Flow controller Type ED/CCB311 Instruction manual
|
|
- Milo Davidson
- 5 years ago
- Views:
Transcription
1 Flow measurement Flow controller Type ED/CCB GENERAL DESCRIPTION page 4 2. DETAILED DESCRIPTION page 4 3. PIPE - EXPLOITATION page 5 4. PREVENTIVE MAINTENANCE page 5 5. REPLACEMENT OF THE CONTACT UNIT (6) or (6 ) page DISASSEMBLY page REASSEMBLING page 5 6. ESSENTIAL SAFETY REQUIREMENTS page 6 7. SPARE PARTS page 7 8. WARRANTY page 7 Houdec Instrument SAS
2 Flow measurement Page 2
3 Flow measurement Read the manual Page 3
4 Flow measurement 1. GENERAL DESCRIPTION - CHARACTERISTICS Metal flow controller in stainless steel used to detect weak flows in horizontal or vertical piping systems (direction of the ascending flow). This is a device with very simple and reliable design. The flow controller is made essentially of a body with fixed flanges PN16 FS or PN20(150lbs) (DN depending on the model) including a diaphragm paddle set, and an aluminum box IP65 with a reed switch bistable inverter (male receptacle Souriau series 8N45 connection or SAIB series NU K2) in it. 2. DETAILED DESCRIPTION - OPERATION Standard flange ends PN16 NF-EN (2007) (ex 29203) DN ØD ØK ØG N ØF f b ØC L H Std (*) or 8(*) (*) Flange 4 holes according to EN (8 holes with request according to NFEN1092-1) Standard flange ends ANSI 150lbs B16.5 (NF-EN ) DN ØD ØK ØG N ØF f b ØC L H Std 1 1/ / optionally, models DN or 1 1/ /2 can be produced 200mm long. -the used joints must be standard and adapted to the joint mounting. Page 4
5 Flow measurement The flow controller consists of : - a body of stainless steel 316L (1). - a diaphragm paddle set (2) of stainless steel 316L - a receptacle SOURIAU (4) ref : 8N or a receptacle SAIB (4 ) réf : K2 - a straight end + plug (5) ref : 8N (optional) a straight end + plug (5 ) ref : K2 (optional) - reed switch (6) for Souriau or (6 ) for SAIB. A paddle joined on the diaphragm, placed at right angle to the flow, moves depending of the flow value in the direction of the fluid. A magnet fixed on the paddle in an inox slot regulates the state of the contact when the cutoff value is reached. IMPORTANT NOTE: The flow controller is factory adjusted for a specific cutoff value. Do not change the position of the contact, which must be up to the stop against the internal wall of the box (red point of the contact with respect to the cover) Identify the type of receptacle on the Box and adapt the correspondent plug according to requirement of the site. For a possible replacement of the switch, it imperative to specify the model of receptacle installed on the box. 3. PIPE EXPLOITATION. - The installation of the flow controller can be performed on a vertical or horizontal pipe (position to be established with precision in the order). - In horizontal installation, the contact box must be located in the lower part. - Verify the direction of circulation of the fluid before installation (red arrow attached to the body) - Be sure that the fluid to be controlled does not contain solid or magnetic particles, which could impede the good operation of the device. 4. PREVENTIVE MAINTENANCE This device needs no special care except the maintenance in good operational state of the diaphragm-paddle set (for example, filters or traps for magnetic particles are to be installed when used with charged fluids). 5. REPLACEMENT OF THE CONTACT UNIT (6) OR (6') This operation does not need any isolation of the line or dismantling of the device. 5.1.DISASSEMBLY - Disconnect the plug (5) / (5 ) from the receptacle (4) / (4 ) - Remove the cover of the box (3) - Unwind and remove the two screws of the contact fixing flange - Unwind the four screws fixing the receptacle (4) / (4 ) on the box (3) - Take out the contact (6) / (6 ) + receptacle (4) / (4 ) unit - Remove the unit consisting of insulating support and contact from its frame - Using a SOURIAU extraction tool ref : or SAIB ref : , take out the three contacts from their insulating support. (See here) 5.2. REASSEMBLING - Take the spare contact with its three contacts (6) / (6 ) - Using an insertion tool SOURIAU ref : or SAIB ref : insert the contacts in their insulating support. - Install this unit in the receptacle (4) / (4 ) placing the actuator up to the stop in the deepest slot - Place and manually tighten the clamping cone and nut - Fix the receptacle (4) / (4 ) on the box (3) - Place and fix the contact using two screws and the fixation flange of the contact Important NOTE: During the installation of the reed switch in the box, its termination must be in contact with the internal wall of the box (red point of the contact facing the cover). - Mount the box cover (3) - Reconnect the plug (5) / (5 ) to the receptacle (4) / (4 ) - Check the correct operation of the contact with respect of the specified alarm flow value. If necessary, make another adjustment to obtain this value moving the contact box in the openings provided for this purpose. After the adjustment, make sure that the fixing screws of the box are tightened. Page 5
