1 Overview. Pressure Measurement Transmitters for general requirements. SITRANS P DS III - Technical description

Size: px
Start display at page:

Download "1 Overview. Pressure Measurement Transmitters for general requirements. SITRANS P DS III - Technical description"

Transcription

1 Siemens AG 204 SITRANS P DS III - Technical description Overview SITRANS P DS III pressure transmitters are digital pressure transmitters featuring extensive user-friendliness and high accuracy. The parameterization is performed using control keys or via HART, PROFIBUS-PA or FOUNDATION Fieldbus interface. Extensive functionality enables the pressure transmitter to be precisely adapted to the plant s requirements. Operation is very simple in spite of the numerous setting options. Transmitters with type of protection "Intrinsic safety" and "Explosion-proof" may be installed within potentially explosive atmospheres (zone ) or in zone 0. The transmitters are provided with an EC type examination certificate and comply with the corresponding harmonized European standards (ATEX). The transmitters can be equipped with various designs of remote seals for special applications such as the measurement of highly viscous substances. Various versions of the DS III pressure transmitters are available for measuring: Gauge pressure Absolute pressure Differential pressure Level Volume level Mass level Volume flow Mass flow Benefits High quality and service life High reliability even under extreme chemical and mechanical loads For aggressive and non-aggressive gases, vapors and liquids Extensive diagnosis and simulation functions Separate replacement of measuring cell and electronics without recalibration Minimum conformity error Good long-term stability Wetted parts made of high-grade materials (e.g. stainless steel, Hastelloy, gold, Monel, tantalum) Infinitely adjustable span from 0.0 bar to 700 bar (0.5 psi to 05 psi) for DS III with HART interface Nominal measuring range from bar to 700 bar (4.5 psi to 05 psi) for DS III with PROFIBUS PA and FOUNDATION Fieldbus interface High measuring accuracy Parameterization over control keys and HART or PROFIBUS PA, or FOUNDATION Fieldbus interface. Application The pressure transmitters of the DS III series, can be used in industrial areas with extreme chemical and mechanical loads. Electromagnetic compatibility in the range 0 khz to GHz makes the DS III pressure transmitters suitable for locations with high electromagnetic emissions. Pressure transmitters with type of protection "Intrinsic safety" and "Explosion-proof" may be installed within potentially explosive atmospheres (zone ) or in zone 0. The pressure transmitters are provided with an EC type examination certificate and comply with the corresponding harmonized European standards (ATEX). Pressure transmitters with the type of protection "Intrinsic safety" for use in zone 0 may be operated with power supply units of category "ia" and "ib". The transmitters can be equipped with various designs of remote seals for special applications such as the measurement of highly viscous substances. The pressure transmitter can be programmed locally using the control buttons or externally via HART or PROFIBUS PA or FOUNDATION Fieldbus interface. /90 Siemens FI 0 205

2 Siemens AG 204 SITRANS P DS III - Technical description Pressure transmitter for gauge pressure Design Measured variable: Gauge pressure of aggressive and non-aggressive gases, vapors and liquids. Span (infinitely adjustable) for DS III with HART: 0.0 bar to 700 bar (0.5 psi to 05 psi) Nominal measuring range for DS III with PROFIBUS PA and FOUNDATION Fieldbus: 2 bar to 700 bar (4.5 psi to 05 psi) Pressure transmitters for absolute pressure Measured variable: Absolute pressure of aggressive and nonaggressive gases, vapors and liquids. 8 Span (infinitely adjustable) Plastic cover as access to for DS III with HART: 8. mbar a bar a ( psia) the input keys 2 Screw cover with Nominal measuring range viewing pane for DS III with PROFIBUS PA and FOUNDATION Fieldbus: Digital display 250 mbar a bar a ( psia) 4 Locking screw 7 There are two series: 5 Process connection Gauge pressure series 6 Screw cover with viewing pane 6 Differential pressure series 7 Rating plate Pressure transmitters for differential pressure and flow Measured variables: Differential pressure Small positive or negative pressure 8 Inlet with cable gland 5 Front view 4 Flow q ~ p (together with a primary differential pressure device (see Chapter "Flow Meters")) the order. The possible versions are listed in the ordering infor- The transmitter consists of various components depending on mation. The components described below are the same for all Span (infinitely adjustable) transmitters. for DS III with HART: mbar... 0 bar ( psi) The rating plate (7, Figure "Front view") with the Article No. is located Nominal measuring range on the side of the housing. The specified number together with the for DS III with PROFIBUS PA and FOUNDATION Fieldbus: ordering information provide details on the optional design details 20 mbar... 0 bar ( psi) and on the possible measuring range (physical properties of built-in Pressure transmitters for level Measured variable: Level of aggressive and non-aggressive liquids in open and closed vessels. sensor element). The approval label is located on the opposite side. The housing is made of die-cast aluminium or stainless steel precision casting. A round cover (6) is screwed on at the front and Span (infinitely adjustable) rear of the housing. The front cover can be fitted with a viewing for DS III with HART: 25 mbar... 5 bar ( psi) pane so that the measured values can be read directly on the Nominal measuring range for DS III with PROFIBUS PA and FOUNDATION Fieldbus: 250 mbar... 5 bar ( psi) Nominal diameter of the mounting flange display. The inlet (8) for the electrical connection is located either on the left or right side. The unused opening on the opposite side is sealed by a blanking plug. The protective earth connection is located on the rear of the housing. DN 80 or DN 00 The electrical connections for the power supply and screen are accessible by unscrewing the rear cover. The bottom part of the inch or 4 inch housing contains the measuring cell with process connection In the case of level measurements in open containers, the lowpressure connection of the measuring cell remains open (mea- screw (4). As the result of this modular design, the measuring (5). The measuring cell is prevented from rotating by a locking surement "compared to atmospheric"). cell and the electronics can be replaced separately from each other. The set parameter data are retained. In the case of measurements in closed containers, the lowerpressure connection has to be connected to the container in order to compensate the static pressure. input keys. At the top of the housing is a plastic cover (), which hides the The wetted parts are made from a variety of materials, depending Example for an attached measuring point label on the degree of corrosion resistance required. Y0 or Y02 = max. 27 char. Y5 = max. 6 char. Y99 = max. 0 char. Y6 = max. 27 char.... to... mbar Measuring point number (TAG No.) 24 Measuring point text Siemens FI /9

3 Siemens AG 204 SITRANS P DS III - Technical description Function Operation of electronics with HART communication Operation of electronics with PROFIBUS PA communication 8 M M Sensor 6 EEPROM 4 μc 5 7 HART interface EEPROM 6 Electronics 0 I A, U H PA μc interface Sensor EEPROM 6 EEPROM 6 Electronics PROFIBUS-PA Power supply 0 Power supply unit Coupler 2 PROFIBUS DP Bus- Master p e Measuring cell Measuring cell sensor 2 Instrument amplifier Analog-to-digital converter 4 Microcontroller 5 Digital-to-analog converter 6 One non-volatile memory each in the measuring cell and electronics 7 HART interface 8 Three input keys (local operation) 9 Digital display 0 Diode circuit and connection for external ammeter I A Output current U H Power supply P e Input variable Function diagram of electronics The bridge output voltage created by the sensor (, Figure "Function diagram of the electronics") is amplified by the measuring amplifier (2) and digitized in the analog-to-digital converter (). The digital information is evaluated in a microcontroller, its linearity and temperature response corrected, and converted in a digital-to-analog converter (5) into an output current of 4 to 20 ma. The diode circuit (0) protects against incorrect polarity. The data specific to the measuring cell, the electronics data, and the parameter data are stored in the two non-volatile memories (6). The one memory is coupled to the measuring cell, the other to the electronics. As the result of this modular design, the electronics and the measuring cell can be replaced separately from each other. Using the input keys (8) you can parameterize the pressure transmitter directly at the measuring point. The input buttons can also be used to control the view of the results, the error messages and the operating modes on the display (9). The HART modem (7) permits parameterization using a protocol according to the HART specification. The pressure transmitters with spans 6 bar measure the input pressure compared to atmosphere, transmitters with spans 60 bar compared to vacuum. p e Measuring cell Measuring cell sensor 2 Instrument amplifier Analog-to-digital converter 4 Microcontroller 5 Electrical isolation 6 One non-volatile memory each in the measuring cell and electronics 7 PROFIBUS-PA interface 8 Three input keys (local operation) 9 Digital display 0 Power supply DP/PA coupler or link 2 Bus master Function diagram of electronics The bridge output voltage created by the sensor (, Figure "Function diagram of the electronics") is amplified by the measuring amplifier (2) and digitized in the analog-to-digital converter (). The digital information is evaluated in the microcontroller, its linearity and temperature response corrected, and provided on the PROFIBUS PA through an electrically isolated PA interface (7). The data specific to the measuring cell, the electronics data, and the parameter data are stored in the two non-volatile memories (6). The one memory is coupled to the measuring cell, the other to the electronics. As the result of this modular design, the electronics and the measuring cell can be replaced separately from each other. Using the three input buttons (8) you can parameterize the pressure transmitter directly at the measuring point. The input buttons can also be used to control the view of the results, the error messages and the operating modes on the display (9). The results with status values and diagnostic values are transferred by cyclic data transmission on the PROFIBUS PA. Parameterization data and error messages are transferred by acyclic data transmission. Special software such as SIMATIC PDM is required for this. p e Input variable /92 Siemens FI 0 205

4 Siemens AG 204 Operation of electronics with FOUNDATION Fieldbus communication SITRANS P DS III - Technical description Mode of operation of the measuring cells Measuring cell for gauge pressure 8 M FF μc interface EEPROM 6 Electronics Foundation Fieldbus Power supply 0 Power supply unit Coupler Measuring cell 2 Process connection Seal diaphragm 4 Filling liquid 5 Silicon pressure sensor Pressure as input variable p e Sensor p e EEPROM 6 Measuring cell Measuring cell sensor 2 Instrument amplifier Analog-to-digital converter 4 Microcontroller 5 Electrical isolation 6 One non-volatile memory each in the measuring cell and electronics 7 FF interface 8 Three input keys (local operation) 9 Digital display 0 Power supply p e Input variable p e Measuring cell for gauge pressure, function diagram The pressure p e is applied through the process connection (2, Figure "Measuring cell for gauge pressure, function diagram) to the measuring cell (). This pressure is subsequently transmitted further through the seal diaphragm () and the filling liquid (4) to the silicon pressure sensor (5) whose measuring diaphragm is then flexed. This changes the resistance of the four piezo-resistors fitted in the diaphragm in a bridge circuit. This change in resistance results in a bridge output voltage proportional to the absolute pressure. Measuring cell for gauge pressure with front-flush diaphragm Function diagram of electronics The bridge output voltage created by the sensor (, Figure "Function diagram of electronics") is amplified by the measuring amplifier (2) and digitized in the analog-to-digital converter (). The digital information is evaluated in the microcontroller, its linearity and temperature response corrected, and provided on the FOUNDATION Fieldbus through an electrically isolated FOUNDATION Fieldbus interface (7). The data specific to the measuring cell, the electronics data, and the parameter data are stored in the two non-volatile memories (6). The one memory is coupled to the measuring cell, the other to the electronics. As the result of this modular design, the electronics and the measuring cell can be replaced separately from each other. Using the three input buttons (8) you can parameterize the pressure transmitter directly at the measuring point. The input buttons can also be used to control the view of the results, the error messages and the operating modes on the display (9). The results with status values and diagnostic values are transferred by cyclic data transmission on the FOUNDATION Fieldbus. Parameterization data and error messages are transferred by acyclic data transmission. Special software such as National Instruments Configurator is required for this. 5 4 p e 2 Measuring cell 2 Process connection Seal diaphragm 4 Filling liquid 5 Silicon pressure sensor Pressure as input variable Measuring cell for gauge pressure, with front-flush diaphragm for paper industry, function diagram The pressure p e is applied through the process connection (2, Figure "Measuring cell for gauge pressure, with front-flush diaphragm for paper industry, function diagram") to the measuring cell (). This pressure is subsequently transmitted further through the seal diaphragm () and the filling liquid (4) to the silicon pressure sensor (5) whose measuring diaphragm is then flexed. This changes the resistance of the four piezo-resistors fitted in the diaphragm in a bridge circuit. This change in resistance results in a bridge output voltage proportional to the absolute pressure. p e Siemens FI /9

5 Siemens AG 204 SITRANS P DS III - Technical description Measuring cell for absolute pressure from gauge pressure series Measuring cell for differential pressure and flow 5 4 p e 2 Measuring cell 2 Process connection Seal diaphragm 4 Filling liquid 5 Silicon absolute pressure sensor p e Absolute pressure as input variable Measuring cell for absolute pressure from the pressure series, function diagram The absolute pressure p e is transmitted through the seal diaphragm (, Figure "Measuring cell for absolute pressure from pressure series, gauge pressure, function diagram ") and the filling liquid (4) to the silicon absolute pressure sensor (5) whose measuring diaphragm is then flexed. This changes the resistance of the four piezo-resistors fitted in the diaphragm in a bridge circuit. This change in resistance results in a bridge output voltage proportional to the absolute pressure. Measuring cell for absolute pressure from differential pressure series Seal diaphragm 2 O-ring Overload diaphragm 4 Silicon pressure sensor 5 Process flange 6 Body of measuring cell 7 Filling liquid Measuring cell for differential pressure and flow, function diagram The differential pressure is transmitted through the seal diaphragms (, Figure "Measuring cell for differential pressure and flow, function diagram") and the filling liquid (7) to the silicon pressure sensor (4). The measuring diaphragm is flexed by the applied differential pressure. This changes the resistance of the four piezo-resistors fitted in the diaphragm in a bridge circuit. This change in resistance results in a bridge output voltage proportional to the absolute pressure. An overload diaphragm is installed to provide protection from overloads. If the measuring limits are exceeded, the overload diaphragm () is flexed until the seal diaphragm rests on the body of the measuring cell (6), thus protecting the silicon pressure sensor from overloads. Measuring cell for level p e 6 Reference vacuum 2 Overload diaphragm Silicon pressure sensor 4 O-ring 5 Process flange 6 Seal diaphragm 7 Body of measuring cell 8 Filling liquid p e Absolute pressure as input variable Measuring cell for absolute pressure from differential pressure series, function diagram The input pressure p e is transmitted through the seal diaphragm (6, Figure "Measuring cell for absolute pressure from differential pressure series, function diagram") and the filling liquid (8) to the silicon pressure sensor (). The difference in pressure between the input pressure p e and the reference vacuum () on the low-pressure side of the measuring cell flexes the measuring diaphragm. This changes the resistance of the four piezo-resistors fitted in the diaphragm in a bridge circuit. This change in resistance results in a bridge output voltage proportional to the absolute pressure. An overload diaphragm is installed to provide protection from overloads. If the measuring limits are exceeded, the overload diaphragm (2) is flexed until the seal diaphragm rests on the body of the measuring cell (7), thus protecting the silicon pressure sensor from overloads. Flange with tube 2 Seal diaphragm on mounting flange Seal diaphragm 4 Body of measuring cell 5 Overload diaphragm 6 Silicon pressure sensor 7 O-ring 8 Process flange 9 Filling liquid 0 Capillary with filling liquid of mounting flange Measuring cell for level, function diagram The input pressure (hydrostatic pressure) acts hydraulically on the measuring cell through the seal diaphragm on the mounting flange (2, Figure "Measuring cell for level, function diagram"). This differential pressure is subsequently transmitted further through the measuring cell () and the filling liquid (9) to the silicon pressure sensor (6) whose measuring diaphragm is then flexed. This changes the resistance of the four piezo-resistors fitted in the diaphragm in a bridge circuit. This change in resistance results in a bridge output voltage proportional to the differential pressure. An overload diaphragm is installed to provide protection from overloads. If the measuring limits are exceeded, the overload diaphragm (5) is flexed until the seal diaphragm rests on the body of the measuring cell (4), thus protecting the silicon pressure sensor from overloads. /94 Siemens FI 0 205

6 Siemens AG 204 Parameterization DS III Depending on the version, there are a range of options for parameterizing the pressure transmitter and for setting or scanning the parameters. Parameterization using the input buttons (local operation) With the input buttons you can easily set the most important parameters without any additional equipment. Parameterization using HART Parameterization using HART is performed with a HART Communicator or a PC. SITRANS P transmitter Communication between a HART Communicator and a pressure transmitter When parameterizing with the HART Communicator, the connection is made directly to the 2-wire cable. SITRANS P transmitter HART communication between a PC communicator and a pressure transmitter When parameterizing with a PC, the connection is made through a HART modem. The signals needed for communication in conformity with the HART 5.x or 6.x protocols are superimposed on the output current using the Frequency Shift Keying (FSK) method. Adjustable parameters, DS III with HART Parameters HART communicator HART modem Ω PC or laptop USB/RS Ω Input keys (DS III HART) Start of scale x x Full-scale value x x Electrical damping x x Start-of-scale value without application x x of a pressure ("Blind setting") Full-scale value without application x x of a pressure ("Blind setting") Zero adjustment x x current transmitter x x Fault current x x Disabling of buttons, write protection x x ) Type of dimension and actual x x dimension Characteristic (linear / squarerooted) x 2) x 2) Input of characteristic x Freely-programmable LCD x Diagnostic functions x ) Cancel apart from write protection 2) Only differential pressure + Power supply + - Power supply HART communication SITRANS P DS III - Technical description Diagnostic functions for DS III with HART Zero correction display Event counter Limit transmitter Saturation alarm Slave pointer Simulation functions Maintenance timer Available physical units of display for DS III with HART Table style: Technical specifications 2 Physical variable Physical dimensions Pressure (setting can also be made in the factory) Pa, MPa, kpa, bar, mbar, torr, atm, psi, g/cm 2, kg/cm 2, inh 2 O, inh 2 O (4 C), mmh 2 O, fth 2 O (20 C), inhg, mmhg Level (height data) m, cm, mm, ft, in Volume m, dm, hl, yd, ft, in, US gallon, lmp. gallon, bushel, barrel, barrel liquid Mass g, kg, t, lb, Ston, Lton, oz volume flow m /d, m /h, m /s, l/min, l/s, ft /d, ft /min, ft /s, US gallon/min, US gallon/s Mass flow t/d, t/h, t/min, kg/d, kg/h, kg/min, kg/s, g/d, g/h, g/min, g/s, lb/d, lb/h, lb/min, lb/s, LTon/d, LTon/h, STon/d, STon/h, STon/min Temperature K, C, F, R Miscellaneous %, ma Parameterization through PROFIBUS PA interface Fully digital communication through PROFIBUS PA, profile.0, is particularly user-friendly. Through the PROFIBUS the DS III with PROFIBUS PA is connected to a process control system, e. g. SIMATIC PSC 7. Communication is possible even in a potentially explosive environment. For parameterization through PROFIBUS you need suitable software, e.g. SIMATIC PDM (Process Device Manager). Parameterization through FOUNDATION Fieldbus interface Fully digital communication through FOUNDATION Fieldbus is particularly user-friendly. Through the FOUNDATION Fieldbus the DS III with FOUNDATION Fieldbus is connected to a process control system. Communication is possible even in a potentially explosive environment. For parameterization through the FOUNDATION Fieldbus you need suitable software, e.g. National Instruments Configurator. Adjustable parameters for DS III with PROFIBUS PA and FOUNDATION Fieldbus Parameters Input keys Electrical damping x x Zero adjustment (correction of position) x x Buttons and/or function disabling x x Source of measured-value display x x Physical dimension of display x x Position of decimal point x x Bus address x x Adjustment of characteristic x x Input of characteristic x Freely-programmable LCD x Diagnostics functions x PROFIBUS PA and FOUNDATION Fieldbus interface Siemens FI /95

7 Siemens AG 204 SITRANS P DS III - Technical description Diagnostic functions for DS III with PROFIBUS PA and FOUNDATION Fieldbus Event counter Slave pointer Maintenance timer Simulation functions Display of zero correction Limit transmitter Saturation alarm Physical dimensions available for the display Physical variable Physical dimensions Pressure (setting can also be made in the factory) Level (height data) Volume MPa, kpa, Pa, bar, mbar, torr, atm, psi, g/cm 2, kg/cm 2, mmh 2 O, mmh 2 O (4 C), inh 2 O, inh 2 0 (4 C), fth 2 O (20 C), mmhg, inhg m, cm, mm, ft, in, yd m, dm, hl, yd, ft, in, US gallon, lmp. gallon, bushel, barrel, barrel liquid volume flow m /s, m /min, m /h, m /d, l/s, l/min, l/h, l/ d, Ml/d, ft /s, ft /min, ft /h, ft /d, US gallon/s, US gallon/min, US gallon/h, US gallon/d, bbl/s, bbl/min, bbl/h, bbl/d Mass flow g/s, g/min, g/h, g/d, kg/s, kg/min, kg/h, kg/d, t/s, t/min, t/h, /t/d, lb/s, lb/min, lb/h, lb/d, STon/s, STon/min, STon/h, STon/d, LTon/s, LTon/min, LTon/h, LTon/d Total mass flow t, kg, g, lb, oz, LTon, STon Temperature K, C, F, R Miscellaneous % /96 Siemens FI 0 205

8 Siemens AG 204 Technical specifications SITRANS P, DS III series for gauge pressure Input Measured variable Spans (infinitely adjustable) or nominal measuring range and max. permissible test pressure HART Span (min.... max.) bar ( psi) bar ( psi) bar ( psi) bar ( psi) bar ( psi) bar ( psi) bar ( psi) Max. perm. test pressure 6 bar (87 psi) 0 bar (45 psi) 2 bar (464 psi) 00 bar (450 psi) 250 bar (626 psi) 600 bar (8700 psi) 800 bar (60 psi) Gauge pressure SITRANS P DS III for gauge pressure PROFIBUS PA and FOUNDATION Fieldbus Nominal measuring range bar (4.5 psi) 4 bar (58 psi) 6 bar (22 psi) 6 bar (94 psi) 60 bar (220 psi) 400 bar (5802 psi) 700 bar (05 psi) Max. perm. test pressure 6 bar (87 psi) 0 bar (45 psi) 2 bar (464 psi) 00 bar (450 psi) 250 bar (626 psi) 600 bar (8700 psi) 800 bar (60 psi) Lower measuring limit Measuring cell with silicone oil filling 0 mbar a (0.44 psia) Measuring cell with inert filling liquid 0 mbar a (0.44 psia) Upper measuring limit 00 % of max. span (for oxygen version and inert filling liquid; max. 20 bar (740 psi)) Output Output signal ma Digital PROFIBUS PA and FOUNDATION Fieldbus signal Lower limit (infinitely adjustable).55 ma, factory preset to.84 ma - Upper limit (infinitely adjustable) 2 ma, factory preset to 20.5 ma or optionally - set to 22.0 ma Load Without HART R B (U H V)/0.02 A in, - U H : Power supply in V With HART R B = (SIMATIC PDM) or - R B = (HART Communicator) Physical bus - IEC Protection against polarity reversal Protected against short-circuit and polarity reversal. Each connection against the other with max. supply voltage. Electrical damping (step width 0. s) Set to 2 s ( s) Measuring accuracy Acc. to IEC Reference conditions (All error data refer always refer to the set span) Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, silicone oil filling, room temperature 25 C (77 F) Span ratio r = max. span/set span Nominal measuring range ratio r = nominal measuring range/set measuring range Error in measurement at limit setting incl. hysteresis and reproducibility Linear characteristic -r 0 ( r ) % ( r+0.07)% - 0 < r 0 ( r ) % ( r+0.07)% -0<r 00 (0.005 r ) % (0.005 r+0.05)% Long-term stability (temp.erature change 0 C ( 54 F))... 4-bar measuring cell (0.25 r) % per 5 years (0.25 r) % per 5 years bar measuring cell (0.25 r) % per 5 years (0.25 r) % per 5 years Influence of ambient temperature at C ( F) (0.08 r+0.) % ) (at 700 bar: (0. r + 0.2) % 2) (0.08 r + 0.) % (at 700 bar: (0. r + 0.2) % 2) at C and C (0. r+0.5)%/0k (0. r + 0.5) %/0 K ( F and F) Measured Value Resolution of nominal measuring range Siemens FI /97

9 Siemens AG 204 SITRANS P DS III for gauge pressure SITRANS P, DS III series for gauge pressure HART PROFIBUS PA and FOUNDATION Fieldbus Rated conditions Degree of protection (to EN 60529) IP66 (optional IP66/IP68), NEMA 4X Temperature of medium Measuring cell with silicone oil filling C ( F) Measuring cell with inert filling liquid C ( F) In conjunction with dust explosion protection C ( F) Ambient conditions Ambient temperature - Transmitter C ( F) (with 4-wire connection, observe temperature values of supplementary 4-wire electronics) - Display readable C ( F) Storage temperature C ( F) Climatic class - Condensation Relative humidity % Condensation permissible, suitable for use in the tropics Electromagnetic Compatibility - Emitted interference and interference Acc. to IEC 626 and NAMUR NE 2 immunity Design Weight (without options) Die-cast aluminum: 2.0 kg ( 4.4 lb) Stainless steel precision casting: 4.6 kg ( 0. lb) Enclosure material Low-copper die-cast aluminum, GD-AlSi 2 or stainless steel precision casting, mat. no Wetted parts materials Connection shank Stainless steel, mat. no..4404/6l or Hastelloy C4, mat. no Oval flange Stainless steel, mat. no..4404/6l Seal diaphragm Stainless steel, mat. no..4404/6l or Hastelloy C276, mat. no Measuring cell filling Silicone oil or inert filling liquid (maximum value with oxygen measurement pressure 00 bar (450 psi) at 60 C (40 F)) Process connection Connection shank G½B to DIN EN 87-, female thread ½ -4 NPT or oval flange (PN 60 (MAWP 220 psi)) to DIN 92 with mounting thread M0 or 7 / 6-20 UNF to EN 658 Material of mounting bracket Steel Sheet-steel, Mat. No..00, chrome-plated Stainless steel Sheet stainless steel, mat. no..40 (SS 04) Power supply U H Supplied through bus Terminal voltage on transmitter V DC V DC in intrinsically-safe mode Separate 24 V power supply necessary - No Bus voltage Not Ex V With intrinsically-safe operation V Current consumption Basic current (max.) ma Start-up current basic current - Yes Max. current in event of fault ma Fault disconnection electronics (FDE) available - Yes /98 Siemens FI 0 205

10 Siemens AG 204 SITRANS P, DS III series for gauge pressure Certificates and approvals HART SITRANS P DS III for gauge pressure PROFIBUS PA and FOUNDATION Fieldbus Classification according to PED 97/2/EC For gases of fluid group and liquids of fluid group ; complies with requirements of article, paragraph (sound engineering practice) Explosion protection Intrinsic safety "i" PTB ATEX 2007 X - Marking Ex II /2 G Ex ia/ib IIC T4/T5/T6 Ga/Gb - Permissible ambient temperature C ( F) temperature class T4; C ( F) temperature class T5; C ( F) temperature class T6 - Connection To certified intrinsically-safe circuits with peak values: U i = 0 V, I i = 00 ma, P i = 750 mw; R i =00 FISCO supply unit: U o = 7.5 V, I o = 80 ma, P o = 5.2 W Linear barrier: U o = 24 V, I o = 74 ma, P o = W - Effective internal inductance/capacitance L i = 0.4 mh, C i = 6 nf L i = 7 H, C i =. nf Explosion-proof "d" PTB 99 ATEX 60 - Marking Ex II /2 G Ex d IIC T4/T6 Gb - Permissible ambient temperature C ( F) temperature class T4; C ( F) temperature class T6 - Connection To circuits with values: U H = V DC To circuits with values: U H = V DC Dust explosion protection for zone 20 PTB 0 ATEX Marking Ex II D IP65 T 20 C Ex II /2 D IP65 T 20 C - Permissible ambient temperature C ( F) - Max. surface temperature 20 C (248 F) - Connection To certified intrinsically-safe circuits with peak values: U i = 0 V, I i = 00 ma, P i = 750 mw, R i = 00 FISCO supply unit: U o = 7.5 V, I o = 80 ma, P o = 5.2 W Linear barrier: U o = 24 V, I o = 250 ma, P o = W - Effective internal inductance/capacitance L i = 0.4 mh, C i = 6 nf L i = 7 H, C i =. nf Dust explosion protection for zone 2/22 PTB 0 ATEX Marking Ex II 2 D IP65 T 20 C - Connection To circuits with values: U H = V DC; P max =.2 W Type of protection "n" (zone 2) To circuits with values: U H = V DC; P max = W PTB ATEX 2007 X - Marking Ex II 2/ G Ex na II T4/T5/T6 Gc Ex II 2/ G Ex ic IIC T4/T5/T6 Gc - Connection (Ex na) U m = 45 V U m = 2 V - Connections (Ex ic) To circuits with values: U i = 45 V FISCO supply unit ic: U o = 7.5 V, I o = 570 ma Linear barrier: U o = 2 V, I o = 2 ma, P o = W - Effective internal inductance/capacitance L i = 0.4 mh, C i = 6 nf L i = 7 H, C i =. nf Explosion protection acc. to FM Certificate of Compliance Identification (XP/DIP) or (IS); (NI) CL I, DIV, GP ABCD T4...T6; CL II, DIV, GP EFG; CL III; CL I, ZN 0/ AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III Explosion protection to CSA Certificate of Compliance Identification (XP/DIP) or (IS) CL I, DIV, GP ABCD T4...T6; CL II, DIV, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III ) Conversion of temperature error per 28 C. Valid for temperature range C < ( r ) % / 28 C (50 F). 2) Conversion of temperature error per 28 C. Valid for temperature range C < (0.08. r + 0.6) % / 28 C (50 F). Siemens FI /99

11 Siemens AG 204 SITRANS P DS III for gauge pressure HART communication HART Protocol HART Version 5.x Software for computer SIMATIC PDM PROFIBUS PA communication Simultaneous communication with 4 master class 2 (max.) The address can be set using Configuration tool or local operation (standard setting address 26) Cyclic data usage Output byte 5 (one measured value) or 0 (two measured values) Input byte 0,, or 2 (register operating mode and reset function for metering) Internal preprocessing Device profile PROFIBUS PA Profile for Process Control Devices Version.0, class B Function blocks 2 Analog input - Adaptation to customer-specific process variables Yes, linearly rising or falling characteristic - Electrical damping, adjustable s - Simulation function Input /Output - Failure mode parameterizable (last good value, substitute value, incorrect value) - Limit monitoring Yes, one upper and lower warning limit and one alarm limit respectively Register (totalizer) Can be reset, preset, optional direction of counting, simulation function of register output - Failure mode parameterizable (summation with last good value, continuous summation, summation with incorrect value) - Limit monitoring One upper and lower warning limit and one alarm limit respectively Physical block Transducer blocks 2 Pressure transducer block - Can be calibrated by applying Yes two pressures - Monitoring of sensor limits Yes - Specification of a container Max. 0 nodes characteristic with - Square-rooted characteristic Yes for flow measurement - Gradual volume suppression Parameterizable and implementation point of square-root extraction - Simulation function for measured pressure value and sensor temperature Constant value or over parameterizable ramp function FOUNDATION Fieldbus communication Function blocks function blocks analog input, function block PID Analog input - Adaptation to customer-specific process variables characteristic Yes, linearly rising or falling - Electrical damping, adjustable s - Simulation function Output/input (can be locked within the device with a bridge) - Failure mode parameterizable (last good value, substitute value, incorrect value) - Limit monitoring Yes, one upper and lower warning limit and one alarm limit respectively - Square-rooted characteristic Yes for flow measurement PID Standard FOUNDATION Fieldbus function block Physical block resource block Transducer blocks transducer block Pressure with calibration, transducer block LCD Pressure transducer block - Can be calibrated by applying Yes two pressures - Monitoring of sensor limits Yes - Simulation function: Measured pressure value, sensor temperature and electronics temperature Constant value or over parameterizable ramp function /00 Siemens FI 0 205

