Operation Maintenance

Size: px
Start display at page:

Download "Operation Maintenance"

Transcription

1 Installation Operation Maintenance RT-SVX17E-EN Important! This document is customer property and must be retained by the unit's maintenance personnel. Library Service Literature Product Section Unitary Product Rooftop Air Conditioning (27½ - 50 Tons) Model TE*, TC*, & YC* Literature Type Installation/Operation/Maintenance Sequence 17E Date July 2007 File No. SV-UN-RT-SVX17E-EN Supersedes RT-SVX17D-EN 11/06 Voyager TM Commercial 27½ to 50 Ton 60 Hz Commercial 23 to 42 Ton 50 Hz CV or VAV Rooftop Air Conditioners with ReliaTel Controls Models "V" and later Design Sequence TC*, TE*, YC*330A, 360A, 420A, 480A, 600A (60 Hz/3 phase) TC*, TE*, YC*275A, 305A, 350A, 400A, 500A (50 Hz/3 phase) Note: The installation of this equipment must comply with all National, State, and Local Codes. 60 Hz units with standard options are certified by Underwriters Laboratory and the Canadian Standards Association American Standard All rights reserved Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. 1

2 About This Manual Literature Change History... 6 Manual Overview... 6 Warnings and Cautions... 6 Commonly Used Acronyms... 6 About the Unit... 7 Unit Inspection... 7 Storage... 7 Installation General Unit Requirements Downflow Models Only: All Units: Electrical Requirements Field Installed Control Wiring Gas Heat Requirements Recommended Clearances Roof Curb and Ductwork Horizontal Ductwork Unit Rigging and Placement Condensate Drain Connection O/A Sensor & Tubing Installation Field Installed Gas Piping General Requirements Connecting the Gas Supply Line to the Furnace Gas Train Field Installed Electrical Wiring Disconnect Switch External Handle (Factory Mounted Option) Main Power Wiring Low Voltage Wiring Field Installed AC Control Wiring Field Installed DC Control Wiring Zone Sensor Wiring Requirements Conventional Thermostat Wiring Requirements Emergency Stop Wiring Zone Sensor Thermostat Connections Remote Panels and Sensors Constant Volume Mode of Operation Zone Panel (BAYSENS006*) Zone Panel (BAYSENS008*) Remote Panel W/O NSB (BAYSENS010*) Remote Panel with NSB (BAYSENS019*) Variable Air Volume Mode of Operation Default Discharge Air Control Remote Panel with NSB (BAYSENS020*) Remote Panel W/O NSB (BAYSENS021*) Remote Zone Sensor (BAYSENS073*) Remote Zone Sensor (BAYSENS074*) Remote Zone Sensor (BAYSENS077*) High Temperature Sensor (BAYFRST001*) Remote Zone Sensor (BAYSENS016*) Remote Minimum Position Potentiometer (BAYSTAT023A) Space Temperature Averaging Unit Control Modules RTRM - ReliaTel Refrigeration Module ECA - Economizer Actuator (Optional) RTAM - ReliaTel Airhandler Module Conventional Thermostat Connections Economizer Operation with a Coventional Thermostat LCI - LonTalk Communication Interface TCI - Trane Communication Interface (Optional) Table of Contents System Operation ReliaTel Control Features Economizer Operation with CV Controls Mechanical Cooling without an Economizer Zone Temperature - Occupied Cooling Zone Temperature - Occupied Heating Supply Fan Supply Air Tempering Variable Air Volume Applications Supply Air Temperature Control - Occupied Cooling Supply Air Temperature Control with an Economizer Zone Temperature Control without a Night Setback Panel or ICS - Unoccupied Cooling Zone Temperature Control without a Night setback Panel or ICS - Unoccupied Heating Morning Warm-up Control Daytime Warm-up Control Supply Duct Static Pressure Control Supply Air Temperature Reset Constant Volume or Variable Air Volume Applications Off Mode Zone Temperature - Unoccupied Cooling Zone Temperature - Unoccupied Heating Mechanical Cooling with an Economizer Gas Heat Control Electric Heat Control Clogged Filter Ventilation Override Control Emergency Stop Low Pressure Control High Pressure Cutout Power Exhaust Control Compressor Winding Protection Lead/Lag Control Coil Frost Protection Condenser Fan/Compressor Sequencing Control Unit Start-Up Preparing the Unit for Operation Electrical Phasing Voltage Supply and Voltage Imbalance Supply Voltage Voltage Imbalance Starting the Unit Test Modes Verifying Proper Fan Rotation Verifying Proper Air Flow (CFM) (CV, IGV's or VFD's) Exhaust Fan Operation Economizer Damper Adjustment Manual Fresh Air Damper Starting the Compressors Compressor Oil Scroll Compressor Operational Noises Compressor Crankcase Heaters At Shutdown: At Low Ambient Start-Up During Normal Operation Charging by Subcooling

3 Table of Contents (Continued) Heater Start Up Gas Heat Units Electric Heat Units Final Unit Checkout For Constant Volume Units; For Variable Air Volume Units; Mechanical Cooling Sequence Of Operation Units without an Economizer Units with An Economizer Economizer Operation Dry Bulb Economizer Operation Reference Enthalpy Economizer Operation Comparative Enthalpy Electric Heat Sequence Of Operation Service and Maintenance Fan Belt Adjustment Monthly Maintenance Filters Cooling Season Heating Season Coil Cleaning Maintenance Log System Troubleshooting System Status Checkout Method Method Resetting Cooling and Ignition Lockout Method 1 (from the space) Method 2 (from the unit) Zone Temperature Sensor Service Indicator Clogged Filter Switch Fan Failure Switch Zone Temperature Sensor Test Procedures Zone Temperature Thermistor Cooling and Heating Setpoint System Model and Fan Selection LED Indicator Test Programmable & Digital Zone Sensor Test Procedure RTRM Default Operation CV and VAV Units DIP Switch Settings ECA Test Procedure VFD Testing System Troubleshooting Chart Component Failure Mode VFD Programming Parameters Warranty Information UV Lights

4 Figures and Tables Figure 1 Unit Dimensions for TC_, TE_, and YC_330, 360 and 420 MBH Units (Low Heat)... 8 Figure 1 (Continued) Unit Dimensions for YC_330, 360 and 420 MBH Units (High Heat)... 9 Figure 1 (Continued) Unit Dimensions for TC_, TE_, and YC_480 and 600 MBH Units (Low & High Heat) Figure 1 (Continued) Fresh Air and Power Exhaust Hood Dimensions for TC_, TE_, and YC_ Units Figure 2 Location of shipwith Items for TC_, TE_, and YC_ Units Figure 3 Center of Gravity Figure 4 Unit Rigging Figure 5 Condensate Trap Installation Figure 6 O/A Pressure Sensor Kit Figure 7 Gas Train Configuration for Low Heat Units Figure 8 Typical Field Power Wiring Figure 9 Electrical Wire Sizing and Protection Device Equations Figure 10 Typical Field Wiring Requirements for CV Control Options Figure 11 Typical Field Wiring Requirement for VAV Control Options Figure 12 Condenser Fan Location Figure 13 VAV Test Modes Figure 14 Supply Fan Performance Curves Figure 15 Economizer (O/A) Damper Assembly Figure 16 Typical Belt Tension Gauge Figure 17 Belt Deflection Table 1 Minimum Operating Clearances for Unit Installation Table 2 Slope Allowances Table 3 Unit Weights and Point Loading Weights Table 4 Optional Component Weights Table 5 Sizing Natural Gas Pipe Mains & Branches Table 5-1 Specific Gravity Multipliers Table Ton Electrical Service Sizing Data Table 7 AC Conductors Table 8 DC Conductors Table 9-1 RTRM Zone Sensor/Thermostat Connections Table 9 Variable Air Volume Mode Operation Table 10 Temperature versus Resistance Table 12 Percent of Damper Travel Table 13 Compressor Staging with Lead/Lag Disabled Table 14 Economizer Configuration Table Table 15 Ventilation Override Sequence Table 16 Condenser Fan Sequence Table 17 TC*/YC* 330 Through 600 MBH Economizer (R/A) Damper Pressure Drop Table 18 TC*, TE* & YC* Component Pressure Drops Table 19 TC*, TE* & YC* 27.5 through 35 Ton Supply Fan Performance Table 20 Supply Fan Drive Selection Table 21 Power Exhaust Fan Performance Table 22 Economizer (O/A) Damper Static Pressure Setup Table , 35 Operating Pressures (Std. 60 Hz) Table Ton Dual Circuit Operating Pressures (Std. 60 Hz). 51 Table Ton Dual Circuit Operating Pressures (Std. 60 Hz). 52 Table , 35 Ton Operating Pressures (Hi Eff 60 Hz) Table Ton Dual Circuit Oper Pressures (Hi Eff 60 Hz) Table Ton Dual Circuit Oper Pressures (Hi Eff 60 Hz) Table 23a 27.5, 35 Operating Pressures (Std. 50 Hz) Table 24a 40 Ton Dual Circuit Operating Pressures (Std. 50 Hz). 59 Table 25a 50 Ton Dual Circuit Operating Pressures (Std. 50 Hz). 60 Table 26a 27.5, 35 Ton Operating Pressures (Hi Eff 50 Hz) Table 27a 40 Ton Dual Circuit Oper Pressures (Hi Eff 50 Hz) Table 28a 50 Ton Dual Circuit Oper Pressures (Hi Eff 50 Hz) Table 29 Humidity versus Current Input Table 30 Grease Recommendations Table 31 Sample Operator's Maintenance Log Table 32 VFD Programming Parameters