6 Flow measurement 6.ESSENTIAL SAFETY REQUIREMENTS These devices must be installed horizontally or vertically and fixed correctly on the piping. Sudden variations of valve areas or installation types causing flow perturbation must be avoided. Attention do not prestress the device during the installation on the piping. Before the installation, check the cleanliness of the piping. The pipes must be free of any solid particles. The valves must be progressively maneuvered to avoid any waterhammer effect or vibration. Never exceed the max. operating pressure of the device. Never exceed the max. operating temperature indicated on the device plate. Do not use the device for any other type of fluid other than indicated on the device plate. Do not use solvents when cleaning the protection box. Do not put the device under sudden temperature changes Regularly check the corrosion state of the device SAFETY RELATED TO TEMPERATURE This pressure equipment being a part of a unit, it is the responsibility of the integrator to take the necessary measures in order to ensure the protection against risks due to temperature (for persons but also the type of ambient materials in conformity with the specification of the device). Protection could be ensured, for example, by insulation of hot elements, by access protection systems, by any system adapted to the site of use and compatible with the regulations in force. Before any action on pressure equipment, the qualified and authorized operator must check if the present conditions : pressure, temperature, etc are compatible with the planned actions. In the case of equipment with alarm contacts, he must also take every precaution in relation to the use of these contacts : voltage, current, elements or machines regulated through these contacts, etc The seals should be replaced, if needed, and the tightening elements of bolts checked. OPENING AND CLOSING OF PRESSURE EQUIPMENT Before any action on pressure equipment, the qualified and authorized operator must make sure that the present conditions : pressure, temperature, etc are compatible with the planned actions. In the case of equipment with alarm contacts, he must also take every precaution in relation to the use of these contacts : voltage, current, elements or machines regulated through these contacts, etc The dismantling of elements necessary for the access to PE (Pressure equipment) must be performed using the proper tools. The reinstallation is performed in the inverse order to the dismantling. The seals should be replaced, if needed, and the tightening elements checked, etc. Before pressurization, the operator checks if all the safety rules (same for new devices) are respected.. The conditions of use must be in conformity with the indicated prescriptions. This equipment must not contain fluids of any other group but the one (or, possibly, several groups), for which it was designed. It is strictly forbidden to perform any temporary or definitive modification, or any operation susceptible of modifying its physical, mechanical, or metallic characteristics on any of its parts, without preliminary written approval of the manufacturer. Any modification with respect to all this information, susceptible of placing at risk the safety related to any use of the equipment, is done outside the responsibility of HOUDEC INSTRUMENT SAS. The user must check that before start-up the safety instructions related to pressure equipment as well as to the good operation of the adjoining elements are observed. This equipment is designed for static loads corresponding to the device own weight and to the specific constraints linked to pressure and temperature as defined in the technical specification. It is not designed for additional loads or constraints related to vibration conditions, except if special agreement has been made during the preliminary studies. SAFETY RELATED TO PRESSURE This pressure equipment being a part of a unit, it is the responsibility of the integrator to take the necessary measures in order to ensure the protection against risks of internal overpressure or those due to improper use. Protection could be ensured, for example, by installation of security devices (valves). The integrator must also perform the necessary actions in order to guarantee safety of personnel in case of interventions on the equipment (for example : installation of insulation devices, valves and elements of measurement of residual pressure, manometer or any other.) He can implement any other mean (or design principle) as far as the latter can guarantee a safety level that is compatible with the essential safety requirements requested by the directive 97/23/CE and/or the regulations in force. Page 6
7 Flow measurement 7. SPARE PARTS Reed switch (Drawing N 14842) with male contacts SOURIAU Spare part N PDR Reed switch (Drawing N ) with male contacts SAIB Spare part N PDR When ordering spare parts, it is very important to quote the precise serial number of the device to be repaired before providing the description of any removed part. 8. WARRANTY The contact is the only quickly exchangeable part. In order to reliably identify the precise references for these parts related to the type of construction, it is necessary to indicate the serial number, written on the label or the marking plate, attached to the device. Tel. Of the aftersale service to be contacted: France : +33 (0) Other countries : contact the local representative This equipment is delivered with a guarantee (please, refer to the contractual conditions of the order for the guarantee period). We attract you attention on the fact that the use of parts that are not in conformity either with the original parts, or with the requested standards, (materials certified according to harmonized standards, class, with respect to the standardized parts, bolting, flanges, connections ), may challenge this guarantee as well as the responsibility that may be associated to it. Page 7
8 Flow measurement Houdec Instrument S.A.S. Z.A. de la Tour ABREST France Tel: +33 (0) Fax: +33 (0) copyright information Page 8
Magnetic level switch type MR783 Instruction Manual
Magnetic level switch Magnetic level switch type MR783 1. DESCRIPTION page 3 1.1 Operation page 3 1.2 Application page 3 1.3 Description page 3 2. SPECIFICATIONS page 3 2.1 Service Conditions page 4 2.2
More informationDifferential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN
Differential Pressure Regulator Type 45-6 Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN Edition March 2008 Contents Contents Page 1 Design and principle of operation...................
