Backflow Preventer Test and Inspection Report Instructions

Size: px
Start display at page:

Download "Backflow Preventer Test and Inspection Report Instructions"

Transcription

1 Backflow Preventer Test and Inspection Report Instructions June

2 Backflow Preventer Test and Inspection Report Form The Backflow Preventer Test and Inspection Report is used to record the annual test and inspection activities conducted by the qualified person. The Report requires information on the owner and facility that the device is located at, the qualified person carrying out the test, the test kit employed for the test and the specifics of device being tested as well as results of the test. June

3 Information for the Facility Facility Address: Indicate the address of facility that backflow preventer is located at. Occupant: Person/Company who currently occupies the facility/building. Contact/Contact Phone #: Specify the person who can be contacted by the City for backflow prevention program. Address of Owner/Postal Code: Indicate the owner s mailing address and postal code. PLEASE NOTE: Please fill out all applicable fields in the form and be as specific as possible. Otherwise, the form will be returned if deemed unacceptable. Contact information for the City of Markham June

4 Information for the Qualified Person Qualified Person Name and OWWA Cert#: Make sure to fill in both fields as they are vital to the form s acceptance since only those testers registered with the City are permitted to do backflow prevention works in the City. Please Note: If the qualified person is an apprentice, the master plumber or journeyman plumber who supervised the test must be co-printed here and co-sign the report as well. Test kit Maker/Model/Serial #: Specify the maker, model and serial number of the test kit employed for this test. Date of last calibration: Indicate the last date the test kit has been calibrated. Business Name/Address/Postal Code/Phone #: Provide that Qualified Person s company information in those fields. June

5 Information for the Backflow Preventer Device Make/Model/Serial #: Find those information indicated on the device and record them on the report correctly and written clearly. Installed on What System: Select the type of water system the device is installed on. Type of Isolation: Indicate which type of isolation the device is used for. Device Orientation: Indicate whether the device is installed horizontally or vertically. If neither of them, specify other type of orientation. Location of Device: Specify which area/which room the device is located. Building Permit #: Building Permit is required for new installations or replacements. Put the Building Permit # for the City s cross reference. June

6 Type of Test and Type of Device Type of Test: Indicate which type of test being conducted. Initial Test It is the first test for newly installed devices. The Building Permit # field must be filled in. Annual Test It is regular test for existing devices. Replaces Serial # It is the first test after the previous device has been replaced. The Building Permit # field must be filled in. Also, the serial # of previous device should be recorded. Type of Device: Specify which type of backflow preventer is being tested. June

7 Testing Information for RP/RPF Backflow Preventer 1. Differential Pressure Relief Valve: The relief valve shall open at a minimum 13.8 kpa (2 psi) pressure differential. 2. Check Valve 1: o Check Valve 1 shall close tight in direction of flow. o Holding a differential pressure for a minimum period of 2 min or until the gauge reading stabilizes. o The differential pressure across Check Valve 1 shall be at least 20.7 kpa (3 psi) higher than the opening pressure of relief valve for an RP Backflow Preventer. But, this doesn t require for an RPF Backflow Preventer. 3. Check Valve 2: o Check Valve 2 shall close tight in reverse direction of flow. o Holding a differential pressure for a minimum period of 2 min or until the gauge reading stabilizes. o Take the reading and record on the form. 4. Static Line Pressure: The static line pressure should be taken at the time of the test and recorded on the test report form. 5. Test Result: Indicate the test result either Passed or Failed. 6. Test Date: Indicate the date test being conducted. June

8 Testing Information for DCVA/DCVAF/SCVAF Backflow Preventer 1. Check Valve 1: o Check Valve 1 shall close tight in direction of flow. o Holding at least 6.9 kpa (1 psi) differential pressure for a DCVA/SCVAF Backflow Preventer. Or, holding at least 3.4 kpa (1/2 psi) differential pressure for a DCVAF Backflow Preventer. 2. Check Valve 2: o Check Valve 2 shall close tight in direction of flow. o Holding at least 6.9 kpa (1 psi) differential pressure for a DCVA Backflow Preventer. Or, holding at least 3.4 kpa (1/2 psi) differential pressure for a DCVAF Backflow Preventer. 3. Static Line Pressure: The static line pressure should be taken at the time of the test and recorded on the test report form. 4. Test Result: Indicate the test result either Passed or Failed. 5. Test Date: Indicate the date test being conducted. June

9 Testing Information for PVB/SRPVB Backflow Preventer 1. Air Inlet Valve: o The Air Inlet Valve begins to open when the pressure is at least 6.9 kpa (1psi) higher than atmosphere pressure. 2. Check Valve : o Check Valve shall close tight in direction of flow. o Holding at least 6.9 kpa (1 psi) differential pressure. 3. Static Line Pressure: The static line pressure should be taken at the time of the test and recorded on the test report form. 4. Test Result: Indicate the test result either Passed or Failed. 5. Test Date: Indicate the date test being conducted. June

10 Area for Repair If the device failed the test, the qualified person should carry out the repair and record the result in this area. June

11 Area for Re-test After the repair of device, the device has to be retested and the re-test results are recorded in this area. June