5 Model Number Description All products are identified by a multiple character model number that precisely identifies a particular type of unit. An explanation of the alphanumeric identification code used with the unit is provided below. Its use will enable the owner/operator, installing contractors and service technicians to define the unit's specific components, type of application, i.e. CV or VAV, and control options for a particular unit. When ordering replacement parts or requesting service, be sure to refer to the specific model number, serial number, and DL number (if applicable) stamped on the unit nameplate. Unit Nameplate A Mylar unit nameplate is located on the unit's corner support just below the main power entrance access into the control panel. It includes the unit model number, serial number, electrical characteristics, weight, refrigerant charge, as well as other pertinent unit data. Compressor Nameplate The Nameplate for the Scroll Compressor is located on the compressor lower housing. YCD A 4 H A 1 A 4 A D 1 A B C D E F G H J K L M N P R 5 1,2,3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, Digit 1, 2 Unit Function TC = DX Cooling, No Heat TE = DX Cooling, Electric Heat YC = DX Cooling, Natural Gas Heat Digit 3 Unit Airflow Design D = Downflow Configuration H = Horizontal Configuration Digit 4, 5, 6 Nominal Cooling Capacity 330 = 27½ Tons 360 = 30 Tons 420 = 35 Tons 480 = 40 Tons 600 = 50 Tons Digit 7 Major Development Sequence A = First Digit 8 Power Supply (See Note 1) E = 208/60/3 F = 230/60/3 4 = 460/60/3 5 = 575/60/3 Digit 9 Heating Capacity (See Note 4) 0 = No Heat (TC only) L = Low Heat (YC only) H = High Heat (YC only) J = Low Heat-Stainless Steel Gas Heat Exchangers (YC only) K = High Heat-Stainless Steel Gas Heat Exchanger (YC only) M = Low Heat-Stainless Steel Gas Heat Exchangers w/modulating control (YC only) P = High Heat-Stainless Steel Gas Heat Exchangers w/modulating control (YC only) Note: When second digit is E for Electric Heat, the following values apply in the ninth digit. A = 36 KW B = 54 KW C = 72 KW D = 90 KW E = 108 KW Digit 10 Design Sequence R = R and later Digit 11 Exhaust 0 = None 1 = Barometric Relief (Available w/economizer only) 2 = Power Exhaust Fan (Available w/economizer only) Digit 12 Filter A = Standard 2 Throwaway Filters B = High Efficiency 2 Throwaway Filters C = High Efficiency 4 Throwaway Filters Digit 13 Supply Fan Motor, HP 1 = 7.5 Hp Std. Eff. 2 = 10 Hp Std. Eff. 3 = 15 Hp Std. Eff. 4 = 20 Hp Std. Eff. 5 = 7.5 Hp Hi. Eff. 6 = 10 Hp Hi. Eff. 7 = 15 Hp Hi. Eff. 8 = 20 Hp Hi. Eff. Digit 14 Supply Air Fan Drive Selections (See Note 3) A = 550 RPM H = 500 RPM B = 600 RPM J = 525 RPM C = 650 RPM K = 575 RPM D = 700 RPM L = 625 RPM E = 750 RPM M = 675 RPM F = 790 RPM N = 725 RPM G = 800 RPM Digit 15 Fresh Air Selection A = No Fresh Air B = 0-25% Manual Damper C = 0-100% Economizer, Dry Bulb Control D = 0-100% Economizer, Reference Enthalpy Control E = 0-100% Economizer, Differential Enthalpy Control F = C Option and Low Leak Fresh Air Damper G = D Option and Low Leak Fresh Air Damper H = E Option and Low Leak Fresh Air Damper Digit 16 System Control 1 = Constant Volume 2 = VAV Supply Air Temperature Control w/o Inlet Guide Vanes 3 = VAV Supply Air Temperature Control w/inlet Guide Vanes 4 = VAV Supply Air Temperature Control w/variable Frequency Drive w/o Bypass 5 = VAV Supply Air Temperature Control w/variable Frequency Drive and Bypass Note: Zone sensors are not included with option and must be ordered as a separate accessory. Digit Miscellaneous Options A = Service Valves (See Note 2) B = Through the Base Electrical Provision C = Non-Fused Disconnect Switch with External Handle D = Factory-Powered 15A GFI Convenience Outlet and Non-Fused Disconnect Switch with External Handle E = Field-Powered 15A GFI Convenience Outlet F = Trane Communication Interface (TCI) G = Ventilation Override H = Hinged Service Access J = Condenser Coil Guards K = LCI (LonTalk) L = Unused digit M = Stainless Steel Drain Pans Digit 29 Condenser Coil Options 0 = Standard Efficiency Condenser Coil N = Standard Efficiency Condenser Coil with Black Epoxy Pre-Coating 3 = High Efficiency Condenser Coil Q = High Efficiency Condenser Coil with Black Epoxy Pre-Coating Digit Miscellaneous Options P = Discharge Temperature Sensor R = Clogged Filter Switch Notes: 1. All voltages are across the line starting only. 2. Option includes Liquid, Discharge, Suction Valves. 3. Supply air fan drives A thru G are used with 27½-35 ton units only and drives H thru N are used with 40 & 50 ton units only. 4. Electric Heat KW ratings are based upon voltage ratings of 240/480/600 V. 5. The service digit for each model number contains 31 digits; all 31 digits must be referenced. 5

6 Literature Change History RT-SVN17E-EN (July 2007) Revised issue: Updated with Modulating Natural Gas Information. Provides specific installation, operational, and maintenance instructions for TC_, TE_, and YC_ units with "R" and later design sequence. RT-SVN17D-EN (June 2006) Revised issue: Updated with High Efficiency Condenser Coil Information. Provides specific installation, operational, and maintenance instructions for TC_, TE_, and YC_ units with "U" and later design sequence. RT-SVN17C-EN (March 2005) Revised issue: Updated Gas Heat Sequence of Operation Section. Provides specific installation, operational, and maintenance instructions for TC_, TE_, and YC_ units with "P" and later design sequence. RT-SVN17C-EN (January 2005) Revised issue: Added Capacitor Discharge Warning. Provides specific installation, operational, and maintenance instructions for TC_, TE_, and YC_ units with "P" and later design sequence. RT-SVN17C-EN (October 2004) Revised issue: Supply fan proving switch change. Provides specific installation, operational, and maintenance instructions for TC_, TE_, and YC_ units with "P" and later design sequence. RT-SVN17B-EN (July 2004) Revised issue: alternate supply fan and belt supplier added. Provides specific installation, operational, and maintenance instructions for TC_, TE_, and YC_ units with "M" and later design sequence. RT-SVN17A-EN (April 2004) Revised issue: ReliaTel Controls added--provides specific installation, operational, and maintenance instructions for TC_, TE_, and YC_ units with "M" and later design sequence. YC-IOM-11 (October 2001) Original issue: provides specific installation, operational, and maintenance instructions for TC_, TE_, and YC_ units with "H" and later design sequence. Manual Overview One copy of the appropriate service literature ships inside the control panel of each unit. The procedures discussed in this manual should only be performed by qualified, experienced HVAC technicians. Note: Do Not release refrigerant to the atmosphere! If adding or removing refrigerant is required, the service technician must comply with all federal, state, and local laws. This booklet describes the proper installation, start-up, operation, and maintenance procedures for TC_, TE_, and YC_27.5 through 50 Ton CV (Constant Volume) and VAV (Variable Air Volume) applications. Refer to page 2 for a detailed table of contents listing specific topics. Refer to the "System Troubleshooting" section at the end of this manual for troubleshooting information. By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized. It is important that periodic maintenance be performed to help assure trouble free operation. A maintenance schedule is provided at the end of this manual. Should equipment failure occur, contact a qualified service organization with qualified, experienced HVAC technicians to properly diagnose and repair this equipment. About This Manual Hazard Identification WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. Commonly Used Acronyms/Abbreviations BAS = building automation system CFM = cubic feet per minute COMM = Module Designation for TCI/LCI CV = constant volume CW = clockwise CCW = counterclockwise DSP = direct space pressure control DTS = discharge air sensor DWU = Daytime Warm-up E/A = exhaust air ECA = Economizer Actuator F/A = fresh air FFS = fan failure switch ICS = Integrated Comfort System (See BAS) IDM = indoor fan motor IGV = inlet guide vanes I/O = input/output IOM = installation, operation and maintenance manual (Ships with each unit) LCI = LonTalk Communication Interface LCI-R = LonTalk Communication Interface with ReliaTel LH = left hand MAS = mixed air sensor MAT = mixed air temperature MWU = morning warm up NSB = night setback (programmable ZSM BAYSENS019*, 20*) O/A = outside air OAH = outside air humidity OAT = outside air temperature PSIG = pounds per square inch gauge pressure R/A = return air RAH = return air humidity RAT = return air temperature sensor RH = right hand RPM = revolutions per minute RTAM = ReliaTel Airhandler Module RTOM = ReliaTel Options Module RTRM = ReliaTel Refrigeration Module S/A = supply air SPT = static pressure transducer TCI = Trane communication interface TCO = temperature cutout VAV = variable air volume VFD = Variable Frequency Drive VHR = ventilation heat relay (VAV box relay) W.C. = water column XFSP = exhaust fan setpoint ZSM = sensor, zone sensor, zone sensor module, zone panel