More informationInstruction Manual Contact Pressure Vacuum Gauge
MS10 Instruction Manual Contact Pressure Vacuum Gauge Table of Contents 1. Safety Instructions 2. Intended Applications 3. Product Description and Functions 4. Installation 5. Commissioning 6. Maintenance
More informationINSTRUCTION MANUAL Pressure Relief Device LPT
INSTRUCTION MANUAL Pressure Relief Device LPT 5COV475800 LPT REV00 CONTENT: 1 SAFETY 1.1 Safety instructions 2 1.2 Specified applications 2 1.3 Safety notes on the equipment operation 2 2 PRESSURE RELIEF
More informationFurther technical information is available on
1 of 5 Manufacture address : Bartec Technor AS Dusavikveien 39 4007 Stavanger Norway Further technical information is available on www.bartec-technor.no Note on instructions When working in hazardous areas,
More informationFIREFIGHTING EQUIPMENT
FIREFIGHTING EQUIPMENT User Manual DEBIKA-INOX Diffuser with adjustable flow & stream settings DOC 1964 En Rev.A - 23/10/13 Identification Product Type Product DESIGNATION Product Reference concerned by
More informationMounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25
Self-operated Pressure Regulators Differential Pressure Regulators (opening) Type 42-20 Type 42-25 Type 42-20 Differential Pressure Regulator Type 42-25 Differential Pressure Regulator Mounting and Operating
More informationAccessories. Differential pressure gauges for air and gas MAG-A & MAG-G (E5275 rev /04/2010)
Accessories Differential pressure gauges for air and gas MAG-A & MAG-G (E5275 rev. 02-12/04/2010) GENERAL WARNINGS: DISPOSAL: ¾ All installation, maintenance, ignition and setting must be performed by
More informationM45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions
BAC 13310 IM-P133-42 ST Issue 2 M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions 1. General safety information 2. General product information 3. Installation 4. Commissioning 5.
More informationRS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.
RS(H)10,15 USER MANUAL Read the complete manual before installing and using the regulator. WARNING INCORRECT OR IMPROPER USE OF THIS PRODUCT CAN CAUSE SERIOUS PERSONAL INJURY AND PROPERTY DAMAGE. Due to
More informationGA24 Technical Datasheet
GA24 Technical Datasheet Variable-area flowmeter Sturdy construction for several applications Local indication without auxiliary power Replaceable mounting parts KROHNE CONTENTS GA24 1 Product features
More informationMeasurement accessories METPOINT OCV for the measurement in systems up to 40 bar
EN - english Instructions for installation and operation Measurement accessories METPOINT OCV for the measurement in systems up to 40 bar Dear customer, Thank you for deciding in favour of the METPOINT
More informationWHEATLEY Series 500 Swing Check Valve
Document Number: TC003001-13 Revision: 02 WHEATLEY Series 500 Swing Check Valve Installation, Operation, and Maintenance Manual TABLE OF CONTENTS BILL OF MATERIALS...3 SCOPE...5 INSTALLATION AND OPERATION
More informationOFFICINE OROBICHE S.p.A. 1/9
OFFICINE OROBICHE S.p.A. 1/9 INSTRUCTIONS MANUAL FOR LEVEL SWITCHES SERIES 7000 mod. 7250 AND 7400 Electric 1. INSTRUMENT DESCRIPTION Series 7000 level switches have been designed for external lateral
More informationSize : Ends : Min Temperature : Max Temperature : Materials : Cast iron body
Size : Ends : Min Temperature : Max Temperature : DN 15 to DN 400 Flanges GN10/16-10 C + 120 C Max Pressure : 16 Bars up to DN 200 ( 10 bars over ) Specifications : Removable stainless steel filter Bolted
More informationInstruction Manual Differential Pressure Transmitter
DE13 Instruction Manual Differential Pressure Transmitter Table of Contents 1. Safety Instructions 2. Intended Applications 3. Product Description and Functions 4. Installation 5. Commissioning 6. Maintenance
More informationTarget disk flowmeter Series DP. Instructions manual DP65 DP500. R-MI-DP Rev.: 4 English version
Target disk flowmeter Series DP Instructions manual DP65 DP500 R-MI-DP Rev.: 4 English version PREFACE Thank you for choosing the flowmeter series DP from Tecfluid S.A. This instruction manual allows the
More informationSTAINLESS STEEL LOW PRESSURE REDUCING VALVE LPRV ELITE
MAIN CHARACTERISTICS The stainless steel LPRV elite low pressure reducer is intended for the pressure reduction of the fluids such as water, air, clear liquids not in charge of and the compatible gases
More informationPSG 901. Pressure Switch for Gas. elektrogas.com EE141-07/12
PSG 901 Pressure Switch for Gas elektrogas.com EE141-07/12 PSG 901 Pressure Switch for Gas (EN1854) Contents Description... 2 Features... 2 Functioning and application... 3 Technical specifications...