12 Signatures and Disclaimer: Remarks/Comments: Place for putting down any comments related to the test it may have. Please read the provision placed above and below the signature box before signing this test Report. Please be advised that both the qualified person and property owner/tenant have to sign off this report prior to its submission to the City of Markham. THIS FIELD IS FOR OFFICE USE ONLY June

S & M Water Consultants

S & M Water Consultants S & M Water Consultants Test Procedures In This Manual TEST Reduced Pressure Assembly One Hose Method PAGE 1 Double Check Assembly One Hose Method 5 Pressure Vacuum Breaker One Hose Method 7 Spill Proof

More information

American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM

American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM ASSE STANDARD #1064-2006 (R2011) - REVISED: 2011 Backflow Prevention Assembly Field Test Kits MANUFACTURER: CONTACT PERSON: E-MAIL:

More information

Reduce pressure zone device suitable for high and medium hazard rated applications BSP screwed connections

Reduce pressure zone device suitable for high and medium hazard rated applications BSP screwed connections Reduce pressure zone device suitable for high and medium hazard rated applications BSP screwed connections Features General application The RP03 provides protection from both backsiphonage and backpressure

More information

VALVCHEQ BACKFLOW PREVENTERS FIGURE RP03

VALVCHEQ BACKFLOW PREVENTERS FIGURE RP03 Reduce pressure zone device suitable for high and medium hazard rated applications BSP screwed connections FEATURES GENERAL APPLICATION The RP03 provides protection from both backsiphonage and backpressure

More information

American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM

American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM ASSE STANDARD #1003 - REVISED: 2009 Water Pressure Reducing Valves for Domestic Water Distribution Systems MANUFACTURER: CONTACT

More information

Approved Installation Method (AIM)

Approved Installation Method (AIM) AIM-08-01 Issue 2 (DRAFT) 2015 Water Undertakers Approved Installation Method (AIM) Type BA Device Verifiable Backflow Preventer with Reduced Pressure Zone (RPZ Valve) Requirements for installation, commissioning

More information

American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM

American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM ASSE STANDARD #1048 - REVISED: 2009 Double Check Detector Fire Protection Backflow Prevention Assemblies Separate, complete laboratory

More information

1 Scope... 2 Functions of cementing float equipment... 3 Definitions... 4 Calibration... 5 Test Categories... 6 General...

1 Scope... 2 Functions of cementing float equipment... 3 Definitions... 4 Calibration... 5 Test Categories... 6 General... American Petroleum Institute Contents Page 1 Scope... 2 Functions of cementing float equipment... 3 Definitions... 4 Calibration... 5 Test Categories... 6 General... 7 Apparatus and Materials... 8 High-temperature/high-pressure

More information

VALVCHEQ BACKFLOW PREVENTERS FIGURE RP03

VALVCHEQ BACKFLOW PREVENTERS FIGURE RP03 Reduce pressure zone device suitable for high and medium hazard rated applications Flanged end connections FEATURES GENERAL APPLICATION The RP03 provides protection from both backsiphonage and backpressure

More information

Reduce pressure zone device suitable for high and medium hazard rated applications Flanged end connections

Reduce pressure zone device suitable for high and medium hazard rated applications Flanged end connections VALVCHEQ Backflow Preventers Reduce pressure zone device suitable for high and medium hazard rated applications Flanged end connections Features General application The RP03 provides protection from both

More information

ASSE International Product (Seal) Listing Program. ASSE Performance Requirements for Air Valve and Vent Inflow Preventer

ASSE International Product (Seal) Listing Program. ASSE Performance Requirements for Air Valve and Vent Inflow Preventer ASSE International Product (Seal) Listing Program ASSE 1063-2016 Performance Requirements for Air Valve and Vent Inflow Preventer Manufacturer: Contact Person: E-mail: Address: Laboratory: Laboratory File

More information

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A 2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A PROJECT ADDRESS TESTING AUTHORITY TELEPHONE Checked by/date Enforcement Agency Use GENERAL INFORMATION OF BLDG. PERMIT PERMIT # BLDG. CONDITIONED FLOOR

More information

Scald Protection Three-Way Thermostatic Mixing Valve

Scald Protection Three-Way Thermostatic Mixing Valve CALEFFI www.caleffi.com 383.04 Scald Protection Three-Way Thermostatic Mixing Valve Copyright 00 Caleffi 3 Series Installation, commissioning and servicing instructions Function Scald Protection Three-Way

More information

ASSE International Product (Seal) Listing Program

ASSE International Product (Seal) Listing Program Manufacturer Contact Person Address ASSE International Product (Seal) Listing Program ASSE 07-05 / ASME A.9.07-05 / CSA B5.7-5 Pressurized Flushing Devices for Plumbing Fixtures Laboratory File Number

More information

RELIEF VALVES. General Description

RELIEF VALVES. General Description RELIEF VALVES FOR CONDENSER SERVICE General Description Graham Viking Valves are produced in three basic designs: Horizontal, Vertical and Angle. The Horizontal and Angle valves are available with various