12 Siemens AG 204 Selection and Ordering data Pressure transmitter for gauge pressure, SITRANS P DS III with HART Article No. 7 M F Y Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Measuring cell cleaning Silicone oil normal } Inert liquid ) grease-free to cleanliness level 2 Measuring span (min.... max.) bar ( psi) } B bar ( psi) } C bar ( psi) } D bar ( psi) } E bar ( psi) } F bar ( psi) } G bar ( psi) } J Wetted parts materials Seal diaphragm Process connection Stainless steel Stainless steel } A Hastelloy Stainless steel B Hastelloy Hastelloy C Version as diaphragm seal 2) ) 4) 5) Process connection Connection shank G½B to EN 87- } 0 Female thread ½-4 NPT Stainless steel oval flange with process connection (Oval flange has no female thread) - Mounting thread 7 / 6-20 UNF to IEC Mounting thread M0 to DIN 92 - Mounting thread M2 to DIN 92 4 Male thread M20 x.5 5 Male thread ½ -4 NPT 6 Non-wetted parts materials Housing made of die-cast aluminium } 0 Housing stainless steel precision casting 6) Version Standard versions International version, English label inscriptions, } 2 documentation in 5 languages on CD (no Order code selectable) Explosion protection None A With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" B - "Explosion-proof (Ex d)" 7) D - "Intrinsic safety and flameproof enclosure" P (Ex ia + Ex d)" 8) - "Ex na/ic (Zone 2)" 9) E - "Intrinsic safety, explosion-proof enclosure } R and dust explosion protection (Ex ia + Ex d + Zone D/2D)" 8)0) FM + CSA intrinsic safe (is) F FM + CSA (is + ep) + Ex ia + Ex d (ATEX) 0) S With FM + CSA, Type of protection: - "Intrinsic Safe und Explosion Proof (is + xp)" 7) N C Electrical connection / cable entry Screwed gland Pg.5 (adapter) ) A Screwed gland M20 x.5 } B Screwed gland ½-4 NPT C Han 7D plug (plastic housing) incl. mating D connector ) M2 connectors (stainless steel) )2) F SITRANS P DS III for gauge pressure Selection and Ordering data Article No. Pressure transmitter for gauge pressure, 7 M F SITRANS P DS III with HART Display Without display 0 Without visible display (display concealed, setting: ma) } With visible display (setting: ma) 6 with customer-specific display (setting as 7 specified, Order code "Y2" or "Y22" required) } Available ex stock We can offer shorter delivery times for configurations designated with the Quick Ship Symbol. For details see page 9/5 in the appendix. Power supply units see Chap. 7 "Supplementary Components". Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation ) For oxygen application, add Order code E0. 2) When the manufacture s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC , it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here. ) If the acceptance test certificate..is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. 4) The diaphragm seal is to be specified with a separate order number and must be included with the transmitter order number, for example 7MF40.-..Y and 7MF B 5) The standard measuring cell filling of configurations with remote seals (Y) is silicone oil. 6) Not in conjunction with Electrical connection "Screwed gland Pg.5" and "Han7D plug". 7) Without cable gland, with blanking plug 8) With enclosed cable gland Ex ia and blanking plug 9) Configurations with HAN and M2 connectors are only available in Ex ic. 0) Only in connection with IP65. ) Only in connection with Ex approval A, B or E. 2) M2 delivered without cable socket Siemens FI /0

13 Siemens AG 204 SITRANS P DS III for gauge pressure Selection and Ordering data Article No. Pressure transmitter for gauge pressure SITRANS P DS III with PROFIBUS PA (PA) 7 M F SITRANS P DS III with FOUNDATION Fieldbus (FF) 7 M F Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Measuring cell cleaning Silicone oil normal Inert liquid ) grease-free to cleanliness level 2 Nominal measuring range bar (4.5 psi) B 4 bar (58 psi) C 6 bar (22 psi) D 6 bar (94 psi) E 60 bar (220 psi) F 400 bar (5802 psi) G 700 bar (05 psi) J Wetted parts materials Seal diaphragm Process connection Stainless steel Stainless steel A Hastelloy Stainless steel B Hastelloy Hastelloy C Version as diaphragm seal 2) ) 4) 5) Y Process connection Connection shank G½B to EN 87-0 Female thread ½-4 NPT Stainless steel oval flange with process connection (Oval flange has no female thread) 6) - Mounting thread 7 / 6-20 UNF to IEC Mounting thread M0 to DIN 92 - Mounting thread M2 to DIN 92 4 Male thread M20 x.5 5 Male thread ½ -4 NPT 6 Non-wetted parts materials Housing made of die-cast aluminium 0 Housing stainless steel precision casting Version Standard versions International version, English label inscriptions, 2 documentation in 5 languages on CD (no Order code selectable) Explosion protection None A With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" B - "Explosion-proof (Ex d)" 7) D - "Intrinsic safety and flameproof enclosure" P (Ex ia + Ex d)" 8) - "Ex na/ic (Zone 2)" 9) E - "Intrinsic safety, explosion-proof enclosure and R dust explosion protection (Ex ia + Ex d + Zone D/2D)" 8) 0) (not for DS III FF) FM + CSA intrinsic safe (is) F FM + CSA (is + ep) + Ex ia + Ex d (ATEX) 0) S With FM + CSA, Type of protection: - "Intrinsic Safe und Explosion Proof (is + xp)" 7) N C Electrical connection/cable entry Screwed gland M20 x.5 B Screwed gland ½-4 NPT C M2 connectors (stainless steel) ) 2) F Selection and Ordering data Article No. Pressure transmitter for gauge pressure SITRANS P DS III with PROFIBUS PA (PA) 7 M F SITRANS P DS III with FOUNDATION Fieldbus (FF) 7 M F Display Without display 0 Without visible display (display concealed, setting: bar) With visible display (setting: bar) 6 with customer-specific display (setting as specified, Order code "Y2" required) 7 Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation ) For oxygen application, add Order code E0. 2) When the manufacture s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC , it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here. ) If the acceptance test certificate..is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. 4) The diaphragm seal is to be specified with a separate order number and must be included with the transmitter order number, for example 7MF40.-..Y and 7MF B 5) The standard measuring cell filling of configurations with remote seals (Y) is silicone oil. 6) M0 fastening thread: Max. span 60 bar (220 psi) 7/6-20 UNF and M2 fastening thread: Max. span 400 bar (5802 psi) 7) Without cable gland, with blanking plug. 8) With enclosed cable gland Ex ia and blanking plug. 9) Configurations with HAN and M2 connectors are only available in Ex ic. 0) Only in connection with IP65. ) M2 delivered without cable socket. 2) Only in connection with Ex approval A, B, E or F. /02 Siemens FI 0 205

14 Siemens AG 204 Selection and Ordering data Order code Further designs HART PA FF Add "-Z" to Article No. and specify Order code. Pressure transmitter with mounting bracket (x fixing angle, 2 x nut, 2 x U- washer or x bracket, 2 x nut, 2 x U- washer) made of: Steel A0 Stainless steel A02 Plug Han 7D (metal) A0 Han 8D (instead of Han 7D) A Angled A2 Han 8D (metal) A Cable sockets for M2 connectors A50 (metal (CuZn)) Rating plate inscription (instead of German) English B French B2 Spanish B Italian B4 Cyrillic (russian) B6 English rating plate B2 Pressure units in inh 2 0 and/or psi Quality inspection certificate (Five-step C factory calibration) to IEC ) Inspection certificate 2) C2 Acc. to EN Factory certificate C4 Acc. to EN Functional safety (SIL2) C20 Devices suitable for use according to IEC 6508 and IEC 65. Includes SIL conformity declaration Functional safety (PROFIsafe) C2 ) Certificate and PROFIsafe protocol Functional safety (SIL2/) C2 Devices suitable for use according to IEC 6508 and IEC 65. Includes SIL conformity declaration Device passport Russia C99 (For price request please contact the technical support Setting of upper limit of output signal to 22.0 ma D05 Manufacturer's declaration acc. to NACE D07 (MR and MR ) Degree of protection IP66/IP68 D2 (only for M20x.5 and ½-4 NPT) Supplied with oval flange D7 ( item), PTFE packing and screws in thread of oval flange Capri cable gland 4F CrNi and clamping D59 device ( ) included Use in or on zone D/2D E0 (only together with type of protection "Intrinsic safety" (transmitter 7MF B.. Ex ia) and IP65) Oxygen application E0 (In the case of oxygen measurement and inert liquid max. 00 bar (450 psi) at 60 C (40 F)) Export approval Korea E CRN approval Canada (Canadian Registration Number) E22 SITRANS P DS III for gauge pressure Selection and Ordering data Order code Further designs Add "-Z" to Article No. and specify Order code. HART PA FF Dual seal E24 Explosion-proof "Intrinsic safety" (Ex ia) E25 4) to INMETRO (Brazil) (only for transmitter 7MF B..) "Flameproof" explosion protection E26 4) according to INMETRO (Brazil) (only for transmitter 7MF D..) Explosion-proof "Intrinsic safety" (Ex ia E28 4) + Ex d) to INMETRO (Brazil) (only for transmitter 7MF P..) Ex Approval IEC Ex (Ex ia) E45 4) (only for transmitter 7MF B..) Ex Approval IEC Ex (Ex d) E46 4) (only for transmitter 7MF D..) Explosion-proof "Intrinsic safety" to E55 4) NEPSI (China) (only for transmitter 7MF B..) Explosion protection "Explosion-proof" E56 4) to NEPSI (China) (only for transmitter 7MF D..) Ex protection "Zone 2" to NEPSI (China) E57 4) (only for transmitter 7MF E..) Ex protection Ex ia, Ex d and E58 4) Zone 2 to NEPSI (China) (only for transmitter 7MF R..) "Intrinsic safety" and "Explosion-proof" E70 4) explosion protection acc. to Kosha (Korea) (only for transmitter 7MF [B, D]..-Z + E) Two coats of lacquer on casing and G0 cover (PU on epoxy) Transient protector 6 kv (lightning protection) J0 Oval flange NAM (ASTAVA) J06 We can offer shorter delivery times for configurations designated with the Quick Ship Symbol. For details see page 9/5 in the appendix. ) When the manufacture s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC , it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here. 2) If the acceptance test certificate..is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. ) Profisafe transmitters can only be operated with the S7 F Systems V6. configuration software in combination with S7-400H 4) Option does not include ATEX approval, but instead includes only the country-specific approval. Siemens FI /0

15 Siemens AG 204 SITRANS P DS III for gauge pressure Selection and Ordering data Order code Additional data Please add "-Z" to Article No. and specify Order code(s) and plain text. HART PA FF Measuring range to be set Y0 ) Specify in plain text (max. 5 characters): Y0:... up to... mbar, bar, kpa, MPa, psi Stainless steel tag plate and entry in Y5 device variable (measuring point description) Max. 6 characters, specify in plain text: Y5:... Measuring point text (entry in device Y6 variable) Max. 27 characters, specify in plain text: Y6:... Entry of HART address (TAG) Y7 Max. 8 characters, specify in plain text: Y7:... Setting of pressure indication in pressure Y2 units Specify in plain text (standard setting: bar): Y2: mbar, bar, kpa, MPa, psi,... Note: The following pressure units can be selected: bar, mbar, mm H 2 O *), inh 2 O *), fth 2 O *), mmhg, inhg, psi, Pa, kpa, MPa, g/cm 2, kg/cm 2, Torr, ATM or % *) ref. temperature 20 C Setting of pressure indication in Y22 + non-pressure units 2) Y0 Specify in plain text: Y22:... up to... l/min, m /h, m, USgpm,... (specification of measuring range in pressure units "Y0" is essential, unit with max. 5 characters) Preset bus address Y25 possible between and 26 Specify in plain text: Y25:... Damping adjustment in seconds Y0 ( s) We can offer shorter delivery times for configurations designated with the Quick Ship Symbol. For details see page 9/5 in the appendix. Only Y0, Y5, Y6, Y7, Y2, Y22, Y25 and D05 can be factory preset = available Ordering example Item line: 7MF40-EA00-AA7-Z B line: A0 + Y0 + Y2 C line: Y0: bar ( psi) C line: Y2: bar (psi) ) 2) Measuring accuracies for PROFIBUS PA transmitters with Option Y0 are calculated in the same way as for HART devices. Preset values can only be changed over SIMATIC PDM. /04 Siemens FI 0 205

16 Siemens AG 204 Dimensional drawings SITRANS P DS III for gauge pressure 5 (0.6) 4 (5.6) 74 (2.9) 5 (2.) 54 (2.) 27 (.) 24 (0.94) approx. 96 (.78) 7 (0.67) 29 (.4) 4) 84 (.) 5 approx. 40 (.6) Ø80 (.5) 7 (6.7) 9 SW (2.8) 2 50 (.97) 7 (4.6) 68 (2.68) 4 20 (4.72) (6.9) 27 (9.) Space for rotation of housing min. 90 (.54) 5) 2 (4.84) Ø ( ) 05 (4.) 2 4 Electronic side, digital display (longer overall length for cover with window) ) Terminal side ) Electrical connection: Screwed gland Pg,5 (adapter)(adapter) 2) ), Screwed gland M20 x,5 or Screwed gland ½-4 NPT or Han 7D/Han 8D 2) ) plug Harting adapter 5 Protective cover over keys 6 Blanking plug 7 Screw cover - safety bracket (only for type of protection "Explosion-proof enclosure", not shown in the drawing) 8 Process connection: Connection shank G½B or Oval flange 9 Mounting bracket (option) ) Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing 2) Not with type of protection "Explosion-proof enclosure" ) Not with type of protection "FM + CSA" [IS + XP]" 4) For Pg,5 with adapter approx. 45 mm (.77 inch) 5) Minimum distance for rotating SITRANS P DS III pressure transmitters for gauge pressure, dimensions in mm (inch) Siemens FI /05

17 Siemens AG 204 SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm Technical specifications SITRANS P DS III series for gauge and absolute pressure, with front-flush diaphragm HART PROFIBUS PA and FOUNDATION Fieldbus Input of gauge pressure, with front-flush diaphragm Measured variable Gauge pressure, front-flush Spans (infinitely adjustable) or nominal measuring range and max. permissible test pressure Span (min.... max.) Max. perm. test pressure Nominal measuring range Max. perm. test pressure /06 Siemens FI bar ( psi) bar ( psi) bar ( psi) bar ( psi) 6 bar (87 psi) 0 bar (45 psi) 2 bar (464 psi) 00 bar (450 psi) bar (4.5 psi) 4 bar (58 psi) 6 bar (22 psi) 6 bar (94 psi) 00 mbar a (.45 psia) 6 bar (87 psi) 0 bar (45 psi) 2 bar (464 psi) 00 bar (450 psi) Lower measuring limit Upper measuring limit 00 % of max. span 00 % of the max. nominal measuring range Input of absolute pressure, with front-flush diaphragm Measured variable Spans (infinitely adjustable) or nominal measuring range and max. permissible test pressure Span (min.... max.) mbar a ( psia) bar a ( psia)... 0 bar a ( psia) Max. perm. test pressure 0 bar a (45 psia) 0 bar a (45 psia) 00 bar a (450 psia) Absolute pressure, front-flush Nominal measuring range 00 mbar a (8.85 psia) 5 bar a (72.5 psia) 0 bar a (45 psia) Max. perm. test pressure 0 bar a (45 psia) 0 bar a (45 psia) 00 bar a (450 psia) Lower measuring limit 0 bar a (0 psia) Upper measuring limit 00 % of max. span 00 % of the max. nominal measuring range Output Output signal ma Digital PROFIBUS PA and FOUNDATION Fieldbus signal Lower limit (infinitely adjustable).55 ma, factory preset to.84 ma - Upper limit (infinitely adjustable) 2 ma, factory preset to 20.5 ma or optionally - set to 22.0 ma Load Without HART R B (U H V)/0.02 A in, - U H : Power supply in V With HART R B = (SIMATIC PDM) or - R B = (HART Communicator) Physical bus - IEC Protection against polarity reversal Protected against short-circuit and polarity reversal. Each connection against the other with max. supply voltage. Electrical damping (step width 0. s) Set to 2 s ( s) Measuring accuracy Acc. to IEC Reference conditions (All error data refer always refer to the set span) Error in measurement at limit setting incl. hysteresis and reproducibility Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, silicone oil filling, room temperature 25 C (77 F) Span ratio r = max. span/set span Nominal measuring range ratio r = nominal measuring range/set measuring range Gauge pressure, front-flush Absolute pressure, front-flush Gauge pressure, front-flush Linear characteristic -r 0 ( r ) % 0.2 % ( r ) % 0.2 % - 0 < r 0 ( r ) % 0.4 % ( r ) % 0.4 % -0<r 00 (0.005 r ) % - (0.005 r+0.05)% - Long-term stability (temperature change 0 C ( 54 F)) (0.25 r) % per 5 years (0.25 r) % per 5 years Absolute pressure, front-flush

18 Siemens AG 204 SITRANS P DS III series for gauge and absolute pressure, with front-flush diaphragm HART SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm Gauge pressure, front-flush Absolute pressure, front-flush PROFIBUS PA and FOUNDATION Fieldbus Gauge pressure, front-flush Absolute pressure, front-flush Influence of ambient temperature at C ( F) (0. r+0.2)% ) (0.2 r + 0.) % (0. r + 0.2) % ) (0.2 r + 0.) % at C and C ( F and F) (0. r + 0.5) %/0 K (0.2 r + 0.) %/0 K (0. r + 0.5) %/0 K (0.2 r + 0.) %/0 K Influence of mounting position 0. mbar (0.04 inh 2 O) per 0 inclination Measured Value Resolution of nominal measuring range Influence of the medium temperature Temperature difference between medium mbar/0 K (0.04 psi/0 K) temperature and ambient temperature Rated conditions Installation conditions Ambient temperature Observe the temperature class in areas subject to explosion hazard. Measuring cell with silicone oil C ( F) Measuring cell with Neobee oil (with front-flush C ( F) diaphragm) Measuring cell with inert liquid (not with frontflush C ( F) diaphragm) Transmitter C ( F) (with 4-wire connection, observe temperature values of supplementary 4-wire electronics) Display readable C ( F) Storage temperature C ( F) (in the case of Neobee: C ( / F)) (for high temperature oil: C ( F)) Climatic class - Condensation Relative humidity % Condensation permissible, suitable for use in the tropics Degree of protection (to IEC 60529) IP66 (optional IP66/IP68), NEMA 4X Electromagnetic Compatibility - Emitted interference and interference immunity Acc. to IEC 626 and NAMUR NE 2 Medium conditions The max. medium temperature of the front-flush process connections is to be taken into account in accordance with the relevant connection standards (e. g. DIN 2676, DIN 85 etc.). Temperature of medium Measuring cell with silicone oil C ( F) Measuring cell with silicone oil (with front-flush C ( F) diaphragm) Measuring cell with Neobee oil (with front-flush C ( F) diaphragm) Measuring cell with silicone oil, with temperature C ( F) decoupler (only for gauge pressure ver- sion with front-flush diaphragm) Measuring cell with Neobee oil, with temperature C ( F) decoupler (only for gauge pressure version with flush-mounted diaphragm) Measuring cell with inert filling liquid C ( F) Measuring cell with high-temperature oil (only C ( F) for gauge pressure version with front-flush diaphragm) Design Weight (without options).5 kg (. lb) Enclosure material Low-copper die-cast aluminum, GD-AlSi2 or stainless steel precision casting, mat. no Wetted parts materials Stainless steel, mat. no..4404/6l or Hastelloy C276, mat. no Measuring cell filling Silicone oil or inert filling liquid Process connection Flanges as per EN and ASME F&B and pharmaceutical flanges Surface quality touched-by-media R a -values 0.8 µm (2 µ-inch)/welds R a).6 µm (64 µ-inch) (Process connections acc. to A; R a -values 0.8 µm (2 µ-inch)/welds R a ) 0.8 µm (2 µ-inch) Siemens FI /07

19 Siemens AG 204 SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm SITRANS P DS III series for gauge and absolute pressure, with front-flush diaphragm Power supply U H Terminal voltage on transmitter HART V DC V DC in intrinsically-safe mode PROFIBUS PA and FOUNDATION Fieldbus Supplied through bus - Separate 24 V power supply necessary - No Bus voltage Not Ex V With intrinsically-safe operation V Current consumption Basic current (max.) ma Start-up current basic current - Yes Max. current in event of fault ma Fault disconnection electronics (FDE) available - Yes Certificates and approvals Classification according to PED 97/2/EC For gases of fluid group and liquids of fluid group ; complies with requirements of article, paragraph (sound engineering practice) Explosion protection Intrinsic safety "i" PTB ATEX 2007 X - Marking Ex II /2 G Ex ia/ib IIC T4/T5/T6 Ga/Gb - Permissible ambient temperature C ( F) temperature class T4; C ( F) temperature class T5; C ( F) temperature class T6 - Connection To certified intrinsically-safe circuits with peak values: U i = 0 V, I i = 00 ma, P i = 750 mw; R i =00 FISCO supply unit: U o = 7.5 V, I o = 80 ma, P o = 5.2 W Linear barrier: U o = 24 V, I o = 250 ma, P o =.2 W - Effective internal inductance/capacitance L i = 0.4 mh, C i = 6 nf L i = 7 H, C i =. nf Explosion-proof "d" PTB 99 ATEX 60 - Marking Ex II /2 G Ex d IIC T4/T6 Gb - Permissible ambient temperature C ( F) temperature class T4; C ( F) temperature class T6 - Connection To circuits with values: U H = V DC To circuits with values: U H = V DC Dust explosion protection for zone 20 PTB 0 ATEX Marking Ex II D IP65 T 20 C Ex II /2 D IP65 T 20 C - Permissible ambient temperature C ( F) - Max. surface temperature 20 C (248 F) - Connection To certified intrinsically-safe circuits with peak values: U i = 0 V, I i = 00 ma, P i = 750 mw, R i = 00 FISCO supply unit: U o = 7.5 V, I o = 80 ma, P o = 5.2 W Linear barrier: U o = 24 V, I o = 250 ma, P o = W - Effective internal inductance/capacitance L i = 0.4 mh, C i = 6 nf L i = 7 H, C i =. nf Dust explosion protection for zone 2/22 PTB 0 ATEX Marking Ex II 2 D IP65 T 20 C - Connection To circuits with values: U H = V DC; P max =.2 W Type of protection "n" (zone 2) PTB ATEX 2007 X - Marking Ex II 2/ G Ex na II T4/T5/T6 Gc Ex II 2/ G Ex ic IIC T4/T5/T6 Gc - Connection (Ex na) U m = 45 V U m = 2 V - Connections (Ex ic) To circuits with values: U i = 45 V To circuits with values: U H = V DC; P max = W FISCO supply unit ic: U o = 7.5 V, I o = 570 ma Linear barrier: U o = 2 V, I o = 2 ma, P o = W - Effective internal inductance/capacitance L i = 0.4 mh, C i = 6 nf L i = 7 H, C i =. nf /08 Siemens FI 0 205

20 Siemens AG 204 SITRANS P DS III series for gauge and absolute pressure, with front-flush diaphragm Certificates and approvals (continued) HART SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm Explosion protection acc. to FM Certificate of Compliance PROFIBUS PA and FOUNDATION Fieldbus - Identification (XP/DIP) or (IS); (NI) CL I, DIV, GP ABCD T4...T6; CL II, DIV, GP EFG; CL III; CL I, ZN 0/ AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III Explosion protection to CSA Certificate of Compliance Identification (XP/DIP) or (IS) CL I, DIV, GP ABCD T4...T6; CL II, DIV, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III ) Conversion of temperature error per 28 C. Valid for temperature range C < ( r ) % / 28 C (50 F). Hygiene version In the case of SITRANS P DSIII with 7MF4x front-flush diaphragm, selected connections comply with the requirements of EHEDG. Siemens FI /09

21 Siemens AG 204 SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm HART communication HART Protocol HART Version 5.x Software for computer SIMATIC PDM PROFIBUS PA communication Simultaneous communication with 4 master class 2 (max.) The address can be set using Configuration tool or local operation (standard setting address 26) Cyclic data usage Output byte 5 (one measured value) or 0 (two measured values) Input byte 0,, or 2 (register operating mode and reset function for metering) Internal preprocessing Device profile PROFIBUS PA Profile for Process Control Devices Version.0, class B Function blocks 2 Analog input - Adaptation to customer-specific process variables Yes, linearly rising or falling characteristic - Electrical damping, adjustable s - Simulation function Input /Output - Failure mode parameterizable (last good value, substitute value, incorrect value) - Limit monitoring Yes, one upper and lower warning limit and one alarm limit respectively Register (totalizer) Can be reset, preset, optional direction of counting, simulation function of register output - Failure mode parameterizable (summation with last good value, continuous summation, summation with incorrect value) - Limit monitoring One upper and lower warning limit and one alarm limit respectively Physical block Transducer blocks 2 Pressure transducer block - Can be calibrated by applying Yes two pressures - Monitoring of sensor limits Yes - Specification of a container Max. 0 nodes characteristic with - Square-rooted characteristic Yes for flow measurement - Gradual volume suppression Parameterizable and implementation point of square-root extraction - Simulation function for measured pressure value and sensor temperature Constant value or over parameterizable ramp function FOUNDATION Fieldbus communication Function blocks function blocks analog input, function block PID Analog input - Adaptation to customer-specific process variables characteristic Yes, linearly rising or falling - Electrical damping, adjustable s - Simulation function Output/input (can be locked within the device with a bridge) - Failure mode parameterizable (last good value, substitute value, incorrect value) - Limit monitoring Yes, one upper and lower warning limit and one alarm limit respectively - Square-rooted characteristic Yes for flow measurement PID Standard FOUNDATION Fieldbus function block Physical block resource block Transducer blocks transducer block Pressure with calibration, transducer block LCD Pressure transducer block - Can be calibrated by applying Yes two pressures - Monitoring of sensor limits Yes - Simulation function: Measured pressure value, sensor temperature and electronics temperature Constant value or over parameterizable ramp function /0 Siemens FI 0 205

22 Siemens AG 204 Selection and Ordering data Pressure transmitter for gauge and absolute pressure, front-flush diaphragm, SITRANS P DS III HART Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Measuring cell cleaning SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm Article No. 7 M F Silicone oil normal Inert liquid grease-free to cleanliness level 2 FDA compliant fill fluid Neobee oil normal 4 Measuring span (min.... max.) bar ( psi) B bar ( psi) C bar ( psi) D bar ( psi) E mbar a ) ( psia) ) S bar a ) ( psia) ) T... 0 bar a ) ( psia) ) U Wetted parts materials Seal diaphragm Connection shank Stainless steel Stainless steel A Hastelloy 2) Stainless steel B Process connection Flange version with Order code M.., N.., R.. or Q.. 7 Non-wetted parts materials Housing made of die-cast aluminium 0 Housing stainless steel precision casting Version Standard versions International version, English label inscriptions, 2 documentation in 5 languages on CD (no Order code selectable) Explosion protection None A With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" B - "Explosion-proof (Ex d)" ) D - Ex na/ic (Zone 2) 4) E FM + CSA intrinsic safe (is) F FM + CSA (is + ep) + Ex ia + Ex d (ATEX) 5) S With FM + CSA, Type of protection: - "Intrinsic Safe und Explosion Proof (is + xp)" ) N C ) Not with temperature decoupler P00 and P0, not for process connections R02, R04, R0 and R, and can only be ordered in conjunction with silicone oil. 2) Only available for flanges with options M.., N.. and Q.. ) Without cable gland, with blanking plug 4) Configurations with HAN and M2 connectors are only available in Ex ic. 5) Only in connection with IP65. 6) Only in connection with Ex approval A, B or E. 7) Only in connection with Ex approval A, B, E or F. 8) M2 delivered without cable socket Electrical connection/cable entry Inner thread M20 x.5 B Female thread ½-4 NPT C Han 7D plug (plastic housing) incl. mating D connector 6) M2 connectors (stainless steel) 7) 8) F Display Without display 0 Without visible display (display concealed, setting: ma) With visible display (setting: ma) 6 With customer-specific display 7 (setting as specified, Order code "Y2" or "Y22" required) Power supply units see Chap. 7 "Supplementary Components". Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation Siemens FI /

23 Siemens AG 204 Selection and Ordering data Article No. Pressure transmitter P for gauge and absolute pressure, front-flush diaphragm: SITRANS P DS III with PROFIBUS PA (PA) 7 M F SITRANS P DS III with FOUNDATION Fieldbus (FF) 7 M F Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Measuring cell cleaning Silicone oil normal Inert liquid grease-free to cleanliness level 2 FDA compliant fill fluid Neobee oil normal 4 Nominal measuring range bar (4.5 psi) B 4 bar (58 psi) C 6 bar (22 psi) D 6 bar (94 psi) E 00 mbar a ) (8.85 psia) ) S 5 bar a ) (72.5 psia) ) T 0 bar a ) (45 psia) ) U Wetted parts materials Seal diaphragm Connection shank Stainless steel Stainless steel A Hastelloy 2) Stainless steel B Process connection Flange version with Order code M.., N.., R.. or 7 Q.. Non-wetted parts materials Housing made of die-cast aluminium 0 Housing stainless steel precision casting Version Standard versions International version, English label inscriptions, 2 documentation in 5 languages on CD (no Order code selectable) Explosion protection None A With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" B - "Explosion-proof (Ex d)" ) D - Ex na/ic (Zone 2) 4) E FM + CSA intrinsic safe (is) F FM + CSA (is + ep) + Ex ia + Ex d (ATEX) 5) S With FM + CSA, Type of protection: - "Intrinsic Safe und Explosion Proof (is + xp)" ) (Available soon) N C Electrical connection/cable entry Screwed gland M20 x.5 B Screwed gland ½-4 NPT C M2 connectors (stainless steel) 6) 7) F Selection and Ordering data Article No. Pressure transmitter P for gauge and absolute pressure, front-flush diaphragm: SITRANS P DS III with PROFIBUS PA (PA) 7 M F SITRANS P DS III with FOUNDATION Fieldbus (FF) 7 M F Display Without display 0 Without visible display (display concealed, setting: bar) With visible display (setting: bar) 6 With customer-specific display (setting 7 as specified, Order code "Y2" required) Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation ) Not with temperature decoupler P00 and P0, not for process connections R0, R02, R04, R0 and R, and can only be ordered in conjunction with silicone oil. 2) Only available for flanges with options M.., N.. and Q.. ) Without cable gland, with blanking plug 4) Configurations with HAN and M2 connectors are only available in Ex ic. 5) Only in connection with IP65. 6) Only in connection with Ex approval A, B, E or F. 7) M2 delivered without cable socket SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm /2 Siemens FI 0 205

24 Siemens AG 204 Selection and Ordering data Further designs Add "-Z" to Article No. and specify Order code. Order code Plug Han 7D (metal) A0 Han 8D (instead of Han 7D) A Angled A2 Han 8D (metal) A SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm HART PA FF Cable sockets for M2 connectors A50 (metal (CuZn)) Rating plate inscription (instead of German) English B French B2 Spanish B Italian B4 Cyrillic (russian) B6 English rating plate B2 Pressure units in inh 2 0 and/or psi Quality inspection certificate (Five-step C factory calibration) to IEC Inspection certificate C2 Acc. to EN Factory certificate C4 Acc. to EN Functional safety (SIL2) C20 Devices suitable for use according to IEC 6508 and IEC 65. Includes SIL conformity declaration Functional safety (PROFIsafe) Certificate and PROFIsafe protocol C2 ) Functional safety (SIL2/) C2 Devices suitable for use according to IEC 6508 and IEC 65. Includes SIL conformity declaration Device passport Russia C99 (For price request please contact the technical support Setting of upper limit of output signal to D ma Degree of protection IP66/IP68 D2 (only for M20x.5 and ½-4 NPT) Capri cable gland 4F CrNi and clamping D59 device ( ) included Oxygen application E0 (In the case of oxygen measurement and inert liquid max. 00 bar (450 psi) at 60 C (40 F)) Export approval Korea E CRN approval Canada E22 (Canadian Registration Number) Dual seal E24 Explosion-proof "Intrinsic safety" (Ex ia) to E25 2) INMETRO (Brazil) (only for transmitter 7MF B..) "Flameproof" explosion protection according E26 2) to INMETRO (Brazil) (only for transmitter 7MF D..) Explosion-proof "Intrinsic safety" (Ex ia + E28 2) Ex d) to INMETRO (Brazil) (only for transmitter 7MF P..) Ex Approval IEC Ex (Ex ia) E45 2) (only for transmitter 7MF B..) Ex Approval IEC Ex (Ex d) E46 2) (only for transmitter 7MF D..) Selection and Ordering data Order code Further designs Add "-Z" to Article No. and specify Order code. HART PA FF Explosion-proof "Intrinsic safety" to NEPSI E55 2) (China) (only for transmitter 7MF B..) Explosion protection "Explosion-proof" to E56 2) NEPSI (China) (only for transmitter 7MF D..) Ex protection "Zone 2" to NEPSI (China) E57 2) (only for transmitter 7MF E..) Ex protection Ex ia, Ex d and Zone 2 E58 2) to NEPSI (China) (only for transmitter 7MF R..) "Intrinsic safety" and "Explosion-proof" E70 2) explosion protection acc. to Kosha (Korea) (only for transmitter 7MF [B, D]..-Z + E) Two coats of lacquer on casing and cover G0 (PU on epoxy) Transient protector 6 kv (lightning protection) J0 Flanges to EN 092-, Form B DN 25, PN 40 ) M DN 25, PN 00 ) M2 DN 40, PN 40 M DN 40, PN 00 M2 DN 50, PN 6 M04 DN 50, PN 40 M4 DN 80, PN 6 M06 DN 80, PN 40 M6 Flanges to ASME B6.5 Stainless steel flange " class 50 ) M40 Stainless steel flange ½" class 50 M4 Stainless steel flange 2" class 50 M42 Stainless steel flange " class 50 M4 Stainless steel flange 4" class 50 M44 Stainless steel flange " class 00 ) M45 Stainless steel flange ½" class 00 M46 Stainless steel flange 2" class 00 M47 Stainless steel flange " class 00 M48 Stainless steel flange 4" class 00 M49 Threaded connector to DIN 852-2, form A, thread to ISO 228 4) G ¾"-A, front-flush R0 G "-A, front-flush R02 G 2"-A, front-flush R04 Tank connection 5) Sealing is included in delivery TG 52/50, PN 40 R0 TG 52/50, PN 40 R Sanitary process connection according DIN 85 (Dairy connection with slotted union nut) DN 50, PN 25 N04 DN 80, PN 25 N06 Tri-Clamp connection according DIN 2676/ISO 2852 DN 50/2", PN 6 N4 DN 65/", PN 0 N5 Varivent connection Certified to EHEDG Type N = 68 for Varivent housing DN und ½"... 6", PN 40 N28 Siemens FI /