More informationPneumatic switch module 3/2-way valve (On/Off) Types P Types FP Function tested for use of the float in Ex-zone 0
Operating Manual LTIA3E Pneumatic switch module 3/2-way valve (On/Off) Types P Types FP Function tested for use of the float in Ex-zone 0 Contents 1. Safety Instructions 2. Conformity to standards 3. Technical
More informationEngineering Data Sheet
Page 1 of 6 CE MARKING AND THE PRESSURE EQUIPMENT DIRECTIVE 97/23/EC Valves must be installed into a well designed system and it is recommended that the system be inspected in accordance with the appropriate
More informationCARTRIDGE FILTERS TECHNICAL MANUAL MT 080. Installation, commissioning and maintenance instructions. 08/02 Edition
CARTRIDGE FILTERS TECHNICAL MANUAL MT 080 Installation, commissioning and maintenance instructions 08/02 Edition 1 2 CONTENTS 1.0 PAGE INTRODUCTION 1.1 MAIN FEATURES 1.2 OPERATION 1.3 CLOSING OF HEAD WITH
More informationSteam Trap BK BK 212-ASME. Original Installation Instructions English
Steam Trap BK 212.. BK 212-ASME EN English Original Installation Instructions 810609-02 1 Contents Page Important Notes Usage for the intended purpose... 3 Safety note... 3 Danger... 3 Attention... 3 Application
More informationCAST IRON SAFETY VALVE TYPE 6301
CHARACTERISTICS The 6301 safety valve is dedicated to protect the equipment from potential overpressure. This is an automatic device that closes when the pressure conditions are back to normal. It is a
More informationSerie 06-M6. Swing wafer check valve. made in. Application fields. Check valves E U R O P E WATER CONDITIONING INDUSTRY
Swing wafer check valve BRANDONI made in E U R O P E Application fields WATER CONDITIONING INDUSTRY HEATING 38 www.brandoni.it The valves in series 06 are swing wafer check valves, manufactured in accordance
More informationBALL VALVE ASSEMBLY AND MAINTENANCE PROCEDURE FOR LCV BALL VALVES REF. DOC. MMM LCVE Rev.0 July 2010 SERIES SFF & SFR.
SERIES SFF & SFR SFF / SFR EN/ANSI/ASME/API/BS/NF SFF EN/DIN/BS/NF Page 1 of 16 REVIEW CONTROL PROCEDURE REF.: DOC. MMM LCVE REV. DATE CARRIED OUT BY APPROVED BY DESCRIPTION 0 19/07/2010 J. Rubio J.Tejedor
More informationBray/ VAAS O-Ported Series Knife Gate Valve 770/780 Series Operation and Maintenance Manual
Bray/ VAAS Knife Gate Valve 770/780 Series Operations and Maintenance Manual Table of Contents Definition of Terms 1 Safety Instructions 1 Introduction 2 Unpacking 2 Storage 2 Installation 2 Commissioning
More informationPneumatic proportional controller Types M Types FM Function tested for use of the float in Ex-zone 0
Operating Manual LTIA5E Pneumatic proportional controller Types M Types FM Function tested for use of the float in Ex-zone 0 Contents 1. Safety Instructions 2. Conformity to standards 3. Technical data
More informationBALL VALVE ASSEMBLY AND MAINTENANCE PROCEDURE. REF. DOC.MMM900N Rev.1 March 2014 SERIES M DIN / ANSI. Page 1 of 17
SERIES M DIN / ANSI Page 1 of 17 REVIEW CONTROL PROCEDURE REF.DOC.MMM900N REV. DATE CARRIED OUT BY APPROVED BY DESCRIPTION 0 12/05/2013 E.Hidalgo J.Tejedor Initial Edition 1 27/03/2014 D.Grau J.Tejedor
More informationATS430 turbidity sensor Retractable insertion assembly
A MEASUREMENT & ANALYTICS INSTRUCTION ATS430 turbidity sensor Retractable insertion assembly Measurement made easy 1 Introduction This publication details installation procedures for the retractable insertion
More informationUser guide DIAPHRAGM SEALS. Industrial instrumentation for Pressure and Temperature
Industrial instrumentation for Pressure and Temperature ENG MI-SEP-ENG_0 10/2011 Copyright Nuova Fima S.p.A. All rights reserved. Any part of this publication should not be reproduced without a written
More informationManual Actuated Boiler Blowdown Valves
Manual Actuated Boiler Blowdown Valves Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Operation 5. Maintenance 6. Spare parts p.1 1. Safety
More informationInstallation Instructions
48011HW NATURAL GAS TO PROPANE CONVERSION KIT 58HDX, 359AAV, PG9YAB, PG9YAA Installation Instructions SAFETY REQUIREMENTS Installing and servicing heating equipment can be hazardous due to gas and electrical
More informationMounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Type Type Differential Pressure Regulators (opening)
Self-operated Pressure Regulators Type 42-20 Type 42-25 Differential Pressure Regulators (opening) Translation of original instructions Type 42-20 Differential Pressure Regulator Type 42-25 Differential
More informationUn-Pressurized Orefice Fittings FIO EZ. Parts List and Operation Instructions TECHNICAL MANUAL. Dn 2-6 Class Lbs
Un-Pressurized Orefice Fittings FIO EZ Parts List and Operation Instructions TECHNICAL MANUAL Dn 2-6 Class 150-600 Lbs US US 2 FIO EZ - MT 108-US - 05-2016 FIO EZ Important Instructions US Pietro Fiorentini
More informationGM Series Dual-Block Multi-Function Gas Control Valves
Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin GM Issue Date 0297 GM Series Dual-Block Multi-Function Gas Control Valves Figure 1: GM Series
More information6-5 Maintenance Manual
Non Return Valve 6-5 Maintenance Manual Contents 1. PRODUCT DESCRIPTION... 1 1.1 How it works... 1 1.2 Overall dimensions... 3 1.3 Technical datasheet... 4 1.3.1 Push flow situation... 4 1.3.2 Pull flow
More informationS1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions
PREVIOUS REFERENCE NO. IMP02355 0231150/13 IMF0501ENISS2 CMGT S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators Installation and Maintenance Instructions 1. Safety information 2. General product information
More information6301 TYPE CAST IRON SAFETY VALVES
Pressure (bar) 6301 TYPE CAST IRON SAFETY VALVES FEATURES The 6301 type safety valve is a device designed to protect installations against possible overpressure. It operates automatically and closes when
More informationNeotecha SAPRO - Aseptic sampling valve SV Installation, operation and maintenance instructions
Before installation these instructions must be fully read and understood 2 Safety Please read these instructions carefully. 2.1 General danger potential Not paying attention to this instruction Incautious
More informationVALVES HIDROMATIC VALVE.
VALVES HIDROMATIC VALVE Hydrodynamic design The Hidromatic valve of Hidroconta is a piston hydraulic valve controlled with the same fluid of the conduction. Its balloon design improves its hydrodynamic
More informationG196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve
Installation Instructions Issue Date August 19, 2008 G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Application The G196 valves are suitable for use with natural gas, Liquefied
More informationPreparation and Installation of the Standard Type Flat Seat Rupture Disc / UNISERT Insert Holder Assembly (Sizes 10 and Larger)
Preparation and Installation of the Standard Type Flat Seat Rupture Disc / UNISERT Insert Holder Assembly (Sizes 10 and Larger) GEP-6029 Rev. V 101251 Ref. I.D.: 1540 WARNING USER SHOULD READ AND THOROUGHLY
More informationSCA Series Inverted Bucket Steam Traps
0770050/5 IM-P077-06 ST Issue 5 SCA Series Inverted Bucket Steam Traps Installation and Maintenance Instructions 1. General safety information 2. General product information 3. Installation 4. Commissioning
More informationKTM 50 (DN ) Installation, maintenance and operating instructions
52 762-306 09.2014 KTM 50 (DN 100-200) Installation, maintenance and operating instructions General High-performing and compact, these pressure-independent control valves for variable flow heating and
More informationMaterials : Stainless steel ASTM A351 CF8M
Certificat 3.1 Size: Ends : Min Temperature : Max Temperature : DN 15 to DN 200 PN16 Flanges R.F. - 20 C + 200 C Max Pressure : 16 Bars Specifiations : Removable stainless steel filter Bolted bonnet with
More informationOPERATION MANUAL PNEUMATIC VALVES
OPERATION MANUAL PNEUMATIC VALVES DIRECTIVE 2014/34/EU ATEX ENGLISH Index 1 Product identification 2 Security 3 Guarantee 4 Transportation 5 Assemblage 6 Setting up 7 Adjustments 8 Technical information
More informationSize : Ends : Min Temperature : Max Temperature : Materials : Cast iron body
Size : Ends : Min Temperature : Max Temperature : DN 40 to DN 300 Flanges R.F. PN10/16-10 C + 80 C Max Pressure : 16 Bars up to DN200 Specifications : Removable stainless steel filter Bolted bonnet with
More informationPressure Independent Control Series
Document No. 155-522 Pressure Independent Control Series Two-Way Cast Iron Flanged Bodies, ANSI 125 and 250 Description Siemens Pressure Independent Control Valves integrate three functions into a single
More informationUSER MANUAL. MACMAG magnetic separator MHK MHF
USER MANUAL MACMAG magnetic separator MHK MHF Important Read the safety precautions before use. Thank you for your purchase. This user manual contains important information on avoiding damage and personal
More informationWHEATLEY WHEATLEY SERIES 500 SWING CHECK VALVE. Installation, Operation and Maintenance Manual
WHEATLEY SERIES 500 SWING CHECK VALVE STANDARD INTEGRAL SEAT & OPTIONAL REMOVABLE SEAT 2" FP - 6" FP 150# - 1500# 8" FP - 12" FP 150# - 900# API 6D and B16.34 2" FP - 4" FP 5000# DRILLING PRODUCTION VALVE
More informationWHEATLEY Series 822/820 Swing Check Valve
Document Number: TC003001-12 Revision: 02 WHEATLEY Series 822/820 Swing Check Valve Installation, Operation, and Maintenance Manual TABLE OF CONTENTS BILL OF MATERIALS...3 SCOPE...4 INSTALLATION AND OPERATION
More informationSLAM-SHUT VALVE. Type OSE CONTENTS INTRODUCTION CHARACTERISTICS. Scope of Manual. Material. Product Description. Connections
Instruction Manual D103687X012 June 2017 Type OSE SLAM-SHUT VALVE CONTENTS Introduction... 1 Characteristics... 1 Labelling... 2 Dimensions and Weights... 3 Operation... 4 Installation... 4 Commissioning...
