications.................... 5 Gas Rangetop
More information1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor)
1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor) 1. According to NFPA 99, SCFM is an acronym for. a) Surface Conditions at Fahrenheit Mercury b) Standard Conditions
More informationS300 Series. Valve Link. Features. Fisher Controls
S0 Series Self-Operated Type VL FIELDVUE Regulators Valve Link Fisher Controls May 198 Bulletin 71.1:S0 The S0 Series self-operated, spring-loaded regulators are used for pressure-reducing control in a
More informationSERIES SAFETY VALVE
R Manufactured by Conbraco Industries, Inc. 10-600 SERIES SAFETY VALVE INSTALLATION, OPERATION, & MAINTENANCE Part I Document Number: ES-1325 Revision Level: B Issued By: T.HAMILTON Date: 3/3/16 Approved
More information1800C & 1800C-HC Service Regulators
SB-855.8 800 & 800-H Service Regulators Maximum Pressure 5 PSIG 800 Regulator Information General Information The merican Meter Series 800 pressure regulators are designed for natural gas applications
More informationG96 Series BASOTROL Dual Operator Valve
Installation Instructions 9. Issue Date February 22, 2013 G96 Series BASOTROL Dual Operator Valve Applications The G96 valves are combination, dual operator, automatic valves available with or without
More informationGM Series Dual-Block Multi-Function Gas Control Valves
Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin GM Issue Date 0297 GM Series Dual-Block Multi-Function Gas Control Valves Figure 1: GM Series
More informationTESCOM 50-4X Series Safety, Installation & Start-Up Procedures
Operations & Service Manual TESCOM 50-4X Series Safety, Installation & Start-Up Procedures Do not attempt to select, install, use or maintain this product until you have read and fully understood this
More informationCertified LP/Propane Line Pressure Regulator Guidebook
3rd Edition Certified LP/Propane Line Pressure Regulator Guidebook 2 & 5 PSI Systems 2 3 The specifications in this Handbook refer to Maxitrol line pressure regulators used in LP/Propane applications only.
More informationGAS DELIVERY PRESSURE AND MEASUREMENT
GAS DELIVERY PRESSURE AND MEASUREMENT I. PURPOSE: To establish a uniform basis on which to provide gas measurement and pressure regulation facilities on customers premises. II. DELIVERY PRESSURES AND PROVISIONS:
More informationG IG-2. INSTALLATION AND INSPECTION OF GAS SERVICE REGULATOR VENT LINE PROTECTORS (VLPs) [Interim Guideline]
LAST REVIEW DATE: REVIEW CYCLE: 2/17/15 5 Years INTERIM GUIDELINE: G-699-2-IG-2 TITLE: VOLUME: REGISTRATION NO. TARGET TRAINING GROUPS: INSTALLATION AND INSPECTION OF GAS [Interim Guideline] 3, 10 and
More information29 SERIES - SAFETY VALVE
INDUSTRIES, INC. 29 SERIES - SAFETY VALVE INSTALLATION, OPERATION, & MAINTENANCE Part I Document Number: ES1016-1 Revision Level: A Issued By: David Edmonds Date: 6/20/04 Approved By: Date: 10/4/04 Conbraco
More informationResidential Swimming pools
City of Republic Community Development Department Residential Swimming pools REVISION DATE: JANUARY 2017 Swimming Pool Safety Definitions: Barrier Requirements: A) Application All swimming pools over 24
More informationLINE PRESSURE REGULATOR GUIDEBOOK 7TH EDITION
CERTIFIED LINE PRESSURE REGULATOR GUIDEBOOK 7TH EDITION 2 AND 5 PSI SYSTEMS 2 3 This Handbook contains information from national heating and plumbing ordinances or codes that may have been adopted or incorporated
More information627 Series Pressure Reducing Regulators
627 Series Pressure Reducing Regulators Introduction The 627 Series direct-operated pressure reducing regulators (Figure 1) are for low and high-pressure systems. These regulators can be used with natural
More informationOperator: Save these instructions for future use!