More information

American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM

American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM ASSE STANDARD #1019 - REVISED: 2011 Wall Hydrant with Backflow Protection and Freeze Resistance MANUFACTURER: CONTACT PERSON: E-MAIL:

More information

ASSE International Product (Seal) Listing Program

ASSE International Product (Seal) Listing Program ASSE International Product (Seal) Listing Program ASSE 1070-2015 / ASME A112.1070-2015 / CSA B125.70-15 Performance Requirements for Water Temperature Limiting Devices Manufacturer: Contact Person: E-mail:

More information

DUAL CHECK VALVES 2NV20-20F PRODUCT CODES OPERATION LOW HAZARD RATING. 20mm FEATURES APPLICATION SPECIFICATION STATEMENT DESCRIPTION

DUAL CHECK VALVES 2NV20-20F PRODUCT CODES OPERATION LOW HAZARD RATING. 20mm FEATURES APPLICATION SPECIFICATION STATEMENT DESCRIPTION BACKF PREVENTION DEVICES DUAL CHECK VALVES PRODUCT CODES 20mm FxF Dual Check Valve 20mm FEATURES Protects against back pressure and back siphonage Suitable for low hazard applications Compact and light

More information

Exhibit 4. Determination of Static Pressure Performance of the Healy Clean Air Separator (Executive Orders VR-201-N and VR-202-N)

Exhibit 4. Determination of Static Pressure Performance of the Healy Clean Air Separator (Executive Orders VR-201-N and VR-202-N) 1 APPLICABILITY Exhibit 4 Determination of Static Pressure Performance of the Healy Clean Air Separator (Executive Orders VR-201-N and VR-202-N) Definitions common to all certification and test procedures

More information

Integrity Testing LifeASSURE BNA045 and BNA065 Series Filter Cartridges

Integrity Testing LifeASSURE BNA045 and BNA065 Series Filter Cartridges Integrity Testing LifeASSURE BNA045 and BNA065 Series Filter Cartridges SAFETY INFORMATION Read, understand, and follow all safety information contained in these instructions and the instructions provided

More information

Scald Protection 3-Way Thermostatic Mixing Valve

Scald Protection 3-Way Thermostatic Mixing Valve 383.06 www.caleffi.com Scald Protection 3-Way Thermostatic Mixing Valve Copyright 06 Caleffi 3 Series Installation, commissioning and servicing instructions Function Scald Protection Three-Way Thermostatic

More information

Piped Air SCBA Refilling System Standard

Piped Air SCBA Refilling System Standard WALT WHITE Fire Chief 5770 Freeport Blvd., Suite 200 Sacramento, CA 95822-3516 Ph: (916) 808-1300 Fax: (916) 808-1629 www.sacfire.org Piped Air SCBA Refilling System Standard SCOPE: This specification

More information

Intamix Thermostatic Mixing Valve

Intamix Thermostatic Mixing Valve Intamix Thermostatic Mixing Valve TMV2 & TMV3 Installation Guide Intatec Ltd Airfield Industrial Estate Hixon Staffordshire ST18 0PF In this procedure document we have endeavoured to make the information

More information

Installation Guide - C01202 & C01203 Thermostatic Mixing Valve TMV2

Installation Guide - C01202 & C01203 Thermostatic Mixing Valve TMV2 The following information is required for use when the Saracen range of thermostatic mixing valves is used in a TMV2 Applications under the requirements of BS EN 1111: 1999 Sanitary tap ware Thermostatic

More information

Pressure Reducing Control Valve w/ Hydraulic Check Feature

Pressure Reducing Control Valve w/ Hydraulic Check Feature PERTIN INSTRUTINS peration The BEE Model PR- Pressure Reducing ontrol alve with Hydraulic heck eature is a pilot controlled diaphragm valve designed to reduce a fluctuating higher upstream pressure to

More information

Installation, commissioning and servicing instructions

Installation, commissioning and servicing instructions www.reece.com.au Tempering valve 38550.08 5213 series Installation, commissioning and servicing instructions The tempering valve is used to regulate the set temperature of mixed hot and cold water even

More information

553 Series.

553 Series. 38467.03 www.caleffi.com Pre-adjustable filling units Copyright 01 Caleffi 3 Series Function The automatic filling valve is a device consisting of a pressure reducing valve with compensating seat, visual

More information

Series 867. Reduced Pressure Zone Assemblies " 3" (65 80mm)** INDEX. Testing INSTALLATION INSTRUCTIONS WARNING NOTICE NOTICE !