More informationOPERATING INSTRUCTIONS
0/05 OPERATING INSTRUCTIONS for gas pressure regulators PN0 with integrated slam shut valve (SSV) and integrated limited capacity safety relief valve (RV) MR 25 F0, MR 25 SF0 p e 20 kpa - 0 MPa (0,2-0
More informationOperating instruction
Operating instruction MV, XV, HG, HP, RKO, D2G, TV, BV, WB & SLV 1 Introduction 2 2 Stafsjö s knife gate valves 2 3 Technical information 2 3.1 Pressure test 2 3.2 Labelling 2 4 Storage 3 5 Transportation
More informationProduct Manual B-Safety ClassicLine & PremiumLine Emergency Eyewash and Eye/Face Wash Equipment
Product Manual B-Safety ClassicLine & PremiumLine Emergency Eyewash and Eye/Face Wash Equipment 1. Application Emergency eyewash and eye/face wash equipment are prescribed first aid installations for workplaces
More informationSteam Trap BK 15 (DN40, DN 50) Original Installation Instructions English
Steam Trap BK 15 (DN40, DN 50) EN English Original Installation Instructions 810682-03 1 Contents Page Important Notes Usage for the intended purpose... 4 Safety note... 4 Danger... 4 Attention... 4 Application
More informationInstallation, Operation and Maintenance Manual for Back Pressure Regulator
Installation, Operation and Maintenance Manual for Back Pressure Regulator Model 8860 2009 Groth Corporation IOM-8860 Rev. B 12541 Ref. ID: 95565 Page 2 of 13 Table of Contents I. INTRODUCTION 3 II. DESIGN
More information* * Data Sheet and Operating Manual. Digital manometer ME01 ## # 87 # HL S#### Dust explosion protection Zone 22.
*09005087* DB_BA_EN_ME01_S Rev.A 12/16 *09005087* d e v e l o p i n g s o l u t i o n s Data Sheet and Operating Manual ME01 Digital manometer Table of Contents ME01 ## # 87 # HL S#### Dust explosion protection
More informationG196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve
Installation Instructions Issue Date March 13, 2013 G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Application The G196 valves are suitable for use with natural gas, Liquefied
More informationKBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions
4059051/3 IM-P405-48 EMM Issue 3 KBV21i and KBV40i Key Operated Boiler Blowdown Valves Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4.
More informationGM-7000 Series CE Approved Gas Control Valve
Installation Instructions GM-7000 Issue Date November 9, 2012 GM-7000 Series CE Approved Gas Control Valve Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing
More informationEASTERN ENERGY SERVICES PTE LTD. 60 Kaki Bukit Place #02-19 Eunos Tech Park Singapore, SG Singapore Telephone: Fax:
2 Table Of Contents 1. Introduction 3 2. About this Manual 3 3. Contacting YZ Systems 3 4. Vessel Components 4 5. Specifications 5 6. Application 6 7. Theory of Operation 7 8. DuraSite Installation & Use
More informationDeclaration of Conformity as per Directive 97/23/EC
Declaration of Conformity as per Directive 97/23/EC The manufacturer declares that:, 47906 Kempen, Germany Multi-way diverting valves Series 29a and Series 29b, with packing with lever 1. The valves are
More informationFPD175 Compact orifice carrier assembly
ABB MEASUREMENT & ANALYTICS OPERATING INSTRUCTION FPD175 Compact orifice carrier assembly The smart solution for remote applications. Measurement made easy Installation, commissioning and operating / maintenance
More informationKBV21i and KBV40i Air Actuated Boiler Blowdown Valves
4059051/1 IM-P405-48 AB Issue 1 KBV21i and KBV40i Air Actuated Boiler Blowdown Valves Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning
More informationBall Float Steam Trap UNA 43 PN 16/CL 125/JIS 10K UNA 46 PN 40/CL 150/CL 300/JIS 10K/JIS 20K DN 80, 100, 150, 3", 4", 6"
Data Sheet 819584-00 Issue Date: 01/17 Ball Float Steam Trap UNA 43 PN 16/C 125/JIS 10K UNA 46 PN 40/C 150/C 300/JIS 10K/JIS 20K DN 80, 100, 150, 3", 4", 6" UNA 43 hl, UNA 46 hl UNA 43 v, UNA 46 v with
More informationApollo Standard Port, Full Port & One Piece Flanged Ball Valves Installation, Operation, & Maintenance Manual
I854000.D Apollo Standard Port, Full Port & One Piece Flanged Ball Valves Installation, Operation, & Maintenance Manual Introduction This manual presents guidelines for the Installation, Operation and
More informationSAPAG. Safety valves, type 5700 Storage, Use, Operation and Maintenance Instructions. IMPORTANT NOTICE
SAPAG IMPORTANT NOTICE Contents Important notice 1 0 Valve identification 2 1 Storage 2 2 Installation 2 3 Operation 2 4 Maintenance 3 4.1 Dismantling 3 4.2 Inspection 3 4.3 Repair 3 4.4 Assembly 4 4.5