Pilot Gas Outlet: Located at outlet end of the valve Type of Gas Suitable for all domestic heating gases Pressure Rating: 1/2 lb. per sq. in. Pressure Regulator Adjust Range (Typical, See Control Label):
More informationGAS FUEL VALVE FORM AGV5 OM 8-03
ALTRONIC AGV5 OPERATING MANUAL GAS FUEL VALVE FORM AGV5 OM 8-03 WARNING: DEVIATION FROM THESE INSTALLATION INSTRUCTIONS MAY LEAD TO IMPROPER ENGINE OPERATION WHICH COULD CAUSE PERSONAL INJURY TO OPERATORS
More information1800CPB2 Service Regulators
SB 8520.5 1800CPB2 Service Regulators Maximum Inlet Pressure 125 PSIG Table of Contents 1800CPB2 Regulator Information................ 2-3 1800CPB2 Capacity Performance................ 4-6 1-1/4" Models,
More information1800CPB2 Pilot-Loaded Service Regulators
1800CPB2 Pilot-Loaded Service Regulators Technical Bulletin www.elster-americanmeter.com Table of Contents 1800CPB2 Regulator Information................ 2-3 1800CPB2 Capacity Performance................
More informationIPG IGNITION GAS PILOTS BACK-LOADED GAS
INSTRUCTIONS IPG IGNITION GAS PILOTS BACK-LOADED GAS WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components
More informationCommittee Input No. 59-NFPA [ Section No. 5.9 ]
Committee Input No. 59-NFPA 54-2012 [ Section No. 5.9 ] 5.9 Overpressure Protection Devices. 5.9.1 General 1 Where required. Overpressure Where the serving gas supplier delivers gas at a pressure greater
More informationTECHNICAL DATA. Dry 132a. October 1, 2008
October 1, 2008 Dry 132a 1. Description Viking High Pressure (HP) Dry Systems utilize a Viking Model E or Model F Deluge Valve to control the water supply to system piping equipped with closed sprinklers.
More information2.0 INSTALLATION & SERVICE
Installation, Operation, and Maintenance Instructions MODEL 5600 / 5600R January 2005 CONTENTS 1.0 GENERAL 1.1 5600 Model Number Information -----------------------------------------------------------------------
More informationType R622 Pressure Reducing Regulator
Type R622 Pressure Reducing Regulator June 2010 Compact Design Protective Inlet Screen High Capacity Internal Relief Light Weight W8806 Inlet and Outlet Pressure Gauge Taps Figure 1. Type R622 Pressure
More informationG92 Series BASOTROL Automatic Pilot Gas Valve
Installation Instructions Issue Date September 17, 2008 G92 Series BASOTROL Automatic Pilot Gas Valve Installation IMPORTANT: Only qualified personnel should install or service BASO Gas Products. These
More informationWaterous Relief Valve
Operating Instructions 1. Reduce pump discharge pressure with engine throttle. Make sure four way (On/Off) valve is OFF. 2. Open at least one discharge valve. Accelerate engine until pressure gage indicates
More informationWARNING: Gas Conversion Kit Instructions Applies to: Model UDAP, UDAS, UDBP, and UDBS Unit Heaters. General and Warnings FOR YOUR SAFETY
Form CP-UD-GC Obsoletes I-UD-GC (Version E) Gas Conversion Kit Instructions Applies to: Model UDAP, UDAS, UDBP, and UDBS Unit Heaters General and Warnings All gas conversion must be done by a qualified
More informationCAPITAL CONTROLS SERIES NXT3000
CAPITAL CONTROLS SERIES NXT3000 Modular design gas feed system with self contained automatic switchover capability. The Series NXT3000 Gas Feed System is a family of vacuumoperated, solution-feed gas dispensing
More informationTECHNICAL DATA. TRIMPAC Model B-5 & B-5B
September 16, 2013 Trimpac 250a 1. DESCRIPTION DEsCRIPTIoN is a factory assembled trim package for a ed an electric/pneumatic release module in a metal enclosure. The standard trim normally required on
More informationMANUAL. Sesame. Thermoplastic Tank Technologies
MANUAL Sesame Thermoplastic Tank Technologies INSTALLATION AND USER GUIDE CONTENT 1. GENERAL 3 2. IMPORTANT 3 3. INSTALLATION EXPANSION VESSEL 4 4. USE EXPANSION VESSEL 5 5. AIR CELL REPLACEMENT 5 5.1
More informationLP-10 LP-GAS SERVICEMAN'S HANDBOOK
LP-10 LP-GAS SERVICEMAN'S HANDBOOK The Fisher Controls LP-Gas Serviceman's Handbook serves as a general reference of information on LP-Gas and for the installation, operation and maintenance of LP-Gas
More informationOperating and Maintenance Instructions
Table of Contents Section 1: Gas Requirements... 1 Section 2: Installation... 2 Section 3: Burner Setup and Adjustment... 5 Section 4: Maintenance... 6 Section 5: Operation... 7 Operating Instructions...