25 Siemens AG 204 SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm Selection and Ordering data Order code Further designs Add "-Z" to Article No. and specify Order code. HART PA FF Temperature decoupler up to 200 C 6) P00 for version with front-flush diaphragm Temperature decoupler up to 250 C P0 Measuring cell filling: High-temperature oil, only in conjunction with measuring cell filling silicone oil Sanitary process connection to DRD DN 50, PN 40 M2 SMS socket with union nut 2 M67 2½ M68 M69 SMS threaded socket 2 M7 2½ M74 M75 IDF socket with union nut ISO M82 2½ M8 M84 IDF threaded socket ISO M92 2½ M9 M94 Sanitary process connection to NEUMO Bio-Connect screw connection Certified to EHEDG DN 50, PN 6 Q05 DN 65, PN 6 Q06 DN 80, PN 6 Q07 DN 00, PN 6 Q08 DN 2", PN 6 Q DN 2½", PN 6 Q4 DN ", PN 6 Q5 DN 4", PN 6 Q6 Sanitary process connection to NEUMO Bio-Connect flange connection Certified to EHEDG DN 50, PN 6 Q2 DN 65, PN 6 Q24 DN 80, PN 6 Q25 DN 00, PN 6 Q26 DN 2", PN 6 Q DN 2½", PN 6 Q2 DN ", PN 6 Q DN 4", PN 6 Q4 Sanitary process connection to NEUMO Bio-Connect clamp connection Certified to EHEDG DN 50, PN 6 Q9 DN 65, PN 0 Q40 DN 80, PN 0 Q4 DN 00, PN 0 Q42 DN 2½", PN 6 Q48 DN ", PN 0 Q49 DN 4", PN 0 Q50 Sanitary process connection to NEUMO Bio-Connect S flange connection Certified to EHEDG DN 2", PN 6 Q72 Selection and Ordering data Order code Further designs HART PA FF Add "-Z" to Article No. and specify Order code. Aseptic threaded socket to DIN 864- Form A approved according to EHEDG DN 50, PN 25 N DN 65, PN 25 N4 DN 80, PN 25 N5 DN 00, PN 25 N6 Aseptic flange with notch to DIN Form A approved according to EHEDG DN 50, PN 6 N4 DN 65, PN 6 N44 DN 80, PN 6 N45 DN 00, PN 6 N46 Aseptic flange with groove to DIN Form A approved according to EHEDG DN 50, PN 6 N4 + P DN 65, PN 6 N44 + P DN 80, PN 6 N45 + P DN 00, PN 6 N46 + P Aseptic clamp with groove to DIN 864- FormA approved according to EHEDG DN 50, PN 25 N5 DN 65, PN 25 N54 DN 80, PN 6 N55 DN 00, PN 6 N56 ) Profisafe transmitters can only be operated with the S7 F Systems V6. configuration software in combination with S7-400H. 2) Option does not include ATEX approval, but instead includes only the country-specific approval. ) Special seal in Viton included in the scope of delivery 4) Lower measuring limit -00 mbar (.45 psi). 5) The weldable socket can be ordered under accessories. 6) Certified to A and EHEDG. The maximum permissible temperatures of the medium depend on the respective cell fillings (see medium conditions). /4 Siemens FI 0 205

26 Siemens AG 204 Selection and Ordering data Order code Additional data HART PA FF Please add "-Z" to Article No. and specify Order code(s) and plain text. Measuring range to be set Y0 ) Specify in plain text (max. 5 characters): Y0:... up to... mbar, bar, kpa, MPa, psi Stainless steel tag plate and entry in Y5 device variable (measuring point description) Max. 6 characters, specify in plain text: Y5:... Measuring point text (entry in device variable) Y6 Max. 27 characters, specify in plain text: Y6:... Entry of HART address (TAG) Y7 Max. 8 characters, specify in plain text: Y7:... Setting of pressure indicator in pressure Y2 units Specify in plain text (standard setting: bar): Y2: mbar, bar, kpa, MPa, psi,... Note: The following pressure units can be selected: bar, mbar, mm H 2 O *), inh 2 O *), fth 2 O *), mmhg, inhg, psi, Pa, kpa, MPa, g/cm 2, kg/cm 2, Torr, ATM or % *) ref. temperature 20 C SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm Setting of pressure indication in non-pressure units 2) Specify in plain text: Y22:... up to... l/min, m /h, m, USgpm,... (specification of measuring range in pressure units "Y0" is essential, unit with max. 5 characters) Y22 + Y0 Preset bus address Y25 possible between and 26 Specify in plain text: Y25:... Damping adjustment in seconds ( s) Y0 Only Y0, Y5, Y6, Y7, Y2, Y22, Y25 and D05 can be factory preset = available ordering example Item line: 7MF4-DB20-AB7-Z B line: A22 + Y0 + Y2 C line: Y0:... 0 bar ( psi) C line: Y2: bar (psi) ) Measuring accuracies for PROFIBUS PA transmitters with Option Y0 are calculated in the same way as for HART devices. 2) Preset values can only be changed over SIMATIC PDM. Siemens FI /5

27 Siemens AG 204 SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm Dimensional drawings 5 (0.6) 4 (5.6) 74 (2.9) 5 (2.) 5 (0.6) 24 (0.94) 29 (.4) 84 (.) 4 50 (.97) Ø80 (.5) 7 2 Space for rotation of housing 50 (.97) (5.2) H = approx. H = approx (2.7) Temperature decoupler min. 90 (.54) 2) 2 Electronic side, digital display (longer overall length for cover with window) ) Terminal side ) Electrical connection: Screwed gland M20 x,5 or screwed gland ½-4 NPT or M2 conector Protective cover over keys Blanking plug Screw cover - safety bracket (only for type of protection "Explosion-proof enclosure", not shown in the drawing) Process connection: see flange tables ) 2) Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing 92 mm (.6 inch) for minimum distance to permit rotation with indicator SITRANS P pressure transmitters, DS III series for gauge pressure, with front-flush diaphragm, dimensions in mm (inch) The diagram shows a SITRANS P DS III with an example of a flange. In this drawing the height is subdivided into H and H 2. H = Height of the SITRANS P00 up to a defined cross-section H 2 = Height of the flange up to this defined cross-section Only the height H 2 is indicated in the dimensions of the flanges. /6 Siemens FI 0 205

28 Siemens AG 204 SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm Flanges as per EN and ASME Sanitary process screw connection to NEUMO Bio-Connect Flange to EN Order DN PN D H 2 EN 092- code Order DN PN D H Q mm (.2 ) Approx. 2 code Q mm (4. ) 52 mm (2 ) M mm (4.5 ) Approx. Q mm (4.5 ) M mm (5.5 ) 52 mm (2 ) Q mm (5.7 ) D D Q mm (.2 ) M mm (5.9 ) Q4 2½ 6 05 mm (4. ) M mm (6.7 ) Q mm (4. ) M mm (6.5 ) Q mm (5.7 ) M mm (6.5 ) M mm (7.9 ) Sanitary process connection to NEUMO Bio-Connect flange M mm (7.9 ) connection Flanges to ASME Order DN PN D H 2 ASME B6.5 code Q mm (4. ) Approx. Order DN PN D H 2 Q mm (5.5 ) 52 mm (2 ) code D Q mm (5.9 ) M mm (4. ) Approx. Q mm (6.9 ) M4 ½ 50 0 mm (5. ) 52 mm (2 ) D Q mm (.9 ) M mm (5.9 ) Q2 2½ 6 0 mm (4. ) M mm (7.5 ) Q 6 40 mm (5.5 ) M mm (9. ) Q mm (6.9 ) M mm (4.9 ) M46 ½ mm (6. ) Sanitary process connection to NEUMO Bio-Connect clamp M mm (6.5 ) connection M mm (8. ) Order DN PN D H 2 M mm (0.0 ) code NuG and pharmaceutical connections Q mm (.0 ) Approx. Connections to DIN Q mm (.6 ) 52 mm (2 ) Q mm (4.2 ) DIN 85 (milk pipe union with slotted union nut) Q mm (4.7 ) D Order DN PN D H 2 Q mm (.0 ) 2 code Q48 2½ mm (.6 ) N mm (.6 ) Approx. Q mm (4.2 ) N mm (5.0 ) 52 mm (2 ) Q mm (4.7 ) H 2 H 2 H 2 H 2 H 2 H 2 D Tri-Clamp nach DIN 2676 Order DN PN D H 2 code N mm (2.5 ) Approx. N mm (.6 ) 52 mm (2 ) H 2 D Other connections Varivent connection Order DN PN D H 2 code N mm Approx. (. ) 52 mm (2 ) H 2 D Sanitary process connection to NEUMO Bio-Connect S flange connection Order DN PN D H 2 code Q mm (4.9 ) Approx. 52 mm (2 ) D H 2 Threaded connection G¾", G" and G2" acc. to DIN 852 Order DN PN D H 2 code R0 ¾ 60 7 mm (.5 ) Approx. 45 mm (.8 ) D R mm (.9 ) Approx. 47 mm (.9 ) R mm (. ) Approx. 52 mm (2 ) H 2 Sanitary process connection to DRD Order DN PN D H 2 code M mm (4. ) Approx. 52 mm (2 ) H 2 D Siemens FI /7

29 Siemens AG 204 SITRANS P DS III for gauge/absolute pressure, with front-flush diaphragm Tank connection TG 52/50 and TG52/50 Order DN PN D H 2 code R mm (2.5 ) Approx. 6 mm (2.5 ) R mm (2.5 ) Approx. D 70 mm (6.7 ) H 2 Aseptic threaded socket to DIN 864- Form A Order DN PN D H 2 code N x /6 Approx. N x /6 52 mm (2 ) N x ¼ N x ¼ H 2 D SMS socket with union nut Order DN PN D H 2 code M mm (. ) Approx. M68 2½ mm (.9 ) 52 mm (2 ) M mm (4.5 ) H 2 D SMS threaded socket Order DN PN D H 2 code M x /6 mm Approx. M74 2½ x /6 mm 52 mm (2 ) M x /6 mm H 2 D IDF socket with union nut Order DN PN D H 2 code M mm ( ) Approx. M8 2½ 25 9 mm (.6 ) 52 mm (2 ) M mm (4.2 ) H 2 D IDF threaded socket Order DN PN D H 2 code M mm (2.5 ) Approx. M9 2½ mm (. ) 52 mm (2 ) M mm (.6 ) H 2 Aseptic flange with notch to DIN Form A Order DN PN D H 2 code N Approx. N mm (2 ) N D N H 2 Aseptic flange with groove to DIN Form A Order DN PN D H 2 code N4 + P Approx. 52 mm (2 ) N D P N P N46 + P H 2 Aseptic clamp with groove to DIN 864- Form A Order DN PN D H 2 code N Approx. N mm (2 ) N N H 2 D D /8 Siemens FI 0 205

30 Siemens AG 204 Technical specifications SITRANS P DS III series for absolute pressure (from the gauge pressure series) Input Measured variable Spans (infinitely adjustable) or nominal measuring range and max. permissible test pressure HART Span (min.... max.) mbar a ( psia) mbar a ( psi a) mbar a ( psia)... 0 bar a ( psia) SITRANS P DS III for absolute pressure (from gauge pressure series) Max. perm. test pressure 6 bar a (87 psia) 0 bar a (45 psia) 0 bar a (45 psia) 00 bar a (450 psia) Absolute pressure PROFIBUS PA and FOUNDATION Fieldbus Nominal measuring range 250 mbar a (.6 psia) 00 mbar a (8.9 psi a) 5 bar a (72.5 psia) 0 bar a (45 psia) Max. perm. test pressure 6 bar a (87 psia) 0 bar a (45 psia) 0 bar a (45 psia) 00 bar a (450 psia) Lower measuring limit Measuring cell with silicone oil filling 0 mbar a (0 psia) Upper measuring limit 00 % of max. span Output Output signal ma Digital PROFIBUS PA and FOUNDATION Fieldbus signal Lower limit (infinitely adjustable).55 ma, factory preset to.84 ma - Upper limit (infinitely adjustable) 2 ma, factory preset to 20.5 ma or optionally - set to 22.0 ma Load Without HART R B (U H V)/0.02 A in, - U H : Power supply in V With HART R B = (SIMATIC PDM) or - R B = (HART Communicator) Physical bus - IEC Protection against polarity reversal Protected against short-circuit and polarity reversal. Each connection against the other with max. supply voltage. Electrical damping (step width 0. s) Set to 2 s ( s) Measuring accuracy Acc. to IEC Reference conditions (All error data refer always refer to the set span) Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, silicone oil filling, room temperature 25 C (77 F) Span ratio r = max. span/set span Nominal measuring range ratio r = nominal measuring range/set measuring range Error in measurement at limit setting incl. hysteresis and reproducibility Linear characteristic -r 0 0. % 0. % - 0 < r % 0.2 % Long-term stability (0. r) %/year (0. r) %/year (temperature change ± 0 C (± 54 F)) Influence of ambient temperature at C ( F) (0. r+0.2)% ) (0. r + 0.2) % ) at C and C (0. r+0.5)%/0k (0. r + 0.5) %/0 K ( F and F) Measured Value Resolution of nominal measuring range Siemens FI /9

31 Siemens AG 204 SITRANS P DS III for absolute pressure (from gauge pressure series) SITRANS P DS III series for absolute pressure (from the gauge pressure series) Rated conditions Degree of protection (to IEC 60529) Temperature of medium Measuring cell with silicone oil filling HART IP66 (optional IP66/IP68), NEMA 4X PROFIBUS PA and FOUNDATION Fieldbus C ( F) C ( F) with 0 bar a measuring cell C ( F) C ( F) Measuring cell with inert filling liquid In conjunction with dust explosion protection Ambient conditions Ambient temperature - Transmitter C ( F) (with 4-wire connection, observe temperature values of supplementary 4-wire electronics) - Display readable C ( F) Storage temperature C ( F) Climatic class - Condensation Relative humidity % Condensation permissible, suitable for use in the tropics Electromagnetic Compatibility - Emitted interference and interference immunity Acc. to IEC 626 and NAMUR NE 2 Design Weight (without options).5 kg (. lb) Enclosure material Low-copper die-cast aluminum, GD-AlSi 2 or stainless steel precision casting, mat. no Wetted parts materials Connection shank Stainless steel, mat. no..4404/6l or Hastelloy C4, mat. no Oval flange Stainless steel, mat. no..4404/6l Seal diaphragm Stainless steel, mat. no..4404/6l or Hastelloy C276, mat. no Measuring cell filling Silicone oil or inert filling liquid (maximum value with oxygen measurement pressure 00 bar (450 psi) at 60 C (40 F)) Process connection Connection shank G½B to EN 87-, female thread ½ -4 NPT or oval flange (PN 60 (MAWP 220 psia)) to DIN 92 with mounting thread M0 or 7 / 6-20 UNF to IEC 658 Material of mounting bracket Steel Sheet-steel, Mat. No..00, chrome-plated Stainless steel Sheet stainless steel, mat. no..40 (SS 04) Power supply U H Supplied through bus Terminal voltage on transmitter V DC V DC in intrinsically-safe mode Separate 24 V power supply necessary - No Bus voltage Not Ex V With intrinsically-safe operation V Current consumption Basic current (max.) ma Start-up current basic current - Yes Max. current in event of fault ma Fault disconnection electronics (FDE) available - Yes /20 Siemens FI 0 205

32 Siemens AG 204 SITRANS P DS III series for absolute pressure (from the gauge pressure series) Certificates and approvals HART SITRANS P DS III for absolute pressure (from gauge pressure series) PROFIBUS PA and FOUNDATION Fieldbus Classification according to PED 97/2/EC For gases of fluid group and liquids of fluid group ; complies with requirements of article, paragraph (sound engineering practice) Explosion protection Intrinsic safety "i" PTB ATEX 2007 X - Marking Ex II /2 G Ex ia/ib IIC T4/T5/T6 Ga/Gb - Permissible ambient temperature C ( F) temperature class T4; C ( F) temperature class T5; C ( F) temperature class T6 - Connection To certified intrinsically-safe circuits with peak values: U i = 0 V, I i = 00 ma, P i = 750 mw; R i =00 FISCO supply unit: U o = 7.5 V, I o = 80 ma, P o = 5.2 W Linear barrier: U o = 24 V, I o = 250 ma, P o =.2 W - Effective internal inductance/capacitance L i = 0.4 mh, C i = 6 nf L i = 7 H, C i =. nf Explosion-proof "d" PTB 99 ATEX 60 - Marking Ex II /2 G Ex d IIC T4/T6 Gb - Permissible ambient temperature C ( F) temperature class T4; C ( F) temperature class T6 - Connection To circuits with values: U H = V DC To circuits with values: U H = V DC Dust explosion protection for zone 20 PTB 0 ATEX Marking Ex II D IP65 T 20 C Ex II /2 D IP65 T 20 C - Permissible ambient temperature C ( F) - Max. surface temperature 20 C (248 F) - Connection To certified intrinsically-safe circuits with peak values: U i = 0 V, I i = 00 ma, P i = 750 mw, R i = 00 FISCO supply unit: U o = 7.5 V, I o = 80 ma, P o = 5.2 W Linear barrier: U o = 24 V, I o = 250 ma, P o =.2 W - Effective internal inductance/capacitance L i = 0.4 mh, C i = 6 nf L i = 7 H, C i =. nf Dust explosion protection for zone 2/22 PTB 0 ATEX Marking Ex II 2 D IP65 T 20 C - Connection To circuits with values: U H = V DC; P max =.2 W Type of protection "n" (zone 2) PTB ATEX 2007 X - Marking Ex II 2/ G Ex na II T4/T5/T6 Gc Ex II 2/ G Ex ic IIC T4/T5/T6 Gc - Connection (Ex na) U m = 45 V U m = 2 V - Connection (Ex ic) To circuits with values: U i = 45 V To circuits with values: U H = V DC; P max = W FISCO supply unit ic: U o = 7.5 V, I o = 570 ma Linear barrier: U o = 2 V, I o = 2 ma, P o = W - Effective internal inductance/capacitance L i = 0.4 mh, C i = 6 nf L i = 7 H, C i =. nf Explosion protection acc. to FM Certificate of Compliance Identification (XP/DIP) or (IS); (NI) CL I, DIV, GP ABCD T4...T6; CL II, DIV, GP EFG; CL III; CL I, ZN 0/ AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III Explosion protection to CSA Certificate of Compliance Identification (XP/DIP) or (IS) CL I, DIV, GP ABCD T4...T6; CL II, DIV, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III ) Conversion of temperature error per 28 C. Valid for temperature range C < (0.08. r + 0.6) % / 28 C (50 F). Siemens FI /2

33 Siemens AG 204 SITRANS P DS III for absolute pressure (from gauge pressure series) HART communication HART Protocol HART Version 5.x Software for computer SIMATIC PDM PROFIBUS PA communication Simultaneous communication with 4 master class 2 (max.) The address can be set using Configuration tool or local operation (standard setting address 26) Cyclic data usage Output byte 5 (one measured value) or 0 (two measured values) Input byte 0,, or 2 (register operating mode and reset function for metering) Internal preprocessing Device profile PROFIBUS PA Profile for Process Control Devices Version.0, class B Function blocks 2 Analog input - Adaptation to customer-specific process variables Yes, linearly rising or falling characteristic - Electrical damping, adjustable 0 to 00 s - Simulation function Input /Output - Failure mode parameterizable (last good value, substitute value, incorrect value) - Limit monitoring Yes, one upper and lower warning limit and one alarm limit respectively Register (totalizer) Can be reset, preset, optional direction of counting, simulation function of register output - Failure mode parameterizable (summation with last good value, continuous summation, summation with incorrect value) - Limit monitoring One upper and lower warning limit and one alarm limit respectively Physical block Transducer blocks 2 Pressure transducer block - Can be calibrated by applying Yes two pressures - Monitoring of sensor limits Yes - Specification of a container Max. 0 nodes characteristic with - Square-rooted characteristic Yes for flow measurement - Gradual volume suppression Parameterizable and implementation point of square-root extraction - Simulation function for measured pressure value and sensor temperature Constant value or over parameterizable ramp function FOUNDATION Fieldbus communication Function blocks function blocks analog input, function block PID Analog input - Adaptation to customer-specific process variables characteristic Yes, linearly rising or falling - Electrical damping, adjustable s - Simulation function Output/input (can be locked within the device with a bridge) - Failure mode parameterizable (last good value, substitute value, incorrect value) - Limit monitoring Yes, one upper and lower warning limit and one alarm limit respectively - Square-rooted characteristic Yes for flow measurement PID Standard FOUNDATION Fieldbus function block Physical block resource block Transducer blocks transducer block Pressure with calibration, transducer block LCD Pressure transducer block - Can be calibrated by applying Yes two pressures - Monitoring of sensor limits Yes - Simulation function: Measured pressure value, sensor temperature and electronics temperature Constant value or over parameterizable ramp function /22 Siemens FI 0 205

34 Siemens AG 204 Selection and Ordering data Pressure transmitters for absolute pressure from gauge pressure series SITRANS P DS III with HART Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Measuring cell cleaning SITRANS P DS III for absolute pressure (from gauge pressure series) Article No. 7 M F Y F Silicone oil normal Inert liquid ) grease-free to cleanliness level 2 Measuring span (min.... max.) mbar a ( psia) D mbar a ( psia) F bar a ( psia) G... 0 bar a ( psia) H Wetted parts materials Seal diaphragm Process connection Stainless steel Stainless steel A Hastelloy Stainless steel B Hastelloy Hastelloy C Version for diaphragm seal2) ) 4) 5) 6) Process connection Connection shank G½B to EN 87-0 Female thread ½-4 NPT Stainless steel oval flange with process connection (Oval flange has no female thread) - Mounting thread 7 / 6-20 UNF to EN Mounting thread M0 to DIN 92 - Mounting thread M2 to DIN 92 4 Male thread M20 x.5 5 Male thread ½ -4 NPT 6 Non-wetted parts materials Housing made of die-cast aluminium 0 Housing stainless steel precision casting 7) Version Standard versions International version, English label inscriptions, 2 documentation in 5 languages on CD (no Order code selectable) Explosion protection None A With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" B - "Explosion-proof (Ex d)" 8) D - "Intrinsic safety and flameproof enclosure" P (Ex ia + Ex d)" 9) - "Ex na/ic (Zone 2)" 0) E - "Intrinsic safety, explosion-proof enclosure R and dust explosion protection (Ex ia+ Ex d + Zone D/2D)" 9)) FM + CSA intrinsic safe (is) F FM + CSA (is + ep) + Ex ia + Ex d (ATEX) ) S With FM + CSA, Type of protection: - "Intrinsic Safe und Explosion Proof (is + xp)" 8) N C Electrical connection/cable entry Screwed gland Pg.5 2) A Screwed gland M20x.5 B Screwed gland ½-4 NPT C Han 7D plug (plastic housing) incl. mating D connector 2) M2 connectors (stainless steel) ) 4) Selection and Ordering data Article No. Pressure transmitters for absolute pressure 7 M F from gauge pressure series SITRANS P DS III with HART Display Without display 0 Without visible display (display concealed, setting: ma) With visible display (setting: ma) 6 with customer-specific display (setting as specified, Order code "Y2" or "Y22" required) 7 We can offer shorter delivery times for configurations designated with the Quick Ship Symbol. For details see page 9/5 in the appendix. Power supply units see Chap. 7 "Supplementary Components". Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation ) For oxygen application, add Order code E0. 2) Version 7MF42-DY... only up to max. span 200 mbar a (80 inh 2 O a). ) When the manufacture s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC , it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here.if the acceptance test certificate..is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. 4) If the acceptance test certificate..is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. 5) The diaphragm seal is to be specified with a separate order number and must be included wiht the tranmitter order number, for example 7MF42.-..Y and 7MF B 6) The standard measuring cell filling for configurations with remote seals (Y) is silicone oil. 7) Not in conjunction with Electrical connection "Screwed gland Pg.5" and "Han7D plug". 8) Without cable gland, with blanking plug. 9) With enclosed cable gland Ex ia and blanking plug. 0) Configurations with HAN and M2 connectors are only available in Ex ic. ) Only in connection with IP65. 2) Only in connection with Ex apporval A, B or E. ) Only in connection with Ex apporval A, B, E or F. 4) M2 delivered without cable socket Siemens FI /2

35 Siemens AG 204 Selection and Ordering data Article No. Pressure transmitters for absolute pressure from gauge pressure series SITRANS P DS III with PROFIBUS PA (PA) 7 M F SITRANS P DS III with FOUNDATION Fieldbus (FF) 7 M F Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Measuring cell cleaning Silicone oil normal Inert liquid ) grease-free to cleanliness level 2 Nominal measuring range 250 mbar a (.62 psia) D 00 mbar a (8.85 psia) F 5 bar a (72.5 psia) G 0 bar a (45 psia) H Wetted parts materials Seal diaphragm Process connection Stainless steel Stainless steel A Hastelloy Stainless steel B Hastelloy Hastelloy C Version as diaphragm seal 2) ) 4) 5) 6) Y Process connection Connection shank G½B to EN 87-0 Female thread ½-4 NPT Stainless steel oval flange with process connection (Oval flange has no female thread) - Mounting thread 7 / 6-20 UNF to IEC Mounting thread M0 to DIN 92 - Mounting thread M2 to DIN 92 4 Male thread M20 x.5 5 Male thread ½ -4 NPT 6 Non-wetted parts materials Housing made of die-cast aluminium 0 Housing stainless steel precision casting Version Standard versions International version, English label inscriptions, 2 documentation in 5 languages on CD (no Order code selectable) Explosion protection None A With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" B - "Explosion-proof (Ex d)" 7) D - "Intrinsic safety and flameproof enclosure" P (Ex ia + Ex d)" 8) - "Ex na/ic (Zone 2)" 9) E - "Intrinsic safety, explosion-proof enclosure and R dust explosion protection (Ex ia + Ex d + Zone D/2D)" 8) 0) (not for DS III FF) FM + CSA intrinsic safe (is) F FM + CSA (is + ep) + Ex ia + Ex d (ATEX) 0) S With FM + CSA, Type of protection: - "Intrinsic Safe und Explosion Proof (is + xp)" 7) N C Electrical connection/cable entry Screwed gland M20 x.5 B Screwed gland ½-4 NPT C M2 connectors (stainless steel) ) 2) F Selection and Ordering data Article No. Pressure transmitters for absolute pressure from gauge pressure series SITRANS P DS III with PROFIBUS PA (PA) 7 M F SITRANS P DS III with FOUNDATION Fieldbus (FF) 7 M F Display Without display 0 Without visible display (display concealed, setting: bar) With visible display (setting: bar) 6 with customer-specific display 7 (setting as specified, Order code "Y2" or "Y22" required) Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation ) For oxygen application, add Order code E0. 2) Version 7MF42-DY... only up to max. span 200 mbar a (2.9 psia). ) When the manufacture s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC , it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here. 4) If the acceptance test certificate..is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. 5) The diaphragm seal is to be specified with a separate order number and must be included wiht the tranmitter order number, for example 7MF42.-..Y and 7MF B 6) The standard measuring cell filling for configurations with remote seals (Y) is silicone oil. 7) Without cable gland, with blanking plug. 8) With enclosed cable gland Ex ia and blanking plug. 9) Configurations with HAN and M2 connectors are only available in Ex ic. 0) Only in connection with IP65. ) Only in connection with Ex approval A, B, E or F. 2) M2 delivered without cable socket. SITRANS P DS III for absolute pressure (from gauge pressure series) /24 Siemens FI 0 205

36 Siemens AG 204 Selection and Ordering data Order code Further designs HART PA FF Add "-Z" to Article No. and specify Order code. Pressure transmitter with mounting bracket (x fixing angle, 2 x nut, 2 x U- washer or x bracket, 2 x nut, 2 x U- washer) made of: Steel A0 Stainless steel A02 Plug Han 7D (metal) A0 Han 8D (instead of Han 7D) A Angled A2 Han 8D (metal) A Cable sockets for M2 connectors A50 (metal (CuZn)) Rating plate inscription (instead of German) English B French B2 Spanish B Italian B4 Cyrillic (russian) B6 English rating plate B2 Pressure units in inh 2 0 and/or psi Quality inspection certificate (Five-step C factory calibration) to IEC ) Inspection certificate 2) C2 Acc. to EN Factory certificate C4 Acc. to EN Functional safety (SIL2) C20 Devices suitable for use according to IEC 6508 and IEC 65. Includes SIL conformity declaration Functional safety (PROFIsafe) C2 ) Certificate and PROFIsafe protocol Functional safety (SIL2/) C2 Devices suitable for use according to IEC 6508 and IEC 65. Includes SIL conformity declaration Device passport Russia C99 (For price request please contact the technical support Setting of upper limit of output signal to D ma Manufacturer's declaration acc. to NACE (MR and MR ) D07 Degree of protection IP66/IP68 D2 (only for M20 x.5 and ½-4 NPT) Supplied with oval flange D7 ( item), PTFE packing and screws in thread of oval flange Capri cable gland 4F CrNi and clamping device ( ) included D59 SITRANS P DS III for absolute pressure (from gauge pressure series) Selection and Ordering data Order code Further designs HART PA FF Add "-Z" to Article No. and specify Order code. Use in or on zone D/2D E0 (only together with type of protection "Intrinsic safety" (transmitter 7MF B.. Ex ia) and IP65) Oxygen application E0 (In the case of oxygen measurement and inert liquid max. 00 bar (450 psi) at 60 C (40 F)) Export approval Korea E CRN approval Canada E22 (Canadian Registration Number) Dual seal E24 Explosion-proof "Intrinsic safety" (Ex ia) E25 4) to INMETRO (Brazil) (only for transmitter 7MF B..) "Flameproof" explosion protection E26 4) according to INMETRO (Brazil) (only for transmitter 7MF D..) Explosion-proof "Intrinsic safety" (Ex ia E28 4) + Ex d) to INMETRO (Brazil) (only for transmitter 7MF P..) Ex Approval IEC Ex (Ex ia) E45 4) (only for transmitter 7MF B..) Ex Approval IEC Ex (Ex d) E46 4) (only for transmitter 7MF D..) Explosion-proof "Intrinsic safety" to E55 4) NEPSI (China) (only for transmitter 7MF B..) Explosion protection "Explosion-proof" E56 4) to NEPSI (China) (only for transmitter 7MF D..) Explosion-proof "Zone 2" to NEPSI E57 4) (China) (only for transmitter 7MF E..) Ex protection Ex ia, Ex d and Zone E58 4) 2 to NEPSI (China) (only for transmitter 7MF R..) "Intrinsic safety" and "Explosion-proof" E70 4) explosion protection acc. to Kosha (Korea) (only for transmitter 7MF [B, D]..-Z + E) Two coats of lacquer on casing and G0 cover (PU on epoxy) Transient protector 6 kv (lightning protection) J0 Oval flange NAM (ASTAVA) J06 We can offer shorter delivery times for configurations designated with the Quick Ship Symbol. For details see page 9/5 in the appendix. ) When the manufacture s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC , it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here. 2) If the acceptance test certificate. is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. ) Profisafe transmitters can only be operated with the S7 F Systems V6. configuration software in combination with S7-400H 4) Option does not include ATEX approval, but instead includes only the country-specific approval. Siemens FI /25