More informationG96 Series BASOTROL Dual Operator Valve
Installation Instructions 9. Issue Date February 22, 2013 G96 Series BASOTROL Dual Operator Valve Applications The G96 valves are combination, dual operator, automatic valves available with or without
More informationFLANGED TWO-PIECE BALL VALVES
INTRODUCTION This instruction manual includes installation, operation, and maintenance information for FNW flanged split-body ball valves. This manual addresses lever operated ball valves only. Please
More informationVane Flow Switches Colima FLU Series
3.797.5275.200 CH Issue 2-2016 Vane Flow Switches Colima FLU Series Installation and Maintenance Instructions 1. General safety information 2. General product information 3. Installation and Maintenance
More informationPROPORTIONING VALVE. Model 150 INSTRUCTION MANUAL. March 2017 IMS Company Stafford Road
PROPORTIONING VALVE Model 150 INSTRUCTION MANUAL March 2017 IMS Company 10373 Stafford Road Telephone: (440) 543-1615 Fax: (440) 543-1069 Email: sales@imscompany.com 1 Introduction IMS Company reserves
More informationInstallation / Operation / Maintenance Manual KLINGER Reflex Level Gauge Type R 25
Klinger Italy S.r.l Via De Gasperi, 88 20017 Rho, Mi - Italy Tel. +39 02 93333.1 Fax +39 02 93901312/3 www.klinger.it Telephone: +61 (08) 9350 1100 Facsimile: +61 (08) 9358 6200 ABN 95 008 679 838 Installation
More informationMaintenance Manual. Liquid Level Transmitter CT801-SI, CT801-TA
CT801-SI, CT801-TA Maintenance Manual SAS au Capital de 2 158 244-444 871 933 R.C.S. Bourges - APE : 2651B Headquarter : 9, rue Isaac Newton - 18000 Bourges - France Maintenance Manual CT801-SI, CT801-TA
More informationInstallation. Use. Maintenance INSTRUCTIONS. Care
ESPACE SWING GATE Installation Use Maintenance INSTRUCTIONS Care E MAINTENANCE INTRODUCTION All the information contained in this specification sheet including pictures and figures is the property of DIRICKX.
More informationInstallation, Operating and Maintenance Instructions. V914 Cast Iron Flanged Swing Check Valve V914
Installation, Operating and Maintenance Instructions V914 Cast Iron Flanged Swing Check Valve V914 THE PRESSURE EQUIPMENT DIRECTIVE 97/23/EC and CE MARKING The Pressure Equipment Regulations 1999 (SI 1999/2001)
More informationDISASSEMBLY AND ASSEMBLY INSTRUCTIONS FOR LIQUID RING COMPRESSORS
DISASSEMBLY AND ASSEMBLY INSTRUCTIONS FOR LIQUID RING COMPRESSORS SA INTRODUCTION These instructions are for the maintenance personnel for maintenance and repair of compressors series SA. Disassembly and
More informationPRS(TC)4,8 USER MANUAL. Read the complete manual before installing and using the regulator.
PRS(TC)4,8 USER MANUAL Read the complete manual before installing and using the regulator. WARNING INCORRECT OR IMPROPER USE OF THIS PRODUCT CAN CAUSE SERIOUS PERSONAL INJURY AND PROPERTY DAMAGE. Due to
More informationPressure Reducing Valve DMV 750 set range: bar
Pressure Reducing Valve DMV 750 set range:.0-6.0 bar Advantage pressure setting possible at any time, also during operation hermetically sealed by valve diaphragm high level of operating safety and long
More informationG type DUCTED EXHAUST SAFETY VALVE 2871 AND 288X SERIES. Model/Ref:
Model/Ref: 28713 www.lauridsenindustri.com CHARACTERISTICS The G type safety valves are dedicated to protect the equipment from potential overpressure. They are automatic and close when the pressure conditions
More informationTP1 and TP2 Temporary Cone Shaped Strainers
1698051/2 IM-P169-07 ST Issue 2 TP1 and TP2 Temporary Cone Shaped Strainers Installation and Maintenance Instructions TP1 1. Safety information 2. General product information 3. Installation and commissioning
More informationMounting and Operating Instructions EB 3009 EN. Self-operated Regulators. Type RS Check Valve (backflow protection)
Self-operated Regulators Type 42-10 RS Check Valve (backflow protection) Type 42-10 RS Check Valve (backflow protection) Mounting and Operating Instructions EB 3009 EN Edition December 2015 Definition
More information1305 Series Pressure Reducing Regulators
Instruction Manual Form 1095 1305 Series October 2009 1305 Series Pressure Reducing Regulators! Warning Fisher regulators must be installed, operated, and maintained in accordance with federal, state,
More informationM10HTi ISO Tobacco Ball Valve Screwed, SW, BW and Flanged versions
IM-P133-75 ST Issue 1 M10HTi ISO Tobacco Ball Valve Screwed, SW, BW and Flanged versions Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4.