More informationTECHNICAL DATA. Trimpac 244a. September 16, 2013
September 16, 2013 Trimpac 244a 1. DEsCrIpTION DESCRIPTION TRIMPAC Model B-1 and B-1B is a factory-assembled trim package with an electric release module in a metal enclosure. The standard trim normally
More informationCapital Controls Series NXT3000 Modular design gas feed system with self-contained automatic switchover capability.
Capital Controls Series NXT3000 Modular design gas feed system with self-contained automatic switchover capability. The Series NXT3000 Gas Feed System is a family of vacuum-operated, solution-feed gas
More information36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS
INLET PRESS TAP WTE-RODGERS 36E96-314 DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL
More informationSERVICE MANUAL SALAMANDER BROILERS RADIANT AND INFRARED 36RB 36IRB VULCAN C36RB C36IRB WOLF
SERVICE MANUAL SALAMANDER BROILERS RADIANT AND INFRARED VULCAN 36RB 36IRB WOLF C36RB C36IRB This Manual is prepared for the use of trained Vulcan Service Technicians and should not be used by those not
More informationExcela-Flo REGULATORS
Exclusive Features and Benefits 5 6 4 1 2 3 1. Dust cap with hex and finger grips 2. Full round flange for evenly distributed diaphragm compression 3. Locating tabs to ensure proper vent relocation 4.
More informationNoth American 7347 High Pressure Gas Regulators
Combustion Noth American 7347 High Pressure Gas s Bulletin 7347 7347 s reduce high gas supply pressures to practical use levels. Since capacities will vary with the pressure drop across the regulator (see
More informationSeptember 2018 Pressure Test
September 2018 Pressure Test The requirements for a pressure test are found in NFPA 54, Chapter 8, Sections 8.1-8.1.53 of the 2012 edition. A pressure test shall not be confused with a leak check. The
More informationFUNDAMENTALS OF PRESSURE RELIEF VALVES IN NATURAL GAS INSTALLATION - OPERATION - MAINTENANCE. Gary S. Beckett
FUNDAMENTALS OF PRESSURE RELIEF VALVES IN NATURAL GAS INSTALLATION - OPERATION - MAINTENANCE Gary S. Beckett Flow Safe Supply 10727 Tower Oaks Boulevard Houston, Texas 77070 What Are They and Why Are They
More informationACCESSORY KIT INSTALLATION MANUAL
ACCESSORY KIT INSTALLATION MANUAL LP (PROPANE) CONVERSION KIT 1NP0366 FOR USE WITH MODELS: G8C & GF8 This conversion kit shall be installed by a qualified service agency in accordance with these instructions
More informationGeneral. Rugged, Reliable with Value-added Features. Pipe Sizes. Temperature Limits. Spring Ranges. Buried Service. Increased Outlet Pipe Sizes
DS-G-REG-13-43-0812-01-A* Model 243-RPC Pilot Operated Regulators Installation and Maintenance Instructions Rugged, Reliable with Value-added Features Genuine, pilot-operated regulators use the same relay
More informationSeries 100 Slam Shut Valve. Technical Bulletin
Series 100 Slam Shut Valve Technical Bulletin 02 Elster The Series 100 Slam Shut protects gas installations against overpressure conditions by automatically shutting off the gas flow. General Information
More informationSystem Pressure Manager Standard & System Pressure Manager Plus
System Pressure Manager Standard & System Pressure Manager Plus Installation, Commissioning & Servicing Instructions Note: THESE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE INSTALLING, COMMISSIONING,
More informationBulletin TCR-104 & 109 Filling and adding to the Glycol pressure system
Bulletin 061013 TCR-104 & 109 Filling and adding to the Glycol pressure system 1. Glycol System and air On this model the glycol system is a closed system, the glycol is not exposed to the air. No external