7 About the Unit Each package rooftop unit ships fully assembled and charged with the proper refrigerant quantity from the factory. They are controlled by a microelectronic unit control processor. Several solid state modules are grouped to form the "Control System". The number of modules within any given control system will be dependent upon the options and accessories ordered with the unit. Acronyms are used extensively throughout this manual when referring to the "Control System" (see acronyms/abbreviations previous page). Basic unit components include: Scroll compressors One (1) Intertwined Evaporator Coil One (1) Intertwined Condenser Coil One (1) Supply Fan Three (3) to Four (4) Condenser Fans Filters (type is dependent on option selection) Overall unit dimensional data is illustrated in Figure 1. Unit Inspection As soon as the unit arrives at the job site: [ ] Verify that the nameplate data corresponds to the sales order and bill of lading (including electrical data). [ ] Visually inspect the exterior of the unit, including the roof, for physical signs of shipping damage. [ ] Check for material shortages. Figure 2 illustrates where "ship with" items are placed inside the unit. If the job site inspection reveals damage or material shortages, file a claim with the carrier immediately. Specify the type and extent of the damage on the "bill of lading" before signing. Do not install a damaged unit without the Appropriate Trane sales representative's approval! [ ] Visually check the internal components for shipping damage as soon as possible after delivery and before it is stored. Do not walk on the sheet metal base pans. WARNING Fiberglass Wool Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. Glass wool fibers may also cause respiratory, skin or eye irritation. Precautionary Measures - Avoid breathing fiberglass dust. - Use a NIOSH approved dust/mist respirator. - Avoid contact with the skin or eyes. Wear longsleeved, loose-fitting clothing, gloves, and eye protection. - Wash clothes separately from other clothing: rinse washer thoroughly. - Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respiration in these situations. First Aid Measures Eye Contact - Flush eyes with water to remove dust. If symptoms persist, seek medical attention. Skin Contact - Wash affected areas gently with soap and warm water after handling. An optional roof curb, specifically designed for the Voyager commercial rooftop units is available from Trane. The roof curb kit must be field assembled and installed according to the latest edition of CURB-IN-35. WARNING No Step Surface! Do not walk on the sheet metal drain pan. Walking on the drain pan could cause the supporting metal to collapse. Failure of the drain pan could result in death or serious injury. Bridging between the unit's main supports may consist of multiple 2 by 12 boards or sheet metal grating. [ ] If concealed damage is discovered, notify the carrier's terminal office immediately by phone and by mail. Concealed damage must be reported within 15 days. Request an immediate joint inspection of the damage by the carrier and the consignee. Do not remove the damaged material from the receiving location. Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery. Storage Take precautions to prevent condensate formation inside the unit's electrical components and motors when: a. The unit is stored before it is installed; or, b. The unit is set on the roof curb and temporary auxiliary heat is provided in the building. Isolate all side panel service entrances and base pan openings (e.g., conduit holes, S/A and R/A openings, and flue openings) to minimize ambient air from entering the unit until it is ready for start-up. Do not use the unit's heater as temporary heat without completing the start-up procedures detailed under "Unit Start-Up". Trane will not assume responsibility for equipment damage resulting from accumulation of condensate on the unit's electrical components.

8 Figure 1 Unit Dimensions for TC_, TE_, and YC_330, 360 and 420 MBH Units (Low Heat) 8

9 Figure 1 (continued) Unit Dimensions for YC_330, 360 and 420 MBH Units (High Heat) 9

10 Figure 1 (continued) Unit Dimensions for TC_, TE_, and YC_480 and 600 MBH Units (Low & High Heat) 10

11 Figure 1 (continued) Fresh Air and Power Exhaust Hood Dimensions for TC_, TE_, and YC_ Units Figure 2 Location of Shipwith Items for TC_, TE_, and YC_ Units 11

12 Installation The checklist listed below is a summary of the steps required to successfully install a Voyager Commercial rooftop unit. This checklist is intended to acquaint the installing personnel with what is required in the installation process. It does not replace the detailed instructions called out in the applicable sections of this manual. General Unit Requirements Downflow Models Only: [ ] Assemble and install the roof curb, including necessary gaskets. (See the current edition of CURB-IN-35.) Make sure the curb is level. [ ] Install and secure the ductwork to the curb. Refer to the current addition of CURB-IN-35. All Units: [ ] Check unit for shipping damage and material shortage. Refer to page 7, Unit inspection. [ ] Rigging the unit. Refer to page 15, Figure 4. [ ] Placing the unit on curb; check for levelness. Refer to page 13. [ ] Ensure that the unit-to-curb seal is tight and without buckles or cracks. [ ] Install an appropriate drain line to the evaporator condensate drain connections, as required. Refer to Figure 5 on page 16. [ ] Service Valve Option; Refer to page 48, "Starting the Compressors". [ ] Return/Fresh-air damper adjustment. Refer to page 46, Economizer Damper Adjustments. Electrical Requirements (See page 20, Field Installed Electrical Power Wiring) [ ] Inspect all control panel components; tighten any loose connections. [ ] Connect properly sized and protected power supply wiring to a field supplied/installed disconnect and unit power terminal block HTB1, or to the optional unitmounted disconnect switch. [ ] Properly ground the unit. Field Installed Control Wiring (Figure 9 & Figure 10) Note: All field-installed wiring must comply with NEC and applicable local codes. [ ] Complete the field wiring connections for the constant volume controls as applicable. Refer to the "Low Voltage Wiring" section on page 23 for guidelines. [ ] Complete the field wiring connections for the variable air volume controls as applicable. Refer to the "Low Voltage Wiring" section on page 23 for guidelines. Gas Heat Requirements (See page 17, Field Piping) [ ] Gas supply line properly sized and connected to the unit gas train. [ ] All gas piping joints properly sealed. [ ] Drip leg Installed in the gas piping near the unit. [ ] Gas piping leak checked with a soap solution. If piping connections to the unit are complete, do not pressurize piping in excess of 0.50 psig or 14 inches w.c. to prevent component failure. [ ] Main supply gas pressure adequate. [ ] Flue Tubes clear of any obstructions. [ ] Verify that the electrical power supply characteristics comply with the unit nameplate specifications. 12

13 Recommended Clearances Adequate clearance around and above each Voyager Commercial unit is required to ensure proper operation and to allow sufficient access for servicing. If the unit installation is higher than the typical curb elevation, a field constructed catwalk around the unit is recommended to provide safe, easy access for maintenance and servicing. Table 1 lists the recommended clearances for single and multiple unit installation. These clearances are necessary to assure adequate serviceability, cataloged capacities, and peak operating efficiency. If the clearances available on the job site appear to be inadequate, review them with your Trane sales representative. Roof Curb and Ductwork The curbs for the 27.5 to 50 Ton commercial rooftop units enclose the entire unit base area. They are referred to as "full perimeter" type curbs. Step-by-step instructions for the curb assembly and installation with curb dimensions and curb configuration for "A", "B", and "C" cabinets ship with each Trane accessory roof curb kit. (See the latest edition of CURB-IN-35) Follow the instructions carefully to assure proper fit when the unit is set into place. The S/A and R/A ductwork adjoining the roof curb must be fabricated and installed by the installing contractor before the unit is set into place. Trane curbs include flanges around the openings to accommodate duct attachment. Ductwork installation recommendations are included in the instruction booklet that ships with each Trane accessory roof curb kit. Installation (Continued) Note: For sound consideration, cut only the holes in the roof deck for the supply and return duct penetration. Do Not remove the roof decking from the inside perimeter of the curb. If a Trane curb accessory kit is not used; a. The ductwork can be attached directly to the S/A and R/A openings. Be sure to use a flexible duct connector at the unit. b. For "built-up" curbs supplied by others, gaskets must be installed around the curb perimeter flange, S/A opening, and R/A openings. c. Insulation must be installed on the bottom of the condenser section of the unit. Horizontal Ductwork When attaching the ductwork to a horizontal unit, provide a water tight flexible connector at the unit to prevent noise transmission from the unit into the ductwork. Refer to Figure 1 for the S/A and R/A opening dimensions. All outdoor ductwork between the unit and the structure should be weather proofed after installation is completed. If optional power exhaust is selected, an access door must be field-installed on the horizontal return ductwork to provide access to exhaust fan motors. Unit Rigging and Placement 1. Verify that the roof curb has the proper gaskets installed and is level and square to assure an adequate curb-tounit seal. Table 1 Minimum Operating Clearances for Unit Installation Recommended Clearances Condenser Coil** Single Unit Econo / Exhaust Orientation Service Side End End / Side Access TC*, TE*, YC* 6 Feet 8 Feet / 4 Feet 4 Feet 27.5 thru 50 Tons Distance Between Units Multiple Unit Econo / Exhaust Service Side End End / Side Access TC*, TE*, YC* 12 Feet 16 Feet / 8 Feet 8 Feet 27.5 thru 50 Tons * Horizontal and Downflow Units. ** Condenser coil is located at the end and side of the unit. The units must be as level as possible in order to assure proper condensate flow out of the unit. The maximum sideto-side and end-to-end slope allowable in any application is listed in Table 2. 13