37 Siemens AG 204 SITRANS P DS III for absolute pressure (from gauge pressure series) Selection and Ordering data Order code Additional data HART PA FF Please add "-Z" to Article No. and specify Order code(s) and plain text. Measuring range to be set Y0 ) Specify in plain text (max. 5 characters): Y0:... up to... mbar a, bar a, kpa abs, MPa abs, psia 2) Stainless steel tag plate and entry in Y5 device variable (measuring point description) Max. 6 characters, specify in plain text: Y5:... Measuring point text (entry in device Y6 variable) Max. 27 characters, specify in plain text: Y6:... Entry of HART address (TAG) Y7 Max. 8 characters, specify in plain text: Y7:... Setting of pressure indication in pressure Y2 units Specify in plain text (standard setting: bar): Y2: mbar, bar, kpa, MPa, psi,... Note: The following pressure units can be selected: bar, mbar, mm H 2 O *), inh 2 O *), fth 2 O *), mmhg, inhg, psi, Pa, kpa, MPa, g/cm 2, kg/cm 2, Torr, ATM or % *) ref. temperature 20 C Setting of pressure indication in Y22 + non-pressure units ) Y0 Specify in plain text: Y22:... up to... l/min, m /h, m, USgpm,... (specification of measuring range in pressure units "Y0" is essential, unit with max. 5 characters) Preset bus address Y25 possible between and 26 Specify in plain text: Y25:... Damping adjustment in seconds Y0 ( s) We can offer shorter delivery times for configurations designated with the Quick Ship Symbol. For details see page 9/5 in the appendix. Factory mounting of valve manifolds, see accessories. Only Y0, Y5, Y6, Y7, Y2, Y22, Y25 and D05 can be factory preset = available ) Measuring accuracies for PROFIBUS PA transmitters with Option Y0 are calculated in the same way as for HART devices. 2) Only absolute pressure units selectable. Negative pressure values not permitted. ) Preset values can only be changed over SIMATIC PDM. /26 Siemens FI 0 205

38 Siemens AG 204 Dimensional drawings SITRANS P DS III for absolute pressure (from gauge pressure series) 5 (0.6) 4 (5.6) 74 (2.9) 5 (2.) 54 (2.) 27 (.) 24 (0.94) approx. 96 (.78) 7 (0.67) 29 (.4) 4) 84 (.) 5 approx. 40 (.6) Ø80 (.5) 7 (6.7) 9 SW (2.8) 2 50 (.97) 7 (4.6) 68 (2.68) 4 20 (4.72) (6.9) 27 (9.) Space for rotation of housing min. 90 (.54) 5) 2 (4.84) Ø ( ) 05 (4.) 2 4 Electronic side, digital display (longer overall length for cover with window) ) Terminal side ) Electrical connection: Screwed gland Pg,5 (adapter)(adapter) 2) ), Screwed gland M20 x,5 or Screwed gland ½-4 NPT or Han 7D/Han 8D 2) ) plug Harting adapter 5 Protective cover over keys 6 Blanking plug 7 Screw cover - safety bracket (only for type of protection "Explosion-proof enclosure", not shown in the drawing) 8 Process connection: Connection shank G½B or Oval flange 9 Mounting bracket (option) ) Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing 2) Not with type of protection "Explosion-proof enclosure" ) Not with type of protection "FM + CSA" [IS + XP]" 4) For Pg,5 with adapter approx. 45 mm (.77 inch) 5) Minimum distance for rotating SITRANS P DS III pressure transmitters for absolute pressure, from the pressure series, dimensions in mm (inch) Siemens FI /27

39 Siemens AG 204 SITRANS P DS III for absolute pressure (from differential pressure series) Technical specifications SITRANS P, DS III for absolute pressure (from the differential pressure series) HART Input Measured variable Spans (infinitely adjustable) or Span (min.... max.) Maximum operating nominal measuring range and pressure max. permissible operating pressure mbar a ( psia) mbar a ( psia) mbar a ( psia)... 0 bar a ( psia) bar a ( psia) 2 bar a (464 psia) 2 bar a (464 psia) 2 bar a (464 psia) 60 bar a (220 psia) 60 bar a (220 psia) (for connection thread M0 and 7/6-20 UNF in the process flanges) Absolute pressure PROFIBUS PA and FOUNDATION Fieldbus Nominal measuring range 250 mbar a (.62 psia) 00 bar a (8.85 psia) 5 bar a (72.5 psia) 0 bar a (45 psia) 00 bar a (450 psia) Maximum operating pressure 2 bar a (464 psia) 2 bar a (464 psia) 2 bar a (464 psia) 60 bar a (220 psia) 60 bar a (220 psia) (for connection thread M0 and 7/6-20 UNF in the process flanges) Lower measuring limit Measuring cell with silicone oil filling 0 mbar a (0 psia) Upper measuring limit 00 % of max. span Output Output signal ma Digital PROFIBUS PA and FOUNDATION Fieldbus signal Lower limit (infinitely adjustable).55 ma, factory preset to.84 ma - Upper limit (infinitely adjustable) 2 ma, factory preset to 20.5 ma or optionally - set to 22.0 ma Load Without HART R B (U H V)/0.02 A in, - U H : Power supply in V With HART R B = (SIMATIC PDM) or - R B = (HART Communicator) Physical bus - IEC Protection against polarity reversal Protected against short-circuit and polarity reversal. Each connection against the other with max. supply voltage. Electrical damping (step width 0. s) Set to 2 s ( s) Measuring accuracy Acc. to IEC Reference conditions (All error data refer always refer to the set span) Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, silicone oil filling, room temperature 25 C (77 F) Span ratio r = max. span/set span Nominal measuring range ratio r = nominal measuring range/set measuring range Error in measurement at limit setting incl. hysteresis and reproducibility Linear characteristic -r 0 0. % 0. % - 0 < r % 0.2 % Long-term stability (0. r) %/year (0. r) %/year (temperature change ± 0 C (± 54 F)) Influence of ambient temperature at C ( F) (0. r+0.2)% ) (0. r + 0.2) % ) at C and C (0. r+0.5)%/0k (0. r + 0.5) %/0 K ( F and F) Measured Value Resolution of nominal measuring range /28 Siemens FI 0 205

40 Siemens AG 204 SITRANS P, DS III for absolute pressure (from the differential pressure series) Rated conditions Degree of protection (to IEC 60529) Temperature of medium Measuring cell with silicone oil filling Measuring cell with inert filling liquid In conjunction with dust explosion protection Ambient conditions Ambient temperature HART SITRANS P DS III for absolute pressure (from differential pressure series) IP66 (optional IP66/IP68), NEMA 4X C ( F) C ( F) C ( F) PROFIBUS PA and FOUNDATION Fieldbus - Transmitter C ( F) (with 4-wire connection, observe temperature values of supplementary 4-wire electronics) - Display readable C ( F) Storage temperature C ( F) Climatic class - Condensation Relative humidity % Condensation permissible, suitable for use in the tropics Electromagnetic Compatibility - Emitted interference and interference immunity Acc. to IEC 626 and NAMUR NE 2 Design Weight (without options) 4.5 kg ( 9.9 (lb) Enclosure material Low-copper die-cast aluminum, GD-AlSi2 or stainless steel precision casting, mat. no Wetted parts materials Seal diaphragm Stainless steel, mat. no..4404/6l or Hastelloy C276, mat. no , Monel, mat. no , tantalum or gold Process flanges and sealing screw Stainless steel, mat. no..4408, Hastelloy C4, mat. no or Monel, mat. no O-Ring FPM (Viton) or optionally: PTFE, FEP, FEPM and NBR Measuring cell filling Silicone oil or inert filling liquid (maximum value with oxigen measurement pressure 00 bar (450 psi) at 60 C (40 F)) Process connection ¼-8 NPT and flange connection with mounting thread M0 to DIN 92 or 7 / 6-20 UNF to IEC 658 Material of mounting bracket Steel Sheet-steel, Mat. No..00, chrome-plated Stainless steel Sheet stainless steel, mat. no..40 (SS 04) Power supply U H Supplied through bus Terminal voltage on transmitter V DC V DC in intrinsically-safe mode Separate 24 V power supply necessary - No Bus voltage Not Ex V With intrinsically-safe operation V Current consumption Basic current (max.) ma Start-up current basic current - Yes Max. current in event of fault ma Fault disconnection electronics (FDE) available - Yes Siemens FI /29

41 Siemens AG 204 SITRANS P DS III for absolute pressure (from differential pressure series) SITRANS P, DS III for absolute pressure (from the differential pressure series) HART PROFIBUS PA and FOUNDATION Fieldbus Certificates and approvals Classification according to PED 97/2/EC For gases of fluid group and liquids of fluid group ; complies with requirements of article, paragraph (sound engineering practice) Explosion protection Intrinsic safety "i" PTB ATEX 2007 X - Marking Ex II /2 G Ex ia/ib IIC T4/T5/T6 Ga/Gb - Permissible ambient temperature C ( F) temperature class T4; C ( F) temperature class T5; C ( F) temperature class T6 - Connection To certified intrinsically-safe circuits with peak values: U i = 0 V, I i = 00 ma, P i = 750 mw; R i =00 FISCO supply unit: U o = 7.5 V, I o = 80 ma, P o = 5.2 W Linear barrier: U o = 24 V, I o = 250 ma, P o =.2 W - Effective internal inductance/capacitance L i = 0.4 mh, C i = 6 nf L i = 7 H, C i =. nf Explosion-proof "d" PTB 99 ATEX 60 - Marking Ex II /2 G Ex d IIC T4/T6 Gb - Permissible ambient temperature C ( F) temperature class T4; C ( F) temperature class T6 - Connection To circuits with values: U H = V DC To circuits with values: U H = V DC Dust explosion protection for zone 20 PTB 0 ATEX Marking Ex II D IP65 T 20 C Ex II /2 D IP65 T 20 C - Permissible ambient temperature C ( F) - Max. surface temperature 20 C (248 F) - Connection To certified intrinsically-safe circuits with peak values: U i = 0 V, I i = 00 ma, P i = 750 mw, R i = 00 FISCO supply unit: U o = 7.5 V, I o = 80 ma, P o = 5.2 W Linear barrier: U o = 24 V, I o = 250 ma, P o =.2 W - Effective internal inductance/capacitance L i = 0.4 mh, C i = 6 nf L i = 7 H, C i =. nf Dust explosion protection for zone 2/22 PTB 0 ATEX Marking Ex II 2 D IP65 T 20 C - Connection To circuits with values: U H = V DC; P max =.2 W Type of protection "n" (zone 2) PTB ATEX 2007 X - Marking Ex II 2/ G Ex na II T4/T5/T6 Gc Ex II 2/ G Ex ic IIC T4/T5/T6 Gc - Connection (Ex na) U m = 45 V U m = 2 V - Connection (Ex ic) To circuits with values: U i = 45 V To circuits with values: U H = V DC; P max = W FISCO supply unit ic: U o = 7.5 V, I o = 570 ma Linear barrier: U o = 2 V, I o = 2 ma, P o = W - Effective internal inductance/capacitance L i = 0.4 mh, C i = 6 nf L i = 7 H, C i =. nf Explosion protection acc. to FM Certificate of Compliance Identification (XP/DIP) or (IS); (NI) CL I, DIV, GP ABCD T4...T6; CL II, DIV, GP EFG; CL III; CL I, ZN 0/ AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III Explosion protection to CSA Certificate of Compliance Identification (XP/DIP) or (IS) CL I, DIV, GP ABCD T4...T6; CL II, DIV, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III ) Conversion of temperature error per 28 C. Valid for temperature range C < (0.08. r + 0.6) % / 28 C (50 F). /0 Siemens FI 0 205

42 Siemens AG 204 HART communication HART Protocol HART Version 5.x Software for computer PROFIBUS PA communication Simultaneous communication with master class 2 (max.) The address can be set using Cyclic data usage Output byte Input byte Internal preprocessing Device profile Function blocks 2 Analog input - Adaptation to customer-specific process variables SIMATIC PDM 4 Configuration tool or local operation (standard setting address 26) 5 (one measured value) or 0 (two measured values) 0,, or 2 (register operating mode and reset function for metering) PROFIBUS PA Profile for Process Control Devices Version.0, class B Yes, linearly rising or falling characteristic - Electrical damping, adjustable s - Simulation function Input /Output - Failure mode parameterizable (last good value, substitute value, incorrect value) - Limit monitoring Yes, one upper and lower warning limit and one alarm limit respectively Register (totalizer) Can be reset, preset, optional direction of counting, simulation function of register output - Failure mode parameterizable (summation with last good value, continuous summation, summation with incorrect value) - Limit monitoring One upper and lower warning limit and one alarm limit respectively Physical block Transducer blocks 2 Pressure transducer block - Can be calibrated by applying Yes two pressures - Monitoring of sensor limits Yes - Specification of a container Max. 0 nodes characteristic with - Square-rooted characteristic Yes for flow measurement - Gradual volume suppression Parameterizable and implementation point of square-root extraction - Simulation function for measured pressure value and sensor temperature Constant value or over parameterizable ramp function SITRANS P DS III for absolute pressure (from differential pressure series) FOUNDATION Fieldbus communication Function blocks function blocks analog input, function block PID Analog input - Adaptation to customer-specific process variables characteristic Yes, linearly rising or falling - Electrical damping, adjustable 0 to 00 s - Simulation function Output/input (can be locked within the device with a bridge) - Failure mode parameterizable (last good value, substitute value, incorrect value) - Limit monitoring Yes, one upper and lower warning limit and one alarm limit respectively - Square-rooted characteristic Yes for flow measurement PID Standard FOUNDATION Fieldbus function block Physical block resource block Transducer blocks transducer block Pressure with calibration, transducer block LCD Pressure transducer block - Can be calibrated by applying Yes two pressures - Monitoring of sensor limits Yes - Simulation function: Measured pressure value, sensor temperature and electronics temperature Constant value or over parameterizable ramp function Siemens FI /

43 Siemens AG 204 Y Selection and Ordering data Article No. Pressure transmitters for absolute pressure from differential pressure series, SITRANS P DS III with HART 7 M F Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Measuring cell cleaning Silicone oil normal Inert liquid ) grease-free to cleanliness level 2 Measuring span (min.... max.) mbar a ( psia) D mbar a ( psia) F bar a ( psia) G... 0 bar a ( psia) H bar a ( psia) K E Wetted parts materials Seal diaphragm Parts of measuring cell Stainless steel Stainless steel A Hastelloy Stainless steel B Hastelloy Hastelloy C Tantalum Tantalum E Monel Monel H Gold Gold L Version for diaphragm seal2) ) 4) 5) 6) Process connection Female thread ¼-8 NPT with flange connection Sealing screw opposite process connection - Mounting thread 7 / 6-20 UNF to EN Mounting thread M0 to DIN 92 0 (only for replacement requirement) Vent on side of process flange 7) - Mounting thread 7 / 6-20 UNF to EN Mounting thread M0 to DIN 92 4 (only for replacement requirement) Non-wetted parts materials process flange screws Electronics housing Stainless steel Die-cast aluminum 2 Stainless steel Stainless steel precision casting 8) Version Standard versions International version, English label inscriptions, 2 documentation in 5 languages on CD (no Order code selectable) Explosion protection None A With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" B - "Explosion-proof (Ex d)" 9) D - "Intrinsic safety and flameproof enclosure" P (Ex ia + Ex d)" 0) - "Ex na/ic (Zone 2)" ) E - "Intrinsic safety, explosion-proof enclosure and R dust explosion protection (Ex ia+ Ex d + Zone D/2D)" 0)2) FM + CSA intrinsic safe (is) F FM + CSA (is + ep) + Ex ia + Ex d (ATEX) 2) S With FM + CSA, Type of protection: - "Intrinsic Safe und Explosion Proof (is + xp)" 9) N C Electrical connection/cable entry Screwed gland Pg.5 ) A Screwed gland M20 x.5 B Screwed gland ½-4 NPT C Han 7D plug (plastic housing) incl. mating D connector ) M2 connectors (stainless steel) 4) 5) F Selection and Ordering data Article No. Pressure transmitters for absolute pressure 7 M F 4 - from differential pressure series, SITRANS P DS III with HART Display Without display 0 Without visible display (display concealed, setting: ma) With visible display (setting: ma) 6 with customer-specific display 7 (setting as specified, Order code "Y2" or "Y22" required) Power supply units see Chap. 7 "Supplementary Components". Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation Sealing plug(s) or sealing screw(s) for the process flanges(s) ) For oxygen applications, add Order code E0. 2) Version 7MF4-DY... only up to max. span 200 mbar a (2.9 psia). ) When the manufacture s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC , it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here. 4) If the acceptance test certificate..is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. 5) The diaphragm seal is to be specified with a separate order number and must be included wiht the tranmitter order number, for example 7MF4.-..Y und 7MF B 6) The standard measuring cell filling for configurations with remote seals (Y) is silicone oil. 7) Not for span " bar a ( psia)". Position of the top vent valve in the process flange (see dimensional drawing). 8) Not in conjunction with Electrical connection "Screwed gland Pg.5" and "Han7D plug". 9) Without cable gland, with blanking plug 0) With enclosed cable gland Ex ia and blanking plug ) Configurations with HAN and M2 connectors are only available in Ex ic. 2) Only in connection with IP65. ) Only in connection with Ex approval A, B or E. 4) Only in connection with Ex approval A, B, E or F. 5) M2 delivered without cable socket. SITRANS P DS III for absolute pressure (from differential pressure series) /2 Siemens FI 0 205

44 Siemens AG 204 Y Selection and Ordering data Article No. Pressure transmitter for absolute pressure from differential pressure series SITRANS P DS III with PROFIBUS PA (PA) 7 M F SITRANS P DS III with FOUNDATION Fieldbus (FF) 7 M F Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Measuring cell cleaning Silicone oil normal Inert liquid ) grease-free to cleanliness level 2 Nominal measuring range 250 mbar a (.62 psia) D 00 mbar a (8.85 psia) F 5 bar a (72.5 psia) G 0 bar a (45 psia) H 00 bar a (450 psia) K E Wetted parts materials Seal diaphragm Parts of measuring cell Stainless steel Stainless steel A Hastelloy Stainless steel B Hastelloy Hastelloy C Tantalum Tantalum E Monel Monel H Gold Gold L Version as diaphragm seal 2) ) 4) 5) 6) Process connection Female thread ¼-8 NPT with flange connection Sealing screw opposite process connection - Mounting thread 7 / 6-20 UNF to IEC Mounting thread M0 to DIN 92 0 (only for replacement requirement) Vent on side of process flange 7) - Mounting thread 7 / 6-20 UNF to IEC Mounting thread M0 to DIN 92 4 (only for replacement requirement) Non-wetted parts materials process flange screws Electronics housing Stainless steel Die-cast aluminum 2 Stainless steel Stainless steel precision casting Version Standard versions International version, English label inscriptions, 2 documentation in 5 languages on CD (no Order code selectable) Explosion protection None A With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" B - "Explosion-proof (Ex d)" 8) D - "Intrinsic safety and flameproof enclosure" P (Ex ia + Ex d)" 9) - "Ex na/ic (Zone 2)" 0) E - "Intrinsic safety, explosion-proof enclosure and R dust explosion protection (Ex ia + Ex d + Zone D/2D)" 9) ) (not for DS III FF) FM + CSA intrinsic safe (is) F FM + CSA (is + ep) + Ex ia + Ex d (ATEX) ) S With FM + CSA, Type of protection: - "Intrinsic Safe und Explosion Proof (is + xp)" 8) N C SITRANS P DS III for absolute pressure (from differential pressure series) Selection and Ordering data Article No. Pressure transmitter for absolute pressure from differential pressure series SITRANS P DS III with PROFIBUS PA (PA) 7 M F SITRANS P DS III with FOUNDATION Fieldbus (FF) 7 M F Display Without display 0 Without visible display (display concealed, setting: bar) With visible display (setting: bar) 6 With customer-specific display (setting as 7 specified, Order code "Y2" required) Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation Sealing plug(s) or sealing screw(s) for the process flanges(s) ) For oxygen application, add Order code E0. 2) Version 7MF44-DY... only up to max. span 200 mbar a (80 inh 2 O a). ) When the manufacture s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC , it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here. 4) If the acceptance test certificate..is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. 5) The diaphragm seal is to be specified with a separate order number and must be included wiht the tranmitter order number, for example 7MF4.-..Y und 7MF B 6) The standard measuring cell filling for configurations with remote seals (Y) is silicone oil. 7) Not for nominal measuring range 00 bar a (450 psia). Position of the top vent valve in the process flange (see dimensional drawing). 8) Without cable gland, with blanking plug 9) With enclosed cable gland Ex ia and blanking plug 0) Configurations with HAN and M2 connectors are only available in Ex ic. ) Only in connection with IP65. 2) Only in connection with Ex approval A, B, E or F. ) M2 delivered without cable socket Electrical connection/cable entry Screwed gland M20 x.5 Screwed gland ½-4 NPT M2 connectors (stainless steel) 2)) B C F Siemens FI /

45 Siemens AG 204 Selection and Ordering data Order code Further designs HART PA FF Add "-Z" to Article No. and specify Order code. Pressure transmitter with mounting bracket (x fixing angle, 2 x nut, 2 x U- washer or x bracket, 2 x nut, 2 x U- washer) made of: Steel A0 Stainless steel A02 O-rings for process flanges (instead of FPM (Viton)) PTFE (Teflon) A20 FEP (with silicone core, approved for food) A2 FFPM (Kalrez, compound 4079), for measured medium temperatures C ( F)) A22 NBR (Buna N) A2 Plug Han 7D (metal) A0 Han 8D (instead of Han 7D) A Angled A2 Han 8D (metal) A Sealing screw A40 ¼-8 NPT, with valve in mat. of process flanges Cable sockets for M2 connectors A50 (metal (CuZn)) Rating plate inscription (instead of German) English B French B2 Spanish B Italian B4 Cyrillic (russian) B6 English rating plate B2 Pressure units in inh 2 0 and/or psi Quality inspection certificate (Five-step factory calibration) to IEC ) C Inspection certificate 2) C2 Acc. to EN Factory certificate C4 Acc. to EN Functional safety (SIL2) C20 Devices suitable for use according to IEC 6508 and IEC 65. Includes SIL conformity declaration Functional safety (PROFIsafe) C2 ) Certificate and PROFIsafe protocol Functional safety (SIL2/) C2 Devices suitable for use according to IEC 6508 and IEC 65. Includes SIL conformity declaration Device passport Russia C99 (For price request please contact the technical support Setting of upper limit of D05 output signal to 22.0 ma Manufacturer's declaration acc. to NACE D07 (MR and MR ) (only together with seal diaphragm made of Hastelloy and stainless steel) Degree of protection IP66/IP68 D2 (only for M20 x.5 and ½-4 NPT) Supplied with oval flange D7 ( item), PTFE packing and screws in thread of process flange Capri cable gland 4F CrNi and clamping device ( ) included D59 Selection and Ordering data Order code Further designs Add "-Z" to Article No. and specify Order code. HART PA FF Use in or on zone D/2D E0 (only together with type of protection "Intrinsic safety" (transmitter 7MF B.. Ex ia) and IP65) Oxygen application E0 (In the case of oxygen measurement and inert liquid max. 00 bar (450 psi) at 60 C (40 F)) Export approval Korea E CRN approval Canada E22 (Canadian Registration Number) Dual seal E24 Explosion-proof "Intrinsic safety" (Ex ia) to E25 4) INMETRO (Brazil) (only for transmitter 7MF B..) "Flameproof" explosion protection according E26 4) to INMETRO (Brazil) (only for transmitter 7MF D..) Explosion-proof "Intrinsic safety" (Ex ia + E28 4) Ex d) to INMETRO (Brazil) (only for transmitter 7MF P..) Ex Approval IEC Ex (Ex ia) E45 4) (only for transmitter 7MF B..) Ex Approval IEC Ex (Ex d) E46 4) (only for transmitter 7MF D..) Explosion-proof "Intrinsic safety" E55 4) to NEPSI (China) (only for transmitter 7MF B..) Explosion protection "Explosion-proof" to E56 4) NEPSI (China) (only for transmitter 7MF D..) Explosion-proof "Zone 2" to NEPSI (China) E57 4) (only for transmitter 7MF E..) Ex protection Ex ia, Ex d and Zone 2 E58 4) to NEPSI (China) (only for transmitter 7MF R..) "Intrinsic safety" and "Explosion-proof" E70 4) explosion protection acc. to Kosha (Korea) (only for transmitter 7MF [B, D]..-Z + E) Two coats of lacquer on casing and cover G0 (PU on epoxy) Interchanging of process connection side H0 Vent on side for gas measurements H02 Stainless steel process flanges for vertical H0 differential pressure lines (not together with K0, K02 and K04) 5) Transient protector 6 kv (lightning protection) J0 Chambered graphite gasket for process J02 flange Chambered PTFE graphite gasket J0 EPDM O-rings for process flange with J05 approval (WRC/WRAS) Vent valve or blanking plug of process J08 flange welded-in (orientation: on right when viewing the display) 6) Vent valve or blanking plug of process flange welded-in (orientation: on left when viewing the display) 6) J09 SITRANS P DS III for absolute pressure (from differential pressure series) /4 Siemens FI 0 205

46 Siemens AG 204 Further designs HART PA FF Add "-Z" to Article No. and specify Order code. Process flange Hastelloy K0 Monel K02 Stainless steel with PVDF insert K04 max. PN 0 (MAWP 45 psi), max. temperature of medium 90 C (94 F) For ½-4 NPT inner process connection on the side in the middle of the process flange, vent valve not possible ) When the manufacture s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC , it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here. 2) If the acceptance test certificate..is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. ) Profisafe transmitters can only be operated with the S7 F Systems V6. configuration software in combination with S7-400H 4) Option does not include ATEX approval, but instead includes only the country-specific approval. 5) Not suitable for connection of remote seals. 6) Blanking plug is standard configuration. Order option A40 if a vent valve is required instead of a blanking plug. SITRANS P DS III for absolute pressure (from differential pressure series) Selection and Ordering data Order code Selection and Ordering data Order code Additional data HART PA FF Please add "-Z" to Article No. and specify Order code(s) and plain text. Measuring range to be set Y0 ) Specify in plain text (max. 5 characters): Y0:... up to... mbar a, bar a, kpa abs, MPa abs, psia 2) Stainless steel tag plate and entry in Y5 device variable (measuring point description) Max. 6 characters, specify in plain text: Y5:... Measuring point text (entry in device variable) Y6 Max. 27 characters, specify in plain text: Y6:... Entry of HART address (TAG) Y7 Max. 8 characters, specify in plain text: Y7:... Setting of pressure indication in pressure Y2 units Specify in plain text (standard setting: bar): Y2: mbar, bar, kpa, MPa, psi,... Note: The following pressure units can be selected: bar, mbar, mm H 2 O *), inh 2 O *), fth 2 O *), mmhg, inhg, psi, Pa, kpa, MPa, g/cm 2, kg/cm 2, Torr, ATM or % *) ref. temperature 20 C Setting of pressure indication in Y22 + non-pressure units ) Y0 Specify in plain text: Y22:... up to... l/min, m /h, m, USgpm,... (specification of measuring range in pressure units "Y0" is essential, unit with max. 5 characters) Preset bus address Y25 possible between and 26 Specify in plain text: Y25:... Damping adjustment in seconds Y0 ( s) Factory mounting of valve manifolds, see accessories. Only Y0, Y5, Y6, Y7, Y2, Y22, Y25 and D05 can be factory preset = available ) Measuring accuracies for PROFIBUS PA transmitters with Option Y0 are calculated in the same way as for HART devices. 2) Only absolute pressure units selectable. Negative pressure values not permitted. ) Preset values can only be changed over SIMATIC PDM. Siemens FI /5

47 Siemens AG 204 SITRANS P DS III for absolute pressure (from differential pressure series) Dimensional drawings 5 (0.6) 4 (5.6) 69 (2.7) 5 (2.) 29 (.4) 4) 24 (0.94) 84 (.) 5 Ø80 (.5) 2 50 (.97) 28 (5.04) (6.54) 2 4 (5.28) min. 90 (.54) 5) Space for rotation of housing approx. 96 (.78) 7 (0.67) 52 (2.05) (.8) 262 (0.) 4 72 (2.8) 05 (4.) 68 (2.7) 20 (4.7) Electronic side, digital display (longer overall length for cover with window) ) Terminal side ) Electrical connection: Screwed gland Pg,5 (adapter)(adapter) 2) ), Screwed gland M20 x,5 or Screwed gland ½-4 NPT or Han 7D/ Han 8D 2) ) plug Harting adapter Protective cover over keys 6 Blanking plug 7 Screw cover - safety bracket (only for type of protection "Explosion-proof enclosure", not shown in the drawing) 8 Lateral venting for liquid measurement (Standard) 9 Lateral venting for gas measurement (suffix H02) 0 Mounting bracket (option) Sealing screw with valve (option) 2 Process connection: ¼-8 NPT (IEC 658) ) Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing 2) Not with type of protection "Explosion-proof enclosure" ) Not with type of protection "FM + CSA" [IS + XP]" 4) 92 mm (.62 inch) for minimum distance to permit rotation with indicator 5) For Pg,5 with adapter approx. 45 mm (.77 inch) SITRANS P DS III pressure transmitters for absolute pressure, from the differential pressure series, dimensions in mm (inch) /6 Siemens FI 0 205

48 Siemens AG 204 Technical specifications SITRANS P, DS III for differential pressure and flow Input Measured variable Spans (infinitely adjustable) or nominal measuring range and max. permissible operating pressure HART Span (min.... max.) mbar ( inh 2 O) 2 bar (464 psi) mbar ( inh 2 O) 60 bar (220 psi) SITRANS P DS III for differential pressure and flow PROFIBUS PA and FOUNDATION Fieldbus Differential pressure and flow Maximum Nominal measuring range operating pressure Maximum operating pressure 20 mbar (8 inh 2 O) 2 bar (464 psi) 60 mbar (24 inh 2 O) 60 bar (220 psi) mbar ( inh 2 O) 250 mbar (00 inh 2 O) mbar ( inh 2 O) 600 mbar (240 inh 2 O) mbar ( inh 2 O) 600 mbar (642 inh 2 O) mbar ( inh 2 O) 5 bar (2000 inh 2 O) bar ( psi) 0 bar (45 psi) mbar ( inh 2 O) 420 bar 250 mbar (00 inh 2 O) 420 bar mbar ( inh 2 O) (609 psi) 600 mbar (240 inh 2 O) (609 psi) mbar ( inh 2 O) 600 mbar (642 inh 2 O) mbar ( inh 2 O) 5 bar (2000 inh 2 O) bar ( psi) 0 bar (45 psi) Lower measuring limit Measuring cell with silicone oil filling -00 % of max. span or 0 mbar a (0.44 psia) (- % with 0 bar (45 psi) measuring cell) Upper measuring limit 00 % of max. span (for oxygen version and inert filling liquid; max. 20 bar (740 psi)) Output Output signal ma Digital PROFIBUS PA and FOUNDATION Fieldbus signal Lower limit (infinitely adjustable).55 ma, factory preset to.84 ma - Upper limit (infinitely adjustable) 2 ma, factory preset to 20.5 ma or optionally set - to 22.0 ma Load Without HART R B (U H V)/0.02 A in, - U H : Power supply in V With HART R B = (SIMATIC PDM) or - R B = (HART Communicator) Physical bus - IEC Protection against polarity reversal Protected against short-circuit and polarity reversal. Each connection against the other with max. supply voltage. Electrical damping (step width 0. s) Set to 2 s ( s) Measuring accuracy Acc. to IEC Reference conditions (All error data refer always refer to the set span) Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, silicone oil filling, room temperature 25 C (77 F) Span ratio r = max. span/set span Nominal measuring range ratio r = nominal measuring range/set measuring range Error in measurement at limit setting incl. hysteresis and reproducibility Linear characteristic -r 0 ( r ) % ( r ) % - 0 < r 0 ( r ) % ( r ) % -0<r 00 (0.005 r ) % (0.005 r ) % Square-rooted characteristic (flow > 50 %) -r 0 0. % 0. % - 0 < r % 0.2 % Square-rooted characteristic (flow > %) -r % 0.2 % - 0 < r % 0.4 % Siemens FI /7