More informationNatural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet)
Natural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet) INSTALLATION INSTRUCTIONS For R7 Series Light Commercial Packaged Gas Electric Units IIMPORTANT: Please
More informationModel 10E Enviro-Line Environmental Pressurization System Installation & Operation Manual
Model 10E Enviro-Line Environmental Pressurization System Installation & Operation Manual Table of Contents Table of Contents Page 2 Purpose and Description Page 8 Dimensions Page 2 Page 3 Identifying
More informationINSTRUCTIONS FOR CONVERTING CONDENSING GAS MOBILE HOME FURNACES MODEL SERIES: CMA3*, CMC1*, VMA3*, VMC1*
INSTRUCTIONS FOR CONVERTING CONDENSING GAS MOBILE HOME FURNACES MODEL SERIES: CMA3*, CMC1*, VMA3*, VMC1* THIS KIT CONTAINS: AOPS7741 (NATURAL TO PROPANE CONVERSION PARTS FOR MODEL SIZE, 50) AOPS7742(NATURAL
More informationWARNING: Installation Instructions. Natural Gas High Altitude Conversion Kit United States Installations Only
Natural Gas High Altitude Conversion Kit United States Installations Only Installation Instructions Light Commercial Packaged Gas Electric Units R7TQ Series 6, - 7 1/2, & 10 Ton (2,001 FT - 10,000 FT)
More informationTECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1
Dry 131h 1. DESCRIPTION The Viking Model G-1 Maintenance Air Compressor is an electric motor-driven, aircooled, single-stage, oil-less compressor. The unit is equipped with a check valve and provides a
More informationTECHNICAL DATA. Q= Cv S
Page 1 of 13 1. DESCRIPTION The Viking 4 inch Model G-4000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry
More informationDischarge Relief Valve Operation & Maint.
Relief Valve Operation & Maint. CZ Series Centrifugal Fire Relief svalve Operation and Maintenance Instructions 1410 Operation and Maintenance Form No. F-1031 Section 2302.6 2111 Issue Date 04/90 11/95
More informationRESIDENTIAL AND COMMERCIAL REGULATORS FOR ABNORMAL OPERATING CONDITIONS (AOC) WITH 3 FOOT CLEARANCE INSTALLATION REQUIREMENTS.
RESIDENTIAL AND COMMERCIAL REGULATORS FOR ABNORMAL OPERATING CONDITIONS (AOC) WITH 3 FOOT CLEARANCE INSTALLATION REQUIREMENTS Presented by Jon Beam Equipment Controls Company 3 FOOT ABNORMAL OPERATING
More informationFRAGMENTATION INSTRUCTION & OPERATION HANDBOOK
FRAGMENTATION INSTRUCTION & OPERATION HANDBOOK Doc. Jordair FRAGMENTATION-MANUAL WARNING! HIGH PRESSURE UNITS Under no circumstances should the fill stations be operated with the safety relief valves removed
More informationG REQUIREMENTS FOR THE INSTALLATION OF GAS BOOSTERS, MICROTURBINES AND ASSOCIATED SYSTEM PROTECTIVE DEVICES
LAST REVIEW DATE: REVIEW CYCLE: 6/22/11 5 Years SPECIFICATION: TITLE: VOLUME: G-2040-9 REQUIREMENTS FOR THE INSTALLATION OF GAS BOOSTERS, MICROTURBINES AND ASSOCIATED 4 and Gas Blue Book REVISIONS: (See
More informationWATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity
WATER HEATER THERMAL EXPANSION TANKS Owner s Manual Safety Instructions Installation Maintenance Warranty Models: 2-5 Gallon Capacity Thank You for purchasing this Thermal Expansion Tank. Properly installed
More informationTECHNICAL DATA. Trimpac 257a. September 16, 2013
September 16, 2013 Trimpac 257a 1. DESCrIpTION DESCRIPTION The Viking Double SUREFIRE SIngle Interlock Preaction TRIMPAC Model D-2 and D-2B used with either a Model E or F Deluge Valve (A.1), a Viking
More informationTECHNICAL DATA PILOT PRESSURE REGULATED DELUGE SYSTEM CONTROLLED BY PNEUMATIC RELEASE. 1. DESCRIPTION (Refer to Figures 1, 2 or 3.