Series 867. Reduced Pressure Zone Assemblies  3 (65 80mm)** INDEX. Testing INSTALLATION INSTRUCTIONS WARNING NOTICE NOTICE ! INSTALLATION INSTRUCTIONS RP/IS-F-867 Series 867 Reduced Pressure Zone Assemblies 2 1 2" 3" (65 80mm)** INDEX 867-NRS Installation Guidelines 2-3 Service, Repair and Maintenance 4-5 Test Procedure for

More information

AIR GAP (AG) Low Hazard High Hazard

AIR GAP (AG) Low Hazard High Hazard AIR GAP (AG) On Low Hazard and High Hazard applications, Air Gap (AG) is used for the physical separation (vertical distance) between the lowest opening point from any pipe or outlet supplying water and

More information

CONTROL VALVE TESTING

CONTROL VALVE TESTING The optimal functioning of the Control valve not only exists of sufficient body & seat tightness, but more important, the total "performance" of the valve and its controls! For an accurate and reliable

More information

Installation, commissioning and servicing instructions

Installation, commissioning and servicing instructions 38512.08 Tempering valve www.caleffi.com 5213 series Copyright 2018 Caleffi Installation, commissioning and servicing instructions The tempering valve is used to regulate the set temperature of mixed hot

More information

SECTION PRESSURE TESTING OF PIPING

SECTION PRESSURE TESTING OF PIPING SECTION 15044 PRESSURE TESTING OF PIPING PART 1 - GENERAL 1.01 DESCRIPTION A. Scope of Work: This section specifies the leakage and pressure testing of piping. B. Testing Records: PART 2 - PRODUCTS 2.01

More information

Tempering valve for solar and instantaneous applications Installation, commissioning and servicing instructions 2522HP series

Tempering valve for solar and instantaneous applications Installation, commissioning and servicing instructions 2522HP series www.reece.com.au 28255.01 Tempering valve for solar and instantaneous applications 2522HP series Installation, commissioning and servicing instructions The tempering valve is used to regulate the set temperature

More information

Warning: NEVER ALTER TEST EQUIPMENT

Warning: NEVER ALTER TEST EQUIPMENT PAGE 1 OF 6 General: Pressure Testing Shop Built Tanks Pressure testing tanks with either positive pressure or vacuum can be a very dangerous exercise. It is important to understand the equipment involved

More information

Installation, commissioning and servicing instructions

Installation, commissioning and servicing instructions 488.03 www.reece.com.au Pressure reducing s Installation, commissioning and servicing instructions Function Pressure reducing s are installed in residential water systems to reduce and stabilise inlet

More information

TOOL BOX 033- HOSEREEL SERVICE / FAULT FINDING

TOOL BOX 033- HOSEREEL SERVICE / FAULT FINDING In SANS 10105 you will find the Minimum water pressure for both the hydrant and the hose reel. Which is 300KPA Manufacturing Standard SANS 543 1 Front & Back plates 2 Curved Plate 3 Waterway assembly 4

More information

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2-12 BERMAD. Application Engineering Bermad Pressure Reducing Valve Model: 720-UL INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 1. Safety First BERMAD believes that the safety of personnel working with and around our equipment

More information

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity WATER HEATER THERMAL EXPANSION TANKS Owner s Manual Safety Instructions Installation Maintenance Warranty Models: 2-5 Gallon Capacity Thank You for purchasing this Thermal Expansion Tank. Properly installed

More information

Technical data sheet. Type overview. Technical data. Safety notes. T5-R2.. Open-close en v Subject to changes 1 / 3

Technical data sheet. Type overview. Technical data. Safety notes.   T5-R2.. Open-close en v Subject to changes 1 / 3 Technical data sheet R2.. Open-close ball valves, 2-way, with internal thread for open and closed cold and warm water systems for shut-off functions on the water side and 2-point controls in air-handling

More information

WHEATLEY WHEATLEY SERIES 500 SWING CHECK VALVE. Installation, Operation and Maintenance Manual

WHEATLEY WHEATLEY SERIES 500 SWING CHECK VALVE. Installation, Operation and Maintenance Manual WHEATLEY SERIES 500 SWING CHECK VALVE STANDARD INTEGRAL SEAT & OPTIONAL REMOVABLE SEAT 2" FP - 6" FP 150# - 1500# 8" FP - 12" FP 150# - 900# API 6D and B16.34 2" FP - 4" FP 5000# DRILLING PRODUCTION VALVE

More information

FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS

FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS CHAPTER 35 FLAMMABLE GASES AND FLAMMABLE CRYOGENIC FLUIDS SECTION 3501 GENERAL 3501.1 Scope. The storage and use of flammable gases shall be in accordance with this chapter. Compressed gases shall also

More information

MyControl Bathing System Signature Series

MyControl Bathing System Signature Series MyControl Bathing System Signature Series Touch Assist Touch Pad and CM Technologies Seal Pressure Regulation Instructions Acceptable seal inflation pressure setting must be varified, and adjusted if necessary,

More information

Mainsboost Installation, Operation & Maintenance Instructions

Mainsboost Installation, Operation & Maintenance Instructions mainsboost Mainsboost Installation, Operation & Maintenance Instructions Please leave this instruction booklet with the home owner as it contains important guarantee, maintenance and safety information

More information

RE: PROPANE SYSTEM & REGULATOR TESTING/INSPECTION PROCEDURE

RE: PROPANE SYSTEM & REGULATOR TESTING/INSPECTION PROCEDURE March 22, 2013 RE: PROPANE SYSTEM & REGULATOR TESTING/INSPECTION PROCEDURE Regulators: Symptom: Pressure Drop Cause: External leaks detected at pigtail hose MPT fitting connection(s) to regulator body