49 Siemens AG 204 SITRANS P DS III for differential pressure and flow SITRANS P, DS III for differential pressure and flow HART PROFIBUS PA and FOUNDATION Fieldbus Long-term stability (temperature change ± 0 C (± 54 F)) 250, 600, 600 and 5000 mbar (0.29, 0.87, 2.2 and 7.25 psi)-measuring cell (0.25 r) per 5 years (0.25 r) per 5 years 20 mbar (8 inh 2 O)-measuring cell (0.2 r) per year (0.2 r) per year 60 mbar (24 inh 2 O)-measuring cell (0.25 r) % per 5 years (0.25 r) % per 5 years 0 bar (45 psi)-measuring cell (0.25 r) % per 5 years (0.25 r) % per 5 years Influence of ambient temperature (Twice the value with 20 mbar (8 inh 2 O)- measuring cell at C ( F) (0.08 r + 0.) % ) (0.08 r + 0.) % ) at C and C (0. r + 0.5) %/0 K (0. r + 0.5) %/0 K ( F and F) Influence of static pressure on the zero point (PKN) (0.5 r) % per 70 bar (05 psi) (0.5 r) % per 70 bar (05 psi) - 20 mbar (0.29 psi)-measuring cell (0.5 r) % per 2 bar (464 psi) (0.5 r) % per 2 bar (464 psi) on the span (PKS) 0.4 % per 70 bar (05 psi) 0.4 % per 70 bar (05 psi) - 20 mbar (0.29 psi)-measuring cell 0.2 % per 2 bar (464 psi) 0.2 % per 2 bar (464 psi) Measured Value Resolution of nominal measuring range Rated conditions Degree of protection (to EN 60529) IP66 (optional IP66/IP68), NEMA 4X Temperature of medium Measuring cell with silicone oil filling C ( F) C ( F) with 0 bar measuring cell Measuring cell with inert filling liquid C ( F) In conjunction with dust explosion protection C ( F) Ambient conditions Ambient temperature - Transmitter C ( F) (with 4-wire connection, observe temperature values of supplementary 4-wire electronics) - Display readable C ( F) Storage temperature C ( F) Climatic class - Condensation Relative humidity % Condensation permissible, suitable for use in the tropics Electromagnetic Compatibility - Emitted interference and interference Acc. to IEC 626 and NAMUR NE 2 immunity Design Weight (without options) Die-cast aluminum: 4.5 kg ( 9.9 lb) Stainless steel precision casting: 7. kg ( 5.6 lb) Enclosure material Low-copper die-cast aluminum, GD-AlSi2 or stainless steel precision casting, mat. no Wetted parts materials Seal diaphragm Stainless steel, mat. no..4404/6l or Hastelloy C276, mat. no , Monel, mat. no , tantalum or gold Measuring cell filling Silicone oil or inert filling liquid (maximum value with oxygen measurement pressure 00 bar (450 psi) at 60 C (40 F)) Process connection Female thread ¼-8 NPT and flange connection with mounting thread M0 to DIN 92 or / 6-20 UNF to IEC 658 Material of mounting bracket Steel Sheet-steel, Mat. No..00, chrome-plated Stainless steel Sheet stainless steel, mat. no..40 (SS 04) /8 Siemens FI 0 205

50 Siemens AG 204 SITRANS P, DS III for differential pressure and flow Power supply U H Terminal voltage on transmitter HART V DC V DC in intrinsically-safe mode SITRANS P DS III for differential pressure and flow PROFIBUS PA and FOUNDATION Fieldbus Supplied through bus - Separate 24 V power supply necessary - No Bus voltage Not Ex V With intrinsically-safe operation V Current consumption Basic current (max.) ma Start-up current basic current - Yes Max. current in event of fault ma Fault disconnection electronics (FDE) available - Yes Certificates and approvals Classification according to PED 97/2/EC PN 2/60 (MAWP 464/220 psi) For gases of fluid group and liquids of fluid group ; complies with requirements of article, paragraph (sound engineering practice) PN 420 (MAWP 6092 psi) For gases of fluid group and liquids of fluid group ; complies with basic safety requirements of Article, paragraph (appendix ); assigned to category III, conformity evaluation module H by the TÜV Nord. Explosion protection Intrinsic safety "i" PTB ATEX 2007 X - Marking Ex II /2 G Ex ia/ib IIC T4/T5/T6 Ga/Gb - Permissible ambient temperature C ( F) temperature class T4; C ( F) temperature class T5; C ( F) temperature class T6 - Connection To certified intrinsically-safe circuits with peak values: U i = 0 V, I i = 00 ma, P i = 750 mw; R i =00 FISCO supply unit: U o = 7.5 V, I o = 80 ma, P o = 5.2 W Linear barrier: U o = 24 V, I o = 250 ma, P o =.2 W - Effective internal inductance/capacitance L i = 0.4 mh, C i = 6 nf L i = 7 H, C i =. nf Explosion-proof "d" PTB 99 ATEX 60 - Marking Ex II /2 G Ex d IIC T4/T6 Gb - Permissible ambient temperature C ( F) temperature class T4; C ( F) temperature class T6 - Connection To circuits with values: U H = V DC To circuits with values: U H = V DC Dust explosion protection for zone 20 PTB 0 ATEX Marking Ex II D IP65 T 20 C Ex II /2 D IP65 T 20 C - Permissible ambient temperature C ( F) - Max. surface temperature 20 C (248 F) - Connection To certified intrinsically-safe circuits with peak values: U i = 0 V, I i = 00 ma, P i = 750 mw, R i = 00 FISCO supply unit: U o = 7.5 V, I o = 80 ma, P o = 5.2 W Linear barrier: U o = 24 V, I o = 250 ma, P o = W - Effective internal inductance/capacitance L i = 0.4 mh, C i = 6 nf L i = 7 H, C i =. nf Dust explosion protection for zone 2/22 PTB 0 ATEX Marking Ex II 2 D IP65 T 20 C - Connection To circuits with values: U H = V DC; P max =.2 W To circuits with values: U H = V DC; P max = W Siemens FI /9

51 Siemens AG 204 SITRANS P DS III for differential pressure and flow SITRANS P, DS III for differential pressure and flow HART PROFIBUS PA and FOUNDATION Fieldbus Type of protection "n" (zone 2) PTB ATEX 2007 X - Marking Ex II 2/ G Ex na IIC T4/T5/T6 Gc Ex II 2/ G Ex ic IIC T4/T5/T6 Gc - Connection (Ex na) U m = 45 V U m = 2 V - Connection (Ex ic) To circuits with values: U i = 45 V FISCO supply unit ic: U o = 7.5 V, I o = 570 ma Linear barrier: U o = 2 V, I o = 2 ma, P o = W - Effective internal inductance/capacitance L i = 0.4 mh, C i = 6 nf L i = 7 H, C i =. nf Explosion protection acc. to FM Certificate of Compliance Identification (XP/DIP) or (IS); (NI) CL I, DIV, GP ABCD T4...T6; CL II, DIV, GP EFG; CL III; CL I, ZN 0/ AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III Explosion protection to CSA Certificate of Compliance Identification (XP/DIP) or (IS) CL I, DIV, GP ABCD T4...T6; CL II, DIV, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III ) Conversion of temperature error per 28 C. Valid for temperature range C < ( r ) % / 28 C (50 F). /40 Siemens FI 0 205

52 Siemens AG 204 HART communication HART Protocol HART Version 5.x Software for PC PROFIBUS PA communication Simultaneous communication with master class 2 (max.) The address can be set using Cyclic data usage Output byte Input byte Internal preprocessing Device profile Function blocks 2 Analog input - Adaptation to customer-specific process variables SIMATIC PDM 4 Configuration tool or local operation (standard setting address 26) 5 (one measured value) or 0 (two measured values) 0,, or 2 (register operating mode and reset function for metering) PROFIBUS PA Profile for Process Control Devices Version.0, class B Yes, linearly rising or falling characteristic - Electrical damping, adjustable s - Simulation function Input /Output - Failure mode parameterizable (last good value, substitute value, incorrect value) - Limit monitoring Yes, one upper and lower warning limit and one alarm limit respectively Register (totalizer) Can be reset, preset, optional direction of counting, simulation function of register output - Failure mode parameterizable (summation with last good value, continuous summation, summation with incorrect value) - Limit monitoring One upper and lower warning limit and one alarm limit respectively Physical block Transducer blocks 2 Pressure transducer block - Can be calibrated by applying Yes two pressures - Monitoring of sensor limits Yes - Specification of a container Max. 0 nodes characteristic with - Square-rooted characteristic Yes for flow measurement - Gradual volume suppression Parameterizable and implementation point of square-root extraction - Simulation function for measured pressure value and sensor temperature Constant value or over parameterizable ramp function SITRANS P DS III for differential pressure and flow FOUNDATION Fieldbus communication Function blocks function blocks analog input, function block PID Analog input - Adaptation to customerspecific process variables characteristic Yes, linearly rising or falling - Electrical damping, adjustable s - Simulation function Output/input (can be locked within the device with a bridge) - Failure mode parameterizable (last good value, substitute value, incorrect value) - Limit monitoring Yes, one upper and lower warning limit and one alarm limit respectively - Square-rooted characteristic Yes for flow measurement PID Standard FOUNDATION Fieldbus function block Physical block resource block Transducer blocks transducer block Pressure with calibration, transducer block LCD Pressure transducer block - Can be calibrated by applying Yes two pressures - Monitoring of sensor limits Yes - Simulation function: Measured pressure value, sensor temperature and electronics temperature Constant value or over parameterizable ramp function Siemens FI /4

53 Siemens AG 204 Y SITRANS P DS III for differential pressure and flow Selection and Ordering data Article No. SITRANS P DS III with HART pressure transmitters 7 M F for differential pressure and flow, PN 2/60 (MAWP 464/220 psi) Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Measuring cell cleaning Silicone oil normal } Inert liquid ) grease-free to cleanliness level 2 Measuring span (min.... max.) PN 2 (MAWP 464 psi) mbar 2) ( inh 2 O) } B PN 60 (MAWP 220 psi) mbar ( inh 2 O) } C mbar ( inh 2 O) } D mbar ( inh 2 O) } E mbar ( inh 2 O) } F mbar ( inh 2 O) } G bar ( psi) } H Wetted parts materials (stainless steel process flanges) Seal diaphragm Parts of measuring cell Stainless steel Stainless steel } A Hastelloy Stainless steel B Hastelloy Hastelloy C Tantalum ) Tantalum E Monel ) Monel H Gold ) Gold L Version for diaphragm seal4) 5) 6) 7) Process connection Female thread ¼-8 NPT with flange connection Sealing screw opposite process connection - Mounting thread 7 / 6-20 UNF to IEC 658 } 2 - Mounting thread M0 to DIN 92 0 (only for replacement requirement) Vent on side of process flange 2) - Mounting thread 7 / 6-20 UNF to IEC Mounting thread M0 to DIN 92 4 (only for replacement requirement) Non-wetted parts materials process flange screws Electronics housing Stainless steel Die-cast aluminum } 2 Stainless steel Stainless steel precision casting 8) Version Standard versions International version, English label inscriptions, } 2 documentation in 5 languages on CD (no Order code selectable) Explosion protection None A With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" B - "Explosion-proof (Ex d)" 9) D - "Intrinsic safety and flameproof enclosure" P (Ex ia + Ex d)" 0) - "Ex na/ic (Zone 2)" ) E - "Intrinsic safety, explosion-proof enclosure } R and dust explosion protection (Ex ia+ Ex d + Zone D/2D)" 0)2) FM + CSA intrinsic safe (is) F FM + CSA (is + ep) + Ex ia + Ex d (ATEX) 2) S With FM + CSA, Type of protection: - "Intrinsic Safe und Explosion Proof (is + xp)" 9) N C Selection and Ordering data Article No. SITRANS P DS III with HART pressure transmitters 7 M F for differential pressure and flow, PN 2/60 (MAWP 464/220 psi) Electrical connection/cable entry Screwed gland Pg.5 ) A Screwed gland M20 x.5 } B Screwed gland ½-4 NPT C Han 7D plug (plastic housing) incl. mating D connector )4) M2 connectors (stainless steel) 5)6) F Display Without display 0 Without visible display (display concealed, setting: ma) } With visible display (setting: ma) 6 with customer-specific display 7 (setting as specified, Order code "Y2" or "Y22" required) } Available ex stock We can offer shorter delivery times for configurations designated with the Quick Ship Symbol. For details see page 9/5 in the appendix. Power supply units see Chap. 7 "Supplementary Components". Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation Sealing plug(s) or sealing screw(s) for the process flanges(s) ) For oxygen application, add Order code E0. 2) Not suitable for connection of remote seal. Position of the top vent valve in the process flange (see dimensional drawing). ) Not in conjunction with max. span 20 and 60 mbar (8.0 und inh 2 O)) 4) When the manufacture s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC , it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here. 5) If the acceptance test certificate..is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. 6) The diaphragm seal is to be specified with a separate order number and must be included wiht the tranmitter order number, for example 7MF44.-..Y und 7MF B 7) The standard measuring cell filling for configurations with remote seals (Y) is silicone oil. 8) Not in conjunction with Electrical connection "Screwed gland Pg.5" and "Han7D plug". 9) Without cable gland, with blanking plug 0) With enclosed cable gland Ex ia and blanking plug ) Configurations with HAN and M2 connectors are only available in Ex ic. 2) Only in connection with IP65. ) Only in connection with Ex approval A, B or E. 4) Permissible only for crimp-contact of conductor cross-section mm 2 5) Only in connection with Ex approval A, B, E or F. 6) M2 delivered without cable socket. /42 Siemens FI 0 205

54 Siemens AG 204 Y Selection and Ordering data Article No. Pressure transmitters for differential pressure and flow PN 2/60 (MAWP 464/220 psi) SITRANS P DS III with PROFIBUS PA (PA) 7 M F SITRANS P DS III with FOUNDATION Fieldbus (FF) 7 M F Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Measuring cell cleaning Silicone oil normal Inert liquid ) grease-free to cleanliness level 2 Nominal measuring range PN 2 (MAWP 464 psi) 20 mbar 2) (8.0 inh 2 O) B PN 60 (MAWP 220 psi) 60 mbar (24.09 inh 2 O) C 250 mbar (00.4 inh 2 O) D 600 mbar (240.9 inh 2 O) E 600 mbar (642.4 inh 2 O) F 5 bar (2008 inh 2 O) G 0 bar (45 psi) H Wetted parts materials (stainless steel process flanges) Seal diaphragm Parts of measuring cell Stainless steel Stainless steel A Hastelloy Stainless steel B Hastelloy Hastelloy C Tantalum ) Tantalum E Monel ) Monel H Gold ) Gold L Version as diaphragm seal 4) 5) 6) 7) Process connection Female thread ¼-8 NPT with flange connection Sealing screw opposite process connection - Mounting thread 7 / 6-20 UNF to IEC Mounting thread M0 to DIN 92 0 (only for replacement requirement) Venting on side of process flanges 2) - Mounting thread 7 / 6-20 UNF to IEC Mounting thread M0 to DIN 92 4 (only for replacement requirement) Non-wetted parts materials process flange screws Electronics housing Stainless steel Die-cast aluminum 2 Stainless steel Stainless steel precision casting Version Standard versions International version, English label inscriptions, 2 documentation in 5 languages on CD (no Order code selectable) Explosion protection None A With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" B - "Explosion-proof (Ex d)" 8) D - "Intrinsic safety and flameproof enclosure" P (Ex ia + Ex d)" 9) - "Ex na/ic (Zone 2)" 0) E - "Intrinsic safety, explosion-proof enclosure and R dust explosion protection (Ex ia + Ex d + Zone D/2D)" 9) ) (not for DS III FF) FM + CSA intrinsic safe (is) F FM + CSA (is + ep) + Ex ia + Ex d (ATEX) ) S With FM + CSA, Type of protection: - "Intrinsic Safe und Explosion Proof (is + xp)" 8) N C SITRANS P DS III for differential pressure and flow Selection and Ordering data Article No. Pressure transmitters for differential pressure and flow PN 2/60 (MAWP 464/220 psi) SITRANS P DS III with PROFIBUS PA (PA) 7 M F SITRANS P DS III with FOUNDATION Fieldbus (FF) 7 M F Electrical connection/cable entry Screwed gland M20 x.5 B Screwed gland ½-4 NPT C M2 connectors (stainless steel) 2) ) F Display Without display 0 Without visible display (display concealed, setting: bar) With visible display (setting: bar) 6 With customer-specific display 7 (setting as specified, Order code "Y2" required) Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation Sealing plug(s) or sealing screw(s) for the process flanges(s) ) For oxygen application, add Order code E0. 2) Not suitable for connection of remote seal. Position of the top vent valve in the process flange (see dimensional drawing). ) Not in conjunction with max. span 20 and 60 mbar (8.0 und inh 2 O)) 4) When the manufacture s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC , it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here. 5) If the acceptance test certificate..is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. 6) The diaphragm seal is to be specified with a separate order number and must be included wiht the tranmitter order number, for example 7MF44.-..Y und 7MF B 7) The standard measuring cell filling for configurations with remote seals (Y) is silicone oil. 8) Without cable gland, with blanking plug. 9) With enclosed cable gland Ex ia and blanking plug. 0) Configurations with HAN and M2 connectors are only available in Ex ic. ) Only in connection with IP65. 2) Only in connection with Ex approval A, B, E or F. ) M2 delivered without cable socket Siemens FI /4

55 Siemens AG 204 SITRANS P DS III for differential pressure and flow Selection and Ordering data Order code Further designs HART PA FF Add "-Z" to Article No. and specify Order code. Pressure transmitter with mounting bracket (x fixing angle, 2 x nut, 2 x U- washer or x bracket, 2 x nut, 2 x U- washer) made of: Steel A0 Stainless steel A02 O-rings for process flanges (instead of FPM (Viton)) PTFE (Teflon) A20 FEP (with silicone core, approved for food) A2 FFPM (Kalrez, compound 4079), for measured medium temperatures C ( F) A22 NBR (Buna N) A2 plug Han 7D (metal) A0 Han 8D (instead of Han 7D) A Angled A2 Han 8D (metal) A Sealing screws (2 units) A40 ¼-8 NPT, with valve in mat. of process flanges Cable sockets for M2 connectors A50 (metal (CuZn)) Rating plate inscription (instead of German) English B French B2 Spanish B Italian B4 Cyrillic (russian) B6 English rating plate B2 Pressure units in inh 2 O and/or psi Quality inspection certificate (Five-step C factory calibration) to IEC ) Inspection certificate 2) to EN C2 Factory certificate to EN C4 Functional safety (SIL2) C20 Devices suitable for use according to IEC 6508 and IEC 65. Includes SIL conformity declaration Functional safety (PROFIsafe) C2 ) Certificate and PROFIsafe protocol Functional safety (SIL2/) C2 Devices suitable for use according to IEC 6508 and IEC 65. Includes SIL conformity declaration Device passport Russia (For price request please contact the technical support C99 Selection and Ordering data Order code Further designs Add "-Z" to Article No. and specify Order code. HART PA FF Setting of upper limit of D05 output signal to 22.0 ma Manufacturer's declaration acc. to NACE (MR and MR ) D07 (only together with seal diaphragm made of Hastelloy and stainless steel) Degree of protection IP66/IP68 D2 (only for M20 x.5 and ½-4 NPT) Process flange screws made of Monel D4 (max. nominal pressure PN20) Supplied with oval flange set D7 (2 items), PTFE packings and screws in thread of process flanges Capri cable gland 4F CrNi and clamping D59 device ( ) included Use in or on zone D/2D E0 (only together with type of protection "Intrinsic safety" (transmitter 7MF B.. Ex ia) and IP65) Overfilling safety device for flammable E08 and non-flammable liquids (max. PN 2 (MAWP 464 psi), basic device with type of protection "Intrinsic safety (Ex ia)", to WHG and VbF, not together with measuring cell filling "inert liquid") Oxygen application E0 (In the case of oxygen measurement and inert liquid max. 00 bar (450 psi) at 60 C (40 F)) Export approval Korea E CRN approval Canada E22 (Canadian Registration Number) Dual seal E24 Explosion-proof "Intrinsic safety" (Ex ia) E25 4) to INMETRO (Brazil) (only for transmitter 7MF B..) "Flameproof" explosion protection E26 4) according to INMETRO (Brazil) (only for transmitter 7MF D..) Explosion-proof "Intrinsic safety" (Ex ia E28 4) + Ex d) to INMETRO (Brazil) (only for transmitter 7MF P..) Ex Approval IEC Ex (Ex ia) E45 4) (only for transmitter 7MF B..) Ex Approval IEC Ex (Ex d) E46 4) (only for transmitter 7MF D..) Explosion-proof "Intrinsic safety" to E55 4) NEPSI (China) (only for transmitter 7MF B..) Explosion protection "Explosion-proof" E56 4) to NEPSI (China) (only for transmitter 7MF D..) Explosion-proof "Zone 2" to NEPSI E57 4) (China) (only for transmitter 7MF E..) Ex protection Ex ia, Ex d and Zone E58 4) 2 to NEPSI (China) (only for transmitter 7MF R..) "Intrinsic safety" and "Explosion-proof" E70 4) explosion protection acc. to Kosha (Korea) (only for transmitter 7MF [B, D]..-Z + E) /44 Siemens FI 0 205

56 Siemens AG 204 Further designs HART PA FF Add "-Z" to Article No. and specify Order code. Two coats of lacquer on casing and G0 cover (PU on epoxy) Interchanging of process connection H0 side Vent on side for gas measurements H02 Stainless steel process flanges for vertical H0 differential pressure lines (not together with K0, K02 and K04) 5) Transient protector 6 kv (lightning protection) J0 Chambered graphite gasket for process J02 flange Chambered PTFE graphite gasket J0 EPDM O-rings for process flange with J05 approval (WRC/WRAS) Vent valve or blanking plug of process J08 flange welded-in (orientation: on right when viewing the display) 6) Vent valve or blanking plug of process J09 flange welded-in (orientation: on left when viewing the display) 6) Process flange Hastelloy K0 Monel K02 Stainless steel with PVDF insert max. PN 0 (MAWP 45 psi), max. temperature of medium 90 C (94 F) For ½-4 NPT inner process connection on the side in the middle of the process flange, vent valve not possible K04 We can offer shorter delivery times for configurations designated with the Quick Ship Symbol. For details see page 9/5 in the appendix. Factory mounting of valve manifolds, see accessories. Supplementary electronics for 4-wire connection, see accessories. = available ) When the manufacture s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC , it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here. 2) If the acceptance test certificate..is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. ) Profisafe transmitters can only be operated with the S7 F Systems V6. configuration software in combination with S7-400H 4) Option does not include ATEX approval, but instead includes only the countryspecific approval. 5) Not suitable for connection of remote seal. 6) Blanking plug is standard configuration. Order option A40 if a vent valve is required instead of a blanking plug. SITRANS P DS III for differential pressure and flow Selection and Ordering data Order code Selection and Ordering data Order code Additional data Please add "-Z" to Article No. and specify Order code(s) and plain text. HART PA FF Measuring range to be set Specify in plain text: in the case of linear characteristic curve (max. 5 characters): Y0:... up to... mbar, bar, kpa, MPa, psi Y0 ) in the case of square rooted characteristic Y02 (max. 5 characters): Y02:... up to... mbar, bar, kpa, MPa, psi Stainless steel tag plate and entry in Y5 device variable (measuring point description) Max. 6 characters, specify in plain text: Y5:... Measuring point text (entry in device Y6 variable) Max. 27 char., specify in plain text: Y6:... Entry of HART address (TAG) Y7 Max. 8 char., specify in plain text: Y7:... Setting of pressure indicator in Y2 pressure units Specify in plain text (standard setting: bar): Y2: mbar, bar, kpa, MPa, psi,... Note: The following pressure units can be selected: bar, mbar, mm H 2 O *), inh 2 O *), fth 2 O *), mmhg, inhg, psi, Pa, kpa, MPa, g/cm 2, kg/cm 2, Torr, ATM or % *) ref. temperature 20 C Setting of pressure indicator in nonpressure units 2) Specify in plain text: Y22:... up to... l/min, m /h, m, USgpm,... (specification of measuring range in pressure units "Y0" or "Y02" is essential, unit with max. 5 characters) Y22 ) + Y0 or Y02 Preset bus address Y25 possible between and 26 Specify in plain text: Y25:... Damping adjustment in seconds ( s) Y0 We can offer shorter delivery times for configurations designated with the Quick Ship Symbol. For details see page 9/5 in the appendix. Factory mounting of valve manifolds, see accessories. Only Y0, Y5, Y6, Y7, Y2, Y22, Y25 und D05 can be factory preset = available ) Measuring accuracies for PROFIBUS PA transmitters with Option Y0 are calculated in the same way as for HART devices. 2) Preset values can only be changed over SIMATIC PDM. ) Not in conjunction with over-filling safety device for flammable and nonflammable liquids (Order code "E08") Siemens FI /45

57 Siemens AG 204 SITRANS P DS III for differential pressure and flow Selection and Ordering data Article No. SITRANS P DS III with HART pressure transmitters 7 M F for differential pressure and flow, PN 420 (MAWP 6092 psi) Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Measuring cell cleaning Silicone oil normal Y F Measuring span (min.... max.) mbar ( inh 2 O) D mbar ( inh 2 O) E mbar ( inh 2 O) F mbar ( inh 2 O) G bar ( psi) H Wetted parts materials (stainless steel process flanges) Seal diaphragm Parts of measuring cell Stainless steel Stainless steel A Hastelloy Stainless steel B Gold ) Gold L Ausführung als Membrandruckmittler 2) ) 4) 5) Process connection Female thread ¼-8 NPT with flange connection Sealing screw opposite process connection - Mounting thread 7 / 6-20 UNF to IEC Mounting thread M2 to DIN 92 (only for replacement requirement) Venting on side of process flanges, location of vent valve at top of process flanges (see dimensional drawing) - Mounting thread 7 / 6-20 UNF to IEC Mounting thread M2 to DIN 92 5 (only for replacement requirement) Non-wetted parts materials process flange screws Electronics housing Stainless steel Die-cast aluminum 2 Stainless steel Stainless steel precision casting 6) Version Standard versions International version, English label inscriptions, 2 documentation in 5 languages on CD (no Order code selectable) Explosion protection None A With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" B - "Explosion-proof (Ex d)" 7) D - "Intrinsic safety and flameproof enclosure" P (Ex ia + Ex d)" 8) - "Ex na/ic (Zone 2)" 9) E - "Intrinsic safety, explosion-proof enclosure and R dust explosion protection (Ex ia+ Ex d + Zone D/2D)" 8)0) FM + CSA intrinsic safe (is) F FM + CSA (is + ep) + Ex ia + Ex d (ATEX) 0) S With FM + CSA, Type of protection: - "Intrinsic safety and explosion-proof (is + xp)" 7), max PN 60 N C Electrical connection/cable entry Screwed gland Pg.5 ) A Screwed gland M20x.5 B Screwed gland ½-4 NPT C Han 7D plug (plastic housing) incl. mating D connector )2) M2 connectors (stainless steel) ) 4) Selection and Ordering data Article No. SITRANS P DS III with HART pressure transmitters for differential pressure and flow, 7 M F PN 420 (MAWP 6092 psi) Display Without display 0 Without visible display (display concealed, setting: ma) With visible display (setting: ma) 6 with customer-specific display 7 (setting as specified, Order code "Y2" or "Y22" required) Power supply units see Chap. 7 "Supplementary Components". Scope of delivery: Pressure transmitter as ordered (Instruction Manual is extra ordering item) ) Not in conjunction with max. span 600 mbar (240.9 inh 2 O) 2) When the manufacture s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC , it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here. ) If the acceptance test certificate..is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. 4) The diaphragm seal is to be specified with a separate order number and must be included wiht the tranmitter order number, for example 7MF45.-..Y und 7MF B 5) The standard measuring cell filling for configurations with remote seals (Y) is silicone oil. 6) Not in conjunction with Electrical connection "Screwed gland Pg.5" and "Han7D plug". 7) Without cable gland, with blanking plug 8) With enclosed cable gland Ex ia and blanking plug 9) Configurations with HAN and M2 connectors are only available in Ex ic. 0) Only in connection with IP65. ) Only in connection with Ex approval A, B or E. 2) Permissible only for crimp-contact of conductor cross-section mm 2 ) Only in connection with Ex approval A, B, E or F. 4) M2 delivered without cable socket. /46 Siemens FI 0 205

58 Siemens AG 204 Selection and Ordering data Article No. Y Pressure transmitters for differential pressure and flow, PN 420 (MAWP 6092 psi) SITRANS P DS III with PROFIBUS PA (PA) 7 M F SITRANS P DS III with FOUNDATION Fieldbus (FF) 7 M F Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Nominal measuring range 250 mbar (00.4 inh 2 O) D 600 mbar (240.9 inh 2 O) E 600 mbar (642.4 inh 2 O) F 5 bar (2008 inh 2 O) G 0 bar (45 psi) H Wetted parts materials (stainless steel process flanges) Seal diaphragm Parts of measuring cell Stainless steel Stainless steel A Hastelloy Stainless steel B Gold ) Gold L Ausführung als Membrandruckmittler 2) ) 4) 5) Process connection Female thread ¼-8 NPT with flange connection Sealing screw opposite process connection - Mounting thread 7 / 6-20 UNF to IEC Mounting thread M2 to DIN 92 (only for replacement requirement) Venting on side of process flanges, location of vent valve at top of process flanges (see dimensional drawing). - Mounting thread 7 / 6-20 UNF to IEC Mounting thread M2 to DIN 92 5 (only for replacement requirement) Non-wetted parts materials Process flange screws Electronics housing Stainless steel Die-cast aluminum 2 Stainless steel Stainless steel precision casting Version Standard versions International version, English label inscriptions, 2 documentation in 5 languages on CD (no Order code selectable) Explosion protection None A With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" B - "Explosion-proof (Ex d)" 6) D - "Intrinsic safety and flameproof enclosure" P (Ex ia + Ex d)" 7) - "Ex na/ic (Zone 2)" 8) E - "Intrinsic safety, explosion-proof enclosure and R dust explosion protection (Ex ia + Ex d + Zone D/2D)" 7) 9) (not for DS III FF) FM + CSA intrinsic safe (is) F FM + CSA (is + ep) + Ex ia + Ex d (ATEX) 9) S With FM + CSA, Type of protection: - "Intrinsic safety and explosion-proof N C (is + xp)" 6), max PN 60 Electrical connection/cable entry Screwed gland M20 x.5 B Screwed gland ½-4 NPT C M2 connectors (stainless steel) 0) ) F SITRANS P DS III for differential pressure and flow Selection and Ordering data Article No. Pressure transmitters for differential pressure and flow, PN 420 (MAWP 6092 psi) SITRANS P DS III with PROFIBUS PA (PA) 7 M F SITRANS P DS III with FOUNDATION Fieldbus (FF) 7 M F Display Without (display hidden) 0 Without visible display (display concealed, setting: bar) With visible display (setting: bar) 6 With customer-specific display (setting as 7 specified, Order code "Y2" required) Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation Sealing plug(s) or sealing screw(s) for the process flanges(s) ) Not in conjunction with max. span 600 mbar (240.9 inh 2 O) 2) When the manufacture s certificate (calibration certificate) has to be ordered for transmitters with diaphragm seals according to IEC , it is recommended only to order this certificate exclusively with the diaphragm seals. The measuring accuracy of the total combination is certified here. ) If the acceptance test certificate..is ordered for the transmitter with mounted diaphragm seals this certificate must also be ordered with the respective remote seals. 4) The diaphragm seal is to be specified with a separate order number and must be included wiht the tranmitter order number, for example 7MF45.-..Y und 7MF B 5) The standard measuring cell filling for configurations with remote seals (Y) is silicone oil. 6) Without cable gland, with blanking plug. 7) With enclosed cable gland Ex ia and blanking plug. 8) Configurations with HAN and M2 connectors are only available in Ex ic. 9) Only in connection with IP65. 0) Only in connection with Ex approval A, B, E or F. ) M2 delivered without cable socket Siemens FI /47