14 Table 2 Cabinet End to End Side to Side (inches) (inches) "A" ( Ton Low Heat) 3 1/2 1 5/8 "B" ( Ton High Heat) 4 1 5/8 "C" (All 40 and 50 Ton Units) 4 1/2 1 5/8 Do not exceed these allowances. Correct the improper slope by building up the curb base. The material used to raise the base must be adequate to support both the curb and the unit weight. WARNING Heavy Objects! Do not use cables (chains or slings) except as shown. Each of the cables (chains or slings) used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift. Other lifting arrangements may cause equipment or propertyonly damage. Failure to properly lift unit may result in death or serious injury. Installation (Continued) 2. Attach adequate strength lifting cables to the lifting lugs within the base rail. Table 3 lists the unit weights and corner weights. To obtain the total unit weight, add the accessory weight listed in Table 4 to the base unit weight. The unit center-of-gravity location and dimensions are shown in Figure 3. Figure 4 illustrates the Installation of spreader bars to protect the unit and to assure a uniform lift. Note that the minimum distance between the lifting hook and the top of the unit should be 7 feet. 3. Test-lift the unit to check all rigging and balance; make any rigging adjustments necessary. 4. Lift the unit and position it over the curb. Align the base rails of the unit up with the curb. 5. Lower the unit onto the curb. Make sure that the gasket on the curb remains intact when positioning the unit. Use spreader bars as shown in the diagram. Refer to the Installation manual or nameplate for unit weight. Refer to the Installation instructions located inside the control panel for further rigging information. Figure 3 Center of Gravity Center-of-Gravity (inches) Unit Model YC Low Heat Dimension YC High Heat Dimension TC/TE Dimension X Y Z X Y Z X Y Z (note 2) ***330* ***360* ***420* ***480* ***600* Note: 1. Center-of-gravity dimensions are approximate, and are based on the unit equipped with: standard efficiency coils, standard efficiency motors, economizer, inlet guide vanes, and throwaway filters 2. Z dimension is upward from the base of the unit. Example: Locating the center-of-gravity for a YC-360 MBH High Heat unit with 100% exhaust. X = 40 inches inward from the control panel side Y = 86 inches inward from the compressor end Z = 33 inches upward from the base Y Z (see note 2) X 14

15 Figure 4 Unit Rigging Table 3 Approximate Unit Operating Weights/Average Point Loading Weights lbs./kg (see notes 1,2,3,4,5) Basic Unit Weights 1,2,3 Unit YC YC TC TE Model Low Heat High Heat **D330/ / / / /1626 **H330/ / / / /1644 **D360/ / / / /1662 **H360/ / / / /1681 **D420/ / / / /1701 **H420/ / / / /1719 **D480/ / / / /2091 **H480/ / / / /2123 **D600/ / / / /2168 **D600/ / / / /2200 A B C D E F 899/ / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / /346 Notes 1. Basic unit weight includes minimum horsepower supply fan motor and standard efficiency 2-row condenser coil. 2. Optional high efficiency motor weights are in addition to the standard motor weights included in the basic unit weight (see component weights). 3. Optional high efficiency 3-row condenser coil weights are in addition to the standard 2-row coil weight included in the basic unit weight (see component weights). 4. Point Loading is identified with corner A being the corner with the compressors. As you move clockwise around the unit as viewed from the top, mid-point B, corner C, corner D, mid-point E and corner F. 5. Point load calculations provided are based on the unit weight for YC high heat gas models. Table 4 Approximate Operating Weights 1 Optional Components lbs./kg Var. Freq. Non- Factory. 0-25% Inlet Drives (VFD s) Thru-the Fused GFI with Hi Eff Roof Unit Baro. Power Hi Eff. Supply Man Guide W/O With Serv base Discon. Discon. Cond Curb Model Relief Exhaust Fan Motor 2 Damper Econ. Vanes Bypass Valves Elec. Switch Switch Coil 3 Lo Hi **D330/ /50 165/74 20/9 50/23 260/117 55/25 85/39 115/52 18/8 6/3 30/14 85/38 104/47 310/ /150 **H330/ /65 200/90 20/9 50/23 285/128 55/25 85/39 115/52 18/8 6/3 30/14 85/38 104/47 310/ /150 **D360/ /50 165/74 20/9 50/23 260/117 55/25 85/39 115/52 18/8 6/3 30/14 85/38 104/47 310/ /150 **H330/ /65 200/90 20/9 50/23 285/128 55/25 85/39 115/52 18/8 6/3 30/14 85/38 104/47 310/ /150 **D420/ /50 165/74 20/9 50/23 260/117 55/25 85/39 115/52 18/8 6/3 30/14 85/38 104/47 310/ /150 **H420/ /65 200/90 20/9 50/23 285/128 55/25 85/39 115/52 18/8 6/3 30/14 85/38 104/47 310/ /150 **D480/ /50 165/74 44/20 50/23 290/131 70/32 115/52 150/68 18/8 6/3 30/14 85/38 162/73 365/ /169 **H480/ /65 200/90 44/20 50/23 300/135 70/32 115/52 150/68 18/8 6/3 30/14 85/38 162/73 365/ /169 **D600/ /50 165/74 44/20 50/23 290/131 70/32 115/52 150/68 18/8 6/3 30/14 85/38 162/73 365/ /169 **H600/ /65 200/90 44/20 50/23 300/135 70/32 115/52 150/68 18/8 6/3 30/14 85/38 162/73 365/ /169 Notes: 1. Basic unit weight includes minimum horsepower supply fan motor and standard efficiency 2-row condenser coil. 2. When an optional high efficiency supply fan motor is selected, the weight shown should be added to the basic unit weight. 3. When an optional high efficiency condenser coil is selected, the weight shown should be added to the basic unit weight. 15

16 Condensate Drain Connection Each commercial rooftop unit is equipped with one (1) 1-1/4 inch Female PVC condensate drain connection. Installation (Continued) Figure 6 Refer to Figure 2 for the location of the connector. A condensate trap must be installed due to the drain connection being on the "negative pressure" side of the fan. Install a P-Trap at the unit using the guidelines in Figure 5. Pitch the drain line at least 1/2 inch for every 10 feet of horizontal run to assure proper condensate flow. Ensure that all condensate drain line installations comply with applicable building and waste disposal codes. Figure 5 Condensate Trap Installation O/A Sensor & Tubing Installation An Outside Air Pressure Sensor is shipped with all units designed to operate on variable air volume applications. A duct pressure transducer and the outside air sensor is used to control the discharge duct static pressure to within a customer-specified controlband. Refer to the illustration in Figure 6 and the following steps to install the sensor and the pneumatic tubing. 1. Remove the O/A pressure sensor kit located inside the fan section. The kit contains the following items; - an O/A static pressure sensor - a sensor mounting bracket - 2' of 3/16" O.D. pneumatic tubing - mounting hardware 2. Using two #10-32 x 1-3/4" screws provided, install the sensor's mounting bracket to the factory provided bracket (near the fan section). 3. Using the #10-32 x 1/2" screws provided, install the O/A static pressure sensor vertically to the sensor bracket. 4. Remove the dust cap from the tubing connector located below the sensor in the vertical support. 5. Attach one end of the 2' x 3/16" O.D. factory provided pneumatic tubing to the sensor's top port, and the other end of the tubing to the connector in the vertical support. Discard any excess tubing. 16

17 General Requirements All internal gas piping for YC* rooftop units are factory installed and leak tested. Once the unit is set into place, a gas supply line must be field installed and connected to the gas train located inside the gas heat compartment. WARNING Hazardous Gases and Flammable Vapors! Exposure to hazardous gases from fuel substances have been shown to cause cancer, birth defects or other reproductive harm. Improper installation, adjustment, alteration, service or use of this product could cause flammable mixtures. To avoid hazardous gases and flammable vapors follow proper installation and set up of this product and all warnings as provided in this manual. Failure to follow all instructions could result in death or serious injury. REFER TO THE INSTALLATION, OPERATION AND MAIN- TENANCE MANUAL PROVIDED WITH THIS UNIT FOR PROPER OPERATION INSTRUCTIONS. Access holes are provided on the unit as shown in Figure 2 to accommodate side panel entry. Following the guidelines listed below will enhance both the installation and operation of the furnace. Note: In the absence of local codes, the installation must conform with the American National Standard Z223.1a of the National Fuel Gas Code, (latest edition). 1. To assure sufficient gas pressure at the unit, use Table 5 to determine the appropriate gas pipe size for the heating capacity listed on the unit's nameplate. If a gas line already exists, verify that it is sized large enough (Table 5) to handle the additional furnace capacity. 2. Take all branch piping from any main gas line from the top at 90 degrees or side at 45 degrees to prevent moisture from being drawn in with the gas. 3. Ensure that all piping connections are adequately coated with joint sealant and properly tightened. Use a piping compound that is resistant to liquid petroleum gases. 4. Provide a drip leg near the unit. Field Installed Gas Piping Note: Gas pressure in excess of 14" w.c. or 0.5 psig will damage the gas train. Failure to use a pressure regulating device will result in incorrect gas pressures. This can cause erratic operation due to gas pressure fluctuations as well as damage to the gas valve. Oversizing the regulator will cause irregular pulsating flame patterns, burner rumble, potential flame outages, as well as possible gas valve damage. 6. Leak test the gas supply line using a soap-and-water solution or equivalent before connecting it to the gas train. WARNING Hazard of Explosion! Never use an open flame to detect gas leaks. Explosive conditions may occur. Use a leak test solution or other approved methods for leak testing. Failure to follow recommended safe leak test procedures could result in death or serious injury or equipment or property-onlydamage. 7. Pressure test the supply line before connecting it to the unit to prevent possible gas valve damage and the unsafe operating conditions that will result. Note: Do not rely on gas train shutoff valves to isolate the unit while conducting gas pressure/leak test. These valves are not designed to withstand pressures in excess of 14" w.c. or 0.5 psig. Connecting the Gas Supply Line to the Furnace Gas Train Follow the steps below to complete the installation between the supply gas line and the furnace. Refer to Figure 7 for the Gas Train configuration. 1. Connect the supply gas piping using a "ground-joint" type union to the furnace gas train and check for leaks. 2. Provide adequate support for the field installed gas piping to avoid stressing the gas train and controls. 3. Adjust the inlet supply gas pressure to the recommended 6" for natural gas or 11" w.c. for LP gas. 5. Install a pressure regulator at the unit that is adequate to maintain 6" w.c. for natural gas and 11" w.c. for LP gas while the unit is operating in the "High Heat" mode. A minimum inlet gas pressure of 2.5" w.c. for natural gas and 8" w.c. for LP gas is required while operating in the "High Heat" mode. 17