More information

Adjustment & Calibration Instructions

Adjustment & Calibration Instructions Adjustment & Calibration Instructions For Dixon Bayco 2180 AND 3180 ADJUSTABLE AIR RELIEF VALVES For Sales and Service Contact USA: Dixon Bayco USA Chestertown, Maryland Phone: 410-778-2000 Fax: 410-778-4702

More information

THE BP-301 SERIES. Operating and Service Manual. Series includes all variants of BP-301 (LF 0.1Cv / MF 0.5Cv)

THE BP-301 SERIES. Operating and Service Manual. Series includes all variants of BP-301 (LF 0.1Cv / MF 0.5Cv) THE BP-301 SERIES Operating and Service Manual Series includes all variants of BP-301 (LF 0.1Cv / MF 0.5Cv) Issue B October 2015 1 TABLE OF CONTENTS 1. Description... 3 2. Installation... 3 3. Operation...

More information

Service Call: Vacuum Prevention System Testing on Category A and B Aerial Devices. Tools Required: 1. Atmospheric Vent Test Set (P/N )

Service Call: Vacuum Prevention System Testing on Category A and B Aerial Devices. Tools Required: 1. Atmospheric Vent Test Set (P/N ) Service Call: Vacuum Prevention System Testing on Category A and B Aerial Devices Tools Required: 1. Atmospheric Vent Test Set (P/N 488180) *An automotive vacuum test kit with various fittings to hook

More information

Installation, commissioning and servicing instructions

Installation, commissioning and servicing instructions 48323 www.caleffi.com Pre-adjustable pressure reducing valve with self-contained cartridge Copyright 2015 Caleffi 5350..H AUS series Installation, commissioning and servicing instructions Function Pressure

More information

HYDROSTATIC LEAK TEST PROCEDURE

HYDROSTATIC LEAK TEST PROCEDURE This information is proprietary and shall not be disclosed outside your organization, nor shall it be duplicated, used or disclosed for purposes other than as permitted under the agreement with Kinetics

More information

Installation, commissioning and servicing instructions

Installation, commissioning and servicing instructions 3838.10 www.caleffi.com Inclined pressure reducing s opyright 2018 aleffi 33 series Installation, commissioning and servicing instructions Function Pressure reducing s are installed in residential water

More information

STANDARD FOR CONTROL VALVE SEAT LEAKAGE

STANDARD FOR CONTROL VALVE SEAT LEAKAGE 11-3 STANDARD FOR CONTROL VALVE SEAT LEAKAGE 1. PURPOSE 1.1 This standard establishes a series of seat leakage classes for control valves and defines the test procedures. 2. SCOPE & LIMITATIONS 2.1 Selection

More information

TExT Thorough Examination & Test of LEV Local Exhaust Ventilation Systems

TExT Thorough Examination & Test of LEV Local Exhaust Ventilation Systems ILEVE -Institute of LEV Engineers CPD & Information Day TExT Thorough Examination & Test of LEV Local Exhaust Ventilation Systems Jane Bastow CMIOSH Chartered Safety and Health Practitioner OSCHR Registered

More information

HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS

HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS Page 1 of 20 Page 2 of 20 TABLE OF CONTENTS Safety Warnings

More information

Overview EUSSAM12. Carry out tightness testing and direct purging of gas installations

Overview EUSSAM12. Carry out tightness testing and direct purging of gas installations Overview This standard covers tightness testing and direct purging of low or medium pressure gas, in accordance with approved procedures and practices. It covers the standards required to meet the requirements

More information

PTF4 Pivotrol Pump (patented) version Dual Mechanism - Pressure Powered Pump

PTF4 Pivotrol Pump (patented) version Dual Mechanism - Pressure Powered Pump Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

CSC-2000 SERIES. Reset Volume Controllers MADE IN U.S.A. DESCRIPTION MODELS SPECIFICATIONS ORDERING

CSC-2000 SERIES. Reset Volume Controllers MADE IN U.S.A. DESCRIPTION MODELS SPECIFICATIONS ORDERING CSC-2000 SERIES Reset Volume Controllers MADE IN U.S.A. DESCRIPTION The CSC-2000 series are designed for use on VAV terminal units in HVAC systems. These are submaster air velocity controllers whose velocity

More information

Deluge Optimo Shower valve and kit 10032CP

Deluge Optimo Shower valve and kit 10032CP Deluge Optimo Shower valve and kit 10032CP Installation, Operation and Maintenance Please leave these instructions with the user Intatec Limited Airfield Industrial Estate, Hixon, Staffordshire, ST18 0PF

More information

Private Swimming Pool Permit Application

Private Swimming Pool Permit Application Private Swimming Pool Permit Application Pool Address: Legal: Lot: Block: Plan: Subdivision: Applicant Information: Are you also the primary contact? Yes No Name: Address: Postal Code: Phone: Email Address:

More information

OCTOBER 2017 ISSUE Page 1 of 7

OCTOBER 2017 ISSUE Page 1 of 7 Field testing is performed on fully assembled pipelines for the purpose of determining pipeline acceptability. Following visual acceptance of joints and pipeline components, pressure pipelines in their