59 Siemens AG 204 SITRANS P DS III for differential pressure and flow Selection and Ordering data Order code Further designs HART PA FF Add "-Z" to Article No. and specify Order code. Pressure transmitter with mounting bracket (x fixing angle, 2 x nut, 2 x U- washer or x bracket, 2 x nut, 2 x U- washer) made of: Steel A0 Stainless steel A02 O-rings for process flanges (instead of FPM (Viton)) PTFE (Teflon) A20 FEP (with silicone core, approved for food) A2 FFPM (Kalrez, compound 4079), for measured medium temperatures C ( F) A22 NBR (Buna N) A2 Plug Han 7D (metal) A0 Han 8D (instead of Han 7D) A Angled A2 Han 8D (metal) A Sealing screws (2 units) A40 ¼-8 NPT, with valve in mat. of process flanges Cable sockets for M2 connection A50 (metal (CuZn)) Rating plate inscription (instead of German) English B French B2 Spanish B Italian B4 Cyrillic (russian) B6 English rating plate B2 Pressure units in inh 2 O and/or psi Quality inspection certificate (Five-step C factory calibration) to IEC Inspection certificate C2 Acc. to EN Factory certificate C4 Acc. to EN Functional safety (SIL2) C20 Devices suitable for use according to IEC 6508 and IEC 65. Includes SIL conformity declaration Functional safety (PROFIsafe) C2 ) Certificate and PROFIsafe protocol Functional safety (SIL2/) C2 Devices suitable for use according to IEC 6508 and IEC 65. Includes SIL conformity declaration Device passport Russia (For price request please contact the technical support C99 Setting of upper limit of output signal to D ma Manufacturer's declaration acc. to NACE D07 (MR and MR ) (only together with seal diaphragm made of Hastelloy and stainless steel) Degree of protection IP66/IP68 D2 (only for M20 x.5 and ½-4 NPT) Nom. press. rating PN 500 (MAWP 7250 psi) D56 (Only for measuring cell 600 mbar... 0 bar (240 inh 2 O psi), SIL- und Ex-options not possible)) 2) Capri cable gland 4F CrNi and clamping device ( ) included D59 Selection and Ordering data Order code Further designs Add "-Z" to Article No. and specify Order code. HART PA FF Use in or on zone D/2D E0 (only together with type of protection "Intrinsic safety" (transmitter 7MF B.. Ex ia) and IP65) Export approval Korea E Dual seal E24 Explosion-proof "Intrinsic safety" (Ex ia) to E25 ) INMETRO (Brazil) (only for transmitter 7MF B..) "Flameproof" explosion protection according E26 ) to INMETRO (Brazil) (only for transmitter 7MF D..) Explosion-proof "Intrinsic safety" (Ex ia + E28 ) Ex d) to INMETRO (Brazil) (only for transmitter 7MF P..) Ex Approval IEC Ex (Ex ia) E45 ) (only for transmitter 7MF B..) Ex Approval IEC Ex (Ex d) E46 ) (only for transmitter 7MF D..) Explosion-proof "Intrinsic safety" E55 ) to NEPSI (China) (only for transmitter 7MF B..) Ex prot. "Explosion-proof" to NEPSI (China) E56 ) (only for transmitter 7MF D..) Explosion-proof "Zone 2" to NEPSI (China) E57 ) (only for transmitter 7MF E..) Ex protection Ex ia, Ex d and Zone 2 E58 ) to NEPSI (China) (only for transmitter 7MF R..) "Intrinsic safety" and "Explosion-proof" E70 ) explosion protection acc. to Kosha (Korea) (only for transmitter 7MF [B, D]..-Z + E) Two coats of lacquer on casing and cover G0 (PU on epoxy) Interchanging of process connection side H0 Stainless steel process flanges for vertical H0 differential pressure lines Transient protector 6 kv (lightning protection) J0 Chambered graphite gasket for process J02 flange EPDM O-rings for process flange with J05 approval (WRC/WRAS) Vent valve or blanking plug of process J08 flange welded-in (orientation: on right when viewing the display) 4) Vent valve or blanking plug of process flange welded-in (orientation: on left when viewing the display) 4) J09 ) Profisafe transmitters can only be operated with the S7 F Systems V6. configuration software in combination with S7-400H 2) Tested according to IEC 600. Only for measuring materials of the group of fluids 2 in accordance with PED permissible. Not for use with dangerous media suitable. ) Option does not include ATEX approval, but instead includes only the country-specific approval. 4) Blanking plug is standard configuration. Order option A40 if a vent valve is required instead of a blanking plug. /48 Siemens FI 0 205

60 Siemens AG 204 Selection and Ordering data Order code Additional data HART PA FF Please add "-Z" to Article No. and specify Order code(s) and plain text. Measuring range to be set Specify in plain text: in the case of linear characteristic curve (max. 5 characters): Y0:... up to... mbar, bar, kpa, MPa, psi Y0 ) in the case of square rooted characteristic Y02 (max. 5 characters): Y02:... up to... mbar, bar, kpa, MPa, psi Stainless steel tag plate and entry in Y5 device variable (measuring point description) Max. 6 characters, specify in plain text: Y5:... Measuring point text (entry in device variable) Y6 Max. 27 char., specify in plain text: Y6:... Entry of HART address (TAG) Y7 Max. 8 char., specify in plain text: Y7:... Setting of pressure indication in pressure Y2 units Specify in plain text (standard setting: bar): Y2: mbar, bar, kpa, MPa, psi,... Note: The following pressure units can be selected: bar, mbar, mm H 2 O *), inh 2 O *), fth 2 O *), mmhg, inhg, psi, Pa, kpa, MPa, g/cm 2, kg/cm 2, Torr, ATM or % *) ref. temperature 20 C Setting of pressure indication in non-pressure units 2) Specify in plain text: Y22:... up to... l/min, m /h, m, USgpm,... (specification of measuring range in pressure units "Y0" or "Y02" is essential, unit with max. 5 characters) Y22 + Y0 or Y02 Preset bus address Y25 possible between and 26 Specify in plain text: Y25:... Damping adjustment in seconds ( s) Y0 Factory mounting of valve manifolds, see accessories. Only Y0, Y5, Y6, Y7, Y2, Y22, Y25 and D05 can be factory preset. = available ) Measuring accuracies for PROFIBUS PA transmitters with Option Y0 are calculated in the same way as for HART devices. 2) Preset values can only be changed over SIMATIC PDM. SITRANS P DS III for differential pressure and flow Siemens FI /49

61 Siemens AG 204 SITRANS P DS III for differential pressure and flow Dimensional drawings 5 (0.6) 4 (5.6) 69 (2.7) 5 (2.) 29 (.4) 4) 24 (0.94) 84 (.) 5 Ø80 (.5) 2 50 (.97) 28 (5.04) (6.54) 2 4 (5.28) min. 90 (.54) 5) Space for rotation of housing approx. 96 (.78) 7 (0.67) 52 (2.05) (.8) 262 (0.) 4 72 (2.8) 05 (4.) 68 (2.7) 20 (4.7) Electronic side, digital display (longer overall length for cover with window) ) Terminal side ) Electrical connection: Screwed gland Pg,5 (adapter)(adapter) 2) ), Screwed gland M20 x,5 or Screwed gland ½-4 NPT or Han 7D/ Han 8D 2) ) plug Harting adapter Protective cover over keys 6 Blanking plug 7 Screw cover - safety bracket (only for type of protection "Explosion-proof enclosure", not shown in the drawing) 8 Lateral venting for liquid measurement (Standard) 9 Lateral venting for gas measurement (suffix H02) 0 Mounting bracket (option) Sealing screw with valve (option) 2 Process connection: ¼-8 NPT (IEC 658) ) Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing 2) Not with type of protection "Explosion-proof enclosure" ) Not with type of protection "FM + CSA" [IS + XP]" 4) 92 mm (.62 inch) for minimum distance to permit rotation with indicator 5) For Pg,5 with adapter approx. 45 mm (.77 inch) SITRANS P DS III pressure transmitters for differential pressure and flow, dimensions in mm (inch) /50 Siemens FI 0 205

62 Siemens AG (5.6) (0.6) 5 (2.) Ø80 (.5) 60 (2.6) 5) 65 (2.56) 24 (0.94) 2 50 (.97) min. 90 (.54) 5) Space for rotation of housing approx. 96 (.78) SITRANS P DS III for differential pressure and flow 4 7 (0.67) approx. 85 (.5) 6) 29 (.4) 8) 8 84 (.) approx. 87 (.4) (5.04) approx. 27 (8.54) 7) 2 4 Electronic side, digital display (longer overall length for cover with window) ) Terminal side ) Electrical connection: Screwed gland Pg,5 (adapter)(adapter) 2) ), Screwed gland M20 x,5 or Screwed gland ½-4 NPT or Han 7D/ Han 8D 2) ) plug Harting adapter 5 Protective cover over keys 6 Blanking plug 7 Screw cover - safety bracket (only for type of protection "Explosion-proof enclosure", not shown in the drawing) 8 Sealing screw with valve (option) 9 Process connection: ¼-8 NPT (IEC 658) ) Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing 2) Not with type of protection "Explosion-proof enclosure" ) Not with type of protection "FM + CSA" [IS + XP]" 4) 92 mm (.6 inch) for minimum distance to permit rotation with indicator 5) 74 mm (2.9 inch) for PN 420 (MAWP 6092 psi) 6) 9 mm (.6 inch) for PN 420 (MAWP 6092 psi) 7) 29 mm (8.62 inch) for PN 420 (MAWP 6092 psi) 8) For Pg,5 with adapter approx. 45 mm (.77 inch) SITRANS P DS III pressure transmitters for differential pressure and flow, with process covers for vertical differential pressure lines, optional "H0", dimensional drawing, dimensions in mm (inch) SITRANS P DS III pressure transmitters for differential pressure and flow, with process covers for vertical differential pressure lines Siemens FI /5

63 Siemens AG 204 SITRANS P DS III for level Technical specifications SITRANS P DS III for level HART Input Measured variable Level Spans (infinitely adjustable) or nominal measuring Span (min.... max.) range and max. permissible operating pressure mbar ( inh 2 O) mbar ( inh 2 O) mbar ( inh 2 O) mbar ( inh 2 O) Lower measuring limit Measuring cell with silicone oil filling Maximum operating pressure See "Mounting flange" See "Mounting flange" See "Mounting flange" See "Mounting flange" PROFIBUS PA or FOUNDATION Fieldbus Nominal measuring range 250 mbar (00 inh 2 O) 600 mbar (240 inh 2 O) 600 mbar (642 inh 2 O) 5bar (2000 inh 2 O) -00 % of max. span or 500 mbar a (7.25 psia) Also available as vacuum-resistant remote seal: 0 mbar a (0.44 psi a) Maximum operating pressure See "Mounting flange" See "Mounting flange" See "Mounting flange" See "Mounting flange" Upper measuring limit 00 % of max. span 00 % of the max. nominal measuring range Output Output signal ma Digital PROFIBUS PA and FOUNDATION Fieldbus signal Lower limit (infinitely adjustable).55 ma, factory preset to.84 ma - Upper limit (infinitely adjustable) 2 ma, factory preset to 20.5 ma or optionally - set to 22.0 ma Load Without HART R B (U H V)/0.02 A in, - U H : Power supply in V With HART R B = (SIMATIC PDM) or - R B = (HART Communicator) Physical bus - IEC Protection against polarity reversal Protected against short-circuit and polarity reversal. Each connection against the other with max. supply voltage. Electrical damping (step width 0. s) Set to 2 s ( s) Measuring accuracy Acc. to IEC Reference conditions (All error data refer always refer to the set span) Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, silicone oil filling, room temperature 25 C (77 F) Span ratio r = max. span/set span) Nominal measuring range ratio r = nominal measuring range/set measuring range Error in measurement at limit setting incl. hysteresis and reproducibility Linear characteristic -r % 0.5 % - 0 < r 0 0. % 0. % -0<r 00 ( r ) % ( r+0.075)% Long-term stability (temperature change ± 0 C (± 54 F)) Influence of ambient temperature at C ( F) (0.25 r)% every 5 years static pressure max. 70 bar (05 psi) (0.25 r)% every 5 years static pressure max. 70 bar (05 psi) mbar- (00 inh 2 O)-measuring cell (0.5 r + 0.2) % ) 4) (0.5 r + 0.2) % ) 4) mbar- (240 inh 2 O)-measuring cell (0. r + 0.2) % 2) 4) (0. r + 0.2) % 2) 4) and 5000 mbar- (642 and 2000 inh 2 O)- measuring cell at C and C ( F and F) mbar- (00 inh 2 O)-measuring cell (0.25 r + 0.5) %/0 K doubled values at 0 < r mbar- (240 inh 2 O)-measuring cell (0.5 r + 0.5) %/0 K doubled values at 0 < r and 5000 mbar- (642 and 2000 inh 2 O)- measuring cell (0.25 r + 0.2) % ) 4) (0.25 r + 0.2) % ) 4) (0.2 r + 0.5) %/0 K double values at 0 < r 0 (0.25 r + 0.5) %/0 K doubled values at 0 < r 0 (0.5 r + 0.5) %/0 K doubled values at 0 < r 0 (0.2 r + 0.5) %/0 K double values at 0 < r 0 /52 Siemens FI 0 205

64 Siemens AG 204 SITRANS P DS III for level SITRANS P DS III for level Influence of static pressure on the zero point HART PROFIBUS PA or FOUNDATION Fieldbus mbar- (00 inh 2 O)-measuring cell (0. r) % per nominal pressure (0. r) % per nominal pressure mbar- (240 inh 2 O)-measuring cell (0.5 r) % per nominal pressure (0.5 r) % per nominal pressure and 5000 mbar- (642 and 2000 inh 2 O)- measuring cell (0. r) % per nominal pressure (0. r) % per nominal pressure on the span (0. r) % per nominal pressure (0. r) % per nominal pressure Measured Value Resolution of nominal measuring range Rated conditions Degree of protection to IEC Temperature of medium Measuring cell with silicone oil filling IP66 (optional IP66/IP68), NEMA 4X Note: Always take into account assignment of max. permissible operating temperature to max. permissible operating pressure of the respective flange connection! ) C ( ) F) - High-pressure side p abs bar: C ( F) p abs < bar: C ( F) - Low-pressure side C ( F) C ( F) in conjunction with dust explosion protection Ambient conditions Ambient temperature - Transmitter C ( F) (with 4-wire connection, observe temperature values of supplementary 4-wire electronics) - -Display readable C ( F) Storage temperature C ( F) Climatic class - Condensation Relative humidity %, condensation permissible, suitable for use in the tropics Electromagnetic Compatibility - Emitted interference and interference immunity Acc. to IEC 626 and NAMUR NE 2 Design Weight (without options) To EN (pressure transmitter with mounting... kg ( (lb) flange, without tube) To ASME (pressure transmitter with mounting... 8 kg ( lb) flange, without tube) Enclosure material Low-copper die-cast aluminum, GD-AlSi2 or stainless steel precision casting, mat. no Wetted parts materials High-pressure side Seal diaphragm of mounting flange Stainless steel, mat. no..4404/6l, Monel, mat. no , Hastelloy B2, mat. no , Hastelloy C276, mat. no , Hastelloy C4, mat. no , tantalum, PTFE, ETCFE, stainless steel Duplex, mat. no Measuring cell filling Silicone oil Process connection High-pressure side Flange to EN and ASME Low-pressure side Female thread ¼-8 NPT and flange connection with mounting thread M0 to DIN 92 or / 6-20 UNF to EN 658 Power supply U H Supplied through bus Terminal voltage on transmitter V DC V DC in intrinsically-safe mode Separate 24 V power supply necessary - No Bus voltage Not Ex V With intrinsically-safe operation V Current consumption Basic current (max.) ma Start-up current basic current - Yes Max. current in event of fault ma Fault disconnection electronics (FDE) available - Yes Siemens FI /5

65 Siemens AG 204 SITRANS P DS III for level SITRANS P DS III for level HART PROFIBUS PA or FOUNDATION Fieldbus Certificates and approvals Classification according to PED 97/2/EC For gases of fluid group and liquids of fluid group ; complies with requirements of article, paragraph (sound engineering practice) Explosion protection Intrinsic safety "i" PTB ATEX 2007 X - Marking Ex II /2 G Ex ia/ib IIC T4/T5/T6 Ga/Gb - Permissible ambient temperature C ( F) temperature class T4; C ( F) temperature class T5; C ( F) temperature class T6 - Connection To certified intrinsically-safe circuits with peak values: U i = 0 V, I i = 00 ma, P i = 750 mw; R i =00 FISCO supply unit: U o = 7.5 V, I o = 80 ma, P o = 5.2 W Linear barrier: U o = 24 V, I o = 250 ma, P o =.2 W - Effective internal inductance/capacitance L i = 0.4 mh, C i = 6 nf L i = 7 H, C i =. nf Explosion-proof "d" PTB 99 ATEX 60 - Marking Ex II /2 G Ex d IIC T4/T6 Gb - Permissible ambient temperature C ( F) temperature class T4; C ( F) temperature class T6 - Connection To circuits with values: U H = V DC To circuits with values: U H = V DC Dust explosion protection for zone 20 PTB 0 ATEX Marking Ex II D IP65 T 20 C Ex II /2 D IP65 T 20 C - Permissible ambient temperature C ( F) - Max. surface temperature 20 C (248 F) - Connection To certified intrinsically-safe circuits with peak values: U i = 0 V, I i = 00 ma, P i = 750 mw, R i = 00 FISCO supply unit: U o = 7.5 V, I o = 80 ma, P o = 5.2 W Linear barrier: U o = 24 V, I o = 250 ma, P o =.2 W - Effective internal inductance/capacitance L i = 0.4 mh, C i = 6 nf L i = 7 H, C i =. nf Dust explosion protection for zone 2/22 PTB 0 ATEX Marking Ex II 2 D IP65 T 20 C - Connection To circuits with values: U H = V DC; P max =.2 W Type of protection "n" (zone 2) PTB ATEX 2007 X - Marking Ex II 2/ G Ex na II T4/T5/T6 Gc Ex II 2/ G Ex ic IIC T4/T5/T6 Gc - Connection (Ex na) U m = 45 V U m = 2 V - Connection (Ex ic) To circuits with values: U i = 45 V To circuits with values: U H = V DC; P max = W FISCO supply unit ic: U o = 7.5 V, I o = 570 ma Linear barrier: U o = 2 V, I o = 2 ma, P o = W - Effective internal inductance/capacitance L i = 0.4 mh, C i = 6 nf L i = 7 H, C i =. nf Explosion protection acc. to FM Certificate of Compliance Identification (XP/DIP) or (IS); (NI) CL I, DIV, GP ABCD T4...T6; CL II, DIV, GP EFG; CL III; CL I, ZN 0/ AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III Explosion protection to CSA Certificate of Compliance Identification (XP/DIP) or (IS) CL I, DIV, GP ABCD T4...T6; CL II, DIV, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III ) Conversion of temperature error per 28 C. Valid for temperature range C < (0.4 r + 0.6) % / 28 C (50 F). 2) Conversion of temperature error per 28 C. Valid for temperature range C < (0.24 r + 0.6) % / 28 C (50 F). ) Conversion of temperature error per 28 C. Valid for temperature range C < (0.2 r + 0.6) % / 28 C (50 F). 4) 0.2 instead of 0.6 at 0 < r < 0 5) This value may be increased if the process connection is sufficiently insulated. /54 Siemens FI 0 205

66 Siemens AG 204 HART communication HART Protocol HART Version 5.x Software for computer PROFIBUS PA communication Simultaneous communication with master class 2 (max.) The address can be set using Cyclic data usage Output byte Input byte Internal preprocessing Device profile Function blocks 2 Analog input - Adaptation to customer-specific process variables SIMATIC PDM 4 Configuration tool or local operation (standard setting address 26) 5 (one measured value) or 0 (two measured values) 0,, or 2 (register operating mode and reset function for metering) PROFIBUS PA Profile for Process Control Devices Version.0, class B Yes, linearly rising or falling characteristic - Electrical damping, adjustable s - Simulation function Input/Output - Failure mode parameterizable (last good value, substitute value, incorrect value) - Limit monitoring Yes, one upper and lower warning limit and one alarm limit respectively Register (totalizer) Can be reset, preset, optional direction of counting, simulation function of register output - Failure mode parameterizable (summation with last good value, continuous summation, summation with incorrect value) - Limit monitoring One upper and lower warning limit and one alarm limit respectively Physical block Transducer blocks 2 Pressure transducer block - Can be calibrated by applying Yes two pressures - Monitoring of sensor limits Yes - Specification of a container Max. 0 nodes characteristic with - Square-rooted characteristic Yes for flow measurement - Gradual volume suppression Parameterizable and implementation point of square-root extraction - Simulation function for measured pressure value and sensor temperature Constant value or over parameterizable ramp function FOUNDATION Fieldbus communication Function blocks SITRANS P DS III for level function blocks analog input, function block PID Analog input - Adaptation to customer-specific process variables characteristic Yes, linearly rising or falling - Electrical damping, adjustable s - Simulation function Output/input (can be locked within the device with a bridge) - Failure mode parameterizable (last good value, substitute value, incorrect value) - Limit monitoring Yes, one upper and lower warning limit and one alarm limit respectively - Square-rooted characteristic Yes for flow measurement PID Standard FOUNDATION Fieldbus function block Physical block resource block Transducer blocks transducer block Pressure with calibration, transducer block LCD Pressure transducer block - Can be calibrated by applying Yes two pressures - Monitoring of sensor limits Yes - Simulation function: Measured pressure value, sensor temperature and electronics temperature Mounting flange Nominal diameter Acc. to EN 092- Constant value or over parameterizable ramp function Nominal pressure - DN 80 PN 40 - DN00 PN6, PN40 To ASMEB6.5 - inch class 50, class 00-4 inch class 50, class 00 Siemens FI /55

67 Siemens AG 204 SITRANS P DS III for level Selection and Ordering data Article No. Pressure transmitter for level, SITRANS P DS III with HART 7 M F Y Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Measuring cell cleaning Silicone oil normal Measuring span (min.... max.) mbar ( inh 2 O) D mbar ( inh 2 O) E mbar ( inh 2 O) F bar ( inh 2 O) G Process connection of low-pressure side Female thread ¼-8 NPT with flange connection Mounting thread 7 / 6-20 UNF to IEC Mounting thread M0 to DIN 92 0 (only for replacement requirement) Non-wetted parts materials process flange screws Electronics housing Stainless steel Die-cast aluminum 2 Stainless steel Stainless steel precision casting ) Version Standard versions International version, English label inscriptions, 2 documentation in 5 languages on CD (no Order code selectable) Explosion protection None A With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" B - "Explosion-proof (Ex d)" 2) D - "Intrinsic safety and flameproof enclosure" P (Ex ia + Ex d)" ) - "Ex na/ic (Zone 2)" 4) E - "Intrinsic safety, explosion-proof enclosure and R dust explosion protection (Ex ia+ Ex d + Zone D/2D)" )5) FM + CSA intrinsic safe (is) F FM + CSA (is + ep) + Ex ia + Ex d (ATEX) 5) S With FM + CSA, Type of protection: - "Intrinsic Safe und Explosion Proof (is + xp)" ) N C Electrical connection/cable entry Screwed gland Pg.5 6) A Screwed gland M20x.5 B Screwed gland ½-4 NPT C Han 7D plug (plastic housing) incl. mating D connector 6) M2 connectors (stainless steel) 7) 8) F Display Without display 0 Without visible display (display concealed, setting: ma) With visible display (setting ma) 6 With customer-specific display (setting as 7 specified, Order code "Y2" or "Y22" required) Ordering information st order item: Pressure transmitter 7MF nd order item: Mounting flange 7MF ordering example Item line : 7MF46-EY20-AA-Z B line: Y0 C line: Y0: 80 to 4 mbar (.6 to 2. psi) Item line 2: 7MF492-GE0 Power supply units see Chap. 7 "Supplementary Components". Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation Sealing plug(s) or sealing screw(s) for the process flanges(s) ) Not in conjunction with electrical connection "Screwed gland Pg.5" and "Han7D plug". 2) Without cable gland, with blanking plug. ) With enclosed cable gland Ex ia and blanking plug. 4) Configurations with HAN and M2 connectors are only available in Ex ic. 5) Only in connection with IP65. 6) Only in connection with Ex approval A, B or E. 7) M2 delivered without cable socket 8) Only in connection with Ex approval A, B, E or F. /56 Siemens FI 0 205

68 Siemens AG 204 Selection and Ordering data Pressure transmitters for level Article No. SITRANS P DS III with PROFIBUS PA (PA) 7 M F SITRANS P DS III with FOUNDATION Fieldbus (FF) 7 M F Click on the Article No. for the online configuration 7 Y in the PIA Life Cycle Portal. Nominal measuring range 250 mbar (00 inh 2 O) D 600 mbar (240 inh 2 O) E 600 mbar (642 inh 2 O) F 5 bar (2000 inh 2 O) G Process connection of low-pressure side Female thread ¼-8 NPT with flange connection Mounting thread 7 / 6-20 UNF to IEC Mounting thread M0 to DIN 92 0 (only for replacement requirement) Non-wetted parts materials process flange screws Electronics housing Stainless steel Die-cast aluminum 2 Stainless steel Stainless steel precision casting Version Standard versions International version, English label inscriptions, 2 documentation in 5 languages on CD (no Order code selectable) Explosion protection None A With ATEX, Type of protection: - "Intrinsic safety (Ex ia)" B - "Explosion-proof (Ex d)" ) D - "Intrinsic safety and flameproof enclosure" P (Ex ia + Ex d)" 2) - "Ex na/ic (Zone 2)" ) E - "Intrinsic safety, explosion-proof enclosure and R dust explosion protection (Ex ia + Ex d + Zone D/2D)" 2)4) (not for DS III FF) FM + CSA intrinsic safe (is) F FM + CSA (is + ep) + Ex ia + Ex d (ATEX) 4) S With FM + CSA, Type of protection: - "Intrinsic Safe und Explosion Proof (is + xp)" ) N C Electrical connection/cable entry Screwed gland M20 x.5 B Screwed gland ½-4 NPT C M2 connectors (stainless steel) 5) 6) F Display Without display 0 Without visible display (display concealed, setting: bar) With visible display (setting: bar) 6 With customer-specific display (setting as 7 specified, Order code "Y2" required) SITRANS P DS III for level Ordering information st order item: Pressure transmitter 7MF nd order item: Mounting flange 7MF ordering example Item line : 7MF464-EY20-AA Item line 2: 7MF492-GE0 Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation Sealing plug(s) or sealing screw(s) for the process flanges(s) ) Without cable gland, with blanking plug. 2) With enclosed cable gland Ex ia and blanking plug. ) Configurations with HAN and M2 connectors are only available in Ex ic. 4) Only in connection with IP65. 5) M2 delivered without cable socket 6) Only in connection with Ex approval A, B, E or F. Siemens FI /57

69 Siemens AG 204 SITRANS P DS III for level Selection and Ordering data Order code Further designs HART PA FF Add "-Z" to Article No. and specify Order code. O-rings for process flanges on low-pressure side (instead of FPM (Viton)) PTFE (Teflon) A20 FEP (with silicone core, approved for food) A2 FFPM (Kalrez, compound 4079), for measured medium temperatures C ( F) A22 NBR (Buna N) A2 Plug Han 7D (metal) A0 Han 8D (instead of Han 7D) A Angled A2 Han 8D (metal) A Sealing screw ¼-8 NPT, with valve in mat. of process flanges A40 Cable sockets for M2 connectors A50 (metal (CuZn)) Rating plate inscription (instead of German) English B French B2 Spanish B Italian B4 Cyrillic (russian) B6 English rating plate B2 Pressure units in inh 2 0 and/or psi Quality inspection certificate (Five-step C factory calibration) to IEC Inspection certificate C2 Acc. to EN Factory certificate C4 Acc. to EN Functional safety (SIL2) C20 Devices suitable for use according to IEC 6508 and IEC 65. Includes SIL conformity declaration Functional safety (PROFIsafe) C2 ) Certificate and PROFIsafe protocol Functional safety (SIL2/) Devices suitable for use according to IEC 6508 and IEC 65. Includes SIL conformity declaration C2 Device passport Russia C99 (For price request please contact the technical support Setting of upper limit of D05 output signal to 22.0 ma Degree of protection IP66/IP68 D2 (only for M20x.5 and ½-4 NPT) Supplied with oval flange D7 ( item), PTFE packing and screws in thread of process flange Capri cable gland 4F CrNi and clamping device ( ) included D59 Selection and Ordering data Order code Further designs HART PA FF Add "-Z" to Article No. and specify Order code. Use on zone D / 2D E0 (only together with type of protection "Intrinsic safety" (transmitter 7MF B.. Ex ia) and IP65) Overfilling safety device for flammable and E08 non-flammable liquids (max. PN 2 (MAWP 464 psi), basic device with type of protection "Intrinsic safety (Ex ia)", to WHG and VbF, not together with measuring cell filling "inert liquid") Export approval Korea E CRN approval Canada E22 (Canadian Registration Number) Dual seal E24 Explosion-proof "Intrinsic safety" (Ex ia) to E25 2) INMETRO (Brazil) (only for transmitter 7MF B..) "Flameproof" explosion protection according E26 2) to INMETRO (Brazil) (only for transmitter 7MF D..) Explosion-proof "Intrinsic safety" (Ex ia + E28 2) Ex d) to INMETRO (Brazil) (only for transmitter 7MF P..) Ex Approval IEC Ex (Ex ia) E45 2) (only for transmitter 7MF B..) Ex Approval IEC Ex (Ex d) E46 2) (only for transmitter 7MF D..) Explosion-proof "Intrinsic safety" E55 2) to NEPSI (China) (only for transmitter 7MF B..) Explosion protection "Explosion-proof" to E56 2) NEPSI (China) (only for transmitter 7MF D..) Ex protection "Zone 2" to NEPSI (China) E57 2) (only for transmitter 7MF E..) Ex protection Ex ia, Ex d and Zone 2 E58 2) to NEPSI (China) (only for transmitter 7MF R..) "Intrinsic safety" and "Explosion-proof" E70 2) explosion protection acc. to Kosha (Korea) (only for transmitter 7MF [B, D]..-Z + E) Two coats of lacquer on casing and cover G0 (PU on epoxy) Replacement of process connection side H0 Transient protector 6 kv (lightning protection) J0 Vent valve or blanking plug of process J08 flange welded-in (orientation: on right when viewing the display) ) Vent valve or blanking plug of process flange welded-in (orientation: on left when viewing the display) ) J09 ) Profisafe transmitters can only be operated with the S7 F Systems V6. configuration software in combination with S7-400H 2) Option beinhaltet keine ATEX-Zulassung, sondern nur die landesspezifische Zulassung. ) Blanking plug is standard configuration. Order option A40 if a vent valve is required instead of a blanking plug. /58 Siemens FI 0 205

70 Siemens AG 204 Selection and Ordering data Order code Additional data HART PA FF Please add "-Z" to Article No. and specify Order code(s) and plain text. Measuring range to be set Y0 ) Specify in plain text (max. 5 characters): Y0:... up to... mbar, bar, kpa, MPa, psi Stainless steel tag plate and entry in Y5 device variable (measuring point description) Max. 6 characters, specify in plain text: Y5:... Measuring point text (entry in device variable) Y6 Max. 27 characters, specify in plain text: Y6:... Entry of HART address (TAG) Y7 Max. 8 characters, specify in plain text: Y7:... Setting of pressure indicator in pressure Y2 units Specify in plain text (standard setting: bar): Y2: mbar, bar, kpa, MPa, psi,... Note: The following pressure units can be selected: bar, mbar, mm H 2 O *), inh 2 O *), fth 2 O *), mmhg, inhg, psi, Pa, kpa, MPa, g/cm 2, kg/cm 2, Torr, ATM or % *) ref. temperature 20 C Setting of pressure indicator in Y22 ) non-pressure units 2) + Y0 Specify in plain text: Y22:... up to... l/min, m /h, m, USgpm,... (specification of measuring range in pressure units "Y0" is essential, unit with max. 5 characters) Preset bus address Y25 possible between and 26 Specify in plain text: Y25:... Damping adjustment in seconds Y0 ( s) Only Y0, Y5, Y6, Y7, Y2, Y22, Y25 and D05 can be factory preset = available ) Measuring accuracies for PROFIBUS PA transmitters with Option Y0 are calculated in the same way as for HART devices. 2) Preset values can only be changed over SIMATIC PDM. ) Not in conjunction with over-filling safety device for flammable and nonflammable liquids (Order code "E08") SITRANS P DS III for level Siemens FI /59