18 Table 5 Sizing Natural Gas Pipe Mains & Branches Gas Input (Cubic Feet/Hour)* Notes: 1. If more than one unit is served by Gas Supply 1-1/4" 1-1/2" 2" 2-1/2" 3" 4" the same main gas supply, consider Pipe Run (ft) Pipe Pipe Pipe Pipe Pipe Pipe the total gas input (cubic feet/hr.) and the total length when determining the appropriate gas pipe size Obtain the Specific Gravity and BTU/Cu.Ft. from the gas company The following example demonstrates the considerations necessary when determining the actual pipe size Example: A 40' pipe run is needed to connect a unit with a 500 MBH furnace to a natural gas supply having a rating of 1, BTU/Cu.Ft. and a specific gravity of Cu.Ft/Hour = Furnace MBH Input Gas BTU/Cu.Ft. X Multiplier (Table 5-1) Cu.Ft/Hour = 500 * Table is based on a specific gravity of Use Table 5-1 for the Table 5 indicates that a 1-1/4" pipe is required. specific gravity of the local gas supply. Table 5-1 Specific Gravity Multipliers Specific Gravity Multiplier Figure 7 Gas Train Configuration for Low Heat units (High Heat Units utilize two Gas Trains.) 18

19 Disconnect Switch External Handle (Factory Mounted Option) Field Installed Electrical Wiring Note: All field installed wiring must conform to NEC guidelines as well as State and Local codes. Units ordered with the factory mounted disconnect switch come equipped with an externally mounted handle. This allows the operator to disconnect power from the unit without having to open the control panel door. The handle location and its three positions are shown below; ON - Indicates that the disconnect switch is closed, allowing the main power supply to be applied at the unit. OFF - Indicates that the disconnect switch is open, interrupting the main power supply at the unit. OPEN COVER/RESET - Turning the handle to this position releases the handle from the disconnect switch, allowing the control panel door to be opened. WARNING Hazardous Voltage! Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury. Once the door has been opened, it can be closed with the handle in any one of the three positions outlined above, provided it matches the disconnect switch position. The handle can be locked in the "OFF" position. While holding the handle in the "OFF" position, push the spring loaded thumb key, attached to the handle, into the base slot. Place the lock shackle between the handle and the thumb key. This will prevent it from springing out of position. Verify that the power supply available is compatible with the unit's name plate ratings for all components. The available power supply must be within 10% of the rated voltage stamped on the nameplate. Use only copper conductors to connect the 3-phase power supply to the unit. CAUTION Use Copper Conductors Only! Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors may result in equipment damage. Main Power Wiring 1. Table 6 lists the electrical data. The electrical service must be protected from over current and short circuit conditions in accordance with NEC requirements. Protection devices must be sized according to the electrical data on the nameplate. Refer to Figure 9 for determining: a. The appropriate electrical service wire size based on "Minimum Circuit Ampacity" (MCA), b. The "Maximum Over current Protection" (MOP) device. c. The "Recommended Dual Element fuse size" (RDE). 2. If the unit is not equipped with an optional factory installed Nonfused disconnect switch, a field supplied disconnect switch must be installed at or near the unit in accordance with the National Electrical Code (NEC latest edition). Refer to Figure 9, DSS calculations, for determining correct size. Location for the electrical service entrance is shown in Figure 1. Complete the unit's power wiring connections onto either the main terminal block HTB1, or the factory mounted nonfused disconnect switch inside the unit control panel. Note: Any electrical entrance holes drilled into the base of the unit when a thru-the-base option is not used, is the responsibility of the installing contractor to prevent water from leaking into the building. 3. Provide proper grounding for the unit in accordance with local and national codes. Thru-the-Base Electrical (Optional Accessory) An overall layout of the field required power wiring is illustrated in Figure 8. To insure that the unit's supply power wiring is properly sized and installed, follow the guidelines outlined below. Liquid-tite conduit couplings are secured to the base of the unit for both power and control wiring. Liquid-tite conduit must be field installed between the couplings and the unit control box to prevent water leaks into the building. If the unit is set on the roofcurb and temporary auxiliary heat is provided in the building, it is recommended that the electrical and control wiring conduit opening in the control box be temporarily sealed to provide a vapor barrier. 19

20 Figure 8 Typical Field Power Wiring Table Ton Electrical Service Sizing Data (Electric Heaters Only) Electric Heat FLA All FLA's in this table are based on heater operation at 208, 240, 480, and 600 v Nominal Nominal Unit Size Unit Heater KW (Tons) Voltage , 30, n/a n/a n/a n/a n/a n/a n/a 575 n/a n/a 40, n/a n/a n/a n/a 230 n/a n/a n/a n/a 460 n/a n/a Note: Heater KW = X Applied Voltage X Amps 20

21 Table 6 (Continued) Ton Electrical Service Sizing Data Supply Fan Condenser Exhaust Compressor Std/Hi-Eff Fan Motors Fan Unit Voltage Voltage RLA LRA FLA FLA Model Range No./Size (Ea) (Ea) HP FLA No. HP (Ea) HP (Ea) 208/60/ /10, / / / /29.0 TC/TE/ 230/60/ / / / YC* / /60/ / / / / /60/ / / / / /60/ / / /28.0 TC/TE/ 230/60/ / YC* / /60/ / / /60/ / / /60/ / / / /41.5 TC/TE/ 230/60/ / YC* / / /60/ / / / /60/ / / / /60/ /14,14, /62.8/ /409/ / /41.5 TC/TE/ 230/60/ /62.8/ /376/ / YC* / /60/ /27.3/ /178/ / / /60/ /21.8/ /143/ / / /60/ / / / /56.1 TC/TE/ 230/60/ / YC* / / /60/ / / / /60/ / / /

Installation Instructions

Installation Instructions 48011HW NATURAL GAS TO PROPANE CONVERSION KIT 58HDX, 359AAV, PG9YAB, PG9YAA Installation Instructions SAFETY REQUIREMENTS Installing and servicing heating equipment can be hazardous due to gas and electrical

More information

ACCESSORY KIT INSTALLATION MANUAL

ACCESSORY KIT INSTALLATION MANUAL ACCESSORY KIT INSTALLATION MANUAL LP (PROPANE) CONVERSION KIT 1NP0366 FOR USE WITH MODELS: G8C & GF8 This conversion kit shall be installed by a qualified service agency in accordance with these instructions

More information

Natural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet)

Natural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet) Natural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet) INSTALLATION INSTRUCTIONS For R7 Series Light Commercial Packaged Gas Electric Units IIMPORTANT: Please

More information

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1 Dry 131h 1. DESCRIPTION The Viking Model G-1 Maintenance Air Compressor is an electric motor-driven, aircooled, single-stage, oil-less compressor. The unit is equipped with a check valve and provides a

More information

LENNOX SLP98UHV DIAGNOSTIC CODES

LENNOX SLP98UHV DIAGNOSTIC CODES Code Status of Equipment Action required to clear and recover - Idle mode (Decimal blinks at 1 Hertz -- 0.5 second ON, 0.5 second OFF) A Cubic feet per minute (cfm) setting for indoor blower (1 second

More information

MAINLINE MLA14 AIR CONDITIONERS

MAINLINE MLA14 AIR CONDITIONERS FORM NO. AML-220 Supersedes Form No. PTZ-789 MAINLINE AIR CONDITIONERS Efficiencies up to 16 /13 Nominal Sizes 1.5-5 Ton [5.28 TO 17.6 KW] Cooling Capacities 17.3 to 60.5 kbtu [5.7 to 17.7 kw] Manufactured

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS 1NP0680 - PROPANE CONVERSION FOR USE WITH MODELS: PM8, PC8, PM9, PC9, FL9M, FL9C, FC9M, FC9C This conversion kit is to be installed by a qualified service agency

More information

SERIES 100 PACKAGED ROOFTOP UNIT WITH IPU CONTROL

SERIES 100 PACKAGED ROOFTOP UNIT WITH IPU CONTROL Supersedes: 100.50-CL1 (1014) Form 100.50-CL1 (517) MECHANICAL CONTRACTOR INSTALLATION CHECKLIST AND UNIT SETUP DATA SHEET CUSTOMER: ADDRESS: PHONE: SERIES 100 PACKAGED ROOFTOP UNIT WITH IPU CONTROL 035-21780-030

More information

INSTALLATION GUIDE Gas Rangetops

INSTALLATION GUIDE Gas Rangetops INSTALLATION GUIDE Gas Rangetops Contents Wolf Gas Rangetops........................... 3 Safety Instructions............................ 4 Gas Rangetop Specifications.................... 5 Gas Rangetop

More information

WARNING: Installation Instructions. Natural Gas High Altitude Conversion Kit United States Installations Only

WARNING: Installation Instructions. Natural Gas High Altitude Conversion Kit United States Installations Only Natural Gas High Altitude Conversion Kit United States Installations Only Installation Instructions Light Commercial Packaged Gas Electric Units R7TQ Series 6, - 7 1/2, & 10 Ton (2,001 FT - 10,000 FT)

More information

Evaporator (DX) Freon Applications 1 12 Tons MHF

Evaporator (DX) Freon Applications 1 12 Tons MHF Evaporator (DX) Freon Applications 1 12 Tons > > Used For small to medium freon applications The Global Leader In Heat Exchange Technology With seven decades of experience and commitment to total client

More information

36E DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

36E DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS INLET PRESS TAP WTE-RODGERS 36E54-214 DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS

More information

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS INLET PRESS TAP WTE-RODGERS 36E96-314 DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL

More information

36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS

36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS 36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING

More information

SPECIFICATIONS Type: Twin stack, single phase Tank: 4 gallon Air Output: PSI; PSI Max PSI: 125 PSI HP: 1.