More information

REDUCED PRESSURE ZONE DEVICES SERIES PRODUCT CODES OPERATION HIGH HAZARD RATING. 15mm - 50mm FEATURES APPLICATION DESCRIPTION

REDUCED PRESSURE ZONE DEVICES SERIES PRODUCT CODES OPERATION HIGH HAZARD RATING. 15mm - 50mm FEATURES APPLICATION DESCRIPTION PRODUCT CODES RPZ15DO RPZ20DO RPZ25DO RPZ32DO RPZ40DO RPZ50DO RPZ15 RPZ20 RPZ25 RPZ32 RPZ40 RPZ50 15mm RPZD Device Only 20mm RPZD Device Only 25mm RPZD Device Only 32mm RPZD Device Only 40mm RPZD Device

More information

Instruction Manual. LKHSP Self-Priming Centrifugal Pump (Appendix) ESE02222-EN

Instruction Manual. LKHSP Self-Priming Centrifugal Pump (Appendix) ESE02222-EN Instruction Manual LKHSP Self-Priming Centrifugal Pump (Appendix) 3005-0011 NOTE! This is an appendix to Operating Manual ESE00698 for LKH Centrifugal pump. This appendix must be used in connection with

More information

Heat Pump Connections and Interior Piping

Heat Pump Connections and Interior Piping Job Sheet 3 Heat Pump Connections and Interior Piping OBJECTIVES In this job sheet, you will observe how the presence of air in the ground loop affects the geothermal heat pump performance. You will also

More information

SINGER MODEL 106/206-RPS-L&H

SINGER MODEL 106/206-RPS-L&H DESCRIPTION: Model 106/206-RPS-L&H dissipates surges caused by power failure to pumps. The valve anticipates the surge by opening on low line pressure associated with sudden stopping of pumps. This assures

More information

American Society of Sanitary Engineering

American Society of Sanitary Engineering ASSE Standard #1013-2011 ASSE Board Approved: August, 2011 ANSI Approved: August, 2011 American Society of Sanitary Engineering Performance Requirements for Reduced Pressure Principle Backflow Preventers

More information

CTG Certification Protocol -- Version 3.0 SUMMARY

CTG Certification Protocol -- Version 3.0 SUMMARY Date of Test: Test Report Number: SUMMARY Date of Prior Certification: Certified by: Re-certification Due Date: Unit Description: Make : Model: Serial Number: Location: CERTIFIER INFORMATION Name: Client

More information

OPERATION MANUAL NTF-15

OPERATION MANUAL NTF-15 OPERATION MANUAL NTF-15 Nitrogen Tire Filling Valve Stem Caps (Qty=200) Order P/N 436075 RTI Technologies, Inc 10 Innovation Drive York, PA 17402 800-468-2321 www.rtitech.com 035-81235-00 (Rev B) TABLE

More information

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply 4.1.1 General The primary function of a system for handling fuel oil is to transfer oil from the storage tank to the oil burner at specified conditions

More information

CSC-2000 SERIES. Reset Volume Controllers MADE IN U.S.A. DESCRIPTION MODELS SPECIFICATIONS ORDERING

CSC-2000 SERIES. Reset Volume Controllers MADE IN U.S.A. DESCRIPTION MODELS SPECIFICATIONS ORDERING CSC-2000 SERIES Reset Volume Controllers MADE IN U.S.A. DESCRIPTION The CSC-2000 series are designed for use on VAV terminal units in HVAC systems. These are submaster air velocity controllers whose velocity

More information

Overview of types. T5-R B2/R B2 en v Subject to changes 1 / 4. k vs (Sequence 2)

Overview of types.   T5-R B2/R B2 en v Subject to changes 1 / 4. k vs (Sequence 2) Technical data sheet R3015-..-..-B2 / R3020-..-..-B2 Characterised control valves, 6-way, with internal threads Two sequences (cooling/heating) With a rotary actuator 90 Water-side switching or modulating

More information

Wafer Check Valve. Contents. User s Manual. (1) Be sure to read the following description of our product warranty 1

Wafer Check Valve. Contents. User s Manual. (1) Be sure to read the following description of our product warranty 1 Serial No. H-V066-E-3 Wafer Check Valve User s Manual Contents (1) Be sure to read the following description of our product warranty 1 (2) General operating instructions 2 (3) General instructions for

More information

SEQUENTIAL SHOWER VALVE INSTRUCTION MANUAL PLEASE LEAVE THIS MANUAL WITH THE END USER

SEQUENTIAL SHOWER VALVE INSTRUCTION MANUAL PLEASE LEAVE THIS MANUAL WITH THE END USER SEQUENTIAL SHOWER VALVE INSTRUCTION MANUAL PLEASE LEAVE THIS MANUAL WITH THE END USER CONTENTS 1. INTRODUCTION & SAFETY 1 2. DIMENSIONS 2 3. TECHNICAL DATA 3 4. OPERATION 4 5. COMPONENTS 5 6. SITE INSTALLATION