71 Siemens AG 204 SITRANS P DS III for level Selection and Ordering data Article No. Ord. code Mounting flange 7 M F Directly mounted on the SITRANS P pressure transmitter (converter part) for level, for DS III series Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Connection to EN 092- Nominal diameter Nominal pressure DN 50 PN 0/6/25/40 A PN 00 B DN 80 PN 0/6/25/40 D DN 00 PN 0/6 G PN 25/40 H Connection to ASME B6.5 Nominal diameter Nominal pressure 2 inch class 50 L class 00 M class 400/600 N class 900/500 P inch class 50 Q class 00 R 4 inch class 50 T class 00 U Other version, add Order code and plain text: Nominal diameter:...; Nominal press.:... Z J Y Wetted parts materials Stainless steel 6L A - Coated with PFA D - Coated with PTFE E 0 Coated with ECTFE ) F Monel 400, mat. no G Hastelloy C276, mat. no J Hastelloy C4, mat. no U Tantalum K Duplex 2205, mat. no Q Duplex 2205, mat. no..4462, incl. main body R Stainless steel 6L, gold plated, S 0 thickness approx. 25 m Tube length None 0 50 mm (.97 inch) 00 mm (.94 inch) 2 50 mm (5.90 inch) 200 mm (7.87 inch) 4 Other version: add Order code and plain text: Z 8 K Y material of parts in contact with medium:..., tubus length:... Filling liquid Silicone oil M5 Silicone oil M50 2 High-temperature oil Halocarbon oil (for O 2 -measurement) 4 Food oil (FDA-listed) 7 Other version, add 9 M Y Order code and plain text: filling liquid:... ) For vacuum on request Selection and Ordering data Order code Further designs HART PA FF Add "-Z" to Article No. and specify Order code. Spark arrester A0 For mounting on zone 0 (incl. documentation) Remote seal nameplate B20 attached out of stainless steel, contains Article No. and order number of the remote seal supplier Oil- and grease-free cleaned version C0 Oil- and grease-free cleaned and packed version, not for oxygen application, only in conjunction with halocarbon oil fill fluid, certified by certificate acc. to EN Quality inspection certificate (Five-step C factory calibration) to IEC Inspection certificate C2 Acc. to EN Certificate of FDA approval of fill oil C7 Only in conjunction with filling liquid "Food oil" (FDA listed)" "Functional safety (SIL2)" certificate C20 to IEC 6508 (only for conjunction with the Order code "C20" in the case of SITRANS P DS III transmitter) "Functional safety (SIL2/)" certificate C2 to IEC 6508 (only for conjunction with the Order code "C2" in the case of SITRANS P DS III transmitter) Certification acc. to NACE MR-075 D07 Includes acceptance test certificate. acc. to EN 0204 (only for wetted parts made of stainless steel.4404/6l and Hastelloy C276) Certification acc. to NACE MR-00 D08 Includes acceptance test certificate. acc. to EN 0204 (only for wetted parts made of stainless steel.4404/6l and Hastelloy C276) Oil- and grease-free cleaned version E0 Oil- and grease-free cleaned and packed version, only for oxygen application, only inert fill fluid may be used. Max. temperature: 60 C (40 F), max. pressure 50 bar (725 psi), only in connection with halocarbon oil, certified by certificate acc. to EN Epoxy painting E5 Not possible with vacuum-proof design Color: transparent, coverage: front and rear of the remote seal, capillary(ies) or connecting tube, process connection of the transmitter. With transmitters 7MF40.. and 7MF42.., only possible with process connection G½B according to EN87-. Sealing surface B or J2 ASME B6.5 RF AA instead of sealing surface B2 or RFSF (only for wetted parts made of Hastelloy C276 (2.489), tantalum and Duplex 2205 (.4462) and for nominal sizes 2", ", DN 50 and DN 80) Sealing surface groove, EN 092-, form D J4 instead of sealing surface B (only for wetted parts made of stainless steel 6L) Sealing surface RJF (groove) ASME B6.5 J24 instead of sealing surface ASME B6.5 RF AA (only for wetted parts made of stainless steel 6L) /60 Siemens FI 0 205

72 Siemens AG 204 Selection and Ordering data Order code Further designs HART PA FF Add "-Z" to Article No. and specify Order code. Elongated pipe, 50 mm instead of 00 mm, R5 max. medium temperature 250 C, observe the maximum permissible media temperature of the filling liquid. Elongated pipe, 200 mm instead of 00 mm, R20 max. medium temperature 00 C, observe the maximum permissible media temperature of the filling liquid. Vacuum-proof design V04 (for use in low-pressure range) Note: suffix "Y0" required with press. transm. = available SITRANS P DS III for level Siemens FI /6

73 Siemens AG 204 SITRANS P DS III for level Dimensional drawings 29 (.4) 5) 77 (6.97) 84 (.) 2 5 (2.) 4 (5.6) 5 74 (2.9) (0.6) min. 90 (.54) 5) Ød 5 Ød 4 Øk ØD 66 (6.54) 9 54 (2.) 08 (4.25) approx. 96 (.78) 7 (0.67) 7 Space for rotation of housing n x d 2 b f L 8 Electrical connection: Screwed gland Pg,5 (adapter)(adapter) 2) ), Screwed gland M20 x,5 or Screwed gland ½-4 NPT or Han 7D/Han 8D 2) ) plug 2 Protective cover over keys Blanking plug 4 Screw cover - safety bracket (only for type of protection "Explosion-proof enclosure", not shown in the drawing) 5 Terminal side ) 6 Electronic side, digital display (longer overall length for cover with window) ) 7 Sealing screw with valve (option) 8 Harting adapter 9 Process connection of low pressure side ¼-8 NPT (IEC 658) ) Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing 2) Not with type of protection "Explosion-proof enclosure" ) Not with type of protection "FM + CSA" [IS + XP]" 4) 92 mm (.62 inch) for minimum distance to permit rotation with indicator 5) For Pg,5 with adapter approx. 45 mm (.77 inch) SITRANS P DS III with HART pressure transmitters for level, including mounting flange, dimensions in mm (inch) /62 Siemens FI 0 205

74 Siemens AG 204 SITRANS P DS III for level Connection to EN 092- Nominal Nominal b D d d 2 d 4 d 5 d M f k n L diameter pressure mm mm mm mm mm mm mm mm mm mm mm DN 50 PN 0/6/ 25/ ) , 50, 00, 50 or 200 PN ) DN 80 PN 0/6/ ) /40 PN ) DN 00 PN 0/ PN 25/ Connection to ASME B6.5 Nominal Nominal b D d 2 d 4 d 5 d M f k n L diameter pressure lb./sq.in inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) 2 inch (9.5) 5.9 (50) 0.79 (20).62 (92).9 (48.).77 ) (45) 0.08 (2) 4.74 (20.5) 4 0, 2,.94, (22.7) 6.5 (65) 0.79 (20).62 (92).9 (48.).77 ) (45) 0.08 (2) 5 (27) or 7.87 (0, 50, 00, 400/ (2.4) 6.5 (65) 0.79 (20).62 (92).9 (48.).77 ) (45) 0.28 (7) 5 (27) 8 50 or 200) 900/ (45.) 8.46 (25).02 (26) 5 (27).9 (48.).77 ) (45) 0.28 (7) 6.5 (65) 8 inch (24.) 7.48 (90) 0.79 (20) 5 (27) (76) 2.8 2) (72) 0.08 (2) 6 (52.5) (29) 8.27 (20) 0.87 (22) 5 (27) (76) 2.8 2) (72) 0.08 (2) 6.6 (68.5) (8.8) 8.27 (20) 0.87 (22) 5 (27) (76) 2.8 2) (72) 0.28 (7) 6.6 (68.5) 8 4 inch (24.) 9.06 (20) 0.79 (20) 6.22 (58).69 (94).5 (89) 0.08 (2) 7.5 (90.5) (2.2) 0.04 (255) 0.87 (22) 6.22 (58).69 (94).5 (89) 0.08 (2) 7.87 (200) (42) 0.04 (255).02 (26) 6.22 (58).69 (94).5 (89) 0.28 (7) 7.87 (200) 8 d: Internal diameter of gasket to DIN 2690 d M : Effective diaphragm diameter ) 59 mm = 2.2 inch with tube length L=0. 2) 89 mm = ½ inch with tube length L=0. Siemens FI /6

75 Siemens AG 204 Overview Structural design Dimensions (W x H x D) in mm (inch) Electrical connection 80 x 20 x 60 (.5 x 4.72 x 2.6) Screw terminals (Pg.5 cable inlet) or Han 7D / Han 8D plug Power supply Supply voltage 20 V AC ( %, Hz, approx. 6 VA) or 24 V AC/DC (24 V AC 0 %, Hz, approx. VA) Permissible ripple (within the specified Approx. 2.5 V pp limits) SITRANS P DS III Supplementary electronics for 4-wire connection Dimensional drawings 22 (8.5) 80 (.5) Direct connection of the supplementary electronics to a SITRANS P DS III pressure transmitter with HART produces a transmitter for 4-wire connection. The supplementary electronics cannot be attached to explosionprotected pressure transmitters. The supplementary electronics is fitted in a light metal housing which is mounted on the left side of the pressure transmitter. Note on ordering: The supplementary electronics can only be ordered as an optional accessory for the corresponding pressure transmitter. Technical specifications SITRANS P, supplementary electronics for 4-wire connection Output Output signal ma or ma Load Max. 750 Voltage measurement Linear (square-rooting in transmitter if necessary) Electrical isolation Between power supply and input/ output Measuring accuracy acc. to IEC Measurement deviation (in addition 0.5 % of set span to transmitter) Influence of ambient temperature 0. % per 0 K Power supply effect 0. % per 0 % change in voltage or frequency Load effect 0. % per 00 % change Rated conditions Ambient temperature 24 V version C( F) 20V version C( F) Storage temperature C( F) Degree of protection IP54 to IEC Electromagnetic compatibility IEC 626 (EMC) Condensation Relative humidity % condensation permissible 4 (4.5) SITRANS P pressure transmitters with supplementary electronics for fourwire connection, dimension drawing, dimensions in mm /64 Siemens FI 0 205

76 Siemens AG 204 Schematics Terminals Han 8D/7D plug 2 plugs AC 20 V UC 24 V SL I a I a Han 7D Han 7D I a Output current SL Protective earth U H Power supply conductor Supplementary electronics for 4-wire connection, connection diagram I a U H SL U H U H Han 7D Han 8D SITRANS P DS III Supplementary electronics for 4-wire connection SL Selection and Ordering data Supplementary electronics for 4-wire connection Article No. of the transmitter 7MF AB. add "-Z" and Order code. Power supply Electrical connection 24 V AC/DC Terminals; 2 Pg screwed glands, to left 2 Han 7D/Han 8D plugs incl. mating connector, to left Han 7D plug incl. mating connector, angled Terminals; Pg screwed gland, downwards Han 8D plug incl. mating connector, downwards (observe arrangement of plug and differential pressure line) 20 V AC Terminals; 2 Pg screwed glands, to left 2 Han 7D plugs incl. mating connector, to left Order code V 7 7 Output current ma ma Accessories Instruction Manual A5E German/English Siemens FI /65

77 Siemens AG 204 SITRANS P DS III Accessories/Spare Parts Selection and Ordering data Article No. Replacement measuring cell for pressure 7 M F for SITRANS P DS III D B 0 Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Measuring cell cleaning Silicone oil Normal Inert liquid grease-free to cleanliness level 2 Measured span (min.... max.) bar ( psi) B bar ( psi) C bar ( psi) D bar ( psi) E bar ( psi) F bar ( psi) G bar ( psi) J Wetted parts materials Seal diaphragm Process connection Stainless steel Stainless steel A Hastelloy Stainless steel B Hastelloy Hastelloy C Process connection Connection shank G½B to EN 87-0 Female thread ½-4 NPT Oval flange made of stainless steel, max. span 60 bar (220 psi) - Mounting thread 7 / 6-20 UNF to IEC Mounting thread M0 to DIN 92 Further designs Order code Please add "-Z" to Article No. and specify Order code. Inspection certificate C2 to EN Selection and Ordering data Article No. Replacement measuring cell for absolute pressure for SITRANS P DS III (from the pressure series) 7 M F D B 0 Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Measuring cell cleaning Silicone oil Normal Inert liquid grease-free to cleanliness level 2 Measured span (min.... max.) mbar a ( psia) D mbar a ( psia) F bar a ( psia) G... 0 bar a ( psia) H Wetted parts materials Seal diaphragm Process connection Stainless steel Stainless steel A Hastelloy Stainless steel B Hastelloy Hastelloy C Process connection Connection shank G½B to EN 87-0 Female thread ½-4 NPT Oval flange made of stainless steel, max. span 60 bar (220 psi) - Mounting thread 7 / 6-20 UNF to IEC Mounting thread M0 to DIN 92 Further designs Order code Please add "-Z" to Article No. and specify Order code. Inspection certificate C2 to EN /66 Siemens FI 0 205

78 Siemens AG 204 Selection and Ordering data Replacement measuring cell for absolute pressure (from the differential pressure series) for SITRANS P DS III with HART, DS III with PROFIBUS PA and DS III with FOUNDATION Fieldbus series Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Measuring cell cleaning Article No. 7 M F D C 0 Silicone oil Normal Inert liquid grease-free to cleanliness level 2 Measured span (min.... max.) mbar a ( psia) D mbar a ( psia) F bar a ( psia) G... 0 bar a ( psia) H bar a ( psia) K E Wetted parts materials Seal diaphragm Parts of measuring cell Stainless steel Stainless steel A Hastelloy Stainless steel B Hastelloy Hastelloy C Tantalum Tantalum E Monel Monel H Gold Gold L Process connection Female thread ¼-8 NPT with flange connection Sealing screw opposite process connection - Mounting thread M0 to DIN Mounting thread 7 / 6-20 UNF to IEC Vent on side of process flange ) - Mounting thread M0 to DIN Mounting thread 7 / 6-20 UNF to IEC Non-wetted parts materials Stainless steel process flange screws 2 Further designs Order code Please add "-Z" to Article No. and specify Order code. O-rings for process flanges (instead of FPM (Viton)) PTFE (Teflon) A20 FEP (with silicone core, approved for food) A2 FFPM (Kalrez, compound 4079), for measured medium A22 temperatures C ( F) NBR (Buna N) A2 Inspection certificate C2 to EN Process connection G½B D6 Remote seal flanges D20 (not together with K0, K02 and K04) Vent on side for gas measurements H02 Process flanges without K00 with process flange made of - Hastelloy K0 - Monel K02 - Stainless steel with PVDF insert K04 max. PN 0 (MAWP 45 psi) max.temperature of medium 90 C (94 F) For ½-4 NPT inner process connection on the side in the middle of the process flange, vent valve not possible ) Not for span bar ( psi) SITRANS P DS III Accessories/Spare Parts Selection and Ordering data Article No. Replacement measuring cell for differential pressure and PN 2/60 (MAWP 464/220 psi) for SITRANS P DS III with HART, DS III with PROFIBUS 7 M F D C 0 PA and DS III with FOUNDATION Fieldbus series Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Measuring cell cleaning Silicone oil Normal Inert liquid grease-free to cleanliness level 2 Measured span (min.... max.) PN 2 (MAWP 464 psi) mbar ) ( inh 2 O) B PN 60 (MAWP 220 psi) mbar ( inh 2 O) C mbar ( inh 2 O) D mbar ( inh 2 O) E mbar ( inh 2 O) F mbar ( inh 2 O) G bar ( psi) H Wetted parts materials (stainless steel process flanges) Seal diaphragm Parts of measuring cell Stainless steel Stainless steel A Hastelloy Hastelloy Stainless steel Hastelloy B C Tantalum 2) Tantalum E Monel 2) Monel H Gold 2) Gold L Process connection Female thread ¼-8 NPT with flange connection Sealing screw opposite process connection - Mounting thread M0 to DIN Mounting thread 7 / 6-20 UNF to IEC Vent on side of process flange - Mounting thread M0 to DIN Mounting thread 7 / 6-20 UNF to IEC Non-wetted parts materials Stainless steel process flange screws 2 Further designs Order code Please add "-Z" to Article No. and specify Order code. O-rings for process flanges (instead of FPM (Viton)) PTFE (Teflon) A20 FEP (with silicone core, approved for food) A2 FFPM (Kalrez, compound 4079), for measured medium A22 temperatures C ( F) NBR (Buna N) A2 Inspection certificate C2 to EN Remote seal flanges D20 (not together with K0, K02 and K04) Vent on side for gas measurements H02 Stainless steel process flanges for vertical H0 differential pressure lines (not together with K0, K02 and K04) Process flanges without K00 with process flange made of -Hastelloy K0 - Monel K02 - Stainless steel with PVDF insert, max. PN 0 K04 (MAWP 45 psi), max. temperature of medium 90 C (94 F). For ½-4 NPT inner process connection on the side in the middle of the process flange, vent valve not possible ) Not suitable for connection of remote seal 2) Only together with max. spans 250, 600, 5000 and 0000 mbar (00 inh 2 O, 642 inh 2 O, 2000 inh 2 O und 45 psi). Siemens FI /67

79 Siemens AG 204 SITRANS P DS III Accessories/Spare Parts Selection and Ordering data Article No. Replacement measuring cell for differential pressure and PN 420 (MAWP 6092 psi) for SITRANS P DS III with HART, DS III with PROFIBUS 7 M F D C 0 PA and DS III with FOUNDATION Fieldbus series Click on the Article No. for the online configuration in the PIA Life Cycle Portal. Measuring cell filling Measuring cell cleaning Silicone oil Normal Measured span (min.... max.) mbar (...00 inh 2 O) D mbar ( inh 2 O) E mbar ( inh 2 O) F mbar ( inh 2 O) G bar ( psi) H Wetted parts materials (stainless steel process flanges) Seal diaphragm Parts of measuring cell Stainless steel Stainless steel A Hastelloy Stainless steel B Gold ) Gold L Process connection Female thread ¼-8 NPT with flange connection Sealing screw opposite process connection - Mounting thread M2 to DIN 92 - Mounting thread 7 / 6-20 UNF to IEC 658 Vent on side of process flange - Mounting thread M2 to DIN Mounting thread 7 / 6-20 UNF to IEC Non-wetted parts materials Stainless steel process flange screws 2 Further designs Order code Please add "-Z" to Article No. and specify Order code. O-rings for process flanges (instead of FPM (Viton)) PTFE (Teflon) A20 FEP (with silicone core, approved for food) A2 FFPM (Kalrez, compound 4079), for measured medium temperatures C ( F) A22 NBR (Buna N) A2 Inspection certificate C2 to EN Stainless steel process flanges for vertical H0 differential pressure lines without process flanges K00 ) Not together with max. span 600 mbar (240.9 inh 2 O) /68 Siemens FI 0 205

80 Siemens AG 204 Selection and Ordering data Spare parts/accessories Article No. Mounting bracket and fastening parts for pressure transmitters SITRANS P DS III with HART, DS III with PROFIBUS PA and DS III with FOUNDATION Fieldbus (7MF C.) For absolute pressure transmitters SITRANS P DS III with HART, DS III with PROFIBUS PA and DS III with FOUNDATION Fieldbus (7MF C.) made of steel 7MF4997-AB made of stainless steel 7MF4997-AH Mounting bracket and fastening parts for pressure transmitters SITRANS P DS III with HART, DS III with PROFIBUS PA and DS III with FOUNDATION Fieldbus (7MF A., -..B.,..D. and..f.) For absolute pressure transmitters SITRANS P DS III with HART, DS III with PROFIBUS PA and DS III with FOUNDATION Fieldbus 7MF A., -..B.,..D. and..f.) made of steel 7MF4997-AC made of stainless steel } 7MF4997-AJ Mounting and fastening brackets For differential pressure transmitters with flange thread M0 SITRANS P DS III with HART, DS III with PROFIBUS PA and DS III with FOUNDATION Fieldbus (7MF and 7MF ) made of steel 7MF4997-AD made of stainless steel } 7MF4997-AK Mounting and fastening brackets For differential pressure transmitters with flange thread M2 SITRANS P DS III with HART, DS III with PROFIBUS PA and DS III with FOUNDATION Fieldbus (7MF ) made of steel 7MF4997-AE made of stainless steel 7MF4997-AL Mounting and fastening brackets For differential and absolute pressure transmitters with flange thread 7/6-20 UNF SITRANS P DS III with HART, DS III with PROFIBUS PA and DS III with FOUNDATION Fieldbus (7MF4.-..., 7MF and 7MF ) made of steel 7MF4997-AF made of stainless steel 7MF4997-AM Cover made of die-cast aluminum, including gasket, for SITRANS P DS III with HART, DS III with PROFIBUS PA and DS III with FOUNDATION Fieldbus without window 7MF4997-BB with window } 7MF4997-BE Cover made of stainless steel, including gasket, for SITRANS P DS III with HART, DS III with PROFIBUS PA and DS III with FOUNDATION Fieldbus without window 7MF4997-BC with window 7MF4997-BF Digital indicator 7MF4997-BR Including mounting material for SITRANS P DS III with HART, DS III with PROFIBUS PA and DS III with FOUNDATION Fieldbus Measuring point label without inscription (5 units) 7MF4997-CA Printed ( unit) Data according to Y0 or Y02, Y5, Y6 and Y99 (see "Pressure transmitters") 7MF4997-CB-Z Y..:... } Available ex stock SITRANS P DS III Accessories/Spare Parts Selection and Ordering data Article No. Mounting screws For measuring point label, grounding and connection terminals or for display 7MF4997-CD (50 units) Sealing screws ( set = 2 units) for process flange made of stainless steel 7MF4997-CG made of Hastelloy 7MF4997-CH Sealing screws with vent valve Complete ( set = 2 units) made of stainless steel } 7MF4997-CP made of Hastelloy 7MF4997-CQ Application electronics for SITRANS P DS III with HART 7MF4997-DK for SITRANS P DS III with PROFIBUS PA 7MF4997-DL for SITRANS P DS III with FOUNDATION 7MF4997-DM Fieldbus Connection board for SITRANS P DS III 7MF4997-DN for SITRANS P DS III PROFIBUS PA and 7MF4997-DP FOUNDATION Fieldbus O-rings for process flanges made of: FPM (Viton) 7MF4997-2DA PTFE (Teflon) 7MF4997-2DB FEP (with silicone core, approved for food) 7MF4997-2DC FFPM (Kalrez, compound 4079) 7MF4997-2DD NBR (Buna N) 7MF4997-2DE Sealing ring for process connection see "Fittings" Weldable sockets for PMC connection PMC Style Standard: Thread ½" 7MF4997-2HA PMC Style Minibolt: front-flush " 7MF4997-2HB Gaskets for PMC connection (packing unit = 5 units) PTFE seal for PMC Style Standard: 7MF4997-2HC Thread ½" Gasket made of Viton for PMC Style Minibolt: 7MF4997-2HD front-flush " Weldable socket for TG52/50 and TG52/50 connection TG52/50 connection 7MF4997-2HE TG52/50 connection 7MF4997-2HF Seals for TG 52/50 and TG 52/50 made of 7MF4997-2HG silicone (FDA compliant) Seals for flange connection with front-flush diaphragm Material FPM (Viton), 0 units DN 25, PN 40 (M) 7MF4997-2HH DN 25, PN 00 (M2) 7MF4997-2HJ ", class 50 (M40) 7MF4997-2HK ", class 00 (M45) 7MF4997-2HL Siemens FI /69

81 Siemens AG 204 SITRANS P DS III Accessories/Spare Parts Selection and Ordering data Article No. Operating Instructions ) for SITRANS DS III with HART -German A5E English A5E French A5E Spanish A5E Italian A5E for SITRANS DS III with PROFIBUS PA -German A5E English A5E French A5E Spanish A5E Italian A5E for SITRANS DS III with FOUNDATION Fieldbus -German A5E English A5E Compact operating instructions English, german, spanish, french, italian, A5E dutch English, estonian, latvian, lithuanian, polish, A5E0446 romanian English, bulgarian, czech, finnish, slovakian, A5E slovenian English, danish, greek, portuguese, swedish, A5E hungarian Korean A5E The compact operating instructions are available in 2 EU languages on the product CD supplied with each transmitter. They can also be downloaded from the SITRANS P web page. Brief instruction (Leporello) German, English for SITRANS DS III with HART A5E German, English for SITRANS DS III with PROFIBUS PA A5E German, English for SITRANS DS III with FOUNDATION A5E Fieldbus - German, English CD with SITRANS P documentation A5E German, English, French, Spanish, Italian incl. compact operating instructions in 2 EU languages Certificates (order only via SAP) instead of Internet download hard copy (to order) A5E on CD (to order) A5E Operating Instructions A5E for replacement of electronics, measuring cell and connection board (only available from the Internet) ) HART modem with USB interface } 7MF4997-DB Supplementary electronics for 4-wire See page /64 connection } Available ex stock Power supply units see Chap. 7 "Supplementary Components". ) You can download these operating instructions free-of-charge from our Internet site at /70 Siemens FI 0 205

82 Siemens AG 204 Dimensional drawings SITRANS P DS III Accessories/Spare Parts , Ø9 R ,5 Ø R0 5 6,5 52, Mounting bracket for SITRANS P DS III and SITRANS P280 gauge and absolute pressure-transmitters, dimensions in mm mounting bracket material: Sheet-steel Mat. No..00, chrome-plated, or stainless steel Mat. No..40 (04) , , R6, Ø R0 72 6,5 52, ,65 R0 Ø20 4, Mounting bracket for SITRANS P DS III differential pressure transmitter, dimensions in mm mounting bracket material: Sheet-steel Mat. No..00, chrome-plated, or stainless steel Mat. No..40 (04) Siemens FI /7

83 Siemens AG 204 Overview SITRANS P DS III - Factory-mounting of valve manifolds on transmitters SITRANS P transmitters DS III for relative and absolute pressure (both designs) and DS III for differential pressure can be delivered factory-fitted with the following valve manifolds: 7MF90-4EA and 7MF90-4FA valve manifolds for gauge pressure and absolute pressure transmitters 7MF94-5BA and 7MF94-5CA valve manifolds for absolute pressure and differential pressure transmitters Design The 7MF90-4EA valve manifolds are sealed with gaskets made of PTFE between transmitter and the valve manifold as standard. Soft iron, stainless steel and copper gaskets are also available for sealing purposes if preferred. The 7MF90-4FA valve manifolds are sealed with PTFE sealing tape between the transmitter and the valve manifold. The 7MF94-5BA and 7MF94-5CA valve manifolds are sealed with PTFE sealing rings between the transmitter and the valve manifold. Once installed, the complete unit is checked under pressure for leaks (compressed air 6 bar (87 psi)) and is certified leak-proof with a test report to EN All valve manifolds should preferably be secured with the respective mounting brackets. The transmitters are mounted on the valve manifold and not on the unit itself. If you order a mounting bracket when choosing the option "Factory mounting of valve manifolds", you will receive a mounting bracket for the valve manifold instead of a bracket for mounting the transmitter. If you order an acceptance test certificate. to EN0204 when choosing the option "Factory mounting of valve manifolds", a separate certificate is provided for the transmitters and the valve manifolds respectively. Selection and Ordering data 7MF94-5AA valve manifold for relative and absolute pressure transmitters Add -Z to the Article No. of the transmitter and add order codes. SITRANS P DSIII 7MF , 7MF , 7MF , 7MF , 7MF , 7MF With process connection oval flange with PTFE gasket and steel mounting screws. Delivery including high-presure test certified by factory certificate according to EN Additional versions: Delivery includes mounting brackets and mounting clips made of stainless steel (instead of the mounting bracket supplied with the transmitter) Supplied acceptance test certificate to EN for transmitters and mounted valve manifold With manufacturer declaration according to NACE, MR-075 Order code T05 A02 C2 D07 7MF94-5AA valve manifold for relative and absolute pressure transmitters Add -Z to the Article No. of the transmitter and add order codes. SITRANS P DSIII 7MF , 7MF , 7MF , 7MF , 7MF , 7MF With process connection oval flange with PTFE gasket and stainless steel mounting screws. Delivery including high-presure test certified by factory certificate according to EN Additional versions: Delivery includes mounting brackets and mounting clips made of stainless steel (instead of the mounting bracket supplied with the transmitter) Supplied acceptance test certificate to EN for transmitters and mounted valve manifold With manufacturer declaration according to NACE, MR-075 Order code T06 A02 C2 D07 /72 Siemens FI 0 205

84 Siemens AG 204 7MF90-4FA valve manifold on relative and absolute pressure transmitters Add -Z to the Article No. of the transmitter and add Order codes SITRANS P DSIII 7MF , 7MF With process connection female thread ½-4 NPT in-sealed with PTFE sealing tape Delivery incl. high-pressure test certified by test report to EN Further designs: SITRANS P DS III - Factory-mounting of valve manifolds on transmitters Order code T0 Delivery includes mounting brackets and A02 mounting clips made of stainless steel (instead of the mounting bracket supplied with the transmitter) Supplied acceptance test certificate to EN C for transmitters and mounted valve manifold With manufacturer declaration according D07 to NACE, MR-075 7MF90-4EA valve manifold on relative and absolute pressure transmitters Add -Z to the Article No. of the transmitter and add Order codes SITRANS P DSIII 7MF , 7MF with process connection collar G/2 A to EN 87- with gasket made of PTFE between valve manifold and transmitter Alternative sealing material: Soft iron Stainless steel, Mat. No. 457 copper Delivery incl. high-pressure test certified by test report to EN Further designs: Delivery includes mounting brackets and mounting clips made of stainless steel (instead of the mounting bracket supplied with the transmitter) Supplied acceptance test certificate to EN for transmitters and mounted valve manifold With manufacturer declaration according to NACE, MR-075 Order code T02 A70 A7 A72 A02 C2 D07 7MF94-5BA valve manifold on absolute and differential pressure transmitters Add -Z to the Article No. of the transmitter and add Order codes SITRANS P DSIII 7MF4.-, 7MF44.- and 7MF45.- ) mounted with gaskets made of PTFE and screws made of chromized steel made of stainless steel Delivery incl. high-pressure test certified by test report to EN Further designs: Delivery includes mounting bracket and mounting clips made of Steel Stainless steel (instead of the mounting bracket supplied with the transmitter) Supplied acceptance test certificate to EN for transmitters and mounted valve manifold With manufacturer declaration according to NACE, MR-075 7MF94-5CA valve manifold on differential pressure transmitters Add -Z to the Article No. of the transmitter and add Order codes SITRANS P DSIII 7MF and 7MF45.- ) mounted with gaskets made of PTFE and screws made of chromized steel Stainless steel Delivery incl. high-pressure test certified by test report to EN Further designs: Delivery includes mounting bracket and mounting clips made of Steel Stainless steel (instead of the mounting bracket supplied with the transmitter) Supplied acceptance test certificate to EN for transmitters and mounted valve manifold With manufacturer declaration according to NACE, MR-075 Order code U0 U02 A0 A02 C2 D07 Order code U0 U04 A0 A02 C2 D07 ) For 7MF transmitters, you require a 7/0-20 UNF connection thread in the process flange Siemens FI /7

85 Siemens AG 204 SITRANS P DS III - Factory-mounting of valve manifolds on transmitters Dimensional drawings Valve manifolds mounted on SITRANS P DS III 7MF90-4EA valve manifold with mounted gauge pressure and absolute pressure transmitters 7MF90-4FA valve manifold with mounted gauge pressure and absolute pressure transmitters 8 (4.65) 84 (.) 58 (6.2) 8 (4.65) 84 (.) 58 (6.2) approx. 285 (.2) approx. 29 (.54) 49 (5.87) 76 (6.9) 92 (7.56) approx. 50 (5.9) 90 (7.5) 7MF90-4EA valve manifold with mounted gauge pressure and absolute pressure transmitters, dimensions in mm (inch) 7MF90-4FA valve manifold with mounted gauge pressure and absolute pressure transmitters, dimensions in mm (inch) /74 Siemens FI 0 205

86 Siemens AG 204 SITRANS P DS III - Factory-mounting of valve manifolds on transmitters 7MF94-5BA valve manifold with mounted differential pressure transmitter 7MF94-5CA valve manifold with mounted differential pressure transmitter 92 (7.56) 244 (9.6) 25 (8.46) 7MF94-5BA valve manifold with mounted differential pressure transmitter, dimensions in mm (inch) 90 (7.48) 245 (9.65) 256 (0.08) 7MF94-5CA valve manifold with mounted differential pressure transmitter, dimensions in mm (inch) Siemens FI /75

Siemens AG psi (6 bar) 145 psi (10 bar) 464 psi (32 bar) 1450 psi (100 bar) 3626 psi (250 bar) 8700 psi (600 bar) psi (800 bar)

Siemens AG psi (6 bar) 145 psi (10 bar) 464 psi (32 bar) 1450 psi (100 bar) 3626 psi (250 bar) 8700 psi (600 bar) psi (800 bar) Technical specifications SITRANS P, DS III series Input Measured variable Spans (infinitely adjustable) or nominal measuring range and max. permissible test pressure HART Gauge pressure Span (min.... max.)