SPECIFICATIONS Type: Twin stack, single phase Tank: 4 gallon Air Output: PSI; PSI Max PSI: 125 PSI HP: 1. 2 GALLON TWIN STACK AIR COMPRESSOR Model: 9526 DO NOT RETURN TO STORE. Please CALL 800-348-5004 for parts and service. CALIFORNIA PROPOSITION 65 WARNING: You can create dust when you cut, sand, drill or

More information

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A 2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A PROJECT ADDRESS TESTING AUTHORITY TELEPHONE Checked by/date Enforcement Agency Use GENERAL INFORMATION OF BLDG. PERMIT PERMIT # BLDG. CONDITIONED FLOOR

More information

AIR CONDITIONERS. Features. Manufactured for Fujitsu General America, Inc. Fairfield, NJ. FORM NO. AFJ-220 Supersedes Form No.

AIR CONDITIONERS. Features. Manufactured for Fujitsu General America, Inc. Fairfield, NJ. FORM NO. AFJ-220 Supersedes Form No. FORM NO. AFJ-220 Supersedes Form No. PTZ-789 AIR CONDITIONERS FO*14C SERIES Efficiencies up to 16 S/13 Nominal Sizes 1 1 /2 to 5 Ton [5.28 to 17.6 kw] Cooling Capacities 17.3 to 60.5 kbtu [5.7 to 17.7

More information

GM Series Dual-Block Multi-Function Gas Control Valves

GM Series Dual-Block Multi-Function Gas Control Valves Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin GM Issue Date 0297 GM Series Dual-Block Multi-Function Gas Control Valves Figure 1: GM Series

More information

Model PSI Compressor with 3-Gallon Air Tank 12VDC

Model PSI Compressor with 3-Gallon Air Tank 12VDC Model 6350 150 PSI Compressor with 3-Gallon Air Tank 12VDC IMPORTANT: It is essential that you and any other operator of this product read and understandd the contents of this manual before installing

More information

Your safety and the safety of others are very important.

Your safety and the safety of others are very important. NATURAL GAS TO PROPANE CONVERSION KIT ALPKT57- INSTALLATION INSTRUCTIONS PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements... Table of Contents INSTALLATION

More information

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Installation Instructions Issue Date August 19, 2008 G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Application The G196 valves are suitable for use with natural gas, Liquefied

More information

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Installation Instructions Issue Date March 13, 2013 G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Application The G196 valves are suitable for use with natural gas, Liquefied

More information

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL USER S INFORMATION MANUAL UPFLOW, DOWNFLOW, UPFLOW/HORIZONTAL & HORIZONTAL ONLY INDUCED DRAFT GAS FURNACES Recognize this symbol as an indication of Important Safety Information If the information in this

More information

AC1810 / AC1810-A TECHNICAL SPECIFICATIONS. Operating Pressure psi ( kgs/cm²) [AC1810] Displacement. Net Weight

AC1810 / AC1810-A TECHNICAL SPECIFICATIONS. Operating Pressure psi ( kgs/cm²) [AC1810] Displacement. Net Weight Technical Specifications Operating Instructions Maintenance Information Troubleshooting Guide Parts Diagrams AC1810 / AC1810-A THE EVOLUTION OF PERFECTION CAUTION: Before attempting to use or service this

More information

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER SUPPLIMENT TO eom IMPORTANT READ THIS MANUAL BEFORE PRODUCT INSTALLATION, OPERATION, INSPECTION & MAINTENANCE Tougher and more rigid guidelines are being established

More information

Operating Instructions for Cobra and Lynx Duct Leakage Testers

Operating Instructions for Cobra and Lynx Duct Leakage Testers Operating Instructions for Cobra and Lynx Duct Leakage Testers Table of Contents Introduction Introduction... 2 Safety Precautions Safety Precautions.. 2 Prior to Testing System Preparation.. 4 Power Requirements...

More information

INSTALLATION & OPERATION MANUAL FOR Stockpot Range

INSTALLATION & OPERATION MANUAL FOR Stockpot Range INSTALLATION & OPERATION MANUAL FOR Stockpot Range MODELS MLS VSP100 ML-052822 VSP200 ML-052823 VSP200F ML-769292 www.vulcanhart.com MODELS MLS WSPR1 ML-760600 WSPR2 ML-760601 WSPR2F ML-769292 www.wolfrange.com

More information

INSTALLATION & OPERATION MANUAL FOR Teppan-Yaki Griddles

INSTALLATION & OPERATION MANUAL FOR Teppan-Yaki Griddles INSTALLATION & OPERATION MANUAL FOR Teppan-Yaki Griddles MODELS MLS TYG48C ML-769368-Z1 TYG60C ML-766505-Z www.wolfrange.com TYG48C ITW Food Equipment Group, LLC An Illinois Tool Works Company 3600 North

More information

AIR CONDITIONERS WA14**W SERIES

AIR CONDITIONERS WA14**W SERIES FORM NO. A66-225 REV. 3 AIR CONDITIONERS Features Outdoor air conditioner designed for ground level or rooftop installations. These units offer comfort and dependability for single, multi-family and light

More information

TWC Services, Inc. Structured On-The-Job Training for JT- 1, 2, 3

TWC Services, Inc. Structured On-The-Job Training for JT- 1, 2, 3 TWC Services, Inc. Structured On-The-Job Training for JT- 1, 2, 3 The following tasks parallel the Jr. Tech (JT-1, 2, 3) description and development plan and use the Refrigeration and Air conditioning

More information

2 GALLON TWIN STACK AIR COMPRESSOR W/ HOSE REEL

2 GALLON TWIN STACK AIR COMPRESSOR W/ HOSE REEL 2 GALLON TWIN STACK AIR COMPRESSOR W/ HOSE REEL Model: 52024 CALIFORNIA PROPOSITION 65 WARNING: You can create dust when you cut, sand, drill or grind materials such as wood, paint, metal, concrete, cement,

More information

English. Introduction. Safety Instructions. All Products. Inspection and Maintenance Schedules. Parts Ordering. Specifications WARNING WARNING

English. Introduction. Safety Instructions. All Products. Inspection and Maintenance Schedules. Parts Ordering. Specifications WARNING WARNING Contents All Products... Gb-1 Control Valves... Gb-2 Control Valve Actuators... Gb-3 Regulators... Gb-3 Relief Valves... Gb-4 Instruments, Switches, and Accessories... Gb-4 Products Covered by Battery

More information

GAS FUEL VALVE FORM AGV5 OM 8-03

GAS FUEL VALVE FORM AGV5 OM 8-03 ALTRONIC AGV5 OPERATING MANUAL GAS FUEL VALVE FORM AGV5 OM 8-03 WARNING: DEVIATION FROM THESE INSTALLATION INSTRUCTIONS MAY LEAD TO IMPROPER ENGINE OPERATION WHICH COULD CAUSE PERSONAL INJURY TO OPERATORS

More information

SUMMITTM 400 & 600. Natural Gas Barbecues. Step-By-Step Guide

SUMMITTM 400 & 600. Natural Gas Barbecues. Step-By-Step Guide SUMMITTM 400 & 600 Natural Gas Barbecues Step-By-Step Guide W E B E R W E B E R W E B E R W E B E R Summit 400 NG Summit 600 NG CANADIAN GAS ASSOCIATION R A P P R O V E D WARNING: Follow all leak check

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! INLET PRESS TAP WHITE-RODGERS 36E93-304 Delay-Opening Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY

More information

VTL VFL VCL. Low Profile Series V RIGGING & ASSEMBLY INSTRUCTIONS

VTL VFL VCL. Low Profile Series V RIGGING & ASSEMBLY INSTRUCTIONS VTL VFL VCL Low Profile Series V RIGGING & ASSEMBLY INSTRUCTIONS Low Profile Series VL units should be rigged and installed as outlined in this bulletin. These procedures should be thoroughly reviewed

More information

36H SERIES Combination Gas Valve

36H SERIES Combination Gas Valve FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION The 36H series combination gas valve is

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS HIGH ALTITUDE APPLICATION CONVERSION INSTRUCTION HIGH EFFICIENCY GAS FURNACES 1PS0306 / 1PS0307 / 1PS0308 / 1PS0309 / 1PS0901 / 1PS0902 / 1PS0903 FOR USE WITH MODELS:

More information

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO 97C COMPRESSOR KIT 12V PART NO. 00097 97C COMPRESSOR KIT 24V PART NO. 02497 98C COMPRESSOR KIT PART NO. 00098 97C 98C IMPORTANT: It is essential that you and any other operator of this product read and

More information

Safety Powder Spray Systems

Safety Powder Spray Systems Instruction Sheet P/N 107 952C Safety Powder Spray Systems 1. Introduction This section contains general safety instructions for using your Nordson equipment. Task- and equipment-specific warnings are

More information

G96 Series BASOTROL Dual Operator Valve

G96 Series BASOTROL Dual Operator Valve Installation Instructions 9. Issue Date February 22, 2013 G96 Series BASOTROL Dual Operator Valve Applications The G96 valves are combination, dual operator, automatic valves available with or without

More information

The conversion of new certified central heating gas appliances must conform to directions outlined in this instruction.