More information

REFER TO AQUATHERM TECHNICAL BULLETIN A-AQTTB FOR ADDITIONAL INFORMATION AND SAFETY PRECAUTIONS

REFER TO AQUATHERM TECHNICAL BULLETIN A-AQTTB FOR ADDITIONAL INFORMATION AND SAFETY PRECAUTIONS Aquatherm Standard Pressure Testing Procedure Aquatherm offers an extensive warranty to protect against damages caused by failure from manufacturer s defect. Aquatherm requires that all installations be

More information

Winter Shut Down Procedure

Winter Shut Down Procedure Winter Shut Down Procedure Although we live in Beautiful BC, we still experience freezing temperatures. To minimize the risk of freeze damage to your irrigation system, you ll need to winterize it. Our

More information

Propane Conversion Kit Instruction

Propane Conversion Kit Instruction Propane Conversion Kit Instruction Condensing gas boiler Required Input Rates GB142-24 84,800 btu/hr GB142-30 106,000 btu/hr GB142-45 160,900 btu/hr GB142-60 214,800 btu/hr This kit and instructions are

More information

ACCURACY, PERFORMANCE, AND HANDLING OF OIL-FILLED DIGIQUARTZ PRESSURE INSTRUMENTATION

ACCURACY, PERFORMANCE, AND HANDLING OF OIL-FILLED DIGIQUARTZ PRESSURE INSTRUMENTATION Application Note Doc. G8108-001 Rev. A - 23-Jul-02 ACCURACY, PERFORMANCE, AND HANDLING OF OIL-FILLED DIGIQUARTZ PRESSURE INSTRUMENTATION For more information regarding Digiquartz products contact: Paroscientific,

More information

SYSTEM REGULATING VALVES PRESSURE RELIEF VALVE - SRV BRASS & S/STEEL ADJUSTABLE

SYSTEM REGULATING VALVES PRESSURE RELIEF VALVE - SRV BRASS & S/STEEL ADJUSTABLE SYSTEM REGULATING VALVES PRESSURE RELIEF VALVE - SRV BRASS & S/STEEL ADJUSTABLE This piston style pressure relief valve with conical shaped needle seat for accurate adjustment is available up to 3 in size.

More information

Propane Conversion Kit Instruction

Propane Conversion Kit Instruction Propane Conversion Kit Instruction Condensing gas boiler Required Input Rates GB42-24 84,800 btu/hr Tab. GB42-30 06,000 btu/hr GB42-45 49,000 btu/hr GB42-60 24,800 btu/hr This kit and instructions are

More information

TITAN FLOW CONTROL, INC.

TITAN FLOW CONTROL, INC. PREFACE: This manual contains information concerning the installation, operation, and maintenance of Titan Flow Control (Titan FCI) Simplex Basket Strainers. To ensure efficient and safe operation of Titan

More information

Bermad Pressure Reducing. Model: 42T

Bermad Pressure Reducing. Model: 42T Bermad Pressure Reducing Pilot Operated Pressure Control Valve Model: 42T Installation Operation Maintenance Manual (IOM) REV. 27.7.17 Page 1 of 12 Safety First BERMAD believes that the safety of personnel

More information

Integrity Testing LifeASSURE BDA020, BGA020 and BNA020 Series Filter Cartridges

Integrity Testing LifeASSURE BDA020, BGA020 and BNA020 Series Filter Cartridges 3M Purification Technical Application Brief Integrity Testing LifeASSURE BDA020, BGA020 and BNA020Series Filter Cartridges 1 Integrity Testing LifeASSURE BDA020, BGA020 and BNA020 Series Filter Cartridges

More information

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE 1 of 10 1. DESCRIPTION (Refer to Figures 1-3.) Viking supervised Single Interlocked Preaction Systems utilize a Viking Deluge Valve and a pneumatically pressurized automatic sprinkler system. The system

More information

Thermostatic Mixing Valves 61022CPB & 61028CPB Intamix Pro V

Thermostatic Mixing Valves 61022CPB & 61028CPB Intamix Pro V Thermostatic Mixing Valves 61022CPB & 61028CPB Intamix Pro V Installation and Maintenance Instructions 2 1 MIN MAX 7 In this procedure document we have endeavoured to make the information as accurate as

More information

Backflow What is it? City Water. Boiler. Make-Up Water Line

Backflow What is it? City Water. Boiler. Make-Up Water Line Backflow What is it? Backflow? You may have heard of it, and you may understand some of what it involves. This booklet will help you to understand it better; exactly what it is, and how to prevent it.

More information

Model: 43T. Bermad Pressure Relief Valve

Model: 43T. Bermad Pressure Relief Valve Model: 43T Bermad Pressure Relief Valve Installation Operation Maintenance Manual () Rev.C1_01.08.17 Page 1 of 10 Safety First BERMAD believes that the safety of personnel working with and around our equipment

More information

Approved Installation Method

Approved Installation Method AIM-08-01 Issue 1 February 2008 Water Suppliers Approved Installation Method Type BA Device Verifiable Backflow Preventer with Reduced Pressure Zone (RPZ Valve) Requirements for installation, on-site testing

More information

VERTICAL BLADDER TANK

VERTICAL BLADDER TANK Balanced Pressure Proportioning System Reliable Foam System Requiring Only Water Power Perfect For Tight Spaces UL Listed, ASME, National Board Registered Bladder-UL162 Approved, High Tensile Pressure