More informationInstruction Manual Differential Pressure Transmitter
DE61 Instruction Manual Differential Pressure Transmitter Table of Contents 1. Safety Instructions 2. Intended Applications 3. Product Description and Functions 4. Installation 5. Commissioning 6. Maintenance
More informationManual winch MANISTOR 100 and 200
Manual wall winch Manual winch MANISTOR 100 and 200 Instruction manual UK 173-192.10-3 PRODUCT DEVELOPED AND MANUFACTURED ACCORDING TO NF EN 13157 STANDARD REGISTERED DESIGN To ensure the constant improvement
More informationUL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function Gas Control Valves
Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin GM-20/25 GM-40/45 Issue Date 1298 UL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function
More informationFloat Operated Level Controllers
CONTENTS Float Operated Level Controllers IM0015 Nov. 2014 PAGE Introduction 1 Scope 1 Description 1 Specification 1 Control Installation 2 INTRODUCTION Side Mount Back Mount Prior to installing, the instructions
More informationLTB013EN. Operating Instruction Trimod Besta Level Switch types XA 5, XB 5 for use in potentially explosive atmospheres acc.
LTB013EN Operating Instruction Trimod Besta Level Switch types XA 5, XB 5 for use in potentially explosive atmospheres acc. to IECEx scheme Subject to technical modification Bachofen AG Ackerstrasse 42
More informationModel MTB-ASME Vertical Bladder Tanks
DATA SHEET Model MTB-ASME Vertical Bladder Tanks Features n UL Listed for use with various proportioners and foam concentrates n 175 psi (12.1 bar) maximum allowable working pressure (design pressure)
More informationInstallation, operation & maintenance manual - original version
Installation, operation & maintenance manual - original version AVK gate valves for water and wastewater Series 01, 02, 06, 12, 15, 18, 20, 26, 32, 33, 36, 38, 50, 55 and 636 COPYRIGHT AVK GROUP A/S 2018
More informationPressure Reducing Valve DMV 755 set range: 1,0-9,0 bar
Pressure Reducing Valve DMV 755 set range:,0-9,0 bar Advantage pressure setting possible at any time, also during operation high reproducibility of the set pressure high level of operating safety and long
More informationType 1367 High-Pressure Instrument Supply System with Overpressure Protection
Instruction Manual D100343X012 Type 1367 November 2017 Type 1367 High-Pressure Instrument Supply System with Overpressure Protection TYPE 252 FILTER 2ND-STAGE TYPE 67CF FILTER-STYLE REGULATOR INLET TYPE
More informationSpiratec ST14, ST16 and ST17 Sensor Chambers and sensors
0862050/1 IM-P086-18 MI Issue 1 Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors Installation and Maintenance Instructions 1. Safety Information 2. General product information 3. Installation 4.
More informationFIREFIGHTING EQUIPMENT
FIREFIGHTING EQUIPMENT User Manual ANTENOR 3000 Base or portable Trailer DOC 1974 En Rev.B - 22/10/13 Tel : 03 25 39 84 78 - Fax : 03 25 39 84 90 - Email : france@pok.fr - Web : www.pok.fr Identification
More informationMixers. Venturi proportional mixers EMM & EMMTR (E2351 rev /07/2017)
Mixers Venturi proportional mixers EMM & EMMTR (E2351 rev. 04-11/07/27) GENERAL WARNINGS: DISPOSAL: ¾ All installation, maintenance, ignition and setting must be performed by qualified staff, respecting
More informationAccessories. Differential pressure gauges for air and gas MAG-A & MAG-G (E5275 rev /04/2010)
Accessories Differential pressure gauges for air and gas MAG-A & MAG-G (E5275 rev. 02-12/04/2010) GENERAL WARNINGS: DISPOSAL: ¾ All installation, maintenance, ignition and setting must be performed by
More informationModel MTB-ASME Vertical Bladder Tanks
DATA SHEET Model MTB-ASME Vertical Bladder Tanks Features n UL Listed for use with various proportioners and foam concentrates n 175 psi (12.1 bar) maximum allowable working pressure (design pressure)
More informationMODEL 200 KNIFE GATE VALVES INSTALLATION & MAINTENANCE MANUAL
MODEL 200 KNIFE GATE VALVES INSTALLATION & MAINTENANCE MANUAL Index 1. List of components / General arrangement 2. Description 3. Handling 4. Installation 5. Actuators / Operation 6. Maintenance a. Changing
More information