More information

Pressure Measurement Transmitters for applications with advanced requirements (Advanced)

Pressure Measurement Transmitters for applications with advanced requirements (Advanced) Siemens AG 206 Technical specifications SITRANS P DS III series for absolute pressure (from the gauge pressure series) Input Measured variable Absolute pressure Span (fully adjustable) or measuring range,

More information

1 Technical specifications

1 Technical specifications Siemens AG 07 Technical specifications SITRANS P, DS III series for gauge pressure Input Measured variable Gauge pressure Span (fully adjustable) or measuring range, max. operating HART pressure (in accordance

More information

Pressure Measurement Transmitters for applications with advanced requirements (Advanced)

Pressure Measurement Transmitters for applications with advanced requirements (Advanced) Siemens AG 207 Technical specifications SITRANS P DS III series for absolute pressure (from the gauge pressure series) Input Measured variable Absolute pressure Span (fully adjustable) or measuring range,

More information

Pressure Measurement Transmitters for applications with advanced requirements (Advanced)

Pressure Measurement Transmitters for applications with advanced requirements (Advanced) Overview SITRANS P DS III - Technical description SITRANS P DS III pressure transmitters are digital pressure transmitters featuring extensive user-friendliness and high accuracy. The parameterization

More information

Pressure Measurement. Transmitters for general requirements SITRANS P DS III Technical description. 2/74 Siemens FI

Pressure Measurement. Transmitters for general requirements SITRANS P DS III Technical description. 2/74 Siemens FI Technical description Overview Siemens AG 010 pressure transmitters are digital pressure transmitters featuring extensive user-friendliness and high accuracy. The parameterization is performed using control

More information

Pressure Measurement Transmitters for applications with advanced requirements (Advanced)

Pressure Measurement Transmitters for applications with advanced requirements (Advanced) Siemens AG 07 Overview SITRANS P DS III - Technical description SITRANS P DS III pressure transmitters are digital pressure transmitters featuring extensive user-friendliness and high accuracy. The parameterization

More information

Pressure Measurement Transmitters for applications with advanced requirements (Advanced)

Pressure Measurement Transmitters for applications with advanced requirements (Advanced) Siemens AG 06 Technical specifications SITRANS P, DS III for differential pressure and flow Input Measured variable Differential pressure and flow Span (fully adjustable) or measuring range, max. operating

More information

1 Technical specifications

1 Technical specifications Siemens AG 06 SITRANS P S III for gauge/absolute pressure, with front-flush diaphragm Technical specifications SITRANS P S III series for gauge and absolute pressure, with front-flush diaphragm Input of

More information

Siemens AG Span (min... max.) Max. perm. test. 87 psi (6 bar) 145 psi (10 bar) 464 psi (32 bar) 1450 psi (100 bar)

Siemens AG Span (min... max.) Max. perm. test. 87 psi (6 bar) 145 psi (10 bar) 464 psi (32 bar) 1450 psi (100 bar) SITRANS P S III for gauge/absolute pressure, Technical specifications SITRANS P S III series for gauge and absolute pressure, HART PROFIBUS PA and FOUNATION Fieldbus Input of gauge pressure, Measured variable

More information

1 Technical specifications

1 Technical specifications Siemens AG 07 Technical specifications SITRANS P, DS III for differential pressure and flow Input Measured variable Differential pressure and flow Span (fully adjustable) or measuring range, max. operating

More information

1 Overview. Pressure Measurement Transmitters for basic requirements. 1/16 Siemens FI SITRANS P220 for gauge pressure

1 Overview. Pressure Measurement Transmitters for basic requirements. 1/16 Siemens FI SITRANS P220 for gauge pressure Siemens AG 204 Overview The pressure transmitter SITRANS P220 measures the gauge pressure of liquids, gases and vapors. Stainless steel measuring cell, fully welded Measuring ranges 2.5 to 600 bar (36.3

More information

SITRANS P measuring instruments for pressure

SITRANS P measuring instruments for pressure SITRANS P measuring instruments for pressure Z series for gage pressure Siemens AG 008 Overview Design The main components of the pressure transmitter are: Brass housing with silicon measuring cell and

More information

Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology

Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology Siemens AG 206 Overview The SITRANS P300 is a digital pressure transmitter for relative and absolute pressure. The conventional thread versions are available as process connections, as are flush-mounted

More information

2 Overview. SITRANS P measuring instruments for pressure. Transmitters for gage and absolute pressure. Z series for gage pressure

2 Overview. SITRANS P measuring instruments for pressure. Transmitters for gage and absolute pressure. Z series for gage pressure Z series for gage pressure Overview Design The main components of the pressure transmitter are: Brass housing with silicon measuring cell and electronics plate Process connection Electrical connection

More information

Pressure Measurement. Transmitters for food, pharmaceuticals and biotechnology. SITRANS P300 for gauge and absolute pressure. 2/34 Siemens FI

Pressure Measurement. Transmitters for food, pharmaceuticals and biotechnology. SITRANS P300 for gauge and absolute pressure. 2/34 Siemens FI Overview The SITRANS P300 is a digital pressure transmitter for relative and absolute pressure All conventional thread versions are available as process connections. In addition, various hygienebased connections

More information

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/16 Siemens FI US Edition

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/16 Siemens FI US Edition Siemens AG 206 Overview Design Device structure without explosion protection The pressure transmitter consists of a piezoresistive measuring cell with a diaphragm installed in a stainless steel enclosure.

More information

Pressure Measurement Single-range transmitters for general applications

Pressure Measurement Single-range transmitters for general applications Siemens A 207 Overview Application The SITRANS P Compact pressure transmitter is designed for the special requirements of the food, pharmaceutical and biotechnology industries. The use of high-grade materials

More information

1 Overview. Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology. SITRANS P300 for gauge and absolute pressure

1 Overview. Pressure Measurement Transmitters for food, pharmaceuticals and biotechnology. SITRANS P300 for gauge and absolute pressure Siemens AG 208 Overview The SITRANS P300 is a digital pressure transmitter for relative and absolute pressure. The conventional thread versions are available as process connections, as are flush-mounted

More information

Pressure Measurement Single-range transmitters for general applications

Pressure Measurement Single-range transmitters for general applications Siemens AG 206 Overview Design Device structure without explosion protection The pressure transmitter consists of a piezoresistive measuring cell with a diaphragm installed in a stainless steel enclosure.

More information

Pressure Measurement. Transmitters for basic requirements SITRANS P Z for gauge pressure. 2/4 Siemens FI Overview

Pressure Measurement. Transmitters for basic requirements SITRANS P Z for gauge pressure. 2/4 Siemens FI Overview f gauge pressure Siemens AG 010 Overview Design The main components of the pressure transmitter are: Brass housing with silicon measuring cell and electronics plate Process connection Electrical connection

More information

TYPE APPROVAL CERTIFICATE

TYPE APPROVAL CERTIFICATE TYPE APPROVAL CERTIFICATE Certificate No: TAA0000123 This is to certify: That the Pressure Transmitter with type designation(s) SITRANS P series DS III, P310, P410 Issued to Siemens AG - Process Industries

More information

Pressure Measurement Single-range transmitters for general applications

Pressure Measurement Single-range transmitters for general applications Siemens AG 07 Overview Function U const. p U I EM Sensor Connection for auxiliary power supply Vent pipe with humidity filter Protective conductor connection/ Equipotential bonding Diaphragm The pressure

More information

Pressure transmitter PASCAL Ci4

Pressure transmitter PASCAL Ci4 Pressure transmitter PASCAL Ci4 for general application,type Series CI4100 Features Pressure transmitter for the measuring of relative and absolute pressures of gases, vapors and liquids High-resolution

More information

SITRANS P measuring instruments for pressure

SITRANS P measuring instruments for pressure Siemens AG 009 SITRANS P measuring instruments for pressure Overview The SITRANS P300 is a digital pressure transmitter for gauge and absolute pressure. All conventional thread versions are available as

More information

2600T Series Pressure Transmitter Models 264DC Differential and 264HC Gage Level Transmitters. Kent-Taylor

2600T Series Pressure Transmitter Models 264DC Differential and 264HC Gage Level Transmitters. Kent-Taylor INDUSTRIAL INSTRUMENTS AND CONTROLS SPECIALIST Kent-Taylor 2600T Series Pressure Transmitter Models 264DC Differential and 264HC Gage Level Transmitters Features Include Base accuracy : ±0.075% Span limits

More information

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI Siemens AG 06 SITRANS LH00 Transmitter for hydrostatic level Overview Function U const. p U I EM The pressure transmitter SITRANS LH00 is a submersible sensor for hydrostatic level measurement. The pressure

More information

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI US Edition

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI US Edition Siemens AG 07 SITRANS LH00 Transmitter for hydrostatic level Overview Function U const. p U I EM The pressure transmitter SITRANS LH00 is a submersible sensor for hydrostatic level measurement. The pressure

More information

IDL01. Battery Powered Precision Digital Gauge for Leak Testing. Stainless Steel Sensor. class 0.05

IDL01. Battery Powered Precision Digital Gauge for Leak Testing. Stainless Steel Sensor. class 0.05 IDL0 Battery Powered Precision Digital Gauge for Leak Testing Stainless Steel Sensor class 0.05 Nominal pressure from 0 00 mbar up to 0... 00 bar Special characteristics modular sensor concept data logger

More information

Differential pressure

Differential pressure Differential pressure 9 Overview Page 200 VEGADIF 65 Page 202 Chemical seal Page 204 Accessory Page 208 199 VEGADIF For differential pressure, level and flow measurements Measuring principle The sensor

More information

DM01. Please visit our website: Battery Powered Precision Digital Gauge. Stainless Steel Sensor. class 0.05

DM01. Please visit our website:  Battery Powered Precision Digital Gauge. Stainless Steel Sensor. class 0.05 DM0 Battery Powered Stainless Steel Sensor class 0.05 Nominal pressure from 0 00 mbar up to 0... 00 bar Special characteristics modular sensor concept data logger graphic display stainless steel housing

More information

DMK 458. Pressure Transmitter for Marine and Offshore. Ceramic Sensor. accuracy according to IEC 60770: standard: 0.25 % FSO option: 0.

DMK 458. Pressure Transmitter for Marine and Offshore. Ceramic Sensor. accuracy according to IEC 60770: standard: 0.25 % FSO option: 0. Pressure Transmitter for Marine and Offshore Ceramic Sensor accuracy according to IEC 60770: standard: 0.5 % FSO option: 0. % FSO Nominal pressure from 0... 40 mbar up to 0... 0 bar Output signals -wire:

More information

Technical Datasheet. D Series SMART Pressure Transmitter Model: DPC D-Series. Key Features. Series Overview. Product applications

Technical Datasheet. D Series SMART Pressure Transmitter Model: DPC D-Series. Key Features. Series Overview. Product applications Technical Datasheet D Series SMART Pressure Transmitter Model: DPC-2000 Key Features ATEX - Flameproof and Intrinsically Safe IECEx - Flameproof and Intrinsically Safe SIL 2 certificate Compliant to NAMUR

More information

SITRANS. Pressure transmitter SITRANS P, Z series for gauge and absolute pressure. Introduction. Safety instructions 2.

SITRANS. Pressure transmitter SITRANS P, Z series for gauge and absolute pressure. Introduction. Safety instructions 2. Introduction 1 Safety instructions 2 SITRANS Pressure transmitter SITRANS P, Z series for gauge and absolute pressure 7MF1564 Description 3 Assembly and connection 4 Technical data 5 Dimensional drawings

More information

Torque Tube TB300 Digital Transmitters

Torque Tube TB300 Digital Transmitters Page 1 of 7 7E.300-E Issue 4-2009 Description Series TB300 torque tube liquid level instruments utilize the buoyancy exerted on a displacer when immersed in a liquid. The buoyancy on the displacer is proportional

More information

ETd 04. Battery Powered Precision Digital Gauge. Stainless Steel Sensor. Type: ETd 04. class 0.05

ETd 04. Battery Powered Precision Digital Gauge. Stainless Steel Sensor.  Type: ETd 04. class 0.05 Battery Powered Stainless Steel Sensor class 0.05 Nominal pressure from 0 100 mbar up to 0... 400 bar Special characteristics modular sensor concept data logger graphic display stainless steel housing

More information

DM01. Battery Powered Precision Digital Gauge. Stainless Steel Sensor. class 0.05

DM01. Battery Powered Precision Digital Gauge. Stainless Steel Sensor. class 0.05 Battery Powered Stainless Steel Sensor class 0.05 Nominal pressure from 0 00 mbar up to 0... 00 bar Special characteristics modular sensor concept data logger graphic display stainless steel housing Ø

More information

Electropneumatic Positioner Type 4763 Pneumatic Positioner Type 4765

Electropneumatic Positioner Type 4763 Pneumatic Positioner Type 4765 Electropneumatic Positioner Type 4763 Pneumatic Positioner Type 4765 Application Single-acting positioner for attachment to pneumatic control valves. Supplied with either an electric input signal from

More information

Precision digital pressure gauge Model CPG1000

Precision digital pressure gauge Model CPG1000 Calibration technology Precision digital pressure gauge Model CPG1000 WIKA data sheet CT 10.01 Applications Oil and gas industry Maintenance and service facilities Calibration service companies and service

More information

SITRANS P measuring instruments for pressure

SITRANS P measuring instruments for pressure Siemens AG 007 SITRANS P measuring instruments for pressure / Product overview /4 Transmitters for gage and absolute pressure /4 Z series for gage and absolute pressure /9 ZD series for gage and absolute

More information

Multi Vision. Digital Transmitter 10/ EN

Multi Vision. Digital Transmitter 10/ EN Multi Vision Digital Transmitter 2010TD for Differential Pressure, Flow Rate and Level Spans: 50 Pa... 10 MPa (0.2 in. H 2 O...1500 psi) 2 kpa... 2 MPa abs. (8 in. H 2 O... 300 psia) 2010TDSW.TIF Measured

More information

Differential Pressure Transmiter

Differential Pressure Transmiter Differential Pressure Transmiter Description The is an economical alternative to established differential pressure transmitters. It combines state of the art electronics and a high performance sensor;

More information

RTX 1000H Series. Versatile Transmitters for a World of Pressure. GE Measurement & Control. Features

RTX 1000H Series. Versatile Transmitters for a World of Pressure. GE Measurement & Control. Features GE Measurement & Control RTX 1000H Series Versatile Transmitters for a World of Pressure GE Measurement & Control is renowned for the design and manufacture of compact and rugged high performance pressure

More information

Hydrostatic. Continuous level measurement. Overview Page 188 VEGAWELL 52 Page 190 VEGABAR 86, 87 Page 192 Accessory Page 196 AL-EN

Hydrostatic. Continuous level measurement. Overview Page 188 VEGAWELL 52 Page 190 VEGABAR 86, 87 Page 192 Accessory Page 196 AL-EN Hydrostatic Continuous level measurement 8 Overview Page 188 VEGAWELL 52 Page 190 VEGABAR 86, 87 Page 192 Accessory Page 196 187 Hydrostatic Level and pressure measurement Measuring principle The pressure

More information

Compact differential pressure switch Flameproof enclosure Ex d Models DE, DEC

Compact differential pressure switch Flameproof enclosure Ex d Models DE, DEC Mechatronic pressure measurement Compact differential pressure switch Flameproof enclosure Ex d Models DE, DEC WIKA data sheet PV 35.41 Process Compact Series Applications Differential pressure monitoring

More information

High-performance submersible pressure transmitter For level measurement Model LH-10

High-performance submersible pressure transmitter For level measurement Model LH-10 Electronic pressure measurement High-performance submersible pressure transmitter For level measurement Model LH-10 WIKA data sheet PE 81.09 Applications Level measurement in rivers and lakes Deep well

More information

9700 Transmitter Submersible hydrostatic level transmitter

9700 Transmitter Submersible hydrostatic level transmitter Specification sheet IP0078 October 2007 Level 9700 Transmitter Submersible hydrostatic level transmitter Description The 9700 series hydrostatic level transmitter is designed to perform in the most arduous

More information

How to specify a product. Process Sensors and Mechanical Instruments

How to specify a product. Process Sensors and Mechanical Instruments How to specify a product Process Sensors and Mechanical Instruments Keep the overview. Here is some guideline information on how to specify our products. Intended as supplementary help to specification

More information

x act i Precision- Pressure Transmitter for Food Industry, Pharmacy and Biotechnology Stainless Steel Sensor

x act i Precision- Pressure Transmitter for Food Industry, Pharmacy and Biotechnology Stainless Steel Sensor Precision- Pressure Transmitter for Food ndustry, Pharmacy and Biotechnology Stainless Steel Sensor accuracy according to EC 60770: 0. % FSO Nominal pressure from 0... 400 mbar up to 0... 40 bar Output

More information

Pressure transmitter. SITRANS P, DS III Series with PROFIBUS PA. Operating Instructions 09/2012 SITRANS. Answers for industry.

Pressure transmitter. SITRANS P, DS III Series with PROFIBUS PA. Operating Instructions 09/2012 SITRANS. Answers for industry. Pressure transmitter SITRANS P, DS III Series with PROFIBUS PA Operating Instructions 09/2012 SITRANS Answers for industry. Introduction 1 Safety information 2 SITRANS Pressure transmitter SITRANS P,

More information

C-Flow Coriolis Mass Flow Meters

C-Flow Coriolis Mass Flow Meters Coriolis Mass Flow Meters Ready for Take Off The New Compact C-Flow Küppers Elektromechanik GmbH The C-Flow The C-Flow Coriolis Mass Meters consist of two components: KCE Transmitter KCM Transducer 2 KEM

More information

Technical Data. Dimensions

Technical Data. Dimensions 0102 Model Number Features 2 mm flush Usable up to SIL2 acc. to IEC 61508 Technical Data specifications Switching element function NAMUR, NC Rated operating distance s n 2 mm Installation flush Output

More information

Type N-10, N-11 Hazardous Area Non-incendive Transmitters

Type N-10, N-11 Hazardous Area Non-incendive Transmitters Electronic Pressure Catalog > Hazardous Area > N-10, N-11 Type N-10, N-11 Hazardous Area Non-incendive Transmitters Applications Natural gas compressors Wellhead monitoring Pipeline pressure General industrial

More information

High-performance submersible pressure transmitter For level measurement Model LH-20

High-performance submersible pressure transmitter For level measurement Model LH-20 Electronic pressure measurement High-performance submersible pressure transmitter For level measurement Model LH-20 WIKA data sheet PE 81.56 Applications Deep well and borehole measurements Groundwater

More information

OPTIBAR P 1010 C Technical Datasheet

OPTIBAR P 1010 C Technical Datasheet Technical Datasheet Pressure transmitter with recessed diaphragm for general applications Wide variety thanks to modular design Measuring ranges up to 250 bar / 3750 psi High overload and temperature stability

More information

Technical Data. General specifications Switching element function Rated operating distance s n 2 mm

Technical Data. General specifications Switching element function Rated operating distance s n 2 mm 0102 Model Number Features 2 mm flush Usable up to SIL 2 acc. to IEC 61508 Accessories EXG-12 Quick mounting bracket with dead stop BF 12 Mounting flange, 12 mm Technical Data specifications Switching

More information

SITRANS P DS III/P410 with PROFIBUS PA SITRANS. Pressure transmitter SITRANS P DS III/P410 with PROFIBUS PA. Introduction 1. Safety information

SITRANS P DS III/P410 with PROFIBUS PA SITRANS. Pressure transmitter SITRANS P DS III/P410 with PROFIBUS PA. Introduction 1. Safety information SITRANS P DS III/P410 with PROFIBUS PA SITRANS Pressure transmitter SITRANS P DS III/P410 with PROFIBUS PA Operating Instructions Introduction 1 Safety information 2 Description 3 Installing / mounting

More information

x act i Precision Pressure Transmitter for Food Industry, Pharmacy and Biotechnology Stainless Steel Sensor accuracy according to IEC 60770: 0.

x act i Precision Pressure Transmitter for Food Industry, Pharmacy and Biotechnology Stainless Steel Sensor accuracy according to IEC 60770: 0. Precision Pressure Transmitter for Food ndustry, Pharmacy and Biotechnology Stainless Steel Sensor accuracy according to EC 60770: 0. % FSO Nominal pressure from 0... 400 mbar up to 0... 40 bar Output

More information

UNIK 5600/5700 Marine Certified Pressure Sensing Platform

UNIK 5600/5700 Marine Certified Pressure Sensing Platform GE Measurement & Control UNIK 5600/5700 Marine Certified Pressure Sensing Platform The new UNIK 5600/5700 carries marine certification for most zones on-board ship, as well as Intrinsically Safe certifications.

More information

High-performance submersible pressure transmitter For level measurement Model LH-20

High-performance submersible pressure transmitter For level measurement Model LH-20 Electronic pressure measurement High-performance submersible pressure transmitter For level measurement Model LH-20 WIKA data sheet PE 81.56 Applications Deep well and borehole measurements Groundwater

More information

Siemens AG Transmitters with WirelessHART 1/42 SITRANS P280 for gauge and abs. pressure. Transmitters for food, pharmaceuticals

Siemens AG Transmitters with WirelessHART 1/42 SITRANS P280 for gauge and abs. pressure. Transmitters for food, pharmaceuticals Siemens AG 07 / Product overview Single-range transmitters for general applications /5 SITRANS P00 for gauge and abs. pressure / SITRANS P0 for gauge pressure /6 SITRANS P0 for gauge pressure Transmitter

More information

High-performance submersible pressure transmitter For level measurement Model LH-10

High-performance submersible pressure transmitter For level measurement Model LH-10 Electronic pressure measurement High-performance submersible pressure transmitter For level measurement Model LH-10 WIKA data sheet PE 81.09 Applications Level measurement in rivers and lakes Deep well

More information

Technical Data. General specifications. Rated operating distance s n 5 mm

Technical Data. General specifications. Rated operating distance s n 5 mm 0102 Model Number Features 5 mm flush Usable up to SIL 2 acc. to IEC 61508 Accessories EXG-18 Quick mounting bracket with dead stop BF 18 Mounting flange, 18 mm Technical Data specifications Switching

More information

Dimensions. Technical Data General specifications Switching element function Rated operating distance s n 5 mm

Dimensions. Technical Data General specifications Switching element function Rated operating distance s n 5 mm Dimensions M18x1 37 40 4 0102 24 LED Model Number Features 5 mm embeddable Usable up to SIL2 acc. to IEC 61508 Connection BN BU Accessories L+ L- EXG-18 Quick mounting bracket with dead stop BF 18 Mounting

More information

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS Electropneumatic Positioner and Pneumatic Positioner Type 3760 Application Single-acting positioners for direct attachment to pneumatic control valves. Supplied with an electric input signal of 4 to 20

More information

Hand-held pressure calibrator with integrated pump Model CPH6600

Hand-held pressure calibrator with integrated pump Model CPH6600 Calibration technology Hand-held pressure calibrator with integrated pump Model CPH6600 WIKA data sheet CT 16.01 Applications Calibration service companies and service industry Measurement and control

More information

Bourdon tube pressure gauge for diaphragm seals

Bourdon tube pressure gauge for diaphragm seals Bourdon tube pressure gauge for diaphragm seals and switch function, Type series BR42.. Features Bourdon tube pressure gauge for diaphragm seal and switch function Nominal range -1 3 bar to -1 15 bar,

More information

Model 261GR for gauge pressure Model 261AR for absolute pressure

Model 261GR for gauge pressure Model 261AR for absolute pressure Change from one to two columns Data Sheet SS/261GR/AR-EN Rev. 07 Model 261GR for gauge pressure Model 261AR for absolute pressure 2600T series pressu re transmitters Engineered solutions for all applications

More information

SITRANS P measuring instruments for pressure

SITRANS P measuring instruments for pressure Remote seals for transmitters and pressure gauges Technical description Overview In many cases the pressure transmitter and the measured medium have to be physically separated. It is then necessary to

More information

1 Overview. Pressure Measurement Remote seals for transmitters and pressure gauges SITRANS P320/P420. 1/352 Siemens FI US Edition

1 Overview. Pressure Measurement Remote seals for transmitters and pressure gauges SITRANS P320/P420. 1/352 Siemens FI US Edition Siemens AG 08 Technical description Overview In many cases the pressure transmitter and the measured medium have to be physically separated. It is then necessary to use a remote seal. The remote seals

More information

ATM.1ST/Ex - High Precision Transmitter

ATM.1ST/Ex - High Precision Transmitter Pressure Transmitter - ATEX / IECEx certified ATM.1ST/Ex - High Precision Transmitter CUSTOMER BENEFITS Certificate: ATEX, IECEx & EAC High measurement accuracy is ensured by sophisticated digital temperature

More information

High-performance submersible pressure transmitter For level measurement Model LH-20

High-performance submersible pressure transmitter For level measurement Model LH-20 Electronic pressure measurement High-performance submersible pressure transmitter For level measurement Model LH-20 WIKA data sheet PE 81.56 Applications Deep well and borehole measurements Groundwater

More information

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS Electropneumatic Positioner and Pneumatic Positioner Type 3760 Application Single-acting positioners for direct attachment to pneumatic control valves. An electric standardized signal of 4 to 20 ma or

More information

SITRANS P DS III/P410 with. FOUNDATION Fieldbus FF SITRANS. Pressure transmitter SITRANS P DS III/P410 with FOUNDATION Fieldbus FF.

SITRANS P DS III/P410 with. FOUNDATION Fieldbus FF SITRANS. Pressure transmitter SITRANS P DS III/P410 with FOUNDATION Fieldbus FF. SITRANS P DS III/P410 with FOUNDATION Fieldbus FF SITRANS Pressure transmitter SITRANS P DS III/P410 with FOUNDATION Fieldbus FF Operating Instructions Introduction 1 Safety instructions 2 Description

More information

Flow Measurement SITRANS F X

Flow Measurement SITRANS F X Overview Using a vortex flowmeter with integrated pressure and temperature compensation such as the allows you not only to lower installation costs but also increase the measuring accuracy of the measuring

More information

3000 Series OPTIMASS Mass Flowmeter. Stainless Steel Hastelloy

3000 Series OPTIMASS Mass Flowmeter. Stainless Steel Hastelloy KROHNE 07/2005 7.02446.25.00 GR 3000 Series OPTIMASS Mass Flowmeter with single Z-shaped measuring tube Stainless Steel Hastelloy Status: 10/99 One tube no limits No limits with tube material No limits

More information

Technical Data. Dimensions

Technical Data. Dimensions 00 Model Number Features mm flush Usable up to SIL acc. to IEC 6508 Accessories V-G Female connector, M, -pin, field attachable V-W Female connector, M, -pin, field attachable V-G-N-M-PUR Female cordset,

More information

L (up to 25 m) Electronic part. working temp.: Ñ IP 66 / IP67. Mounting bracket ÐÑ. Sensor type. working temp.:

L (up to 25 m) Electronic part. working temp.: Ñ IP 66 / IP67. Mounting bracket ÐÑ. Sensor type. working temp.: Smart level probe type APC-2000ALW/L Programmable zero shift, range and damping ratio 4...20 ma output signal + HART protocol Accuracy 0,16% Local display Intrinsic safety certificate (ATEX, IECEx) II

More information

High-performance submersible pressure transmitter For level measurement in hazardous areas Model LH-20

High-performance submersible pressure transmitter For level measurement in hazardous areas Model LH-20 Electronic pressure measurement High-performance submersible pressure transmitter For level measurement in hazardous areas Model LH-20 WIKA data sheet PE 81.56 Applications Deep well and borehole measurements

More information

ATM.ECO/IS - Analog Transmitter with Temperature compensation

ATM.ECO/IS - Analog Transmitter with Temperature compensation Pressure Transmitter - FM / FM-C certified ATM.ECO/IS - Analog Transmitter with Temperature compensation CUSTOMER BENEFITS Certificate: FM, FM-C & IECEx & ATEX Entry level series into precision pressure

More information

Technical Data. Dimensions

Technical Data. Dimensions 0102 Model Number Features Comfort series 15 mm flush Accessories MHW 01 Modular mounting bracket MH 04-2057B Mounting aid for VariKont and +U1+ V1-G-N-2M-PUR Female cordset, M12, 2-pin, NAMUR, PUR cable

More information

2600T Series Pressure Transmitter

2600T Series Pressure Transmitter Data Sheet 2600T Series Pressure Transmitter Model 261GC/GG/GJ/GM/GN Gauge Model 261AC/AG/AJ/AM/AN Absolute with direct mount seal Base accuracy: ±0.15 % Span limits 0.3 to 60000kPa; 1.2inH 2 O to 8700psi

More information

Fig. 1/20 SITRANS P transmitters, DS III series for pressure, absolute pressure, differential pressure, flow and level, with visible digital display

Fig. 1/20 SITRANS P transmitters, DS III series for pressure, absolute pressure, differential pressure, flow and level, with visible digital display Measuring instruments for pressure SITRNS P transmitters for pressure, absolute pressure, diff. pressure, flow, level Measuing instruments for pressure S III series Fig. /0 SITRNS P transmitters, S III

More information

User s Manual EJX/EJA-E Series NEPSI Certification [Option code: /NF2, /NS21, /NS24 and /NS25] IM 01C25A00-12E

User s Manual EJX/EJA-E Series NEPSI Certification [Option code: /NF2, /NS21, /NS24 and /NS25] IM 01C25A00-12E User s Manual EJX/EJA-E Series NEPSI Certification [Option code: /NF2, /NS21, /NS24 and /NS25] 12th Edition 1 1. Introduction Thank you for purchasing the DPharp electronic pressure transmitter. This manual

More information

Technical Data. Dimensions

Technical Data. Dimensions 00 Model Number Features Comfort series 30 mm non-flush Accessories MHW 0 Modular mounting bracket V-G Female connector, M, 4-pin, field attachable V-W-N-M-PUR Female cordset, M, -pin, NAMUR, PUR cable

More information

Pressure Switches Application Guideline

Pressure Switches Application Guideline Pressure Switches Application Guideline Product Overview The Fema Pressure Switch product portfolio provides devices suitable for many applications. The portfolio contains Special functions and equipment

More information

SITRANS P pressure transmitters The best in pressure measurement. sitrans

SITRANS P pressure transmitters The best in pressure measurement. sitrans SITRANS P pressure transmitters The best in pressure measurement sitrans The SITRANS P family The right choice every time No two processes are alike. No two infrastructures are alike. No two ambient conditions

More information

JUMO dtrans p30 Pressure Transmitter

JUMO dtrans p30 Pressure Transmitter 609 Fulda, Germany Postal address: 605 Fulda, Germany Phone: +49 661 600-0 Fax: +49 661 600-607 Phone: +44 179 6 55 Data Sheet 40466 Page 1/6 JUMO dtrans p0 Pressure Transmitter General application Pressure

More information

Gas density monitor With integrated transmitter Model GDM-100-TI

Gas density monitor With integrated transmitter Model GDM-100-TI SF 6 gas solutions Gas density monitor With integrated transmitter Model GDM-100-TI grid Products WIKA data sheet SP 60.05 for further approvals see page 5 Applications Gas density monitoring of closed

More information

Level transmitter LT 100

Level transmitter LT 100 KROHNE 09/2001 7.02363.21.00 GR/PRINTO Level transmitter LT 100 Status: 10/99 Variable area flowmeters Vortex flowmeters Flow controllers Electromagnetic flowmeters Ultrasonic flowmeters Mass flowmeters

More information

Reliable, low-maintenance pressure measurement with SITRANS P

Reliable, low-maintenance pressure measurement with SITRANS P Processes require precision Reliable, low-maintenance pressure measurement with SITRANS P www.usa.siemens.com/pressure Pressure measurement under control It s impossible to imagine today s process industries

More information

Pressure switch with bourdon tube

Pressure switch with bourdon tube Pressure switch with bourdon tube for plants requiring special supervision,type series BN4 Features Pressure switch with bourdon tube for plants requiring special supervision, Nominal ranges -1...0 bar

More information

LMP 307. Stainless Steel Probe. Stainless Steel Sensor. accuracy according to IEC 60770: standard: 0.35 % FSO option: 0.25 % / 0.

LMP 307. Stainless Steel Probe. Stainless Steel Sensor. accuracy according to IEC 60770: standard: 0.35 % FSO option: 0.25 % / 0. LMP 07 Stainless Steel Sensor accuracy according to IEC 60770: standard: 0.5 % FSO option: 0.5 % / 0. % FSO Nominal pressure from 0... mho up to 0... 50 mho Output signals -wire: 4... 0 ma -wire: 0...

More information

Precision pressure sensor Basic version Model CPT6020

Precision pressure sensor Basic version Model CPT6020 Calibration Precision pressure sensor Basic version Model CPT6020 WIKA data sheet CT 25.13 Applications Calibration technology High-accuracy pressure monitoring Pressure sensing in critical applications

More information

Programmable pressure and temperature transmitters PTM/RS485

Programmable pressure and temperature transmitters PTM/RS485 Programmable pressure and temperature transmitters PTM/RS485 Version: 03-28-2012 Technical Specifications Pressure measuring range (bar) 0.1... 0.5 > 0.5 2 > 2 25 Overpressure 3 bar 3 x FS ( 3 bar) 3 x

More information

Vortex flow sensor VA Di Ex-d with integrated, configurable transducer UVA in a flameproof enclosure for applications in explosive atmospheres

Vortex flow sensor VA Di Ex-d with integrated, configurable transducer UVA in a flameproof enclosure for applications in explosive atmospheres Vortex flow sensor VA Di Ex-d with integrated, configurable transducer UVA in a flameproof enclosure for applications in explosive atmospheres Drawing 1 VA Di ZG1 Ex-d Measured variables actual flow rate

More information

Pressure transmitters EMP 2

Pressure transmitters EMP 2 Data sheet Pressure transmitters EMP 2 The high accuracy pressure transmitter EMP 2 is designed for monitoring and control in marine and industial applications and offers a reliable pressure measurement,

More information

sitrans p Operating Instructions (de/en) Edition 03/2004

sitrans p Operating Instructions (de/en) Edition 03/2004 (de/en) Edition 03/2004 sitrans p Messumformer für Food, Pharma und Biotechnik Transmitters for food, pharmaceuticals and biotechnologgy 7FM8010 Contents Information for the operator...27 Important security

More information

Mechanical Pressure Measurement

Mechanical Pressure Measurement Mechanical Pressure Measurement Differential Pressure Gauges Model GDP, Universal Version, with Diaphragm Element High Overpressure Safety PN 40, 100, 250 or 400 Applications Differential pressure measurement

More information