The conversion of new certified central heating gas appliances must conform to directions outlined in this instruction. ACCESSORY KIT INSTALLATION INSTRUCTIONS HIGH ALTITUDE APPLICATION CONVERSION MID-EFFICIENCY SINGLE-STAGE INDUCED COMBUSTION FURNACES MODELS: P*HU/G8T-UH/L8T-UH/FL8 UPFLOW / HORIZONTAL P*DN/G8T-DN/L8T-DN

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS PROPANE CONVERSION - INDUCED COMBUSTION FURNACES 1NP0501 FOR USE WITH 95% MODELS: TG9S, GG9S (130,000 BTU ONLY) FOR USE WITH 80% MODELS: TG(8,L)S, GG(8,L)S (130,000

More information

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST OIL-LESS TYPE IMPORTANT: PLEASE READ CAREFULLY BEFORE STARTING OPERATIONS. THE CONTENTS ARE FOR GENERAL INFORMATION OF ALL THE SIMILAR MODELS. Record

More information

FXT. FXT Cooling Tower RIGGING & ASSEMBLY INSTRUCTIONS

FXT. FXT Cooling Tower RIGGING & ASSEMBLY INSTRUCTIONS FXT FXT Cooling Tower RIGGING & ASSEMBLY INSTRUCTIONS FXT Cooling Towers should be rigged and assembled as outlined in this bulletin. These procedures should be thoroughly reviewed prior to the actual

More information

Installation Instructions

Installation Instructions LP and High Altitude LP Gas Conversion Kit For United States Installations Installation Instructions For Model Series *G6/PGF1 Furnaces, *L1/PGC1 Furnaces, and *R4/PPG1 Gas/Electric Appliances using Honeywell

More information

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION

More information

Natural Gas to L.P. Gas Conversion Kit

Natural Gas to L.P. Gas Conversion Kit Natural Gas to L.P. Gas Conversion Kit For Bosch 96% AFUE Gas Furnace, BGH96 Model Installation Instructions 3124627 2 Natural Gas to L.P. Gas Conversion Kit Installation Instructions Data subject to change

More information

AIR CONDITIONERS WA14 SERIES

AIR CONDITIONERS WA14 SERIES FORM NO. A66-220 REV. 3 AIR CONDITIONERS Features Outdoor air conditioner designed for ground level or rooftop installations. These units offer comfort and dependability for single, multi-family and light

More information

User s Information Manual

User s Information Manual 48HC with EnergyX R System Factory Installed Energy Recovery Single---Package Rooftop Unit (RTU) Gas Heating/Electric Cooling Units 15 to 25 Nominal Tons with Puronr (R---410A) Refrigerant User s Information

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS Type 36C67 Combination (24 Volt Models) INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING

More information

36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS

36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS INLET PRESS TAP WHITE-RODGERS 36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS

More information

Dual Solenoid Gas Valve Installation

Dual Solenoid Gas Valve Installation Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing or servicing FLYNN Gas Products. Carefully follow all instructions in this bulletin and all instructions

More information

MEDICAL EQUIPMENT CATALOG

MEDICAL EQUIPMENT CATALOG THE MOST TRUSTED MEDICAL EQUIPMENT IN NORTH AMERICA MEDICAL EQUIPMENT CATALOG Total Components Including Bulk Oxygen Supply, Back up and Delivery Equipment Designs for High Pressure, Liquid or Bulk Applications

More information

AIR CONDITIONERS. Features. Manufactured for Fujitsu General America, Inc. Fairfield, NJ. FORM NO. AFJ-222 Supersedes Form No.

AIR CONDITIONERS. Features. Manufactured for Fujitsu General America, Inc. Fairfield, NJ. FORM NO. AFJ-222 Supersedes Form No. FORM NO. AFJ-222 Supersedes Form No. PTZ-789 AIR CONDITIONERS FO*16C SERIES Efficiencies up to 16 SEER/13 EER Nominal Sizes 1 1 /2 to 5 Ton [5.28 to 17.6 kw] Cooling Capacities 17.3 to 60.5 kbtu [5.7 to

More information

GM-7000 Series CE Approved Gas Control Valve

GM-7000 Series CE Approved Gas Control Valve Installation Instructions GM-7000 Issue Date November 9, 2012 GM-7000 Series CE Approved Gas Control Valve Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing

More information

VR8205S,T Direct Ignition Combination Gas Controls

VR8205S,T Direct Ignition Combination Gas Controls VR805S,T Direct Ignition Combination Gas Controls INSTALLATION INSTRUCTIONS APPLICATION TheVR805S,T Direct Ignition Combination Gas Controls are used in gas-fired appliances with up to 70 ft 3 /hr capacity

More information

444C DUAL PERFORMANCE VALUE PACK

444C DUAL PERFORMANCE VALUE PACK (Chrome) PART NO. 44432 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual before installing and using this product. SAVE THIS MANUAL

More information

AIR COMPRESSOR. Failure to follow all instructions as listed below may result in electrical shock, fire, and/or serious personal injury.

AIR COMPRESSOR. Failure to follow all instructions as listed below may result in electrical shock, fire, and/or serious personal injury. 2 GALLON AIR COMPRESSOR Model: 7517 DO NOT RETURN TO STORE. Please CALL 800-348-5004 for parts and service. CALIFORNIA PROPOSITION 65 WARNING: You can create dust when you cut, sand, drill or grind materials

More information

G92 Series BASOTROL Automatic Pilot Gas Valve

G92 Series BASOTROL Automatic Pilot Gas Valve Installation Instructions Issue Date September 17, 2008 G92 Series BASOTROL Automatic Pilot Gas Valve Installation IMPORTANT: Only qualified personnel should install or service BASO Gas Products. These

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS 36C53 Combination Gas Valves (24 Volt Model) INSTALLATI INSTRUCTIS Electrical Rating: Voltage: 24 Volts, (30 Volts Max.), 60 Hz. Current Rating: 0.23 Amps Type of Gas Natural Gas Pressure

More information

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289 3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS Item #31289 The EASTWOOD 3 GALLON, OILLESS PANCAKE COMPRESSOR, with an Integral Air Regulator, efficiently supplies all compressed air requirements for

More information

APCO ARV CLEAN WATER AIR RELEASE VALVES. Model 50A

APCO ARV CLEAN WATER AIR RELEASE VALVES. Model 50A APCO ARV CLEAN WATER AIR RELEASE VALVES Model 50A Instruction D12013 February 2017 Instructions These instructions provide installation, operation and maintenance information for APCO ARV Clean Water Air

More information

Installation and Operation Instructions

Installation and Operation Instructions Bentintoshape llc Installation and Operation Instructions Fire Pit - Hidden Tank Models www.bentintoshape.net INTRODUCTION Your bentintoshape Cor-Ten Steel Gas Fire Pit is designed for installation in

More information

Propane Conversion Kit Instruction

Propane Conversion Kit Instruction Propane Conversion Kit Instruction Condensing gas boiler Required Input Rates Logamax plus GB62-80 kw 270,000 btu/hr Logamax plus GB62-00 kw 35,000 btu/hr This kit and instructions are for converting the

More information

INSTRUCTION MANUAL MST AFTERCOOLER SYSTEM MODEL

INSTRUCTION MANUAL MST AFTERCOOLER SYSTEM MODEL INSTRUCTION MANUAL MST AFTERCOOLER SYSTEM MODEL 8059601 To be used with MST Model 8050501 Ambient Air Pump 7/12/05 2 TABLE OF CONTENTS GENERAL INFORMATION... 3 WARNING...4,5 UNPACKING AND AFTERCOOLER ASSEMBLY

More information

TABLE OF CONTENTS PART 2 - CONFINED SPACES

TABLE OF CONTENTS PART 2 - CONFINED SPACES May 11, 2006 TABLE OF CONTENTS PART 2 - CONFINED SPACES Page DEFINITIONS... 2-1 GENERAL... 2-2 RESPONSIBILITIES... 2-2 HAZARD ASSESSMENT AND WORK PROCEDURES... 2-3 IDENTIFICATION AND ENTRY PERMITS... 2-3

More information

FMU4X, FMC4X FMU4P, FMC4P

FMU4X, FMC4X FMU4P, FMC4P ENVIRONMENTALLY SOUND REFRIGERANT FMU4X, FMC4X FMU4P, FMC4P Product Specifications HORIZONTAL FAN COILS FMU4P and FMC4P 1 1/2, 2, 2 1/2, and 3 Tons FMU4X and FMC4X 1 1/2, 2 and 2 1/2 Tons ALL MODELS Horizontal

More information

MODEL NUMBER: PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank

MODEL NUMBER: PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank IMPORTANT SAFETY INSTRUCTIONS CAUTION - To reduce risk of electrical shock or Electrocution: MODEL NUMBER: 20008 200 PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank IMPORTANT: It is

More information

Aquavar SOLO 2 Frequently Asked Questions

Aquavar SOLO 2 Frequently Asked Questions Aquavar SOLO 2 Frequently Asked Questions How do I size the Aquavar SOLO 2 for the appropriate pump/motor combination? Can I use a 208 Volt motor? Can I run the Aquavar SOLO 2 up to 80HZ? What are the

More information

DEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers

DEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers g DEH 40050 Instructions Three-Phase, Platform-Mounted Distribution Transformers Introduction The equipment covered by these instructions should be operated and serviced only by competent technicians familiar

More information

INSTALLATION, OPERATION AND SERVICE MANUAL ABS AIR BAG LIFT

INSTALLATION, OPERATION AND SERVICE MANUAL ABS AIR BAG LIFT INSTALLATION, OPERATION AND SERVICE MANUAL ABS AIR BAG LIFT P.O. Box 1058 1058 West Industrial Avenue Guthrie, OK 73044-1058 405-282-5200 FAX: 405-282-8105 www.autoquip.com Item # 830ABS Version 1.0 07/2001

More information

Model 26.5 WEAU242AA WEAU244BA 29.0 WEAU242BA 29.0 WEAU304AA 33.0 WEAU302AA WEAU304BA 33.0 WEAU302BA 33.