Page 1 of 8 1. DESCRIPTION A Viking Pilot Pressure Regulated Deluge System utilizes a Viking Flow Control Valve to control water flow into the deluge system. The flow control valve must be installed with
More informationBGA158 Series CE Approved Class A Shutoff Gas Valve
Installation Instructions BGA158 Issue Date August 24, 2011 BGA158 Series CE Approved Class A Shutoff Gas Valve Applications The BGA158 Series shutoff gas valve is an electrically operated gas valve that
More informationACCESSORY KIT INSTALLATION INSTRUCTIONS
ACCESSORY KIT INSTALLATION INSTRUCTIONS 1NP0680 - PROPANE CONVERSION FOR USE WITH MODELS: PM8, PC8, PM9, PC9, FL9M, FL9C, FC9M, FC9C This conversion kit is to be installed by a qualified service agency
More informationTECHNICAL DATA. Trimpac 256a. October 31, 2013
October 31, 2013 Trimpac 256a 1. DESCRIPTION The Viking SUREFIRE SIngle Interlock Preaction TRIMPAC Model D-1 and D- 1B used with either a Model E or F Deluge Valve (A.1), a Viking Easy Riser check valve
More informationTECHNICAL DATA. Trimpac 251a. Spetember 16, 2013
Spetember 16, 2013 Trimpac 251a 1. DEsCrIpTION DESCRIPTION TRIMPAC Model B-6 and B-6B is a factory assembled trim package for a double interlocked preaction system with an electric/pneu-lectric release
More informationOperator: Save these instructions for future use!
WHITE-RODGERS 36C53 Combination Gas Valves (24 Volt Model) INSTALLATI INSTRUCTIS Electrical Rating: Voltage: 24 Volts, (30 Volts Max.), 60 Hz. Current Rating: 0.23 Amps Type of Gas Natural Gas Pressure
More informationSummary of the MRA LPG Codes of Practice
Summary of the MRA LPG Codes of Practice COP A1 DESIGN and INSTALLATION Code COP A1 deals with above ground installations where LPG is stored under pressure at ambient temperatures in fixed vessels larger
More informationPremAire INSTRUCTIONS FOR VORTEX TUBE MODE OF OPERATION
DUAL SUPPLY REGULATOR ESCAPE CYLINDER VORTEX MAIN INLET PremAire INSTRUCTIONS FOR VORTEX TUBE MODE OF OPERATION WARNING THIS MANUAL MUST BE READ CAREFULLY BY ALL PERSONS WHO HAVE OR WILL HAVE THE RESPONSIBILITY
More informationGAS SUPPLY DESIGN GUIDE
GAS SUPPLY DESIGN GUIDE Natural Gas, Propane Gas, or Dual Fuel Fired Modulating, Condensing Boilers BENCHMARK Series Gas-Fired Boilers For models: BMK750 to BMK6000 Last Update: 06/20/2014 PR1 06/20/14
More informationSWIMMING POOL, SPA, & HOT TUB GUIDELINES
SWIMMING POOL, SPA, & HOT TUB GUIDELINES A. Adopted construction codes and installation requirements 1. 2015 edition of the International Residential Code and Appendix Q, 2. 2014 edition of the National
More informationO.K. Safety first CDN USA. Table of Contents. Approvals. Attention IFGC CSA UL ANSI NFPA
FRS 7../6 & FRS 5... Gas Pressure Regulator Installation Instructions USA CDN Table of Contents Table of Contents... Page 1 Approvals... Page 1 Attention... Page 1 Specification... Page 2 Lock-up Pressure
More informationSDS -Series 4C-D201/-D202 Supplemental Drying System User s Manual
SDS -Series 4C-D201/-D202 Supplemental Drying System User s Manual 8 Executive Drive P.O. Box 2105 Toms River, NJ 08754 (732) 244-0010 (800) 337-3762 fax (732) 244-8140 www.permapure.com info@permapure.com
More informationTECHNICAL DATA. Q = C v P S
Page 1 of 13 1. DESCRIPTION The Viking 6 Model G-6000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler
More informationRESIDENTIAL SWIMMING POOLS AND SPAS A GUIDE FOR HOMEOWNERS
RESIDENTIAL SWIMMING POOLS AND SPAS A GUIDE FOR HOMEOWNERS City of Redding 777 Cypress Avenue Redding CA 96001 Telephone: (530) 225-4013 FAX: (530) 225-4360 A Swimming Pool is any body of water 18 inches
More informationBGA158 Series CE Approved Class B Shutoff Gas Valve
Installation Instructions BGA158 Issue Date March 22, 2016 BGA158 Series CE Approved Class B Shutoff Gas Valve Applications The BGA158 Series shutoff gas valve is an electrically operated shutoff valve
More information