More information

Products no longer available

Products no longer available Technical data sheet R2.. Characterized control valves, 2-way, with internal thread for open and closed cold and warm water systems for modulating control on the water side of air-handling and heating

More information

BS12N Piezoresistive OEM Pressure Sensor

BS12N Piezoresistive OEM Pressure Sensor BS12N Piezoresistive OEM Pressure Sensor Model: BS12N-1 Model: BS12N-2 Feature Pressure range (-0.1~60)Mpa; Pressure reference: Gauge, absolute and sealed gauge; Constant current power supply; Isolated

More information

Part 3.0. Storage Tanks

Part 3.0. Storage Tanks Part 3.0 Storage Tanks Title Section SV Series 3.1 GXC Series 3.2 LEX Series 3.3 EX Series 3.4 EHX Series 3.5 SHX Series 3.6 HEV Series 3.7 TC Series 3.8 05/07 SV Storage Tank 3.1 This information expands

More information

29 SERIES - SAFETY VALVE

29 SERIES - SAFETY VALVE INDUSTRIES, INC. 29 SERIES - SAFETY VALVE INSTALLATION, OPERATION, & MAINTENANCE Part I Document Number: ES1016-1 Revision Level: A Issued By: David Edmonds Date: 6/20/04 Approved By: Date: 10/4/04 Conbraco

More information

Testing Procedures of Watertight Compartments

Testing Procedures of Watertight Compartments (1996) (Rev.1 Feb 2001) (Rev.2 May 2001) (Rev.3 May 2010) (Rev.4 Aug 2012) Testing Procedures of Watertight Compartments.1 Application Revision 4 of this UR is to be complied with in respect of the testing

More information

HORIZONTAL BLADDER TANK

HORIZONTAL BLADDER TANK Balanced Pressure Proportioning System Reliable Foam System Requiring Only Water Power Perfect For Low Ceilings UL Listed, ASME, National Board Registered Bladder-UL162 Approved, High Tensile Pressure

More information

WHEATLEY Series 500 Swing Check Valve

WHEATLEY Series 500 Swing Check Valve Document Number: TC003001-13 Revision: 02 WHEATLEY Series 500 Swing Check Valve Installation, Operation, and Maintenance Manual TABLE OF CONTENTS BILL OF MATERIALS...3 SCOPE...5 INSTALLATION AND OPERATION

More information

BODY OF KNOWLEDGE TANK ENTRY SUPERVISOR CERTIFICATION PROGRAM Revision 2, October 2013

BODY OF KNOWLEDGE TANK ENTRY SUPERVISOR CERTIFICATION PROGRAM Revision 2, October 2013 BODY OF KNOWLEDGE TANK ENTRY SUPERVISOR CERTIFICATION PROGRAM Revision 2, October 2013 This API Individual Certification Examination is designed to identify applicants possessing the required knowledge

More information

Function. Code Automatic filling units with pressure gauge connection Size 1/2 Code Automatic filling units with pressure gauge Size 1/2

Function. Code Automatic filling units with pressure gauge connection Size 1/2 Code Automatic filling units with pressure gauge Size 1/2 utomatic filling units series 55 cert. n ISO 9 5/5 G Replaces 5/ G unction he automatic filling unit is a device consisting of a pressure reducing valve with compensating seat, an inlet strainer, a shut-off

More information

2.0 Dates and Times Tests to be carried out starting Monday 28 Nov for completion Friday 2 Dec.

2.0 Dates and Times Tests to be carried out starting Monday 28 Nov for completion Friday 2 Dec. MS No: :. A 1.0 Scope of Work Preparation notes: delete column before issuing. 1.1 General Description of Works, Location & Boundaries Strength and tightness testing of Glycol System between plant room

More information

BODY OF KNOWLEDGE API TES TANK ENTRY SUPERVISOR

BODY OF KNOWLEDGE API TES TANK ENTRY SUPERVISOR BODY OF KNOWLEDGE API TES TANK ENTRY SUPERVISOR CERTIFICATION EXAMINATION November 2018 (Replaces November 2015) This API Individual Certification Examination is designed to identify applicants possessing

More information

InstrumentationTools.com

InstrumentationTools.com Author: Instrumentation Tools Categories: Level Measurement Basics of DP Level Measurement Level the parameters that exist in virtually every industrial process, there are many ways to measure the level,

More information

CERTIFYING DRAINLAYER

CERTIFYING DRAINLAYER No. 9198 REGISTRATION EXAMINATION, NOVEMBER 2017 CERTIFYING DRAINLAYER ANSWER SCHEDULE Plumbers, Gasfitters and Drainlayers Board, 2017. All rights reserved. No part of this publication may be reproduced

More information

Safety. April 2018 Supersedes all previous publications 2018 Chevron Phillips Chemical Company LP

Safety. April 2018 Supersedes all previous publications 2018 Chevron Phillips Chemical Company LP Technical Note 802 Leak Testing of Polyethylene Pipe For Municipal and Industrial Applications Part 1 Pre-Test Considerations Leak testing may be used to find leaks in a newly constructed or newly modified

More information