Model 26.5 WEAU242AA WEAU244BA 29.0 WEAU242BA 29.0 WEAU304AA 33.0 WEAU302AA WEAU304BA 33.0 WEAU302BA 33. EVAPORATOR COILS A COIL UNCASED R 22 or R 410A SYSTEMS 1 5 Tons WEAU Certification applies only when the complete system is listed with ARI ISO 9001:2000 REGISTERED R 410A R 22 Size Shipping Weight Size

More information

WARNING: FOR OUTDOOR USE ONLY

WARNING: FOR OUTDOOR USE ONLY Certified to CSA International 4.96 US For Outdoor Gas Fireplaces A HIGHER STANDARD IN QUALITY AND APPEARANCE SAFE AND BEAUTIFUL OUTDOOR LARGO FIRE PIT FOR PROPANE AND *NATURAL GAS OWNER S MANUAL WARNING:

More information

Installation Instructions For Natural Gas Conversion

Installation Instructions For Natural Gas Conversion Installation Instructions For Natural Gas Conversion (Kit Part No. 1175405) This kit is designed to convert PGX4 and PX4 Two -Stage Gas units for use with Natural Gas. Table 1 Heating Value at Altitude

More information

MODEL NUMBER: M20005 AIR SOURCE KIT. 30% Duty Compressor on. 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE

MODEL NUMBER: M20005 AIR SOURCE KIT. 30% Duty Compressor on. 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE MODEL NUMBER: M20005 AIR SOURCE KIT 30% Duty Compressor on 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE USER MANUAL IMPORTANT SAFETY INSTRUCTIONS CAUTION - To reduce risk of electrical shock

More information

Installation Instructions WARNING: WARNING: WARNING: LP AND HIGH ALTITUDE LP GAS CONVERSION KIT FOR UNITED STATES INSTALLATIONS

Installation Instructions WARNING: WARNING: WARNING: LP AND HIGH ALTITUDE LP GAS CONVERSION KIT FOR UNITED STATES INSTALLATIONS LP AND HIGH ALTITUDE LP GAS CONVERSION KIT FOR UNITED STATES INSTALLATIONS Installation Instructions For Model Series *G7/*GC2 Furnaces and Appliances Using Honeywell Gas Valves. BEFORE THE CONVERSION

More information

OC Panel High Limit Aquastat Kit, Manual Reset p/n

OC Panel High Limit Aquastat Kit, Manual Reset p/n OC Panel High Limit Aquastat Kit, Manual Reset p/n 233202 Instruction Sheet APPLICATION The OC (Option Control) Panel High Limit Aquastat Kit provides electronic temperature sensing in a UL limit-rated

More information

Operator Manual Gas Griddle / Cheesemelter

Operator Manual Gas Griddle / Cheesemelter Operator Manual Gas Griddle / Cheesemelter HDB2031 & HDB2042 Model: HDB2042 Table of Contents Safety Information...2 Unpacking...3 Installation...3 Lighting Instructions...3 Preparing Griddle...4 Operation...4

More information

SPECIFICATIONS ATTENTION

SPECIFICATIONS ATTENTION VPS 504 S06 Installation Manual - P/N 80122 - Ed. 01/09 VPS 504 S06 and S05 Valve Proving System Installation Instructions VPS 1 6 Gases Natural gas, air and other inert gases. NOT suitable for butane

More information

200 PSI COMPRESSORS - MODEL NUMBERS

200 PSI COMPRESSORS - MODEL NUMBERS 200 PSI COMPRESSORS - MODEL NUMBERS 380C AIR COMPRESSOR KIT PART NO. 38033 480C AIR COMPRESSOR KIT PART NO. 48043 380C 480C IMPORTANT: It is essential that you and any other operator of this product read

More information

Misaligned Folds Paper Feed Problems Double Feeds Won t Feed FLYER Won t Run iii

Misaligned Folds Paper Feed Problems Double Feeds Won t Feed FLYER Won t Run iii Operator s Manual Table of Contents Operator Safety... 1 Introduction... 2 Unpacking and Setup... 3 Unpacking... 3 Setup... 4 FLYER Overview... 5 FLYER Diagram... 5 Capabilities... 5 Control Panel... 6

More information

100C Air Compressor Kit

100C Air Compressor Kit 10010 100C Air Compressor (standard mounting bracket, CE Spec) 10014 100C Air Compressor (no leader hose or check valve, CE Spec) 10016 100C Air Compressor (with Omega Bracket, CE Spec) IMPORTANT: It is

More information

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator. RS(H)10,15 USER MANUAL Read the complete manual before installing and using the regulator. WARNING INCORRECT OR IMPROPER USE OF THIS PRODUCT CAN CAUSE SERIOUS PERSONAL INJURY AND PROPERTY DAMAGE. Due to

More information

S Surge Arresters

S Surge Arresters Surge Arresters UltraSIL Polymer-Housed VariSTAR Type US, UH, and UX Station-Class Surge Arresters Installation and Maintenance Instructions Service Information S235-88-1 Contents Product Information...........................1

More information

IMPORTANT SAFETY INSTRUCTIONS

IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS CAUTION - To reduce risk of electrical shock: - Do not disassemble. Do not attempt repairs or modifications. Refer to qualified service agencies for all service and repairs.

More information

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series Introduction Powerex manifolds are cleaned, tested and prepared for the indicated gas service and are built in accordance with the Compressed Gas Association guidelines. The manifold consists of a regulator

More information

400C & 450C DUAL PERFORMANCE VALUE PACKS

400C & 450C DUAL PERFORMANCE VALUE PACKS (Chrome) PART NO. 40013 (Silver) PART NO. 45012 (Chrome) PART NO. 45013 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual before

More information

High-Pressure Boiler Inspection Procedures: A Complete Checklist

High-Pressure Boiler Inspection Procedures: A Complete Checklist High-Pressure Boiler Inspection Procedures: A Complete Checklist Inspecting high-pressure boilers is a complex process requiring preparation, planning, and a multitude of safety precautions. Regular inspections

More information

BGA158 Series CE Approved Class A Shutoff Gas Valve

BGA158 Series CE Approved Class A Shutoff Gas Valve Installation Instructions BGA158 Issue Date August 24, 2011 BGA158 Series CE Approved Class A Shutoff Gas Valve Applications The BGA158 Series shutoff gas valve is an electrically operated gas valve that

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CTROL COULD CAUSE PERSAL INJURY AND/OR PROPERTY DAMAGE.

More information

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Models: EPS Single Pump EPT Twin Pump EPS-HP EPT-HP Single Pump High Pressure Twin Pump High Pressure

More information

200 PSI FAST-FILL AIR SOURCE KIT

200 PSI FAST-FILL AIR SOURCE KIT 200 PSI FAST-FILL AIR SOURCE KIT 55% Duty Compressor on 2.0 Gallon Air Tank PART NO. 20007 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of

More information

Budget Range Operators Handbook

Budget Range Operators Handbook Budget Range Operators Handbook BAMBI AIR COMPRESSORS LTD 152 Thimble Mill Lane Heartlands Birmingham B7 5HT United Kingdom Tel: 0121 322 2299 Fax: 0121 322 2297 Email: sales@bambi-air.co.uk www.bambi-air.co.uk

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! Pilot Gas Outlet: Located at outlet end of the valve Type of Gas Suitable for all domestic heating gases Pressure Rating: 1/2 lb. per sq. in. Pressure Regulator Adjust Range (Typical, See Control Label):

More information

AE R8 December 2004 Reformatted November Copelametic Two-Stage Compressors Application and Service Instructions

AE R8 December 2004 Reformatted November Copelametic Two-Stage Compressors Application and Service Instructions AE19-1132 R8 December 2004 Reformatted November 2010 Copelametic Two-Stage Compressors Application and Service Instructions The Copeland two stage compressors have been developed to efficiently achieve

More information

Vision Painting Inc Safety Management System

Vision Painting Inc Safety Management System Abrasive Blasting 1. PURPOSE The purpose of this program is to provide training and qualification guidelines for the safe operation of Abrasive Blasting. The Safety Officer is responsible for facilitating

More information

GAS SUPPLY DESIGN GUIDE

GAS SUPPLY DESIGN GUIDE GAS SUPPLY DESIGN GUIDE Natural Gas, Propane Gas, or Dual Fuel Fired Modulating, Condensing Boilers BENCHMARK Series Gas-Fired Boilers For models: BMK750 to BMK6000 Last Update: 06/20/2014 PR1 06/20/14

More information

AIR CONDITIONERS. Features. Manufactured for Fujitsu General America, Inc. Fairfield, NJ. FORM NO. AFJ-221 Supersedes Form No.

AIR CONDITIONERS. Features. Manufactured for Fujitsu General America, Inc. Fairfield, NJ. FORM NO. AFJ-221 Supersedes Form No. FORM NO. AFJ-221 Supersedes Form No. PTZ-789 AIR CONDITIONERS FO*13C SERIES Efficiencies 13-15.5 SEER/11.5-13 EER Nominal Sizes 1 1 /2 to 5 Ton [5.28 to 17.6 kw] Cooling Capacities 17.3 to 60.5 kbtu [5.7

More information

Propane Conversion Kit Instructions

Propane Conversion Kit Instructions 604 8 0/ US/CA For heating engineers Propane Conversion Kit Instructions Logano G4 X gas-fired boiler This conversion kit and the accompanying instructions are for conversion of G4 X gas-fired boilers

More information